Menu listThis menu function can be used together with system software type AKM. The description is divided
up into function groups that can be displayed on the PC screen. Within each group it is now possible
to show the measured values, or settings. Regarding the use of AKM, reference is made to the AKM
Manual.
ValidityThis menu operation (from January 2016 applies to controller type AK-CH 650, code number/
080Z0132 with programme version 2.0x.
Function groups
The operation is divided up into several
function groups. When a selection has been
made, push “OK”, and you may continue to
the next display. By way of example, “Suction
capacity control” has been selected here.
From the measure line the dierent values can be read. The values are constantly
updated.
In the list of settings the set values can be
seen. If a setting has to be changed, select
the parameter and proceed via “OK”.
MeasurementsThe various measurements can be read directly. If a graphic display of the measurements is required,
up to eight of them can be shown. Select the required measurements and push “Trend”.
SettingsSettings can only be made for the daily operation. Conguration settings cannot be seen, changed or
written out. They can only be made from the Service Tool programme.
There are four kinds of settings, ON/OFF settings, settings with a variable value, time settings and
“reset alarms”.
Enter the new value or move the sliding scale up or down.
The new value will apply, when “OK” is pushed.
Go through the individual functions one by one and make the required settings. When settings have
been made for one controller, the set values may be used as basis in the other controllers of the same
type and with the same software version. Copy the settings by using the copy settings function in the
AKM programme, and adjust subsequently any settings where there are deviations.
NB! If a list is required for noting down the individual settings, a printout can be made of it with a function in the AKM programme. Read the next section, “Documentation”.
DocumentationDocumentation of the settings of the individual controllers can be made with the print function in the
AKM programme. Select the controller for which documentation of the settings is required and select
the “Print Settings” function (cf. also the AKM Manual).
FunctionsShown below are function groups with corresponding measurements and settings. A printout of the
given settings can be made using the AKM function “Print Settings” (see above).
NoteIt has been necessary to make selections among the many measurements and settings coming from
the controller.
The operation from the AKM programme cannot contain them all.
If there is a need for access to all measurements and settings, you should make use of Service Tool
type AK-ST 500.
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
External Main Switch Status of input “Extern Main Switch”. In pos. “OFF” the regulation is stopped by force
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Conguration lock Lock of conguration.
In order to select quick setup or select refrigerant type, the conguration lock must
be “open”. Note: ”Main switch” must be OFF in order to set conguration lock in “open”
position
0: Open
1: Locked
Select quick setup Select a pre dened application. All in- and outputs will be pre-dened.
All setpoint will be adapted to the selected application. Please notice that the control
ler will make a restart when a selection has been made.
See AK-PC 840 manual for further details about the predened applications.
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
MC dP0 oset K Actual displacement value for the suction pressure in connection with a “P0 Optimiser” function (Master control function in AKA gateway)
S3 oset Contribution from reference displacement via S3 sensor
Ext. Ref. Oset °C Contribution from external reference displacement
Night setback Status of night setback function
ON: Night (An increase of the evaporating pressure is permitted)
OFF: Normal situation
Suction status 0: Power up Controller has been powered up (power supply re-connected) 1: Stopped Capacity control has been stopped ("Main switch" = OFF or "Control mode" = OFF)
2: Manual Capacity is controlled manually ("Control mode" = MAN)
3: Alarm Capacity control is in alarm condition (fx. alarm on Po Min or Pc Max)
4: Restart Capacity control is waiting for elapse of “Restart time”
5: Standby Capacity control is ready to start
10: Full loaded All capacity cutin
11: Running Capacity control is running
Actual Zone Actual zone for capacity regulation:
0: P0-error
1: - - Zone
2: - Zone
3: NZ
4: + Zone
5: + + Zone
Load shed input 1 Actual status on Load shed input 1
Load shed input 2 Actual status on Load shed input 2
Liq. Inj. heat exch Liquid injection can be coordinated with the compressor operation:
0: no coordination
1: Synchronization with compressor operation
2: Last compressor is stopped only after pump down
No. of compressors Dened number of compressors
Comp. application Select the compressor application required (see AK-CH 650 manual for further details)
0: Single step only
1: 1xComp. w. unloaders + Single step
2: 2xComp. w. unloaders + Single step
3: Comp. w. unloaders only
4: 1xVariable speed + Single step
5: 1xVariable speed + Comp. w. unloaders
6: 2xVariable speed + Single step
Step control mode Selected coupling pattern for compressors
Sequential: Compressors are cut in/out in strict accordance
with compressor number
Cyclic: Runtime equalisation between compressors
Best t: Compressors are cut in/out in order to
make the best possible t to actual load
0: Sequential
2: Cyclic
3: Best t
S4 Min 24h Minimum value for S4 temp. For the last 24 hours
S4 Max 24h Maximum value for S4 temp. For the last 24 hours
S4 Average 24h Average value for S4 temp. For the last 24 hours
Extra cooling req. Brine temperature is higher than desired, and the relay "extra cooling" is active.
