AK-CH 650A is a water chiller control for capacity control of max. 8
compressors in two groups and capacity control of one air-cooled
condensers on indirect refrigeration systems within commercial
refrigeration.
In addition to capacity control, the controller can control pumps
etc.
SW = 1.8
The controller uses the following signals for control/monitoring:
S4 Charge temperature (control signal)
S3 Return temperature
P0.1, P0.2 Suction pressure
Pc Condensing pressure
Sc3 Ambient temperature
S4.1, S4.2 Frost protection
Flow switch Frost protection / pump change
Sd.1, Sd.2 Discharge gas temperature (monitoring)
Ss.1, Ss.2 Suction gas temperature (reading)
Compressor capacity is controlled by charge temperature S4 and
by suction pressure P0 as frost protection. Condenser capacity is
controlled by condensing pressure Pc or, alternatively, temperature sensor S7.
If the system has a condenser for each suction group, the condenser capacity must be externally regulated, e.g. by two AK-PC
530 units.
If the system has dry coolers and heat recovery, it must be externally regulated, e.g. by an AK-PC 420.
A couple of examples are shown in the section on condenser
regulation.
Among the dierent functions are:
- Capacity control of up to 8 compressors (2x4 pcs.)
- Max. 3 unloaders/compressor
- Speed control of two compressors
- Up to 6 safety inputs for each compressor
- Capacity limitation to minimize consumption peaks
- Twin pump control with automatic operating time equalisation
- Speed control of twin pump
- Start/stop signal for injection in evaporator
- Defrost control with time or temperature stop (Applicance
controls)
- Safety monitoring of high pressure / low pressure / pressure
temperature
- Frost protection
- Capacity control of up to 8 fans
- Floating condenser reference with regard to outside temperature
- Heat recovery function
- Fan capacity with regard to Step coupling, speed regulation or a
combination
- Safety monitoring of fans
- Alarm signals can be generated directly from the controller and
via data communication
- Alarms are shown with texts so that the cause of the alarm is
easy to see.
- Plus some completely separate functions that are totally inde-
pendent of the regulation – such as alarm inputs, thermostats,
pressostat and voltage inputs.
The great advantage of this series of controllers is that it can
be extended as the size of the plant is increased. It has been
developed for refrigeration control systems, but not for any
specic application – variation is created through the read-in
software and the way you choose to dene the connections.
It is the same modules that are used for each regulation and the
composition can be changed, as required. With these modules
(building blocks) it is possible to create a multitude of various
kinds of regulations. But it is you who must help adjusting the
regulation to the actual needs – these instructions will assist you
to nd your way through all the questions so that the regulation
can be dened and the connections made.
Controller
Top part
Advantages
• The controller’s size can “grow” as systems grow
• The software can be set for one or more regulations
• Several regulations with the same components
• Extension-friendly when systems requirements are changed
• Flexible concept:
- Controller series with common construction
- One principle – many regulation uses
- modules are selected for the actual connection requirements
- The same modules are used from regulation to regulation
Extension modules
Bottom part
The controller is the cornerstone of the regulation. The module has inputs and
outputs capable of handling small systems.
• The bottom part – and hence the terminals – are the same for all controller types.
• The top part contains the intelligence with software. This unit will vary according
to controller type. But it will always be supplied together with the bottom part.
• In addition to the software the top part is provided with connections for data
communication and address setting.
Examples
A regulation with few connections can
be performed with the controller module
alone
If the system grows and more functions have to be controlled, the regulation can be
extended.
With extra modules more signals can be received and more relays cut in and out
– how many of them – and which – is determined by the relevant application.
If there are many connections one or more
extension modules have to be mounted
Setup and operation of an AK controller must be accomplished via
the “AK-Service Tool” software program.
The programme is installed on a PC, and setup and operation of
the various functions are carried out via the controller’s menu
displays.
Displays
The menu displays are dynamic, so that dierent settings in one
menu will result in dierent setting possibilities in other menus.
A simple application with few connections will give a setup with
few settings.
A corresponding application with many connections will give a
setup with many settings.
From the overview display there is access to further displays for
the compressor regulation and the condenser regulation.
At the bottom of the display there is access to a number of general
functions, such as “time table”, “manual operation”, “log function”,
“alarms”, and “service” (conguration).
Network linking
The controller can be linked up into a network together with other
controllers in an ADAP-KOOL® refrigeration control system. After
the setup operation can be performed at a distance with, say, our
software program type AKM.
Users
The controller comes supplied with several languages, one of
which can be selected and employed by the user. If there are
several users, they may each have their choice of language. All
users must be assigned a user prole which either gives access to
full operation or gradually limits the operation to the lowest level
that only allows you “to see”.
Language selection is part of the service tool settings.
If the language selection is not available in the service tool for the
current regulator, English texts will be displayed.
External display
An external display can be tted in order for brine temperature, P0
(Suction) and Pc (Condensing) readings to be displayed.
A total of 4 displays can be tted and with one setting it is possible to choose between the following readings: S4, S3, P01, P02,
S4.1, S4.2, Cond. regulation sensor, Pc1, Pc2, Sd1, Sd2, Ss1, Ss2.
A number of light-emitting diodes makes it possible to follow the
signals that are received and transmitted by the controller.
Log
From the log function you can dene the measurements you wish
to be shown.
The collected values can be printed, or you may export them to a
le. You can open the le in Excel.
If you are in a service situation you can show measurements in a
trend function. The measurements are then made realtime and
displayed instantly.
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
Slow ash = OK
Quick ash = answer from gateway
Constantly ON = error
Constantly OFF = error
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
Alarm
The display gives you an overview of all active alarms. If you wish
to conrm that you have seen the alarm you can cross it o in the
acknowledge eld.
If you want to know more about a current alarm you can click on it
and obtain an information display on the screen.
A corresponding display exists for all earlier alarms. Here you can
upload information if you need further details about the alarm
history.
This section describes how the controller is designed.
The controller in the system is based on a uniform connection
platform where any deviations from regulation to regulation is
determined by the used top part with a specic software and
by which input and output signals the relevant application will
require. If it is an application with few connections, the controller
module (top part with belonging bottom part) may be sucient.
If it is an application with many connections it will be necessary to
use the controller module plus one or more extension modules.
This section will give you a survey of possible connections plus
assistance in selecting the modules required by your actual
application.
• Controller module – capable of handling minor plant requirements.
• Extension modules. When the complexity becomes greater
and additional inputs or outputs are required, modules can be
attached to the controller. A plug on the side of the module will
transmit the supply voltage and data communication between
the modules.
• Top part
The upper part of the controller module contains the
intelligence. This is the unit where the regulation is dened and
where data communication is connected to other controllers in a
bigger network.
• Connection types
There are various types of inputs and outputs. One type may, for
example, receive signals from sensors and switches, another may
receive a voltage signal, and a third type may be outputs with
relays etc. The individual types are shown in the table below.
Extension module with
additional analog inputs
External display for
suction pressure etc.
• Optional connection
When a regulation is planned (set up) it will generate a need for
a number of connections distributed on the mentioned types.
This connection must then be made on either the controller
module or an extension module. The only thing to be observed
is that the types must not be mixed (an analog input signal must
for instance not be connected to a digital input).
• Programming of connections
The controller must know where you connect the individual
input and output signals. This takes place in a later conguration where each individual connection is dened based on the
following principle:
- to which module
- at which point (”terminals”)
- what is connected (e.g. pressure transmitter/type/
pressure range)
Extension module with additional
relay outputs and additional
analog inputs.
Controller with analog inputs and
relay outputs.
Top part
Extension module with
2x analog output signals
The module with additional relay outputs is
also available in a version where the top part
is provided with change-over switches so
that the relays can be overridden.
Pressure transmitter type AKS 32R / AKS
2050 / AKS 32 (1-5 V)
Other pressure transmitter:
Ratiometric signal
Min. and Max. pressure must be set
Voltage signal 0-10 V
Contact function (On/O )On at R < 20 ohm
On/o supply voltage inputsLow voltage
Relay outputs
SPDT
Solid state outputsCan be used for loads that are cut in and
0 / 80 V a.c./d.c.
High voltage
0 / 260 V a.c.
AC-1 (ohmic)4 A
AC-15 (inductive)3 A
UMin. 24 V
out frequently, e.g. :
fans and AKV valve
Accuracy: +/- 0.5°C
Resolution:1 mV
Accuracy +/- 10 mV
Max. connection of 5 pressure transmitters on one module
O at R > 2K ohm
(Gold -plated contacts not necessary)
O: U < 2 V
On: U > 10 V
O: U < 24 V
On: U > 80 V
Max. 230 V
Low and high voltage must not be connected to the same
output group
Max. 240 V a.c. , Min. 48 V a.c.
Max. 0.5 A,
Leak < 1 mA
Max. 1 AKV
Ambient temperatureDuring transport-40 to 70°C
During operation-20 to 55°C ,
0 to 95% RH (non condensing)
No shock inuences / vibrations
EnclosureMaterialPC / ABS
ClassIP10 , VBG 4
MountingFor mounting on panel wall or DIN rail
Weight with screw terminalsmodules in100- / 200- / controller-seriesCa. 200 g / 500 g / 600 g
ApprovalsEU low voltage directive and EMC require-
ments are complied with
UL 873,
The mentioned data applies to all modules.
If data is specic, this is mentioned together with the module in question.
Capacitive load
The relays cannot be used for the direct connection of capacitive loads such as LEDs
and on/o control of EC motors.
All loads with a switch mode power supply must be connected with a suitable contactor or similar.
LVD tested according to EN 60730
EMC tested
Immunity according to EN 61000-6-2
Emission according to EN 61000-6-3
UL le number: E166834 for XM modules
UL le number: E31024 for CH modules
The module dimension is 72 mm.
Modules in the 100-series consist of one
module
Modules in the 200-series consist of two
modules
Controllers consist of three modules
The length of an aggregate unit = n x 72 + 8
There are several controllers in the series. The function is
determined by the programmed software, but outwardly the
controllers are identical – they all have the same connection
possibilities:
11 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputs
Supply voltage
24 V a.c. or d.c. to be connected to the controller.
The 24 V must not be retransmitted and used by other controllers
as it is not galvanically separated from inputs and outputs. In
other words, you must use a transformer for each controller. Class
II is required. The terminals must not be earthed.
The supply voltage to any extension modules is transmitted via
the plug on the right-hand side.
The size of the transformer is determined by the power
requirement of the total number of modules.
The supply voltage to a pressure transmitter can be taken either
from the 5 V output or from the 12 V output depending on
transmitter type.
PIN
Data communication
If the controller is to be included in a system, communication
must take place via the LON connection.
The installation has to be made as mentioned in the separate
instructions for LON communication.
Address setting
When the controller is connected to a gateway type AKA 245, the
controller’s address must be set between 1 and 119.
Service PIN
When the controller is connected to the data communication
cable the gateway must have knowledge of the new controller.
This is obtained by pushing the key PIN. The LED “Status” will ash
when the gateway sends an acceptance message.
Operation
The conguration operation of the controller must take place from
the software programme “Service Tool”. The program must be
installed on a PC, and the PC must be connected to the controller
via the network plug on the front of the unit.
Light-emitting diodes
There are two rows with LED’s. They mean:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row:
• Software status (slow ash = OK)
• Communication with Service Tool
• Communication on LON
• Alarm when LED ashes
- 3 LED’s that are not used
• “Service Pin” switch has been activated
Address
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
Slow ash = OK
Quick ash = answer from gateway
Constantly ON = error
Constantly OFF = error
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
Keep the safety
distance!
Low and high
voltage must not
be connected to
the same output
group
A small module (option board) can be placed on the bottom part
of the controller. The module is described later in the document.
The supply voltage to the module comes from the previous
module in the row.
AK-XM 204B only
Override of relay
Eight change-over switches at the front make it possible to
override the relay’s function.
Either to position OFF or ON.
In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They indicate the following:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 204B only):
• Override of relays
ON = override
OFF = no override
AK-XM 204A AK-XM 204B
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic)
AC-15: max. 3 A (Inductive)
AK-XM 204B
Override of relay
Keep the safety distance!
Low and high voltage
must not be connected to
the same output group
The module contains:
8 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous
module in the row.
AK-XM 205B only
Override of relay
Eight change-over switches at the front make it possible to
override the relay’s function.
Either to position OFF or ON.
In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They mean:
Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 205B only):
• Override of relays
ON = override
OFF = no override
AK-XM 205A AK-XM 205B
max. 10 V
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic)
AC-15: max. 3 A (Inductive)
AK-XM 205B
Override of relay
Keep the safety distance!
Low and high voltage
must not be connected to
the same output group
The module is a real time clock module with battery backup.
