Installation Guide
Temperature Sensor
Type AK-HS 1000
<![if ! IE]> <![endif]>084R8011 |
Mounting |
|
For controllers with galvanic separated |
For controllers with non-galvanic |
power supply |
separated power supply |
<![endif]>084R8011
Calibration
In order to achieve an accuracy better than ±1 K of the temperature controlled, the accuracy of the sensor and the connecting cables must be better than ±0.6 K.
All sensors have a measuring accuracy below ±0.45 K within the HACCP defined temperature range of -30 °C to +20 °C. This is why it is essential that the cable resistance does not exceed 0.15 K.
The cable resistance expressed in Kelvin can be calculated by using the formula below:
ρ x L
R = -------------
3.85 x q
R = Cable resistance expressed in Kelvin
ρ = Specific resistance of the material [Ω/m/mm²] L = The length of the wire [in m there and back] q = Cross-section of the wire [mm2]
Example: ρ = 0.018
L = 10 m x 2 = 20 m q = 0.75 mm2
R = |
-----------------0.018 x 20 |
= 0.12 K |
|
3.85 x 0.75 |
|
Pt 1000 ohm / 0 °C
°C |
ohm |
°C |
ohm |
0 |
1000.0 |
0 |
1000.0 |
1 |
1003.9 |
-1 |
996.1 |
|
|
|
|
2 |
1007.8 |
-2 |
992.2 |
3 |
1011.7 |
-3 |
988.3 |
|
|
|
|
4 |
1015.6 |
-4 |
984.4 |
5 |
1019.5 |
-5 |
980.4 |
|
|
|
|
6 |
1023.4 |
-6 |
976.5 |
7 |
1027.3 |
-7 |
972.6 |
8 |
1031.2 |
-8 |
968.7 |
9 |
1035.1 |
-9 |
964.8 |
10 |
1039.0 |
-10 |
960.9 |
|
|
|
|
11 |
1042.9 |
-11 |
956.9 |
12 |
1046.8 |
-12 |
953.0 |
|
|
|
|
13 |
1050.7 |
-13 |
949.1 |
14 |
1054.6 |
-14 |
945.2 |
|
|
|
|
15 |
1058.5 |
-15 |
941.2 |
16 |
1062.4 |
-16 |
937.3 |
17 |
1066.3 |
-17 |
933.4 |
18 |
1070.2 |
-18 |
929.5 |
19 |
1074.0 |
-19 |
925.5 |
|
|
|
|
20 |
1077.9 |
-20 |
921.6 |
21 |
1081.8 |
-21 |
917.7 |
|
|
|
|
22 |
1085.7 |
-22 |
913.7 |
23 |
1089.6 |
-23 |
909.8 |
|
|
|
|
24 |
1093.5 |
-24 |
905.9 |
25 |
1097.3 |
-25 |
901.9 |
26 |
1101.2 |
-26 |
898.0 |
27 |
1105.1 |
-27 |
894.0 |
28 |
1109.0 |
-28 |
890.1 |
|
|
|
|
29 |
1112.8 |
-29 |
886.2 |
30 |
1116.7 |
-30 |
882.2 |
|
|
|
|
35 |
1136.1 |
|
|
40 |
1155.4 |
|
|
|
|
|
|
45 |
1174.7 |
|
|
50 |
1193.9 |
|
|
© Danfoss A/S (IA-MS/IM), 2014-11 |
IC.PI.P30.1A.02 / 520B6546 |
1 |
CERTIFICATE OF PERFORMANCE
It is herewith approved that AK-HS 1000 product sensors for temperature logging in combination with the HACCP certified ADAP-KOOL® controllers comply with EN 13485 in respect to temperature monitoring according to the EC regulation. 2005/37/EC.
Name and Address of Manufacturer within the European Community
Danfoss A/S
Nordborgvej 81
DK 6430 Nordborg
Denmark
Description of Equipment
Product Temperature sensor for refrigerated cabinets and cold rooms requiring monitoring for HACCP documentation and alarm.
Technical Summary
Temperature Range: |
-30 °C to +20 °C |
Accuracy: |
+/- 0,3 °C at 0 °C and +/- 0,005 °C x temp |
Time Constant: |
T90 = 3–15 mins. |
Sensor Type: |
Platinum-based sensors, Pt-1000 Ohm according to EN 60751 Class B |
Cable Connection: |
AK temperature sensors are two-wire devices, (Cable: 2 x 0.22 ~ 1.5 mm2). All connections are interchangeable |
Enclosure: |
IP54 [Materials: Cover: ABS / Base: Polycarbonate (PC)] thereby protecting the sensor against heat radiation |
|
from external ambient |
Nordborg 2014-11-20 |
Thomas Matzen |
______________________ |
__________________________ |
Place and date of issue |
Production Quality Manager |
To be completed by Installer/Contractor for site HACCP Manager Reference and Documentation
This AK-HS 1000 has been applied to the following application:
Location Name/Address: _______________________________________________
Cabinet / Cold Room Reference: _________________________________________
Installer / Contractor Name: _______________________________________
Signed: _________________________________________
Date: _____/_____/__________