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Cap. control mode 0: MAN (The compressor capacity will be controlled manually)
1: OFF (The capacity control will be stopped)
2: AUTO (The capacity is controlled by the PI controller)
Manual capacity % Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller
Control sensor Choise of regulation sensor
0: P0
3: S4
Reference mode Choice of suction pressure reference
0: SP + Ext. Ref + Night + S3 oset: Used if you require override via 0-10V signal, S3
sensor or night setback.
1: SP + Po optimization: Used if you want to optimize the reference from the
refrigeration appliance (network function) which is most used
Setpoint °C Setting of required suction pressure in °C
++Zone delay s Time delay between step cut-ins in the regulation band over the “+Zone band”
Set in seconds
+Zone delay s Time delay between step cut-ins in the regulation band over the neutral zone
Set in seconds
+Zone band K Regulation band over the neutral zone
Neutral zone K Neutral zone for suction pressure
-Zone band K Regulation band under the neutral zone
-Zone delay s Time delay between step cut-outs in the regulation band under the neutral zone
Set in seconds
--Zone delay s Time delay between step cut-outs in the regulation band under the “-Zone band”
Set in seconds.
Kp S4 Amplication factor for P0 regulation
Night oset K Displacement value for suction pressure in connection with an active night
setback signal (set in Kelvin)
Tref S3 oset Reference temperature for the temperature signal S3, i.e. when = Tref, there is no displacement of the reference.
K1 S3 oset Displacement of the reference for the charge temperature S4 on an increase in S3
temperature in relation to ”Tref S3 oset” of 1°C (K1 = 0 gives no displacement)
Max.Reference °C Max. permissible suction pressure reference
Min.Reference °C Min. permissible suction pressure reference
VSD Min. speed Hz Minimum allowed speed before stop of Variable Speed drive (Low load condition)
VSD Start speed Hz Minimum speed for start of Variable speed drive (Must be set higher than “VSD Min. Speed Hz”)
VSD Max. speed Hz Highest permissible speed for the compressor motor
Load shed limit 1 Set max capacity limit for load shed input 1
Load shed limit 2 Set max capacity limit for load shed input 2
Override limit Po Set max load shedding override limit for suction pressure Po
Override delay 1 min Override delay for load shed limit 1. If the suction pressure exceeds
“Override limit Po” during load shedding and the set delay has expired, the load shed
limit 1 will be cancelled
Override delay 2 min Override delay for load shed limit 2. If the suction pressure exceeds
“Override limit Po” during load shedding and the set delay has expired, the load shed
limit 2 will be cancelled
Po pump down limit °C Set the actual pump down limit for the last compressor
Initial start time The time after start-up where the cut-in capacity is limited to the rst compressor step.
1 comp. start delay On new start the start of the rst compressor is delayed by the set delay time so that the
brine pumps can bring the brine up to speed before start of the rst compressor.
Extra cooling mode A relay is reserved and it will be activated if the brine temperature is higher than desired.
Extra cooling oset Set the value (K above the reference) where the relay is to activated
Extra cooling delay Delay time before the relay can be active. The time applies during normal regulation
Extra cooling init d. Delay time before the relay can be active. The time applies during cooling after start-up
and after defrosting.