The module can be used in controllers that are not linked up in
a data communication unit together with other controllers. The
module is used here if the controller needs battery backup for the
following functions
• Clock function
• Fixed times for day/night change-over
• Fixed defrost times
• Saving of alarm log in case of power failure
• Saving of temperature log in case of power failure
Connection
The module is provided with plug connection.
Placing
The module is placed on the PC board inside the top part.
Point
No point for a clock module to be dened – just connect it.
Working life of the battery
The working life of the battery is several years – even if there are
frequent power failures.
An alarm is generated when the battery has to be replaced.
After the alarm there are still several months of operating hours
left in the battery.
Display of important measurements from the controller, e.g. brine
temperature, suction pressure or condensing pressure.
Setting of the individual functions can be performed by using the
display with control buttons.
It is the controller used that determines the measurements and
settings that can occur.
Connection
The extension module is connected to the controller module via
a cable with plug connections. You have to use one cable per
module. The cable is supplied in various lengths.
Both types of display (with or without control buttons) can be
connected to either display output A, B, C or D.
When the controller starts up, the display will show the output
that is connected.
- - 1 = output A
- - 2 = output B
etc.
EKA 163B EKA 164B
Placing
The extension module can be placed at a distance of up to 15 m
from the controller module.
Point
No point has to be dened for a display module – you simply connect it.
Be aware of the following when the number of extension modules
is being planned. A signal may have to be changed, so that an
additional module may be avoided.
• An ON/OFF signal can be received in two ways. Either as a
contact signal on an analog input or as voltage on a low or highvoltage module.
• An ON/OFF output signal can be given in two ways. Either with a
relay switch or with solid state. The primary dierence is the permitted load and that the relay switch contains a cutout switch.
Mentioned below is a number of functions and connections
that may have to be considered when a regulation has to be
planned. There are more functions in the controller than the ones
mentioned here, but those mentioned have been included in
order that the need for connections can be established.
Functions
Clock function
Clock function and change-over between summer time and
winter time are contained in the controller.
The clock is zeroset when there is power failure.
The clock’s setting is maintained if the controller is linked up in a
network with a gateway, or a clock module can be mounted in the
controller.
Start/stop of regulation
Regulation can be started and stopped via the software. External
start/stop can also be connected.
Alarm function
If the alarm is to be sent to a signal transmitter, a relay output will
have to be used.
Extra temperature sensors and pressure sensors
If additional measurements have to be carried out beyond the
regulation, sensors can be connected to the analog inputs.
Forced control
The software contains a forced control option. If an extension
module with relay outputs is used, the module’s top part can
be with change-over switches – switches that can override the
individual relays into either OFF or ON position.
Data communication
The controller module has terminals for LON data communication.
The requirements to the installation are described in a separate
document.
In principle there are the following types of connections:
Analog inputs ”AI”
This signal must be connected to two
terminals.
Signals can be received from the following
sources:
• Temperature signal from Pt 1000 ohm
temperature sensor
• Contact signal where the input is shortcircuited or ”opened”, respectively
• Voltage signal from 0 to 10 V
• Signal from pressure transmitter AKS 32,
AKS 32R or AKS 2050
The supply voltage is supplied from the
module’s terminal board where there is
both a 5 V supply and a 12 V supply.
When programming the pressure
transmitter’s pressure range must be set.
ON/OFF voltage inputs ”DI”
This signal must be connected to two
terminals.
• The signal must have two levels, either 0 V
or ”voltage” on the input.
There are two dierent extension
modules for this signal type:
- low-voltage signals, e.g. 24 V
- high-voltage signals, e.g. 230 V
ON/OFF output signals ”DO”
There are two types, as follows:
• Relay outputs
All relay outputs are with change-over
relay so that the required function can be
obtained when the controller is without
voltage.
• Solid state outputs
Reserved for AKV valves, but output can
cut an external relay in and out, as with a
relay output.
The output is only found on the
controller module.
When programming the function must be set:
• Active when the output is activated
• Active when the output is not activated.
Analog output signal ”AO”
This signal is to be used if a control signal is
to be transmitted to an external unit, e.g. a
frequency converter.
When programming the signal range must
be dened: 0-5 V, 1-5 V, 0-10 V or 2-10 V.
Or conversely 5-0 V, 5-1 V, 10-0 V or 10-2 V.
When programming the function must be set:
• Active when the input is without voltage
• Active when voltage is applied to the
input.
Limitations
As the system is very exible regarding the number of connected
units you must check whether your selection complies with the
few limitations there are.
The complexity of the controller is determined by the software,
the size of the processor, and the size of the memory. It provides
the controller with a certain number of connections from which
data can be downloaded, and others where coupling with relays
can be performed.
✔ The sum of connections cannot exceed 80.
✔ The number of extension modules must be limited so that the
total power will not exceed 32 VA (including controller).
✔ No more than 5 pressure transmitters may be connected to one
controller module.
✔ No more than 5 pressure transmitters may be connected to one
2. Check that the controller’s functions cover the required application
3. Consider the connections to be made
4. Use the planning table. / Note down the number of connections
./ add up
5. Are there enough connections on the controller module? – If
not, can they be obtained by changing an ON/OFF input signal
from voltage signal to contact signal, or will an extension module be required?
Regulation of up to 8 compressors. Up to three unloaders per
compressor. Compressor No. 1 in each group can be speed-regulated.
Condenser pressure reference
Floating condensing pressure referencex
Setting of reference for heat recovery functionx
Safety functions
Preventing the temperature from dropping below the accepted
limit at S4.1 and S4.2.
Min. suction pressurex
Max. suction pressurex
Max. condensing pressurex
Max. discharge gas temperaturex
Min. / Max. superheatx
Safety monitoring of compressorsx
Common high pressure monitoring of compressorsx
Safety monitoring of condenser fansx
General alarm functions with time delay10
Frost protectionx
Miscellaneous
Extra sensors7
Option for connection of separate display2
Separate thermostat functions5
Separate pressostat functions5
Separate voltage measurements5
Condenser
Regulation of up to 8 condenser steps.
Fans can be speed-regulated. Either all on one signal or only the
rst fan of several.
Relay outputs and solid state outputs may be used, as desired.
x
Speed regulation of condenser fans
The function requires an analog output module.
A relay output may be used for start/stop of the speed regulation.
The fans may also be cut in and out by relay outputs.
Safety circuit
If signals are to be received from one or more parts of a safety
circuit, each signal must be connected to an ON/OFF input.
Day/night signal for raising the suction pressure
The clock function can be used, but an external ON/OFF signal
may be used instead.
If the “P0 optimisation” function is used, no signal will be
given concerning the raising of the suction pressure. The P0
optimisation will see to this.
Separate thermostat and pressure control functions
A number of thermostats can be used according to your wishes.
The function requires a sensor signal and a relay output. In the
controller there are settings for cutin and cutout values. An associated alarm function may also be used.
Separate voltage measurements
A number of voltage measurements can be used according to
your wishes. The signal can for example be 0-10 V. The function
requires a voltage signal and a relay output. In the controller there
are settings for cutin and cutout values. An associated alarm function may also be used.
If you want to know more about the functions, go to
chapter 5.
3
Connections
Here is a survey of the possible connections. The texts can be read
in context with the table in point 4.
Analog inputs
Temperature sensors
• S4 and S3 (regulation sensors for brine temperature)
Must always be used.
• S4.1, S4.2 (frost protection sensor)
• Ss1, Ss2 (suction gas temperature)
The measurement is reserved, but the connection can be deleted.
• Sd1, Sd2 (discharge gas temperature)
The measurement is reserved, but the connection can be deleted.
• Sc3 (outdoor temperature)
To be used when regulation is performed with oating
condenser reference.
• S7 (Hot brine return temperature))
This must be used when the control sensor for the condenser
has been selected as S7.
• Saux (1-4), Extra temperature sensors, if applicable
Up to four additional sensors for monitoring and data collection
may be connected.
These sensors can be used for general thermostat functions.
• Shrec (heat recovery thermostat)
Must be used when heat recovery is controlled via a thermostat
function.
Pressure transmitters
• P01. P02 Suction Pressure
Must always be used
• Pc (Pc1, Pc2) Condensing Pressure
Must always be used in connection with compressor and condenser regulation
• Paux (1-3)
Up to 3 extra pressure transmitters can be connected for monitoring and data collection.
These sensors can be used for general pressure switch functions.
A pressure transmitter type AKS 32 or AKS 32R can supply signals
to a maximum of ve controllers.
Voltage signal
• Ext. reference
Used when overriding signal is received from another control.
• Volt indputs (1-5)
Up to 5 extra voltage signals can be connected for monitoring
and data collection. These signals can be used for general voltage input functions.
On/O-inputs
Contact function (on an analog input) or voltage signal (on an
extension module)
• Frost protection
• Flow switch or pressure dierence for pump monitoring
• Start of defrost
• Up to 6 signals from each compressors safety circuits
• Signal from the condenser fans’ safety circuit
• Any signal from the frequency converter’s safety circuit (comp.
and/or fans)
• External start/stop of regulation
• External start stop of heat recovery
• Up to 2 Inputs for capacity limitation
• External day/night signal (raise/lower the suction pressure reference). The function is not used if the “P0 optimisation” function
is used.
• DI alarm (1-10) inputs.
Up to 10 extra on/o signals for general alarm monitoring and
data collection can be connected.
On/o-outputs
Relay outputs
• Compressors (1-8)
• Unloaders (max. 3/compressor)
• Fan motor (1-8)
• Start/stop of liquid injection in evaporator
• Defrost output
• Start/stop of heat recovery
• Start/stop of twin pumps (1-2)
• Start/stop of speed control (1-2) (comp. / fans / pumps)
• Alarm relay
• General functions from thermostats (1-5), pressostats (1-5) and
voltage inputs (1-5).
Solid state outputs
The solid state outputs on the controller module may be used
for the same functions as those mentioned under “relay outputs”.
(The output will always be “OFF” when the controller has a power
failure).
Analog outputs
• Speed regulation of the condenser’s fans.
• Speed regulation of compressors.
• Speed regulation of pumps
Example
Compressor group:
• Refrigerant R404A
• 4 compressors (15 kW)
• Safety monitoring of each compressor
• Capacity limitation of compressors via contact signal (load shedding)
• Injection signal to heat exchanger
• S4 setting 2°C
Air cooled condenser:
• 4 fans, step regulation
• Pc regulates based on outdoor temperature sensor Sc3
Pumps + defrost:
• start/stop of 2 pumps
• Speed regulation of pumps
• Monitoring via ow switch (contact signal)
• Output for defrost
Fan in plant room
• Thermostat control of fan in engine room (sensor + output)
Safety functions:
• Monitoring of S4, P0, Pc, Sd and superheat in suction line
• P0 min. = -10°C
• Pc max. = 50°C
• Sd max. = 120°C
• SH min. = 5°C, SH max. = 35°C
Other:
• Alarm output used
• External main switch used (contact signal)
Data from this example is used on the next page.
The result is that the following modules should be used:
The table helps you establish whether there are enough
4
inputs and outputs on the basic controller.
If there are not enough of them, the controller must be
extended by one or more of the mentioned extension
modules.
Note down the connections you will require and add
them up
If you use many extension modules the controller’s length will
grow accordingly. The row of modules is a complete unit which
cannot be broken.
The module dimension is 72 mm.
Modules in the 100-series consist of one module
Modules in the 200-series consist of two modules
The controller consist of three modules
The length of an aggregate unit = n x 72 + 8
or in an other way:
Module Type Number at Length
Controller module 1 x 224 = 224 mm
Extension module 200-series _ x 144 = ___ mm
Extension module 100-series _ x 72 = ___ mm
Total length = ___ mm
9
Linking of modules
Start with the controller module and then mount the selected
extension modules. The sequence is of no importance.
However, you must not change the sequence, i.e. rearrange the
modules, after you have made the setup where the controller
is told which connections are found on which modules and on
which terminals.
The modules are attached to one another and kept together by a
connection which at the same time transmits the supply voltage
and the internal data communication to the next module.
Example continued:
Controller module + 1 extension module in 200-series + 1 extension
module in 100-series =
224 + 144 + 72 = 440 mm.
Mounting and removal must always be performed when there is
no voltage.
The protective cap mounted on the controller’s plug connection
must be moved to the last vacant plug connection so that the
plug will be protected against short-circuit and dirt.
When the regulation has started the controller will all the time
check whether there is connection to the connected modules. This
status can be followed by the light-emitting diode.
When the two catches for the DIN rail mounting are in open
position the module can be pushed into place on the DIN rail – no
matter where in the row the module is found.
Removal is likewise carried out with the two catches in the open
position.
All connections must be programmed with module and point, so
in principle it does not matter where the connections are made, as
long as it takes place on a correct type of input or output.
• The controller is the rst module, the next one is 2, etc.
• A point is the two or three terminals belonging to an input or
output (e.g. two terminals for a sensor and three terminals for a
relay).
