Menu listThis menu function can be used together with system software type AKM. The description is divided
up into function groups that can be displayed on the PC screen. Within each group it is now possible
to show the measured values, or settings. Regarding the use of AKM, reference is made to the AKM
Manual.
ValidityThis menu operation (from January 2016 applies to controller type AK-CH 650, code number/
080Z0132 with programme version 2.0x.
Function groups
The operation is divided up into several
function groups. When a selection has been
made, push “OK”, and you may continue to
the next display. By way of example, “Suction
capacity control” has been selected here.
From the measure line the dierent values can be read. The values are constantly
updated.
In the list of settings the set values can be
seen. If a setting has to be changed, select
the parameter and proceed via “OK”.
MeasurementsThe various measurements can be read directly. If a graphic display of the measurements is required,
up to eight of them can be shown. Select the required measurements and push “Trend”.
SettingsSettings can only be made for the daily operation. Conguration settings cannot be seen, changed or
written out. They can only be made from the Service Tool programme.
There are four kinds of settings, ON/OFF settings, settings with a variable value, time settings and
“reset alarms”.
Enter the new value or move the sliding scale up or down.
The new value will apply, when “OK” is pushed.
Go through the individual functions one by one and make the required settings. When settings have
been made for one controller, the set values may be used as basis in the other controllers of the same
type and with the same software version. Copy the settings by using the copy settings function in the
AKM programme, and adjust subsequently any settings where there are deviations.
NB! If a list is required for noting down the individual settings, a printout can be made of it with a function in the AKM programme. Read the next section, “Documentation”.
DocumentationDocumentation of the settings of the individual controllers can be made with the print function in the
AKM programme. Select the controller for which documentation of the settings is required and select
the “Print Settings” function (cf. also the AKM Manual).
FunctionsShown below are function groups with corresponding measurements and settings. A printout of the
given settings can be made using the AKM function “Print Settings” (see above).
NoteIt has been necessary to make selections among the many measurements and settings coming from
the controller.
The operation from the AKM programme cannot contain them all.
If there is a need for access to all measurements and settings, you should make use of Service Tool
type AK-ST 500.
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
External Main Switch Status of input “Extern Main Switch”. In pos. “OFF” the regulation is stopped by force
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Conguration lock Lock of conguration.
In order to select quick setup or select refrigerant type, the conguration lock must
be “open”. Note: ”Main switch” must be OFF in order to set conguration lock in “open”
position
0: Open
1: Locked
Select quick setup Select a pre dened application. All in- and outputs will be pre-dened.
All setpoint will be adapted to the selected application. Please notice that the control
ler will make a restart when a selection has been made.
See AK-PC 840 manual for further details about the predened applications.
Measurements AK error When “ON”, the controller is in alarm condition.
Comp. Ctrl. temp. Actual temperature for compressor control
S4 Cold brine supply Actual cold brine supply temperature measured with S4 temp. sensor
S3 Cold brine return Actual cold brine return temperature measured with S3 temp. sensor
P0 °C Suction pressure in °C. (Measured with the pressure transmitter)
Comp. ctrl. Ref. °C Actual reference temperature for compressor control
Compressor cap. % Cut-in compressor capacity in % (of total capacity)
Request Comp. Cap % Reference for compressor capacity (deviations may be due to time delays)
Cond. ctrl. temp °C Actual temperature for control sensor (Pc or S7)
S7 warm brine °C Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Pc °C Condensing pressure in °C. (measured with the pressure transmitter)
Cond. ctrl. ref. °C Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cond. cap. % Cut-in condenser capacity in % (of total capacity)
Request Cond. cap % Reference for condenser capacity
MC dP0 oset K Actual displacement value for the suction pressure in connection with a “P0 Optimiser” function (Master control function in AKA gateway)
S3 oset Contribution from reference displacement via S3 sensor
Ext. Ref. Oset °C Contribution from external reference displacement
Night setback Status of night setback function
ON: Night (An increase of the evaporating pressure is permitted)
OFF: Normal situation
Suction status 0: Power up Controller has been powered up (power supply re-connected) 1: Stopped Capacity control has been stopped ("Main switch" = OFF or "Control mode" = OFF)
2: Manual Capacity is controlled manually ("Control mode" = MAN)
3: Alarm Capacity control is in alarm condition (fx. alarm on Po Min or Pc Max)
4: Restart Capacity control is waiting for elapse of “Restart time”
5: Standby Capacity control is ready to start
10: Full loaded All capacity cutin
11: Running Capacity control is running
Actual Zone Actual zone for capacity regulation:
0: P0-error
1: - - Zone
2: - Zone
3: NZ
4: + Zone
5: + + Zone
Load shed input 1 Actual status on Load shed input 1
Load shed input 2 Actual status on Load shed input 2
Liq. Inj. heat exch Liquid injection can be coordinated with the compressor operation:
0: no coordination
1: Synchronization with compressor operation
2: Last compressor is stopped only after pump down
No. of compressors Dened number of compressors
Comp. application Select the compressor application required (see AK-CH 650 manual for further details)
0: Single step only
1: 1xComp. w. unloaders + Single step
2: 2xComp. w. unloaders + Single step
3: Comp. w. unloaders only
4: 1xVariable speed + Single step
5: 1xVariable speed + Comp. w. unloaders
6: 2xVariable speed + Single step
Step control mode Selected coupling pattern for compressors
Sequential: Compressors are cut in/out in strict accordance
with compressor number
Cyclic: Runtime equalisation between compressors
Best t: Compressors are cut in/out in order to
make the best possible t to actual load
0: Sequential
2: Cyclic
3: Best t
S4 Min 24h Minimum value for S4 temp. For the last 24 hours
S4 Max 24h Maximum value for S4 temp. For the last 24 hours
S4 Average 24h Average value for S4 temp. For the last 24 hours
Extra cooling req. Brine temperature is higher than desired, and the relay "extra cooling" is active.
Settings Main switch Main switch: ON: Regulation
OFF: Controller stopped
Cap. control mode 0: MAN (The compressor capacity will be controlled manually)
1: OFF (The capacity control will be stopped)
2: AUTO (The capacity is controlled by the PI controller)
Manual capacity % Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller
Control sensor Choise of regulation sensor
0: P0
3: S4
Reference mode Choice of suction pressure reference
0: SP + Ext. Ref + Night + S3 oset: Used if you require override via 0-10V signal, S3
sensor or night setback.
1: SP + Po optimization: Used if you want to optimize the reference from the
refrigeration appliance (network function) which is most used
Setpoint °C Setting of required suction pressure in °C
++Zone delay s Time delay between step cut-ins in the regulation band over the “+Zone band”
Set in seconds
+Zone delay s Time delay between step cut-ins in the regulation band over the neutral zone
Set in seconds
+Zone band K Regulation band over the neutral zone
Neutral zone K Neutral zone for suction pressure
-Zone band K Regulation band under the neutral zone
-Zone delay s Time delay between step cut-outs in the regulation band under the neutral zone
Set in seconds