Suction compressor status
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
VSD 1 safety Status on safety input for variable speed controller on compressor 1
ON: Alarm
OFF: No alarm
VSD 2 safety Status on safety input for variable speed controller on compressor 2
ON: Alarm
OFF: No alarm
Comp. 1 Status 0: Power up Controller has been powered up/Compressor is not used 1: Stopped Compressor hat been stopped
2: Manual Compressor capacity is controlled manually
3: Alarm Compressor is in alarm condition (cut out on safety)
4: Restart Compressor is waiting for elapse of “Recycle time”
5: Standby Compressor is ready to start
10: Full loaded All capacity cutin
11: Running Capacity control is running
Comp 2 … Status As above for compressor no. 2 to 6
VSD Speed % The present speed of the compressor motor controlled by the frequency converter
Comp 1 capacity % Actual cut-in capacity on this compressor
Comp 2 …capacity % As above for compressor no. 2 to 6
Comp 1 Runtime % 24 Running time for compressor 1 in percent within the past 24 hours
Comp 2 …Runtime % 24 As above for compressor no. 2 to 6
Comp 1 Cycles / 24 h Number of compressor starts during the past 24 hours
Comp 2 …Cycles / 24 h As above for compressor no. 2 to 6
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
1 Min. ON-time m Minimum duration of ON period
2 …Min. ON-time m As above for compressor no. 2 to 6
1 Min. OFF-time m Minimum duration of OFF period
2 …Min. OFF-time m As above for compressor no. 2 to 6
1 recycle time m Minimum period of time between two successive starts.
2 …recycle time m As above for compressor no. 2 to 6
1 runtime h Compressor’s total run time in hours
2 …runtime h As above for compressor no. 2 to 6
Pump control
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Cold pump running Reading of pump status
0: Pumps have stopped
1: Cold pump 1 is in use
2: Cold pump 2 is in use
3: Both pumps are in use
Flow switch status Current status for ow switch input
Pump 1 safety Actual status for input "Pump 1"
Pump 2 safety Actual status for input "Pump 2"
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Cold Pump ctrl. Choice of pump operation
0: Both pumps are stopped
1: Cold pump 1 is in constant use
2: Cold pump 2 is in constant use
3: Both pumps are in constant use
4: O set of operational time between the two pumps. Start before stop
5: O set of operational time between the two pumps. Stop before start
Pump cycle time The operational times of the pumps before pump switch is carried out (pump’s opera tional time before changeover to the other pump)
Pump switch time Overlap time during pump changeover where both pumps are in use or break time
when switching between two pumps (only relevant if "Cold Pump ctrl" is set to 4 or 5)
Pump alarm delay Delay on pump alarm before alarm is activated and automatic pump changeover car
ried out (only if "Cold Pump ctrl" is set to 4 or 5)
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Defrost status Current status for defrost function
Defrost temp. Current temperature of chosen defrost stop sensor
Defrost time Defrosting time for current or most recently completed defrost
Average defrost time Average defrosting time for the 10 most recent defrosts
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Start defrost Manual start of defrost
Stop defrost Manual stop of defrost
Defrost control Select if defrost function is required
Defrost stop sensor Select defrost stop method
0: Stop exclusively on time
1: Stop at S3 temp. With time as backup
2: Stop at S4 temp. With time as backup
Defrost stop temp. Temperature value for defrost stop (the defrost is stopped when the temperature of
the selected defrost sensor reached the set value)
Max. defrost time Max. permitted defrosting time in minutes (security time for stop using temperature)
Drip delay Delay time after defrost where compressors may not start so that the water has time
to run o the refrigeration surfaces before start of refrigeration
Comp. run at def. Select if compressors are permitted to run during defrost
Condenser capacity control
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Condenser status 0: Power up Controller has been powered up (power supply re-connected)
1: Stopped Capacity control has been stopped (“Main switch” = OFF or “Control mode” = OFF)
2: Manual Capacity is controlled manually (“Control mode” = MAN)
3: Alarm Capacity control is in alarm condition (f.ex. Pc Max or Sd Max)
4: Restart Capacity control is waiting for elapse of “Restart time”
5: Standby Capacity control is ready to start
10: Full loaded All capacity cutin
11: Running Capacity control is running
Air ow status 0: No RFG. select No refrigerant has been selected (monitoring of air ow can not start)
1: Tuning Monitoring function adapts to the condenser in question
2: OFF Monitoring function is switched OFF
3: OK Air ow is OK
4: Little dirt The amount of dirt decreases the performance of the condenser,
clean when possible
5: Dirty The amount of dirt leads to considerable air ow problems, clean
as soon as possible
6: Blocking The amount of dirt might lead to high pressure problems, clean now
Sc3 Air on °C Outdoor temperature in °C measured with Sc3 temperature sensor
VSD Speed % Status of analogue output signal “AO” for variable speed drive (in percent of full scale f.ex. 0 -10 V d.c.)