The preparation of the connection diagram and the subsequent
programming (conguration) should take place at the present
time. It is most easily accomplished by lling in the connection
survey for the relevant modules.
Principle:
Name On module On Point Function
fx Compressor 1 x x Close
fx Compressor 2 x x Close
fx Alarm relay x x NC
fx Main switch x x Close
fx P0 x x AKS 32R 1-6 bar
The connection survey from the controller and any extension
modules are uploaded from the paragraph "Module survey. E.g.
controller module:
SignalModulePoint Terminal
1 (AI 1)1 - 2
2 (AI 2)3 - 4
3 (AI 3)5 - 6
4 (AI 4)7 - 8
- Columns 1, 2, 3 and 5 are used for the programming.
- Columns 2 and 4 are used for the connection diagram.
Signal type /
Active at
Module Point
Mind the numbering.
The right-hand part of the
controller module may look like
a separate module. But it isn’t.
Hint
In appendix B, 16 general installation types are illustrated.
If your installation is nearly similar to one of those illustrated, you can advantageously use the given connection
points.
Supply voltage is only connected to the controller module. The
supply to the other modules is transmitted via the plug between
the modules. The supply must be 24 V +/-20%. One transformer
must be used for each controller. The transformer must be a class
II. The 24 V must not be shared by other controllers or units. The
analog inputs and outputs are not galvanically separated from the
supply.
The + and – 24V input must not be earthed.
Example continued:
Controller module 8 VA
+ 1 extension module in 200-series 5 VA
+ 1 extension module in 100-series 2 VA
------
Transformer size (least) 15 VA
Transformer size
The power consumption grows with the number of modules used:
Module Type Number á Eect
Controller 1 x 8 = 8 VA
Extension module 200-series _ x 5 = __ VA
Extension module 100-series _ x 2 = __ VA
Total ___ VA
The basic module must not be connected to voltage.
Press in the plate on the left-hand side of the light-emitting
diodes and the plate on the right-hand side for the red address
changers.
Lift the top part o the basic module.
The analog extension module will supply a signal to the variable frequency drive.
2. Mount the extension module in the basic module
3. Put the top part back on the basic module
There are two outputs, but we only use
one in the example.
Remove the protective cap from the connection plug on the
right-hand side of the basic module.
Place the cap on the connection plug to the right of the extension module that is to be mounted on the extreme right-hand
side of the AK assembly.
2. Assemble the extension module and the basic
module
The basic module must not be connected to voltage.
In our example two extension modules are to be tted to the basic
module. We have chosen to t the module with relays directly on the
basic module and then the module with input signals. The sequence is
thus:
3
All the subsequent settings that aect the two extension modules are
determined by this sequence.
When the two snap catches for the DIN rail mounting are in the open
position, the module can be pushed into place on the DIN rail – regardless of where the module is on the row.
Disassembly is thus done with the two snap catches in the open position.
Warning
Keep signal cables separate from
cables with high voltage.
The screen on the pressure transmitter
cables must only be connected at the
end of the controller.
Comp. 1 Gen. safety
Comp. 3 Gen. safety
Comp. 2 Gen. safety
External main switch
Pump ow switch
Comp. 4 Gen. safety
evaporators
Pack 1, comp. 1
Frequency converter
Pack 2, domp. 1
Pack 2, comp. 2
Pack 1, domp. 2
Liquid injection in
2. Connect LON communication network
The installation of the data communication must comply with
the requirements set out in document RC8AC.
3. Connect supply voltage
Is 24 V, and the supply must not be used by other controllers or
devices. The terminals must not be earthed.
4. Follow light-emitting diodes
When the supply voltage is connected the controller will go
through an internal check. The controller will be ready in just
under one minute when the light-emitting diode ”Status” starts
ashing slowly.
5. When there is a network
Set the address and activate the Service Pin.
Internal communication
between the modules:
Quick ash = error
Constantly On = error
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
Status on output 1-8
Room Fan
Slow ash = OK
Quick ash = answer from gateway
in 10 min. after network
installation
Constantly ON = error
Constantly OFF = error
External communication
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled
We have decided to work on the basis of the example we went
through previously, i.e. compressor control with 4 compressors
and condenser control with 4 fans.
The example is shown overleaf.
The modules used are selected in the design phase.
Conguration
Connect PC
PC with the program “Service Tool” is connected to the controller.
The controller must be switched on rst and the LED “Status” must
ash before the Service Tool programme is started.
Start Service Tool programme
For connecting and operating the "AK service tool" software,
please see the manual for the software.
The rst time the Service Tool is connected to a new version of a controller the start-up of the Service Tool will take longer than usual while
information is retrieved from the controller.
Time can be followed on the bar at the bottom of the display.
Login with user name SUPV
Select the name SUPV and key in the access code.
When the controller is supplied the SUPV access code is 123.
When you are logged into the controller an overview of it will always
appear.
In this case the overview is empty. This is because the controller has not
yet been set up.
The red alarm bell at the bottom right tells you that there is an active
alarm in the controller. In our case the alarm is due to the fact that the
time in the controller has not yet been set.
Press the orange setup button with the spanner at the bottom
of the display.
2. Select Authorization
3. Change setting for the user ‘SUPV‘
When the controller is supplied it has been set with standard authorization for dierent user interfaces. This setting should be changed and
adapted to the plant. The changes can be made now or later.
You will use this button again and again whenever you want to get to
this display.
On the left-hand side are all the functions not shown yet. There will be
more here the further into the setup we go.
Press the line Authorization to get to the user setup display.
4. Select user name and access code
5. Carry out a new login with the user name and then
access code
Mark the line with the user name SUPV.
Press the button Change
This is where you can select the supervisor for the specic system and a
corresponding access code for this person.
The controller will utilize the same language that is selected in the
service tool but only if the controller contains this language. If the
language is not contained in the controller, the settings and readings
will be shown in English.
To activate the new settings you must carry out a new login to the controller with the new user name and the relevant access code.
You will access the login display by pressing the padlock at the top left
corner of the display.
All system settings can be changed by pressing in the blue eld with the
setting and then indicating the value of the required setting.
In the rst eld you enter a name for what the controller will be controlling.
When the time is set the PC’s time can be transferred to the controller.
When the controller is connected to a network, date and time will
automatically be set by the system unit in the network. This also applies
to change-over Daylight saving.
Quick setup consists of a
number of settings that are all
based on a system with
two evaporators and one
condenser.
When the installation
type is to be congured, it
can be done in two ways:
Either one of these two (we
chose to use the lowest).
The higher of the two settings gives
a choice between a number of pre-
dened combinations, which at the
same time determine the connec-
tion points.
At the end of the manual there is
an overview of the options and
connection points.
4. Set Common functions
In our example the plant contins of two evaporators and a
condenser. We therefore select
the plant type Two evap. + one cond.
The controller can control one
condenser group, but not two.
Two groups must be controlled separately.
Here we opt to let the controller control the condenser
group. Set to Yes .
Further settings:
External main switch to Yes
Use Alarm output to High. (At ”High” the relay is only activated for
high-priority alarms).
The conguration menu in the
Service Tool has changed now. It
shows the possible settings for the
selected plant type.
In our example we select the
settings:
- Set point = 2°C
The settings are shown here in the
display.
There are several pages, one after
the other.
The black bar in this eld tells you
which of the pages is currently
displayed.
Move between the pages using the
+ and - buttons.
In our example we select:
- 4 compressors
- S4 as signal to the regulation
- Refrigerant = R404A
The settings are shown here in the
display.
If you want to know more about the dierent conguration
options, they are listed below.
The number refers to the number and picture in the column
on the left.
3 - Reference mode
Displacement of suction pressure as a function of external
signals
0: Reference = set reference + night oset + oset from
external 0-10 V signal
1: Reference = set reference + oset from P0 optimization
+ Night displacement
Set point ( -80 to +30°C)
Setting of required suction pressure in °C
Oset via Ext. Ref
Select whether a 0-10V external reference override signal
is required
Oset at max input (-100 to +100 °C)
Displacement of reference at max. Ext. Ref. signal
Oset at min input (-100 to +100 °C)
Displacement of reference at min. Ext. Ref signal
Oset lter (10 - 1800 Sec)
Filter for displacement of reference, higher value results in
slower displacement
Night select via DI
Select whether a digital input is required for activation
of night operation. Night operation can alternatively be
controlled via internal weekly schedule or from the system
manager via data communication
Night Oset (-25 to +25 K)
Displacement of the brine temperature during night
operation (set in Kelvin)
Oset via S3
The reference selection must be displaced by a signal from
S3.
(The function is only relevant when the controller's sensor
is set to S4. If it is set to S3, the oset function will lapse.)
Tref S3 oset
Set the S3 temperature where it is not to be oset.
K1 S3 oset
Set the size of the change to be made in the reference
when the S3 temperature deviates 1 degree from the setting. (-10 to 10 K)
Max reference (-50 to +80 °C)
Max. permissible brine reference
Min reference (-80 to +25 °C)
Min. permissible brine reference.
4 - Compressor application
Select the compressor application required
No. of compressors
Set number of compressors
No. of unloaders
Set number of unloader valves
Regulation sensor
Select either S3 or S4
P0 Refrigerant
Select refrigerant type
Po refrigerant factors K1, K2, K3
Only used if “Po refrigerant type” is set to custom (contact
Danfoss for information)
Injection evaporator 1 (2)
If the function is selected, injection can be coordinated
with compressor operation:
No Synchronisation
Synchronisation: Here is the signal on, if just one compressor is in operation.
VSD min speed (0.5 – 60.0 Hz)
Minimum allowed speed before stop of Variable Speed
drive (Low load condition)
In our example there are no
unloaders and hence no changes.
VSD start speed (20.0 – 60.0 Hz)
Minimum speed for start of Variable speed drive (Must be set
higher than “VSD Min. Speed Hz”)
VSD max speed (40.0 – 120.0 Hz)
Highest permissible speed for the compressor motor
VSD safety monitoring
Select this if input for monitoring of the frequency converter
is required.
Start delay rst compressor (5-600 sec.)
To ensure brine ow before startup, a delay before start of
the rst compressor can be entered.
Load shed limits
Select how many load shedding inputs are required
Load shed limit 1
Set max capacity limit for load shed input 1
Load shed limit 2
Set max capacity limit for load shed input 2
Override limit for S4 (S3)
Any load below the limit value is freely permitted. If the S4
(S3) exceeds the value, a time delay is started. If the time
delay expires, the load limit is cancelled
Override delay 1
Max. time for capacity limit, if S4 (S3) is too high
Override delay 2
Max. time for capacity limit, if S4 (S3) is too high
Advanced control settings
Select whether the advanced capacity control settings
should be visible
Kp
Amplication factor for PI regulation (0.1 – 10.0)
Min. capacity change (0 – 100 %)
Minimum change in requested capacity that will result in cut
in/out of compressors.
Initial start time (15 – 900 s)
The time after start-up where the cut-in capacity is limited to
the rst compressor step.
Unloading mode
Select whether one or two capacity controlled compressors
are allowed to be unloaded at the same time at decreasing
capacity
Press the +-button to go on to the
next page
7. Set values for safe operation
Press the +-button to go on to the
next page
In our example we select the
settings shown in the display
5 - Compressors
In this screen the capacity distribution between the compressors is dened.
Capacities that need to be set depend upon the “compressor
application” and “Step control mode” that has been selected.
Nominal capacity (0.0 – 100000.0 kW)
Set the nominal capacity for the compressor in question.
For compressors with variable speed drive the nominal
capacity must be set for the mains frequency (50/60 Hz)
Unloader
Number of unload valves for each compressor (0-3)
6 - Readout of capacity distribution
The settings are made in the earlier displays.
Main step
0 - 100%.
Unload
Readout of the capacity on every unloading
7 - Safety
Emergency cap. day
The desired cut-in capacity for daily use in the case of emergency operations resulting from error in the suction pressure
sensor/ media temperature sensor.
Emergency cap. night
The desired cut-in capacity for night operations in the case
of emergency operations resulting from error in the suction
pressure sensor/ media temperature sensor.
Sd max limit
Max. value for discharge gas temperature
10 K below the limit, the compressor capacity should be
reduced and the entire condenser capacity will be cutin.
If the limit is exceeded, the entire compressor capacity will
be cutout
- One general safety monitoring
unit for each compressor
(The remaining options could
have been selected if specic
safety controls for each
compressor had been required)
Set min. OFF-time for the compressor relay
Set min. ON-time for the compressor relay
Set how often the compressor is
allowed to start
The settings only apply to the
relay that cuts the compressor
motor in and out.
They do not apply to unloaders.
If the restrictions overlap, the
controller will use the longest
restriction time.
In our example we do use
Alarm monitoring of the S4
temperature.
