Danfoss AK-CT 201A, AK-CT 200A, AK-CT 450A, AK-CT 550A Installation guide

Identication / Princip
Instructions
Controller tray AK-CT 200A
+
+
AK-CT 200A (084B0040)
AK-CT 201A, Manual = RS8GT AK-CT 450A, Manual = RS8GR AK-CT 550A, Manual = RS8GS
Required stripping lenght for spring connectors.
Supply samples
+
RI8RA802 10-2016
!
Important! N must always be connected when power is on.
Data
Supply voltage
Main switch
400 V 3N a.c. / 400 V 2N a.c. / 230 V N a.c. +10/-15%, 30 VA, 50 Hz
Automated fuse, 4 terminals, 16 A, SIL­approved
Display 2 plugs for connecting external display
Accuracy
I-measuring (L11-L18)
0-10 A: +/- 15%, min +/- 1 A
External display EKA 163B or 164B. (any EKA 163A or 164A)
Digital inputs DI1, DI2, DI3, DI4, DI5, DI6
Digital inputs DI7, DI8
Electricity supply cable
Relays
Signal from contact functions Requirements to contacts: None Cable length must be max. 15 m Use auxiliary relays when the cable is longer
230 V a.c.
On: DI > 80 V a.c. O: DI < 24 V a.c.
Max. 2.5 mm2
DO1-DO8
Max. 16 (12) A Imax adjustable: 4-16 A Imax=0 = no fuse
Alarm relay 4 (3) A, Min. 100 mA*
0 to +55°C, During operations
Environments
-40 to +70°C, During transport
20 - 80% Rh, not condensed
No shock inuence / vibrations
Enclosure IP 20
Weight 3,8 Kg
Fixed MODBUS
Data communication
Approvals
Extension options
EU Low Voltage Directive and EMC demands re CE-marking complied with LVD-tested acc. EN 60730-1, EN 60730-2-1 and EN 60730-2-9 EMC-tested acc. EN 61000-6-2 and EN 61000-6-3
LON RS485
MODBUS
Supply voltage
Main switch
400 V 3N a.c. / 400 V 2N a.c. / 230 V N a.c. +10/-15%, 30 VA, 50 Hz
Automated fuse, 4 terminals, 16 A, SIL­approved
Sensor S2 Not used
Sensor S3, S3B, S4, S5, S5B, S6, S6B
Accuracy
Pt 1000 or PTC 1000 ohm / 25°C (All must be of the same type)
Measuring range
Controller
Pt 1000 sensor
I-measuring (L11-L18)
-60 to +120°C
±1 K below -35°C ± 0,5 K between -35 til +25°C; ±1 K above +25°C
±0,3 K at 0°C ±0,005 K per degree
0-10 A: +/- 15%, min +/- 1 A
Display 2 plugs for connecting external display
External display EKA 163B or 164B. (any EKA 163A or 164A)
Digital inputs DI1, DI2, DI3, DI4, DI5, DI6
Digital inputs DI7, DI8
Electrical con­nection cable
Relays
Signal from contact functions Requirements to contacts: None Cable length must be max. 15 m Use auxiliary relays when the cable is longer
230 V a.c.
On: DI > 80 V a.c. O: DI < 24 V a.c.
Max. 2.5 mm2
DO1-DO8
Max. 16 (12) A Imax adjustable: 4-16 A Imax=0 = no fuse
Alarm relay 4 (3) A, Min. 100 mA*
Max. 240 V half wave rectied
Solid state output
Analog voltage output
Environments
DOA (for coil)
AO1
0 to +55°C, During operations
-40 to +70°C, During transport
20 - 80% Rh, not condensed
Max. 0.5 A Leakage < 1 mA Max. 1 coil. Electronic coil controller EEC may not be used
0-10 V R
> 1 kΩ
Load
No shock inuence / vibrations
Enclosure IP 20
Weight 3.8 kg
Fixed MODBUS
Data communication
Power reserve for the clock
Approvals
Extension options
24 hours
EU Low Voltage Directive and EMC demands re CE-marking complied with LVD-tested acc. EN 60730-1, EN 60730-2-1 and EN 60730-2-9 EMC-tested acc. EN 61000-6-2 and EN 61000-6-3
LON RS485
MODBUS
AK-CT 550AAK-CT 450AAK-CT 201A
Supply voltage
Main switch
Sensor S2 Pt 1000
Sensor S3, S3B, S4, S5, S5B, S6, S6B
Accuracy
Measuring of Pe
Display 2 plugs for connecting external display
External display EKA 163B or 164B. (any EKA 163A or 164A)
Digital inputs DI1, DI2, DI3, DI4, DI5, DI6
Digital inputs DI7, DI8
Electrical con­nection cable
Relays
Solid state output
Analog voltage output
Environments
Enclosure IP 20
Weight 3.8 kg
Data communication
Power reserve for the clock
Approvals
400 V 3N a.c. / 400 V 2N a.c. / 230 V N a.c. +10/-15%, 30 VA, 50 Hz
Automated fuse, 4 terminals, 16 A, SIL­approved
Pt 1000 or PTC 1000 ohm / 25°C (All must be of the same type)
Measuring range
Controller
Pt 1000 sensor
I-measuring (L11-L18)
Pressure transmitter
Signal from contact functions Requirements to contacts: None Cable length must be max. 15 m Use auxiliary relays when the cable is longer
230 V a.c.
-60 to +120°C
±1 K below -35°C ± 0,5 K between -35 til +25°C; ±1 K above +25°C
±0,3 K at 0°C ±0,005 K per degree
0-10 A: +/- 15%, min +/- 1 A
AKS 32R / AKS 2050
On: DI > 80 V a.c. O: DI < 24 V a.c.
Max. 2.5 mm2
DO1-DO8
Max. 16 (12) A Imax adjustable: 4-16 A Imax=0 = no fuse
Alarm relay 4 (3) A, Min. 100 mA*
Max. 240 V half wave rectied
DOA (for coil)
AO1
0 to +55°C, During operations
-40 to +70°C, During transport
Max. 0.5 A Leakage < 1 mA Max. 1 coil. Electronic coil controller EEC may not be used
0-10 V R
> 1 kΩ
Load
20 - 80% Rh, not condensed
No shock inuence / vibrations
Fixed MODBUS
Extension options
LON RS485
MODBUS
24 hours
EU Low Voltage Directive and EMC demands re CE-marking complied with LVD-tested acc. EN 60730-1, EN 60730-2-1 and EN 60730-2-9 EMC-tested acc. EN 61000-6-2 and EN 61000-6-3
The Product contains electrical components And may not be disposed together with domestic waste. Equipment must be separate collected with Electrical and Elec­tronic waste. According to Local and currently valid legislation.
*) Gold plating ensures make function with small contact loads
2 Instructions RI8RA802 © Danfoss 10/2016 Controller tray AK-CT 200A