VSD safety Status of safety monitoring input for Variable Speed Drive
ON: Alarm on VSD A safety monitoring input
OFF: No alarm on VSD A safety monitoring input
Heat rec. temp. °C Temperature at the sensor for the heat recovery function
Heat recovery Status on function "Heat recovery"
No. of fans Dened number of fans
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Cap. control mode 0: MAN (The condenser capacity will be controlled manually)
1: OFF (The capacity control will be stopped)
2: AUTO (The capacity is controlled by the PI controller)
Manual capacity % Manual setting of condenser capacity
The value is in % of total capacity controlled by the controller
Reference mode 0: Set point Reference = “PcA setpoint °C”
1: Floating Reference is changed as a function of the outdoor temperature
measured by the “Sc3 air on” sensor, the set “Dimensioning tm K”
and the actual compressor load.
Setpoint °C Setting of required discharge pressure in °C
Dimensioning tm K Dimensioning mean temperature dierential between air- and condensing temperature at full load for the condenser in question (Typical 8 – 15K).
Min. tm k tm value at minimum load.
Min. Reference °C Min. permissible condensing pressure reference
Max. Reference °C Max. permissible condensing pressure reference
Heat rec. SP °C Condensing pressure reference when the thermostat for heat recovery is cut in.
Heat rec. Cut In °C Temperature value when the thermostat changes over to heat recovery.
Heat rec. CutOut °C Temperature value when the thermostat cuts out the heat recovery again
Xp P-band K Proportional band for PI controller
Tn Integr. time s Integration time for PI controller
Control type Selection of regulation type:
0: P regulation
1: PI regulation
VSD Min. speed % Minimum allowed speed before stop of Variable Speed drive (Low load condition)
VSD Start speed % Minimum speed for start of Variable speed drive (Must be set higher than “VSD Min. Speed %”)
Cap. limit night % Capacity limitation during night operation
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Fan1/VSD status Status of the Fan 1
ON: Fan is running
OFF: Fan is not running
Fan2.... status As above for fan 2 to 8
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Fan 1 runtime Total on time for fan 1
Fan 2.... runtime Total on time for fan 2 to 8
Safety Functions
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Ss suction gas °C Suction gas temperature in °C
Suction superheat K Superheat in suction line
Sd discharge gas °C Discharge gas temperature in °C
Anti freeze safety Actual status of general shared frost protection input for all compressors
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Pc max. limit °C Max. value of discharge pressure in °C
(If the value is exceeded, the entire compressor capacity will be cut out)
(At 3 K under PcA max. the entire condenser capacity will be cut in and
the compressor capacity will be reduced)
Sd max. limit °C Max. value of discharge pressure in °C
(If the value is exceeded, the entire compressor capacity will be cut out and the entire
condenser capacity will be cut in)
P0 min. limit °C Min. value of suction pressure in °C
(If the value becomes less, the entire compressor capacity will be cut out) P0 min del at start On start of the rst compressor the security switch on the low-pressure security
function ”Po My limit” is delayed by the set time to prevent low-pressure dropout at
start.
P0 max. alarm °C Alarm limit for P0
P0 max. delay m Delay time before alarm for "P0 max. alarm °C"
SH min. Alarm K Alarm limit for min. superheat
SH max. Alarm K Alarm limit for max. superheat
SH Alarm delay m Time delay before alarm for “SH min limit” and “SH min limit”
Restart time m Time delay before restart of compressors
(Applies to the functions: "Sd max limit", "Pc max limit" and "P0 min limit")
Liq.inj. SH CutIn K Liquid injection in the suction line. Set superheat value where liquid injection is to
start.
Liq.inj. Sd CutIn °C Liquid injection in suction line. Set Sd temperature where liquid injection is to start.
Alarm monitoring S4 Select if alarm monitoring is required on charge temperature S4
S4 High limit High alarm limit for cold brine charge temperature
S4 High delay Delay on high charge temperature under normal regulation
S4 High del pulldown Delay on high charge temperature on start or during defrost
S4 Low limit Low alarm limit for cold bring charge temperature
S4 low delay Delay on low charge temperature
General alarm inputs
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
DI 1 Alarm Alarm status on the function dened as a DI1 alarm
ON: Alarm is active
OFF: No alarm, normal situation
DI 2.... Alarm As above, but for the alarm functions 2 to 8
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
DI 1 Alarm delay m Time delay for the alarm "DI 1 Alarm"
DI 2.... Alarm delay m As above, but for the alarm functions 2 to 8
Thermostat/pressostats
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Thermostat 1 °C Temperature measurement of function dened in Thermostat 1.