3 K below the limit, the compressor capacity reduced.
If the limit is exceeded, the entire compressor capacity will
be cutout.
P0 Min limit
Minimum value for the suction pressure in °C
If the limit is reduced, the respective compressor capacity will
be cutout.
P0 min delay at start-up (0-600 sec)
Low pressure cut-out can be delayed for cut-out to be
avoided.
P0 max alarm
Issues an alarm when the delay time has expired
P0 max delay
Delay time for P0 max. alarm
S4 Min limit
Cut-out limit. If S4.1 or S4.2 measures a value lower than the
set one, the respective compressor group will cut out.
Safety restart time
Common time delay before restarting the compressor.
(Applicable to the functions: "Sd max. limit", Pc max. limit"
and "P0 min. limit and S4 min limit).
8 - Compressor safety
Frost protection
Choose whether an overall, joint DI-security inlet for all compressors is desired. If the alarm is activated, all compressors
will be disengaged.
Oil pressure etc
Dene here whether this type of protection should be connected.
For "General", there is a signal from each compressor.
9 - Minimum operation times
Congure the operation times here so "unnecessary operation" can be avoided.
Restart time is the time interval between two consecutive
starts.
10 - Safety timer
Cutout delay
The time delay resulting from drop-out of automated safety
measures and until the compressor-error is reported. This
setting is common for all safety inputs for the relevant
compressor.
Restart delay
Minimum time that a compressor should be OK after a safety
cut-out. After this interval it can start again.
11 - Misc. functions
Alarm monitoring S4
Alarm option in the case of too high and too low S4
Dierent time delays are connected
12 - Pumps
No of pumps (0, 1 or 2)
Cold pump control
Pump operation is dened here:
0: No pumps in operation
1: Only pump 1 in operation
2: Only pump 2 in operation
3: Both in operation
4: Operating time equalisation. Start before stop
5: Operating time equalisation. Stop before start
Pump cycle time
Operating time before changeover to the second pump
(1-500h)
Pump switch time
Overlapping time, where both pumps are in operation with
"start before stop" or break time with "stop before start"
(0-600 sec)
Pump alarm delay
Delay from drop out of ow switch to alarm.
Variable pump speed
Yes: Speed controlled by a 0-10 V signal.
No: Pump controlled on/o
Speed factor for pump
0.1-1: Non-linear correlation (the higher the value, the higher
the output voltage at the same compressor capacity).
Min. pump speed
Set the desired frequency. The same value must be set in the
frequency converter.
Max. pump speed
Set the desired frequency. The same value must be set in the
frequency converter.
In our example the condenser
pressure is controlled on the
basis of the outdoor temperature
(oating reference).
The settings shown here in the
display.
3 - PC reference
Control sensor
Pc: The condensing pressure PC is used for regulation
S7: Media temperature is used for regulation
Reference Mode
Choice of condenser pressure reference
Fixed setting: Used if a permanent reference is required =
“Setting”
Floating: Used if the reference is changed as a function of Sc3
the external temperature signal, the congured "Dimensioning tm K"/"Minimum tm K" and the actual cut in compressor
capacity.
Setpoint
Setting of desired condensing pressure in °C
Min. tm
Minimum average temperature dierence between Sc3 air
and Pc condensing temperature with no load.
Dimensioning tm
Dimensioning average temperature dierential between Sc3
air and Pc condensing temperature at maximum load (tm
dierence at max load, typically 8-15 K).
Min reference
Min. permitted condenser pressure reference
Max reference
Max. permitted condenser pressure reference
Heat recovery mode
Choice of method for heat recovery
No: Heat recovery not used
Thermostat: Heat recovery operated from thermostat
Digital input: Heat recovery operated from signal on a digital
input.
Heat recovery relay
Choose whether an output is required that should be activated during heat recovery.
Heat recovery ref
Reference for the condensing pressure, when heat recovery
is activated.
Heat recovery ramp down
Congure how quickly the reference for the condenser
pressure should be ramped down to normal level after heat
recovery. Congure in Kelvin per minute.
Heat recovery cutout
Temperature value where the thermostat cuts-out the heat
recovery.
Heat recovery cutin
Temperature value where the thermostat cuts-out the heat
recovery.
Used in our example are four stepcontrolled fans.
The settings shown here in the
display.
For your information the function
”Monitor fan safety” will require an
input signal from each fan.
4 - Capacity control
No of fans
Set number of fans.
Monitoring fan safety
Safety monitoring of fans. A digital input is used to monitor
each fan.
Capacity control mode
Select control mode for condenser
Step: Fans are step-connected via relay outputs
Step/speed: The fan capacity is controlled via a combination of speed control and step coupling
Speed: The fan capacity is controlled via speed control
(frequency converter)
Speed control on rst step, rest=step
Control type
Choice of control strategy
P-band: The fan capacity is regulated via P-band control.
The P band is congured as "Proportional band Xp"
PI-Control: The fan capacity is regulated by the PI controller.
Capacity curve
Choice of capacity curve type
Linear: The same amplication in the entire area
Square: Square curve shape, which gives higher amplication at higher loads.
Continued
VSD start speed
Minimum speed for start of speed control (Must be congured higher than "VSD Min. Speed %")
VSD min Speed
Minimum speed whereby speed control is cut-out (low
load).
Proportional band Xp
Proportional band for P/PI controller
Integration time Tn
Integration time for PI controller
VSD safety monit.
Choice of safety monitoring of frequency converter. A digital inlet is used for monitoring the frequency converter.
Capacity limit at night
Setting of maximum capacity limit during night operations.
Can be used to limit fan speed at night in order to limit the
noise level.
When no input is used to start a defrost
cycle, this allows use of a schedule where
the defrost startup times are specied.
The schedule is located under the daily user
interface. See page 72.
3 - Defrost functions
Defrost function
Select whether defrost control is to be used
Defrost start via DI
Select whether a DI input to start the defrost
cycle is to be used. .
If not, this allows a defrost schedule to be attached to the "daily user interface"..
Defrost stop
Select a defrost stop procedure. By time. / By S3
temperature. By S4 temperature
Defrost stop temp.
Value setting (-5 to 60)
Max. defrost time
Max. permitted defrost time Refrigeration will
always start once this time has passed.
Drip delay
Time after defrost end, where the water is dripping from the refrigeration surfaces.
Defrost outputs
Select whether an output is to be activated during defrosting..
Comp.operation during defrost
Select whether the compressors are to run during defrosting.
In our example we have no general alarm
inputs. The image is included for guidance.
One alarm function is shown.
The name of the alarm function and the alarm
text can be dened as desired.
3 - General alarm input
This function can be used to monitor all kinds of
digital signals.
The general thermostats can be used to monitor
the temperature sensors that are used, as well
as 4 extra temperature sensors. Each thermostat
has a separate outlet to control external automation.
No. of thermostats
Set the number of general thermostats.
For each thermostat adjust
• Name
• Which of the sensors is used
Actual temp.
Temperature measurement on the sensor that is
attached to the thermostat
Actual state
Actual status on the thermostat outlet
Cut out temp.
Cut-out value for the thermostat
Cut in temp.
Cut-in value for the thermostat
High alarm limit
High alarm limit
Alarm delay high
Time delay for high alarm
Alarm text high
Indicate alarm text for the high alarm
Low alarm limit
Low alarm limit
Alarm delay low
Time delay for low alarm
Alarm text low
Indicate alarm text for low alarm
3b - Pressostats
There are similar settings for up to 3 pressure
Via the +- button you can move to similar settings for the pressure control functions. (Not
used in the example)
In our example we do not use this function,
so the display has been included for your
information only.
The name of the function may be xx and
further down in the display the alarm texts
may be entered.
The values ”Min. and Max. Readout” are your
settings representing the lower and upper
values of the voltage range. 2V and 10V, for
example. (The voltage range is selected during
the I/O setup).
For each voltage input dened the controller
will reserve a relay output in the I/O setup.
It is not necessary to dene this relay if all
you require is an alarm message via the data
communication.
3 - Voltage inputs
The general volt inlet can be used to monitor
external voltage signals. Each volt inlet has a
separate outlet to control external automatic
controls.
No. of voltage inp.
Set the number of general voltage inputs,
specify 1-5:
Name
Actual value
= read-out of the measurement
Actual state
= read-out of outlet status
Min. readout
State read-out values at minimum voltage signal
Max. readout
State read-out values at maximum voltage signal
Cutout
Cut-out value for outlet
Cutin
Cut-in value for outlet
Cutout delay
Time delay for cut-out
Cut in delay
Time delay for cut-in
Limit alarm high
High alarm limit
Alarm delay high
Time delay for high alarm
Alarm text high
Set alarm text for high alarm
Limit alarm low
Low alarm limit
Alarm delay low
Time delay for low alarm
Alarm text low
Indicate alarm text for low alarm
The following displays will depend on the earlier denitions. The
displays will show which connections the earlier settings will require.
The tables are the same as shown earlier.
• Digital outputs
• Digital inputs
• Analog outputs
• Analog inputs
LoadOutputModule PointActive at
Compressor 1 (group A no. 1) DO1112ON
Compressor 2 (group B no. 1)DO2113ON
Compressor 3 (group A no.2)DO3114ON
Compressor 4 (group B no. 2)DO4115ON
Liq. Injec. evap. 1DO5116
Liq.injec. evap. 2DO6117ON
Pump 1DO7118ON
Pump 2DO8119ON
Fan 1DO1210ON
Fan 2DO2211ON
Fan 3DO3212ON
Fan 4DO4213ON
DefrostDO529ON
Fan in plant roomDO6214ON
AlarmDO7215OFF !!!
!!! The alarm is inverted so that there will be an alarm if the supply
voltage to the controller fails.
We set up the controller’s digital outputs by keying in which module
and point on this module each one of these has been connected to.
We furthermore select for each output whether the load is to be active
when the output is in pos. ON or OFF.
FunctionInputModule PointActive at
External main switchAI323Closed
Flow switch, brineAI828Open
3 - Outputs
The possible functions are
the following:
Pack 1 Comp. 1-4
Unloader 1-1, 1-2, 1-3
Pack 2 Comp. 2-4
Cold pump 1
Cold pump 2
Injec in evaporator
Defrost
Fan 1 / VSD
Fan 2 - 8
Heat recovery
Alarm
Thermostat 1 - 5
Pressostat 1 - 5
Voltage input 1 - 5
4 - Digital inputs
The possible functions are
the following:
Ext. Main switch
Night setback
Load shed 1
Load shed 2
Frost protection
All compressors:
Pack X Comp x
Oil pressure safety
Over current safety
Motor protect. safety
Disch. temp. safety
Disch. press. safety
General safety
VSD comp_. error 1-2
Flow switch (cold)
Fan 1 protection
Fan 2......8 protection
VSD Cond. protection
Heat recovery
DI Alarm 1
DI Alarm 2.....10
Defrost
Press the +-button to go on to the
next page
4. Setup On/o input functions
Press the +-button to go on to the
next page
Compressor 1 Gen. SafetyDI131Open
Compressor 2 Gen. SafetyDI232Open
Compressor 3 Gen. SafetyDI333Open
Compressor 4 Gen. SafetyDI434Open
Capacity limitationDI636Closed
We set up the controller’s digital input functions by keying in which
module and point on this module each one of these has been connected to.
We furthermore select for each output whether the function is to be
active when the output is in pos. Closed or Open.
Open has been selected here for all the safety circuits. This means that
the controller will receive signal under normal operation and register
it as a fault if the signal is interrupted.
The pump's ow switch is used here for frost protection. This means
that all compressors stop in the event of insucient ow.
The bottom setting for the pump's ow switch is set here to 0-0,
but it will give incorrect information in the daily user display.
This can be corrected by repeating the threading to an available
input, and then dening this instead of 0-0.
The controller will now make a comparison of selected functions and dene inputs and outputs. The result can be seen in
the next section where the setup is controlled.
The setup of the controller has now been locked. If you subsequently
want to make any changes in the controller’s setup, remember rst to
unlock the conguration.
The selected module and point numbers for Sc3 Air on are shown in a
red eld instead of a blue one.
This is due to the fact that this input has been set up, but that the setup
has later been changed so that the outdoor temperature sensor Sc3 is no
longer to be used. For instance by changing the Pc reference selection
for condenser A from Floating to Fixed setting.
The problem is corrected by setting Sc3 air on to module number 0 and
point number 0.
(IN THIS EXAMPLE WE RETAIN SETTINGS 2 AND 1. The wrong setting has
only been shown for your information).
Remember that the setup must be unlocked before you can change
module and point numbers.
Before the control is started we check that all inputs and outputs have
been connected as expected.
This controls requires that the setup is locked
By means of the manual control of each output it can be checked
whether the output has been correctly connected.
AUTOThe output is controlled by the controller
MAN OFFThe output is forced to pos. OFF
MAN ONThe output is forced to pos ON
Press the +-button to go on to the next page
4. Check Digital Inputs
Press the +-button to go on to the next page
Cut out the safety circuit for compressor 1.
Check that LED DI1 on the extension module (module 3) goes out.
Check that the value of the alarm for the safety monitoring of compressor 1 changes to ON.
The remaining digital inputs are checked in the same way.
3. Move on through all the individual displays for the
suction group
Before the control starts, we check that all the settings are as they should
be.
The overview display will now show one line for each of the general
functions. Behind each icon there is a number of displays with the
dierent settings. It is all these settings that have to be checked.
Change displays with the +- button. Remember the settings at
the bottom of the pages – the ones that can only be seen via
the ”Scroll bar”.
4. Safety limits
5. Go back to the overview
The last page contains safety limits and restart times.
6. Select condenser group
7. Move on through all the individual displays for the
condenser group
Before regulation is started we will set the schedule function for the
night setback of the S4 temperature.
In other cases where the controller is installed in a network with one
system unit, this setting may be made in the system unit which will then
transmit a day/night signal to the controller.
Press a weekday and set the time for the day period.
Continue with the other days.
A complete weekly sequence is shown in the display.
Turn the right-hand address switch so that the arrow will point
at 3.
The arrow of the two other address switches must point at 0.
2. Push the Service Pin
Press down the service pin and keep it down until the Service
Pin LED lights up.
The controller has to be remote-monitored via a network. In this net-
work we assign address number 3 to the controller.
The same address must not be used by more than one controller in the
same network.
Requirement to the system unit
The system unit must be a gateway type AKA 245 with software version
6.0 or higher. It is capable of handling up to 119 AK controllers.
3. Wait for answer from the system unit
Depending on the size of the network it may be up to one
minute before the controller receives an answer as to whether
it has been installed in the network.
When it has been installed the Status LED will start to ash
faster than normal (once every half second). It will continue
with this for about 10 minutes
4. Carry out new login via Service Tool
If the Service Tool was connected to the controller while you
installed it in the network, you must carry out a new login to
the controller via the Service Tool.
If there is no answer from the system unit
If the Status LED does not start ashing faster than normal, the controller has not been installed in the network. The reason for this may be
one of the following:
The controller has been assigned an address out of range
Address 0 cannot be used.
If the system unit in the network is an AKA 243B Gateway only the addresses between 1 and 10 can be used.
The selected address is already being used by another controller or
unit in the network:
The address setting must be changed to another (vacant) address.
The wiring has not been carried out correctly.
The termination has not been carried out correctly.
The data communication requirements are described in the document:
”Data communication connections to ADAP-KOOL® Refrigeration Controls” RC8AC.
Press the blue overview button with the compressor and condenser at the bottom left of the display.
2. Go to the Alarm list
Press the blue button with the alarm bell at the bottom of the
display.
3. Check active alarms
In our case, we have a series of alarms. We will tidy them up so that we
only have those that are relevant.
4. Remove cancelled alarm from the alarm list
Press the red cross to remove cancelled alarms from the alarm
list.
5. Check active alarm again
In our case an active alarm remains because the control has stopped.
This alarm must be active when control has not started. We are now
ready for the startup of control.
Please note that active plant alarms are automatically cancelled when the
main switch is in pos. OFF.
If active alarms appear when the control is started the reason for these
should be found and remedied.
AK-CH 650A can control up to 8 compressors with up to 3 unloader
valves each. The rst compressor in each group can be equipped
with speed regulation.
The calculation of the requested compressor capacity takes place
on the basis of a PI control, but the set up is carried out in the
same way as for a neutral zone controller which is divided into 5
dierent control zones as shown in below sketch.
Brine temperature
The width of some of the zones can be set via the settings “+ Zone
K”, “NZ K” and “- Zone K”.
Furthermore it is possible to adjust zone timers which is equal to
the Tn integration time for the PI controller whenever the suction
pressure is in the zone in question (please see sketch above).
By setting a zone timer to a higher value will make the PI controller
slower in this zone and by setting the zone timer lower will make
the PI controller faster in this zone.
The amplication factor Kp is adjusted as parameter ”Kp S4”
In the neutral zone the controller is only allowed to increase or
decrease the capacity by means of speed control and/or switching
of unloader valves.
In the other zones the controller is also allowed to increase/
decrease capacity by means of starting and stopping compressors.
The last compressor is only allowed to be stopped when the brine
temperature is in the “- Zone” or “- - Zone”
At start-up the refrigeration system must have time to be stable
before the PI controller takes over the control. For this purpose
at start-up of a plant a limitation is made of the capacity so that
only the rst capacity step will cutin after a set period (to be set via
"runtime rst step").
Requested capacity
The readout “Requested capacity” is the output from the PI
controller and it shows the actual requested compressor capacity
by the PI controller. The rate of change in the requested capacity
depends upon in which zone the brine temperature is and
whether the brine temperature is stable or whether it is constantly
changing.
The Integrator is looking at the deviation between the set point
and the current temperature only and increases/reduces the
requested capacity correspondingly. The amplication factor
Kp on the other hand only looks at the temporary temperature
changes.
In the “+ Zone” and “++ Zone” the controller will normally increase
the requested capacity as the temperature is above the set point.
But if the temperature is decreasing very fast the requested
capacity might decrease also in these zones.
In the “- Zone” and “-- Zone” the controller will normally decrease
the requested capacity as the temperature is below the set
point. But if the temperature is increasing very fast the requested
capacity might increase also in these zones.
Change capacity
The controller will cutin or cutout capacity based on these basic
rules:
Increase capacity:
The capacity distributor will start extra compressor capacity as
soon as the requested capacity has increased to a value, which
allows the next compressor step to start. Referring to below
example - a compressor step is added as soon as there is “Room”
for this compressor step below the requested capacity curve.
Decrease capacity:
The capacity distributor will stop compressor capacity as soon
as the requested capacity has decreased to a value, which allows
the next compressor to stop. Referring to below example - a
compressor step is stopped as soon as there is no more “Room” for
this compressor step above the requested capacity curve.
Example:
4 compressor of equal size (two in each group) - The capacity
curve will look like this
Odd number is from group 1. Equal number is from group 2
Cut-out of the last compressor stage:
Normally, the last compressor step will only be cut-out when the
required capacity is 0% and the suction pressure is at "-Zone" or in
"—Zone"
The regulating sensor can be set at S4 or S3.
By setting the regulating sensor to S4, the S3 temperature can be
included in the regulation with an oset function.
(Frost protection must be performed by the sensors S4.1 and
S4.2).
The Reference
The reference for the regulation can be dened in 2 ways:
Either
Ref = P0 setting + P0 optimisation + Night displacement
or
Ref = setting + night displacement + Ext. Ref + S3 oset
Setting
A basic value for the brine temperature is set.
P0 optimization
This function displaces the reference so that regulation will not
take place with a lower brine temperature than required.
The function cooperates with controllers on the individual
refrigeration appliances and network system manager. The system
manager obtains data from the individual appliance sections and
adapts the brine temperature to the optimum energy level. The
function is described in the manual for the system manager.
With this function you can read which appliance is most heavily
loaded at the moment as well as the displacement allowed for the
brine temperature reference.
Night displacement
The function is used to change the suction pressure reference for
night time operation as an energy saving function.
With this function the reference can be displaced by up to 25 K
in positive or negative direction. (When you displace to a higher
temperature, a positive value is set).
Displacement can be activated in three ways:
• Signal on an input
• From a system managers override function
• Internal time schedule
The “night displacement” function can not be used when
regulation with the override function “P0-optimisation” is
performed. (Here the override function will itself adapt the brine
temperature to the max. permissible).
The function can be used if a short change in the brine temperature (e.g. up to 15 min.) is needed. Here the P0 optimisation will
not be able to compensate for the modication.
Ext. Ref. - Override with a 0 - 10 V signal
When a voltage signal is connected to the controller the reference
can be displaced. In the setup it is dened how big a displacement
is to take place at max. signal (10 V).
S3 oset
(Only if the regulating sensor is set to S4.)
With this function it is possible to delay the reference, based on a
measured S3 temperature.
The sensor can be located, for example, in the return temperature
of the brine or in the store premises. This allows a reference to be
achieved that is adjusted to the current load. In the case of an error on the S3 sensor, the contribution to the reference is omitted.
The oset is calculated on the basis of the following expression:
S3 oset = K1 (S3 temp. – TrefS3Oset.),
where K1 is a multiplication factor and "TrefS3Oset" is the S3
temperature that does not give reference oset.
For example:
- The reference temperature of the brine is to be oset based on
the shop temperature
- At 18°C no reference oset is required, i.e. S3 ref = 18
- For each increase of 1°C in shop temperature, a reduction in
reference of 0.5K is required, i.e. K1 = -0.5
- The contribution to the reference therefore becomes: -0.5 x ("S3
temp" - 18)
Limitation of reference
To safeguard yourself against a too high or too low regulation
reference, a limitation of the reference must be set.
S4 (S3) ref
Max.
Min.
Forced operation of the compressor capacity
A forced operation of the capacity can be carried out which
disregards the normal regulation.
Depending on the selected form of forced operation, the safety
functions will be cancelled.
Forced operation via overload of requested capacity
The control is set to manual and the desired capacity is set in % of
the possible compressor capacity.
Forced operation via overload of digital outlets
The individual outputs can be set to MAN ON or MAN OFF in the
software. The control function disregards this but an alarm is sent
out that the outlet is being overridden.
Forced operation via change-over switches
If the forced operation is done with the switch-over on the front of
an expansion model, this is not registered by the control function
and no alarm is sounded. The controller continues to run and
couples with the other relays.
All compressors should be of the same type and size.
The capacity is connected in alternating fashion between the two
groups:
1: First in group A
2: First in group B
3: Second in group A
4: Second in group B
etc.
The compressor cuts-in and cuts-out in accordance with the "First
In First Out" principle (FIFO) to equalise operating hours between
the compressors.
Speed-regulated compressors will always be cut in rst, and the
variable capacity is used to ll capacity gaps between the subsequent steps.
When there is one compressor with relief valves, it will always cut
in as the rst.
Timer restrictions and safety cut outs
If a compressor is prevented from starting because it is “hanging”
on the restart timer or is safety cut out, this step is replaced by
another compressor.
The controller is able to control power packs with up to 8
compressors of various types:
- Two speed controlled compressors
- Capacity controlled reciprocating compressors with up to 3
unloader valves
- Single step compressors – reciprocating or scroll
The chart below shows the compressor combination which the
controller is capable of controlling.
Group AGroup BDescription
*1) The one-step compressors must be the same size.
*2) For compressors with unload valves, it is generally true that they must have the
same size, the same number of unload valves (max 3) and the same sized main
steps. If compressors with unload valves are combined with one-step compres-
sors, all compressors should be the same size.
(The rst two or all are with unload valves)
*3) Speed-regulated compressors can have dierent sizes in relation to subsequent
compressors. Speed-regulated compressors must have the same frequency range.
One-step compressors. *1
A compressor with an unload
valve, combined with one-step
compressors. *2
All compressors with unload
valves. *2
A speed-regulated compressor combined with one-step
compressors. *1 and *3
Operating time equalisation
The operating hour equalizing is carried out between compressors
of the same type with the same total capacity.
-At the dierent startups the compressor with the lowest number
of operating hours will be started rst.
- At the dierent stops the compressor with the highest number of
operating hours will be stopped rst.
- For compressors with several steps, the operating time equalizing
is carried out between the compressors’ main steps.
"Unloader control mode" determines how the capacity distributor
should handle these compressors.
Unloader control mode = 1
Here the capacity distributor allows only one of the compressors
to be unloaded at a time. The advantage of this setting is that it
avoids operating with several compressors unloaded, which is not
energy ecient.
For example:
Two capacity-regulated compressors of 20 kW, each with 2 unload
valves, cyclical coupling pattern.
• For decreasing capacity, the compressor with the most operating
hours is unloaded (C1).
• When C1 is completely unloaded, it is cut-out before compressor
C2 is unloaded.
Speed control compressors:
The controller is able to use speed control on the st compressor
in each group. The variable part of the speed controlled
compressor is used to ll in capacity gaps of the following
compressor steps.
General regarding handling:
An output is connected to the frequency converter’s ON/OFF
input and at the same time an analog output ”AO” is connected to
the frequency converter’s analog input.
The ON/OFF signal will start and stop the frequency converter and
the analog signal will indicate the speed.
It is only the compressors dened as compressor 1 and 2 that can
be speed controlled.
Unloader control mode = 2
Here the capacity distributor allows two compressors to be unloaded while capacity is decreasing.
The advantage of this setting is it reduces the number of compressor start/stops.
For example:
Two capacity-regulated compressors of 20 kW, each with 2 unload
valves, cyclical coupling pattern.