Thermostat 2 °C Temperature measurement of function dened in Thermostat 2.
Thermostat 3 °C Temperature measurement of function dened in Thermostat 3.
Pressostat 1 Bar Pressure measurement of function dened in Pressure Control 1
Pressostat 2 Bar As above, but for pressostat 2
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Ther. 1 Cutin °C Cutin value for function dened in ”Thermostat 1”.
Ther. 1 Cutout °C Cutout value for function dened in ”Thermostat 1”.
Ther. 1 High Alarm °C High alarm limit "Thermostat 1"
Ther. 1 Low Alarm °C Low alarm limit "Thermostat 1"
Ther. 1 High ALDly m Time delay for high alarm "Thermostat 1"
Ther. 1 Low ALDly m Time delay for low alarm "Thermostat 1"
Ther. 2............ As above, but for thermostat 2
Ther. 3............ As above, but for thermostat 3
Pres. 1 Cutin bar Cutin value for function dened in ”Pressure Control 1”.
Pres. 1 Cutout bar Cutout value for function dened in ”Pressure Control 1”.
Pres. 1 High alarm bar High alarm limit "Pressostat 1"
Pres. 1 Low alarm bar Low alarm limit "Pressostat 1"
Pres. 1 High ALDly m Time delay for high alarm "Pressostat 1"
Pres. 1 Low ALDly m Time delay for low alarm "Pressostat 1"
Pres. 2............ As above, but for pressostat 2
(Use Service Tool if data concerning thermostats 4 and 5 or from pressure controls 3, 4 and 5 have to be downloaded).
Voltage inputs
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Volt 1 readout Voltage measurement on the function dened in Volt 1.
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Volt 1 Cutin The value where the relay is to cut in
Volt 1 Cutout The value where the relay is to cut out
Volt 1 Cutin del. m Time delay for cutin of relay
Volt 1 Cutout del. m Time delay for cutout of relay
Volt 1 High Al.Limit The value for the high alarm limit
Volt 1 Low Al.Limit The value for the low alarm limit
Volt 1 High Al.Dly m Time delay for high alarm
Volt 1 Low Al.Dly m Time delay for low alarm
(Use Service Tool if data concerning Volt 2, 3, 4 and 5 are to be downloaded).
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
The alarm priority of the following alarms can be changed:
High priority is dened with setting = 1
Medium priority is dened with setting = 2
Low priority is dened with setting = 3
Overriding the alarms is dened with setting = 0
Standby mode Regulation has stopped
Low P0 Minimum safety limit for suction pressure P0 has been violated
High S4 High alarm limit for S4 has been exceeded
Low S4 Low alarm limit for S4 has been exceeded
High Pc/Sd Safety limit for condensing pressure Pc /discharge gas temperature is exceeded
Superheat min/max Superheat i suction line to low / high
Load Shedding Load shedding has been activated
P0/S4 sensor error Sensor signal for P0 / S4 is defective
Misc. sensor error Sensor signal for Ss, Sd, S3, Sc3, Saux is defective
Cold pump alarm Pump alarm. One of the pumps has fallen out. Signal from ow switch
Cold pump 1 & 2 alarm Pump alarm. Both pumps has fallen out. Signal from ow swich
Anti freeze safety All compressors have been cut out on frost protection
Compr VSD safety Variable speed drive for compressor has been cut out on safety
Comp. 1 safety Compressor has been cut out on safety
Comp. 2 safety Compressor has been cut out on safety
Comp. 3 safety Compressor has been cut out on safety
Comp. 4 safety Compressor has been cut out on safety
Comp. 5 safety Compressor has been cut out on safety
Comp. 6 safety Compressor has been cut out on safety
Pc/S7 sensor error Signal from pressure transmitter /temperature sensor is defective
Blocked air ow The intelligent air ow monitoring of the condenser reports that a cleaning is due
Fan safety Variable speed drive for condenser fans has been cut out on safety
Max def. time Defrost is stopped because of too long defrost time. Check evaporator.
AKM menu: "For DANFOSS only"
This menu contains data and setting values for special internal controller functions.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.