• For decreasing capacity, the compressor with the most operating
hours is unloaded (C1).
• When C1 is completely unloaded, compressor C2 with one-step
is unloaded before C1 is cut out.
When the step is in operation it will consist of a xed capacity
and a variable capacity. The xed capacity will be the one that
corresponding to the mentioned min. speed and the variable
one will lie between the min. and max. speed. To obtain the
best regulation the variable capacity must be bigger than the
subsequent capacity steps it has to cover during the regulation.
If there are major short-term variations in the plant’s capacity
requirement it will increase the demand for variable capacity.
This is how you cut the step in and out:
Cutin
The speed-controlled compressors will always be the rst to start
and the last to stop. The frequency converter will be started when
a capacity requirement corresponding to the mentioned ”Start
speed” arises (the relay output for compressor 1 changes to ON
and the analog output is supplied with a voltage corresponding
to this speed). It is now up to the frequency converter to bring the
speed up to ”Start speed”.
The capacity step will now be cut in and the required capacity
determined by the controller.
The start speed always ought to be set so high that a fast
lubrication of the compressor is obtained during the start.
Controlling – increasing capacity
If the need for capacity becomes larger than “Max. Speed” then
the subsequent compressor step will be cut-in. At the same time,
the speed on the capacity step will be reduced so the capacity
is reduced with a size that corresponds to exactly the cut-in
compressor step. Thereby a completely "frictionless" transition is
achieved without capacity holes (refer also to sketch).
1 1+2 1+2 1+2
+3 +3+4
As mentioned before the variable part of the speed capacity
should be bigger than the capacity of the following one-step
compressor steps in order to achieve a capacity curve without
“holes”.
The precondition for using this regulating method is that both
compressors have the same frequency range.
Controlling – decreasing capacity
If the capacity requirement becomes less than “Min. speed” then
the subsequent compressor step will be cut-out. At the same
time, the speed on the capacity step is increased so the capacity
is increased with a size that corresponds to exactly the cut-out
compressor step.
Cut-out
The capacity step will be cut-out when the compressor has
reached “Min. Speed” and the requested capacity has dropped to
1%.
Timer restriction on the speed controlled compressors
If a speed controlled compressor is not allowed to start due to a
timer restriction, no other compressor is allowed to start. When
the timer restriction has expired the speed controlled compressor
will start.
Safety cutout on speed controlled compressors
If a speed controlled compressor is cutout on safety other
compressors are allowed to start. As soon as the speed controlled
compressor is ready to start it will be the rst compressor to start.
To protect the compressor against frequent restarts three time
delays can be put in.
- A minimum time to run from a compressor’s startup and until it
may be restarted.
- A minimum time (ON-time) for the compressor to operate before
it may be stopped again.
- A minimum OFF time to run from a compressor stops and until it
may be restarted
When unloaders are cut in and out, the time delays will not be
used.
Overriding of load shedding:
To avoid load shedding leading to temperature problems for the
chilled products, an overriding function is tted.
A overriding limit is set for the regulation temperature as well as a
delay time for each digital inlet.
If the temperature during load shedding exceeds the set overriding limit and the attached delay times for the two digital inlets
expire then load shedding overrides the signals so that the compressor capacity can be increased until the temperature is again
under the normal reference value. The load shedding can then be
activated again.
Timer
The operating time of a compressor motor is registered continuously. You can read out:
- operating time for the previous 24-hour period
- total operating time since the timer was last set to zero-set.
Coupling counter
The number of relay cutins and cutouts is registered continuously.
The number of starts can be read out here:
- Number during the previous 24-hour period
- Total number since the counter was last set to zero-set.
Load shedding
On some installations there is the desire to limit the cut-in compressor capacity so that one can limit the total electrical load in
the store for periods.
There are 1 or 2 digital inlets available for this purpose.
For each digital inlet a limit value is attached for the maximum
allowable cut-in compressor capacity so that one can carry out the
capacity limitation in 2 steps.
Alarm:
When a load shedding digital inlet is activated, an alarm will be
activated to inform that the normal control has been bypassed.
This alarm can however be suppressed if so desired.
Injection in evaporators
The controller can emit a start/stop signal for liquid injection in
the evaporator of each group.
The function can be connected with compressor operation so that
the uid injection is synchronised with compressor start/stop
Here the injection signal comes ON when the rst compressor is
started and goes OFF when the last compressor cuts out.
When a digital inlet is activated, the maximum allowable compressor capacity is limited to the set limit. This means that if the actual
compressor capacity upon activation of the digital inlet is higher
than this limit, then so much compressor capacity is cut-out that
it will then be on or under the set maximum limit value for this
digital inlet.
When both load-shedding signals are active, the lowest limit value
for the capacity will be the one that is applicable.
The controller can perform a central defrost of the entire cold
brine circuit.
When a defrost is commenced, the compressors stop (selectable),
and the pumps continue to circulate the cold brine.
Defrost can be stopped by time, or when the cold brine has
reached a set temperature.
After defrost has been stopped, it is possible to specify a drip
delay time before the compressors restart.
There is the option for the defrost function to use an output for
activation of external automatic controls.
Defrost start
Defrost can be started in several ways.
- Manual defrost
After activation, the setting automatically returns to OFF once
defrost has been completed.
- External contact signal
Defrost start is performed with a signal on a DI input.
The signal must be a pulse signal of at least 3 seconds' duration.
Defrost starts when the signal changes from OFF to ON.
- Internal schedule
Defrost is started via a weekly program set in the controller.
The times are related to the controller's clock function. Up to 8
defrosts per day can be set.
- Network signal
Defrost can be started via a signal from the network (system
manager).
Start after defrost
It is possible to input a drip delay after defrost, so that any water
droplets can drip o the evaporators before refrigeration is
restarted. This ensures that the evaporator is as free as possible of
water on refrigeration restart.
Defrost output
It is possible to dene a defrost output to control external automatic controls during defrost. The output will be activated during
defrost itself, but deactivated during any drip delay that might be
input.
Compressors
It is possible to dene whether normal compressor capacity control is to be active during defrost or not.
Pumps
Pump control will always be active during defrost.
Status
It is possible to read o the following status values for defrost:
- Defrost status (ON/OFF)
- Current temp. at defrosting sensor
- Duration of defrost in progress or last completed defrost
- Average duration of the last 10 defrosts.
Defrost stop
The following types of defrost stop can be selected:
Stop by temperature with time as security
Here the temperature of the cold brine is measured. Once the
temperature is equal to the set stop temperature, defrost is
stopped.
Stopping defrost by S4 or S3 temperature may be selected.
If the defrost time exceeds the set max. defrost time, defrost is
stopped. This happens even if the temperature for defrost stop
has not been reached. At the same time as defrost is stopped, the
alarm message "Defrost time has been exceeded" is output. The
alarm is automatically acknowledged after 5 min.
Stop by time
Here a permanent defrost time is set. Once this time has elapsed,
defrost is stopped.
Manual stop
A defrost in progress can be stopped manually by activating
the "Stop defrost" function.
The controller can monitor the status of each compressor’s safety
circuit. The signal is taken directly from the safety circuit and
connected to an input.
(The safety circuit must stop the compressor without involving the
controller).
If the safety circuit is cut out the controller will cut out all
output relays for the compressor in question and give an alarm.
Regulation will continue with the other compressors.
General safety circuit
If a low-pressure switch is placed in the
safety circuit it must be placed at the end of
the circuit. It must not cut out the DI signals.
(There is a risk that the regulation will become locked and that it will not start again).
This also applies to the example below.
If an alarm is needed which also monitors
the low-pressure thermostat, a “general
alarm” can be dened (an alarm that does
not aect the control).
See the following section “General monitoring functions”.
Extended safety circuit
Instead of a general monitoring of the safety circuit this monitoring function
can be extended. In this way a detailed alarm message is issued which tells you
which part of the safety circuit has dropped out.
The sequence of the safety circuit must be established as shown, but not all of
them need necessarily be used.
Oil pressure cutout
Overload current cut-out
Motor temperature cutout
Discharge temp. cutout
Output pressure cut-out
General protection
Common safety circuit- Frost protection with ow switch
A common safety signal can also be received from the whole suction group. All
compressors will be cut out when the safety signal cuts out.
Time delays with safety cut-out:
In connection with safety monitoring of a compressor it is possible
to dene two delay times:
Cut-out delay time: Delay time from alarm signal from the
safety circuit until the compressor outlet cuts out (note that the
delay time is common to all security inlets for the compressor
concerned)
Safety re-start time: The minimum time a compressor must be OK
after a safety cut-out until it may start again.
Monitoring of max. discharge gas temperature (Sd1, Sd2)
The function promptly cuts out all compressor steps in the group
if the discharge temperature becomes higher than permitted. A
message alert. The cutout limit is common for both groups and
can be dened in the range from 0 to +195°C.
The alarm is cancelled and renewed cutin of compressor steps is
permitted when the delay time prior to restart has been passed.
(see later)
Monitoring of min. suction pressure (P01, P02)
The function promptly cuts out all compressor steps in the group
if the suction pressure becomes lower than the permitted value.
The cutout limit is common for both groups and can be dened in
the range from -120 to +30°C.
At cutout the the alarm function is activated:
The alarm is cancelled and renewed cutin of compressor steps is
permitted when the following conditions are met:
- the pressure (temperature) is above the cutout limit
- the time delay has elapsed (see later).
(On startup of the rst compressor it is possible to delay the function so that cut-out can be avoided.)
Alarm at max. suction pressure
An alarm is issued if the value is exceeded, but the regulation
continues.
Monitoring of max. condensing pressure (Pc,Pc1, Pc2)
(Pc is used for a common condenser; if separate condensers are
used for each group, Pc1 and Pc2 are used.)
The function cuts out all compressor steps in the group if the
condensing pressure becomes higher than permitted. The cutout
limit is common for both groups and can be dened in the range
from –30 to +100°C.
The condensing pressure is measured with pressure transmitter
Pc, Pc1, Pc2.
At common condensor (Pc) the function takes eect at a
value which is 3 K below the set value. At this time 33% of the
compressor capacity is cut out (but min. one step). This is repeated
every 30 seconds. The alarm function is activated.
If the temperature (pressure) rises to the set limit value, the
following will happen:
- all compressor steps will immediately be cut out
- the condenser capacity will remain cut in
The alarm will be cancelled and renewed cutin of compressor
steps is permitted when the following conditions are met:
- the temperature (pressure) falls to 3 K below the limit value
Common condenser (Pc)
If the limit value is exceeded, all compressors will cut out. An
alarm will be issued.
Time delay
There is a joint time delay for “Monitoring of max. discharge gas
temperature” and “Min. suction pressure” and monitoring of max.
condensing pressure Pc.
After a cutout, regulation cannot be recommenced until the time
delay has been passed.
Frost protection
The temperature of the evaporator are measured by sensors S4.1
and S4.2.
Common limit value "S4 min. Limit" has to be set.
If measured lower temperatures, all compressors in the group
stopped immediately. The pump operation continues.
Re-engagement of the compressors is not permitted as long as
the temperature is below the value limit.
Startup procedure
The controller contains functions that ensure the proper interaction of pumps, compressors and injection on startup.
Pumps
On startup, the pumps must accelerate a large brine mass to normal ow rate before the compressors are allowed to start.
In the controller there is an adjustable delay time, "Comp. Wait s",
which must expire before the rst compressor can start.
Capacity limit
If too much compressor capacity is connected in the startup
situation, there is a risk that the compressors will drop out at low
pressure.
To prevent this situation, a capacity limit is input on startup of
the system, so only the rst capacity step is engaged in a set time
period (set via "operation time rst step").
S4 Alarm thermostat
The function is used to emit an alarm if the S4 brine temperature
becomes critical.
Alarm limits and delay times can be set for high and low temperature.
An alarm is emitted if the set limit is exceeded, but only after the
delay time has expired.
There are no alarms when refrigeration has been stopped due to
the main switch being set to O.
Alarm limits
The alarm limits for high and low S4 temperature are set as absolute values in °C.
The alarm limits are not aected during night operation or on
external reference displacement via a voltage signal.
Time delays
Three time delays are set:
• At too low a temperature
• At too high a temperature during normal control
• At too high a temperature during pull-down
- After activation of an internal or external main switch
- During defrosting
- After a power failure
The time delay during pull-down applies until the S4 temperature
drops below the upper alarm limit
S4 status information
To be able to assess how well the system is operating, the following can be read:
• Min, Max and average S4 temperature for the last 24 hours
• Operation time outside alarm limits within the last 24 hours, as a
percentage
Example
Delay on P0 min cut-out
As further protection against cut-out at low pressure during startup, it is possible to delay the "P0 Min" cut-out.
The delay time can be set via "P0 Min. delay".
Curve 1: Pull-down phase
(1): The time delay is passed. The alarm becomes active.
Curve 2: Normal control where the temperature becomes too high
(2): The time delay is passed. The alarm becomes active.
Curve 3: The temperature becomes too low
(3): The time delay is passed. The alarm becomes active.
The controller can control and monitor one or two pumps that
circulate the brine.
If two pumps are used, and operating time equalisation is selected, the controller can also perform a changeover between the
two pumps if operating alarms occur.
Activity in the case of operating alarm
Pump selection is performed using the following setting:
0: Both pumps are stopped
1: Pump 1 is started up
2: Pump 2 is started up
3: Both pumps are started up
4: Automatic changeover between the pumps is permitted. Start
before stop.
5: Automatic changeover between the pumps is permitted. Stop
before start.
(This function is used when both pumps are controlled in shifts by
the same frequency converter.)
Automatic changeover between the pumps (only for setting = 4
and 5)
Start before stop
case where there is no ow.
Depending on whether pump changeover neutralises the alarm
situation or not, the following occurs:
1) Pump changeover neutralises the alarm situation before the
alarm delay expires.
If pump changeover neutralises the alarm situation, the nonfaulty pump, now in operation, will run until the normal cycle
time has expired. After that, there is changeover again to the
"faulty pump", as it is assumed to have been repaired. At the
same time, the alarm situation is reset (the alarm is acknowledged).
If the faulty pump has not been repaired, this will still trigger
an alarm and still result in changeover to the pump that is not
faulty. This is repeated until conditions are returned to normal.
2) Pump changeover does not neutralise the alarm situation
before the alarm delay expires.
If the alarm, on the other hand, is active after pump changeover,
the controller will also emit an alarm for the second pump. At
the same time, both pump outputs are activated in an attempt
to create enough ow for the alarm situation to be neutralised.
From now on, the controller will have both pump outputs
activated until the normal cycle time has expired, after which
the alarm situation is reset and pump changeover to one pump
is performed again.
Separate alarm priorities can be set for drop out of one pump and
for drop out of both pumps. See the Alarms and Messages section.
Stop before start
Using this setting there can be alternation between the two
pumps so that a type of operating time equalisation is achieved.
The period between the pump changeovers can be set as "PumpCycle". On changeover to the second pump, the rst one will
remain in operation for the "PumpDel" time. It will then stop.
At stop before start "PumpDel" will be the break time for changeover.
Pump monitoring
The controller monitors pump operation via the "Flowswitch"
safety input. The signal can originate, for instance, from a pressure
dierence pressure switch or a ow switch.
Here too, set an alarm delay time that applies during startup and
on pump changeover.
The delay time is to ensure that on startup/pump changeover, no
error is signalled for a pump before brine ow has been established.
If a ow switch is used to stop the compressors, it must be connected
to the compressors' "frost protection" safety function.
The special case of operating time equalisation
If the pumps are running with automatic operating time equalisation, the controller can perform a changeover of the pumps in a
Alarm handling
Pump alarms are suppressed/acknowledged when normal pump
changeover is performed after the cycle time has expired.
Pump alarms can also be suppressed by setting pump selection
to the "faulty" pump - if the ow switch is OK, the alarm will be
acknowledged/suppressed as a result.
Variable pump speed
The controller can supply a 0-10 V signal, which indicates the
desired speed of the pump. The signal is connected to a frequency
converter.
Speed factor
The desired characteristic is dened by a factor that the output
signal must have in relation to the cut-in compressor capacity. The
relationship is linear at a factor = 0.
Cut in
compressor capacity
Min. and Max. frequency to be set for both the controller and the
frequency converter.
The controller can control a condenser that is common to the two
suction groups. If there is a condenser for each suction group, the
condensers must be controlled by another device.
Capacity control of the condenser can be accomplished via step
regulation or speed control of the fans.
• Step regulation
The controller can control up to 8 condenser steps that are cut in
and out sequentially.
• Speed control
The analog output voltage is connected to a speed control. All
fans will now be controlled from 0 to max. capacity. If an ON/
OFF signal is required it can be obtained from a relay output.
Regulation can be carried out based on one of the following
principles:
- all fans operate at the same speed
- Only the necessary number of fans is cut in.
- Combination with one fan speed regulated and the rest step
regulated
Capacity control of condenser
The cut-in condenser capacity is controlled by the condenser pressure’s actual value and depends on whether the pressure is rising
or falling. Regulation is performed by a PI controller which may
however be changed into a P controller if the design of the plant
necessitates this.
PI regulation
The controller cuts in capacity in such a way that the deviation
between the actual condensing pressure and the reference value
becomes as small as possible.
P regulation
The controller cuts in capacity that depends on the deviation
between the actual condensing pressure and the reference value.
The proportional band Xp indicates the deviation at 100%
condenser capacity.
This means that the capacity controller requires more amplication at high capacities than at low capacities. Consequently, the
capacity controller for condenser regulation functions with an
arc-shaped capacity curve so that amplication is optimal at both
high and low capacities.
On some units, compensation is already made for the "problem"
described above, by binary connection of the condenser fans: i.e.
a few fans are connected at low capacity and many fans at high
capacity, for example 1-2-4-8 etc. In this case, the non-linear amplication is already compensated for, and there is no need for an
arc-shaped capacity curve.
It is therefore possible to choose on the controller whether you
require an arc-shaped or a linear capacity curve to manage the
condenser capacity.
Capacity curve = Linear / Power
Capacity curve = Power Capacity curve = Linear
Regulating sensor selection
The capacity distributor can either regulate from the condenser
pressure PC or from the average temperature S7.
Cap. Ctrl sensor = Pc /S7
If the regulation sensor is selected for media temperature S7, then
Pc is still used as the safety function for high condenser pressure
and will therefore ensure cut-out of the compressor capacity when
condenser pressure is too high.
Handling sensor errors:
Cap. Ctrl. Sensor = Pc
If Pc is used as the regulation sensor, an error in the signal will
result in a cut-in of 100% condenser capacity, but the compressor
regulation will remain normal.
Cap Ctrl. Sensor = S7
If S7 is used as the regulation sensor, an error in this sensor will
result in further regulation that follows the Pc signal, but in accordance with a reference that is 5K over the actual reference. If there is
an error on both S7 and Pc, 100% condenser capacity cuts-in, but
the compressor regulation remains normal.
Capacity curve
On air-cooled condensers, the rst capacity step will always give
comparatively more capacity than the subsequent capacity steps.
The increase in capacity produced by each extra step decreases
gradually as more and more steps are cut in.
The reference for the regulation can be dened in two ways. Either
as a xed reference or as a reference that varies according to the
outdoor temperature.
Fixed reference
The reference for the condensing pressure is set in °C.
Floating reference
This function allows the condensing pressure’s reference value to
vary according to the outdoor temperature within a dened area.
PI regulation
The reference is based on:
- the outdoor temperature measured with Sc3 sensor
- The minimum temperature dierence between the air
temperature and the condensing temperature at 0% compressor
capacity.
- the condenser’s dimensioned temperature dierence between
the air temperature and the condensing temperature at 100%
compressor capacity (Dim tmK)
- how large a part of the compressor capacity has been cut in.
Pc ref
DI
2. Use of a thermostat for the function.
This function can be used with advantage where the heat
recovery is used to warm up a water tank. A temperature sensor is used to activate/deactivate the heat recovery function.
When the temperature sensor becomes lower than the set cut
in limit, the heat recovery function is activated and the reference for the condenser temperature will be raised to a set value
and simultaneously the chosen relay outlet is used to activate
a solenoid valve which leads the warm gas through the heat
exchanger in the water tank. When the temperature in the tank
has reached the set value, the heat recovery is cut-out again.
In both cases it applies that when the heat recovery function is
de-activated, the reference for the condensing temperature will
then decline slowly in accordance with the set rate in Kelvin/
minute.
The minimum temperature dierence (min tm) at low load should
be set at approximately 6 K as this will eliminate the risk that all
fans will be running when no compressors are running.
Set the dimensioned dierence (dim tm) at max. load (e.g. 15 K).
The controller will now contribute with a value to the reference
which depends on how large a part of the compressor capacity
has been cut in.
P-regultion
With P regulation the reference will be three degrees above the
measured outdoor temperature. The proportional band Xp indicates the deviation with 100% condenser capacity.
Heat recovery function
The heat recovery function can be used on the installation
when you want to make use of warm gas for heating purposes.
When the function is activated the reference for the condenser
temperature will be raised to a set value and the attached relay
outlet is used to activate a solenoid valve.
The function can be activated in two ways:
Limitation of the reference
To safeguard yourself against a too high or too low regulation
reference, a limitation of the reference must be set.
PcRef
Max
Min
Forced operation of condenser capacity
Forced operation of the capacity can be arranged where the normal regulation is ignored.
The safety functions are cancelled during forced operation.
Forced operation via setting
The regulation is set to Manual.
The capacity is set in percent of the regulated capacity.
Forced operation of relays
If the forced operation is carried out with the switches at the
front of an extension module, the safety function will register
any exceeding of values and transmit alarms, if required, but the
controller cannot cut the relays in or out in this situation.
1. A digital input signal is received
In this instance, the heat recovery function is activated via
an external signal from, for example a building management
system. When the function is activated the reference for the
condenser temperature will be raised to a set value and the
attached relay outlet is used to activate a solenoid valve.
Cutins and cutouts are carried out sequentially. The last cut-in unit
will be cut out rst.
Speed regulation
When an analog output is used the fans can be speed regulated,
e.g. with a frequency converter type AKD.
Speed regulation + step regulation
Start
Min.
The controller starts the frequency converter and the rst fan
when the capacity requirement corresponds to the set starting
speed.
The controller cuts in several fans step by step as the capacity
requirement grows and then adapts the speed to the new
situation.
The controller cuts out fans when the capacity requirement
becomes lower than the set minimum speed.
Joint speed regulation
The analog output voltage is connected to the speed regulation.
All fans will now be regulated from 0 to max. capacity. If an ON/
OFF signal is required for the frequency converter, so that the fans
can be stopped completely, a relay output can be dened.
Start
Min.
The controller starts the frequency converter when the capacity
requirement corresponds to the set starting speed. The controller
stops the frequency converter when the capacity requirement
becomes lower than the set minimum speed.
In the conguration of the controller’s outputs it will be the output “FanA1”” that will start and stop
the frequency converter.
Speed regulation of rst fan + step regulation of the rest
The controller starts the frequency converter and increases the
speed of the rst fan.
If additional capacity is required, the next fan cuts in at the same
time as the rst fan switches to minimum speed. From here, the
rst fan can increase speed again, etc.
The function is used to reduce the noise from the fans to a
minimum. It is primarily used in conjunction with a speed control,
but it will also be active when steps are cut in and out.
The setting is arranged as a percentage of the max. capacity.
The limitation will be disregarded when safety functions Sd max.
and Pc max. take eect.
Condenser couplings
Coupling of condenser steps
There are no time delays in connection with cutin and cutout of
condenser steps beyond the time delay inherent in the PI/Pregulation.
Timer
The operating time of a fan motor is registered continuously. You
can read out:
- operating time for the previous 24-hour period
- total operating time since the timer was last set to zero-set.
Safety functions for condenser
Signal from fan and frequency converter’s safety controls
The controller can receive signals on the status of each individual
condenser step’s safety circuit.
The signal is obtained directly from the safety circuit and
connected to a “DI” input.
If the safety circuit is cut out the controller will give alarm.
Regulation continues with the remaining steps.
The ancillary relay outlet is not cut-out. The reason for this is that
the fan are often connected in pairs but with one safety circuit.
With fault on the one fan, the other will continue to operate.
Coupling counter
The number of couplings is registered continuously. Here the
number of starts can be read out:
- number during the previous 24-hour period
- total number since the counter was last set to zero-set.
If each suction circuit has its own condenser, each condenser must
be controlled separately by its own separate capacity controller,
e.g. an AK-PC 530.
Example
If the condenser side requires a complete control of a dry cooler
circuit, AK-CH 650A can be combined with a dry cooler control,
type AK-PC 420.
General alarm inputs (10 units)
An input can be used for monitoring an external signal.
The individual signal can be adapted to the relevant use as it is
possible to give the alarm function a name and to indicate your
own alarm text.
A time delay can be set for the alarm.
General thermostat functions (5 units)
The function may freely be used for alarm monitoring of the plant
temperatures or for ON/OFF thermostat control. An example could
be thermostat control of the fan in the compressor compartment.
The thermostat can either use one of the sensors used by the
regulation (Ss_, Sd_, Sc3, S3, S4_, S7, Shrec) or an independent
sensor (Saux1, Saux2, Saux3, Saux4).
Cutin and cutout limits are set for the thermostat. Coupling
of the thermostat’s output will be based on the actual sensor
temperature. Alarm limits can be set for low and high temperature,
respectively, including separate alarm delays.
The individual thermostat function can be adapted to the relevant
application as it is possible to give the thermostat a name and to
indicate alarm texts.
General voltage input with ancillary relay (5 units)
5 general voltage inputs are accessible for monitoring of
various voltage measurements of the installation. Examples
are monitoring of a leak detector, moisture measurement
measurement and level signal - all with ancillary alarm functions.
The voltage inputs can be used to monitor standard voltage
signals (0-5V, 1-5V, 2-10V or 0-10V). If required, one can also use
0-20mA or 4-20mA if external resistance is placed at the inlet to
adjust the signal to the voltage. A relay outlet can be attached to
the monitoring so that one can control external units.
For each inlet, the following can be set/read out:
- Freely denable name
- Selection of signal type (0-5V, 1-5V, 2-10V, or 0-10V)
- Scaling of read-out so it corresponds to measuring unit
- High and low alarm limit including delay times
- Freely denable alarm text
- Attach a relay output with cut in and cut-out limits including
delay times
General pressure control functions (5 units)
The function may freely be used for alarm monitoring of plant
pressure or for ON/OFF pressure control regulation.
The pressure control can either use one of the sensors used by
the control function (Po_, Pc_) or an independent sensor (Paux1,
Paux2, Paux3).
Cutin and cutout limits are set for the pressure control. Coupling of
the pressure control’s output will be based on the actual pressure.
Alarm limits can be set for low and high pressure, respectively,
including separate alarm delays.
The individual pressure control function can be adapted to the
relevant application as it is possible to give the pressure control a
name and indicate alarm texts.
The main switch is used to stop and start the controlling function.
The switch-over has 2 positions:
- Normal controlling state (Setting = ON)
- Control stopped. (Setting = OFF)
In addition, one can also choose to use a digital input as an
external main switch.
If the switch-over or the external main switch is set at OFF, all the
control’s functions are inactive and an alarm is generated to draw
attention to this – all other alarms cease.
Refrigerant
Before regulation can be commenced, the refrigerant must be
dened.
You can select one of the following refrigerants:
1 R12 11 R11421 R407A31 R422A
2 R22 12 R142b22 R407B32 R413A
3 R134a 13 User dened23 R410A33 R422D
4 R502 14 R3224 R17034 R427A
5 R717 15 R22725 R29035 R438A
6 R13 16 R401A26 R60036 R513A
7 R13b1 17 R50727 R600a37 R407F
8 R23 18 R402A28 R744
9 R50019 R404A29 R1270
10 R50320 R407C30 R417A
The refrigerant can only be changed if the “Main switch” is set at
“stopped control”.
Warning: Incorrect selction of refrigerant can cause damage to the
compressor.
Sensor failure
If lack of signal from one of the connected temperature sensors or
pressure transmitters is registered an alarm will be given.
• When there is a S4 and P0 error regulation will continue with xx%
cut-in capacity during day operation and xx% cut-in capacity
during night operation – but minimum one step. (The values
can be set).
• In the case of an S3 or S4 error, control continues by emergency
cooling in which values from the other sensors are used.
• When there is a Pc error all compressors will be cut out.
• In the event of a Pc1 or Pc2 error, the appertaining compressor
group is cut out.
• When there is an error on the Sd sensor the safety monitoring of
the discharge gas temperature will be discontinued.
• When there is an error on the Ss sensor the monitoring of the
superheat on the suction line will be discontinued.
• When there is an error on the outdoor temperature sensor Sc3
the regulation with variable condensing pressure reference
cannot be carried out. Instead you use the PC ref. min. value as
reference.
• S7 error: See page 90.
NB: An incorrect sensor must be in order for 10 minutes before the
sensor alarm deactivates.
Sensor calibration:
The input signal from all connected sensors can be corrected. A
correction will only be necessary if the sensor cable is long and
has a small cross-sectional area. All displays and functions will
reect the corrected value.
Clock function
The controller contains a clock function.
The clock function is used only to change between day/night.
The year, month, date, hour and minutes must be set.
Note: If the controller is not equipped with a RTC module
(AK-OB 101A) the clock must be reset after each mains voltage
outage.
If the controller is connected to an installation with an AKAgateway or an AK system manager, this will automatically reset
the clock function.
Alarms and messages
In connection with the controller’s functions, there are a number
of alarms and messages that become visible in cases of fault or
erroneous operation.
Alarm history:
The controller contains an alarm history (log) that contains all
active alarms as well as the last 40 historical alarms. In the alarm
history you can see when the alarm began and when it stopped.
In addition, one can see the priority of each alarm as well as when
the alarm has been acknowledged and by which user.
Alarm priority:
Dierentiation is made between important and not-so-important
information. The importance – or priority – is set for some alarms
whilst others can be changed voluntarily (this change can only
be done with attachment of AK-ST service tool software to the
system and settings must be made in each individual controller).
The setting decides which sorting / action must be carried out
when an alarm is sounded.
• “High” is the most important
• “Log only” is the lowest
• “Interrupted” results in no action
Alarm relay
One can also choose whether one requires an alarm output on
the controller as a local alarm indication. For this alarm relay it is
possible to dene on which alarm priority it must react to – one
can choose between the following:
• “Non” – no alarm relay is used
• “High’ – Alarm relay is activated only with alarms with high
priority
• “Low - High’ – Alarm relay is activated only with alarms with “low”
priority, “medium” or “high” priority.
Alarm acknowledgement
If the controller is connected to a network with an AKA gateway or
an AK system manager as alarm receiver, these will automatically
acknowledge the alarms that are sent to them.
If the controller on the other hand is not included in a network,
the user must acknowledge all alarms.
Alarm LED
The alarm LED on the front of the controller indicates the
controller’s alarm status.
Blinking: There is an active alarm or an unacknowledged alarm.
Fixed light: There is an active alarm that has been acknowledged.
Switched o: There are no active alarms and no unacknowledged
alarms.
IO Status and manual
The function is used in connection with installation, servicing and
fault-nding on the equipment.
With the help of the function, the connected outputs are
controlled.
Forced operation via network
The controller contains settings that can be operated from the
gateway’s forced operation function via data communication.
When the forced operation function asks about one change,
all the connected controllers on this network will be set
simultaneously.
There are the following options:
- Change to night operation
- Forced closure of injection valves (Injection ON)
- Optimising of suction pressure (Po)
Operating AKM / Service tool
The setup of the controller itself can only be carried out via AK-ST
500 service tool software. The operation is described in tters on
site guide.
If the controller is included in a network with an AKA gateway one
can subsequently carry out the daily operation of the controller
via AKM system software, i.e. one can see and change daily readouts/settings.
Note: AKM system software does not provide access to all
conguration settings of the controller. The settings/read-outs
that may be made appear in the AKM menu operation (see also
Literature overview).
Authorisation / Passwords
The controller can be operated with System software type AKM
and service tool software AK-ST 500.
Both methods of operation provide the possibility for access
to several levels according to the user’s insight into the various
functions.
Measurements
The status of all inlets and outlets can be read and controlled here.
Forced operation
One can carry out an override of all outlets here to control
whether these are correctly attached.
Note: There is no monitoring when the outlets are overridden.
Logging/registration of parameters
As a tool for documentation and fault-nding, the controller
provides the possibility of logging of parameter data in the
internal memory.
Via AK-ST 500 service tool software one can:
a) Select up to 10 parameter values the controller will
continuously register
b) State how often they must be registered
The controller has a limited memory but as a rule of thumb, the 10
parameters can be saved, which are registered every 10 minutes
for 2 days.
Via AK-ST 500 one can subsequently read the historical values in
the form of graph presentations.
System software type AKM:
The various users are dened here with initials and key word.
Access is then opened to exactly the functions that the user may
operate.
The operation is described in the AKM manual.
Service tool software AK-ST 500:
The operation is described in tters on site guide.
When a user is created, the following must be stated:
a) State a user name
b) State a password
c) Select user level
d) Select units – either US (e.g. °F and PSI) or Danfoss SI (°C and
Bar)
e) Select language
Access is given to four user levels.
1) DFLT – Default user – Access without use of password
See daily settings and read-outs.
2) Daily – Daily user
Set selected functions and carry out acknowledgement of alarms.
3) SERV – Service user
All settings in the menu system except for creation of new users
4) SUPV – Supervisor user
All settings including the creation of new users.
Display of brine temperature and condensing pressure
One to four separate displays can be connected to the controller.
Connection is accomplished by means of wires with plug connections. The display may be placed in a control box front, for
example.
When a display is connected, it will show the value for what is indicated in the conguration:
fx.
- Brine regulation sensor
1)
- P01, P02
- S3
- S4, S4.1 3), S4.2
4)
- Ss1, Ss2
- Sd1, Sd2
- Condensors regulation sensor
2)
- Pc, Pc1, Pc2
- S7
1) - 4)
= factory set display outlet
u48Actual regulation status on condenser
0: Power up
1: Stopped
2: Manuel
3: Alarm
4: Restart
5: Standby
10: Full loaded
11: Running
u49Cut in condenser capacity in %xx
u50R eference for condenser capacity in %xx
u51Actual regulation status on suction group
0: Power up
1: Stopped
2: Manuel
3: Alarm
4: Restart
5: Standby
10: Full loaded
11: Running
u52Cut in compressor capacity in %xx
u53R eference for compressor capacityxx
u54S d discharge gas temperature in °Cxx
u55Ss Suc tion gas temperature in °Cxx
u98Actual temperature for S7 media sensorxx
U01Actual Pc1 condensing pressure in °Cxx
U29Actual Pc2 condensing pressure in °Cxx
U30Actual Suction pressure P01 in °Cxx
U31Actual Suction pressure P02 in °Cxx
U32Actual brine supply S4.1 in °Cxx
U33Actual brine supply S4.2 in °Cxx
AL1Alarm suction pressurexx
AL2Alarm condenserxx
xx
xx
When a display with control buttons is chosen, a simple operation
via a menu system can be performed in addition to the display of
brine temperature and condensing pressure.
No.FunctionCond. Suc-
d02Defrost stop temperaturexxx
d04Max defrost time (safety time at stop on temperature)xxx
d06Drip delay. Time before cooling starts after defrostxxx
o30R efrigerant settingxxx
o57Capacit y setting for condenser
0: MAN, 1: OFF, 2: AUTO
058Manual setting of condenser capacityxx
o59Capacit y setting for suction group
0: MAN, 1: OFF, 2: AUTO
o60M anual setting of suction capacityxx
o62S elect of predened conguration
This setting will give a selection of predened combina-
tions which at the same time establish the connections
points.. At the end of the manual an overview of options
and connection points is shown. After the conguration
of this function the controller will shut down and restart
o93Lock of conguration
It is only possible to select a predened conguration or
change refrigerant when the conguration lock is open.
0 = Conguration open
1 = Conguration locked
P31Pump status
0=stopped. 1=pump 1 running. 2=pump 2 running.
3=both pumps running
P35Selection of pump control
0=both pumps are stopped. 1=only pump 1 must run.
2=only pump 2 must run. 3=both pumps must run.
4= equalization of operation time (start before stop).
5=equalization of operation time (stop before start)
r12Main switch
0: Controller stopped
1: Regulating
r23Set point suction pressure
Setting of required brine temperature in °C
r24Suction pressure reference
Actual reference temperature for brine regulation
r28Set point condenser
Setting of required condenser pressure in °C
r29Condenser reference
Actual reference for temperature for condenser capacity
u09Temperature at defrost sensorxxx
u11D efrost time or duration of last defrostxxx
u12S3 temperaturexxx
u16Actual media temperature measured with S4xx
u44S c3 out door temperature in °Cxx
xx
xxx
xxx
xxx
xxx
xxx
xx
xx
tion
xx
xx
xx
Pack
If you want to see one of the values in the menu list under "function" you should use the buttons in the following way:
1. Press on the upper button until a parameter is shown
2.Press on the upper or lower button and nd the parameter you
want to read
3. Press on the middle button until the value of the parameter is
displayed.
After a short time, the display will return automatically to the
"Read out display".
Secondary display
The following readings can be displayed by pressing the bottom
button on the display:
For display A: Condenser's regulating sensor
For display B: Compressor's regulating sensor.
For display C: S4.1 brine temperature
For display D: S4.2 brine temperature
Light-emitting diodes on the controller
Internal communication
between the modules:
Quick ash = error
Constantly On = error
Status of output 1-8
Slow ash = OK
Quick ash = answer from gateway
■ Power
■ Comm
■ DO1 ■ Status
■ DO2 ■ Service Tool
■ DO3 ■ LON
■ DO4
■ DO5 ■ Alarm
■ DO6
■ DO7
■ DO8 ■ Service Pin
remains on for 10 mins after network
registration
Constantly ON = error
Constantly OFF = error
External communication
Flash = active alarm/not cancelled
Constant ON = Active alarm/cancelled