Danfoss AK-CH 650 User guide

User Guide
Capacity controller for water chillers
AK-CH 650 SW 2.0
ADAP-KOOL® Refrigeration control systems
Contents
1. Introduction ............................................................................. 3
Principles .............................................................................................. 4
2. Design of a controller ..............................................................7
Common data for modules .................................................................10
Controller ...........................................................................................12
Extension module AK-XM 101A .................................................14
Extension module AK-XM 102A / AK-XM 102B .....................16
Extension module AK-XM 103A .................................................18
Extension module AK-XM 204A / AK-XM 204B .....................20
Extension module AK-XM 205A / AK-XM 205B .....................22
Extension module AK-OB 110 ....................................................24
Extension module AK-OB 101A..................................................25
Extension module EKA 163B / EKA 164B ................................ 26
Power supply module AK-PS 075 / 150 ...................................27
Preface to design ....................................................................................28
Functions ............................................................................................28
Connections ...................................................................................... 29
Limitations ......................................................................................... 29
Design of a compressor and condenser control .........................30
Procedure: ..........................................................................................30
Sketch .................................................................................................. 30
Compressor and condenser functions ....................................30
Connections ...................................................................................... 31
Planning table .................................................................................. 33
Length .................................................................................................34
Linking of modules ......................................................................... 34
Determine the connection points ............................................35
Connection diagram ...................................................................... 36
Supply voltage ................................................................................. 37
Ordering ..................................................................................................... 38
3. Mounting and wiring .............................................................39
Mounting ................................................................................................... 40
Mounting of analog output module ........................................ 40
Mounting of extension module on the basic module ....... 41
Wiring .......................................................................................................... 42
4. Conguration and operation ................................................45
Conguration ...........................................................................................47
Connect PC ........................................................................................ 47
Authorization .................................................................................... 48
System setup ....................................................................................50
Set plant type ................................................................................... 51
Set control of compressors ..........................................................52
Setup control of condenser .........................................................55
Setup Display .................................................................................... 57
Setup defrost .................................................................................... 58
Setup general alarm inputs ......................................................... 59
Setup separate thermostat functions ...................................... 60
Setup separate voltage functions ............................................. 61
Conguration of inputs and outputs .......................................62
Set alarm priorities..........................................................................64
Lock conguration ..........................................................................66
Check conguration .......................................................................67
Check of connections ............................................................................ 69
Check of settings.....................................................................................71
Schedule function .................................................................................. 73
Installation in network .......................................................................... 74
First start of control ................................................................................75
Check alarms ..................................................................................... 75
Start the control ............................................................................... 76
Manual capacity control ............................................................... 77
Manual defrost ......................................................................................... 78
5. Regulating functions .............................................................79
Suction group ..........................................................................................80
Capacity control of compressors ...............................................80
Reference for compressor control ..................................... 81
Capacity distribution methods ........................................... 82
Power pack types – compressor combinations ............82
Load shedding ..........................................................................87
Liquid injection in suction line ........................................... 88
Heat exchanger injection .....................................................88
Defrost .................................................................................................89
Safety functions ............................................................................... 90
Pump control ....................................................................................92
Condenser ................................................................................................. 93
Capacity control of condenser ...................................................93
Reference for condensing pressure ..........................................94
Capacity distribution ..................................................................... 95
Step regulation ........................................................................................95
Speed regulation ....................................................................................95
Condenser couplings .....................................................................96
Safety functions for condenser .................................................. 96
General monitoring functions ...........................................................97
Miscellaneous ..........................................................................................98
Appendix A – Compressor combinations and coupling pat-
terns ...........................................................................................................101
Appendix B - Alarm texts ...................................................................108
Appendix C - ..........................................................................................110
Recommended connection ..............................................................110
2 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650

Application

1. Introduction

AK-CH 650 is a water chiller control for capacity control of compressors and air-cooled condensers on indirect refrigeration systems within commercial refrigeration. In addition to capacity control, the controller can control pumps, injection signals to heat exchangers, defrosting sequences and safety monitoring, etc.
Among the dierent functions are:
- Capacity control of up to 6 compressors (max. 3 unloads/comp) – Relay output, which is activated by a request for extra cooling
- Speed control of one or two compressors
- Up to 6 safety inputs for each compressor
- Capacity limitation to minimize consumption peaks
- Twin pump control with automatic operating time equalisation
- Start/stop signal for heat exchanger injection, incl. pump down
function
- Defrost control with time or temperature stop
- Liquid injection into suction line
- Safety monitoring of high pressure / low pressure / discharge
temperature
- Frost protection
- Capacity control of up to 8 fans
- Floating condenser reference with regard to outside temperature
- Heat recovery function
- Fan capacity with regard to Step coupling, speed regulation or a
combination
- Safety monitoring of fans
- Alarm signals can be generated directly from the controller and
via data communication
- Alarms are shown with texts so that the cause of the alarm is
easy to see.
- Plus some completely separate functions that are totally inde-
pendent of the regulation – such as alarm inputs, thermostats, pressostat and voltage inputs.
The controller uses the following signals for control/monitoring: S4 Charge temperature (control signal) S3 Return temperature Ss Suction gas temperature Sd Discharge gas temperature Po Suction pressure (frost-proong). Pc: Condensing pressure S7 Return temperature for any hot brine Sc3 Ambient temperature
Compressor capacity is controlled by charge temperature S4 and by suction pressure P0 as frost protection. Condenser capacity is controlled by condensing pressure Pc or, alternatively, tempera­ture sensor S7.
Example If the condenser end needs full control of a dry refrigeration circuit, AK-CH 650 can be combined with a type AK-PC 420 dry refrigeration control.
SW = 2.0x
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 3

Principles

The great advantage of this series of controllers is that it can be extended as the size of the plant is increased. It has been developed for refrigeration control systems, but not for any specic application – variation is created through the read-in software and the way you choose to dene the connections. It is the same modules that are used for each regulation and the composition can be changed, as required. With these modules (building blocks) it is possible to create a multitude of various kinds of regulations. But it is you who must help adjusting the regulation to the actual needs – these instructions will assist you to nd your way through all the questions so that the regulation can be dened and the connections made.
Controller
Top part
Advantages
• The controller’s size can “grow” as systems grow
• The software can be set for one or more regulations
• Several regulations with the same components
• Extension-friendly when systems requirements are changed
• Flexible concept:
- Controller series with common construction
- One principle – many regulation uses
- modules are selected for the actual connection requirements
- The same modules are used from regulation to regulation
Extension modules
Bottom part
The controller is the cornerstone of the regulation. The module has inputs and outputs capable of handling small systems.
• The bottom part – and hence the terminals – are the same for all controller types.
• The top part contains the intelligence with software. This unit will vary according to controller type. But it will always be supplied together with the bottom part.
• In addition to the software the top part is provided with connections for data communication and address setting.
Examples
A regulation with few connections can be performed with the controller module alone
If the system grows and more functions have to be controlled, the regulation can be extended. With extra modules more signals can be received and more relays cut in and out – how many of them – and which – is determined by the relevant application.
If there are many connections one or more extension modules have to be mounted
4 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Direct connection
Setup and operation of an AK controller must be accomplished via the “AK-Service Tool” software program.
The programme is installed on a PC, and setup and operation of the various functions are carried out via the controller’s menu displays.
Displays
The menu displays are dynamic, so that dierent settings in one menu will result in dierent setting possibilities in other menus.
A simple application with few connections will give a setup with few settings. A corresponding application with many connections will give a setup with many settings. From the overview display there is access to further displays for the compressor regulation and the condenser regulation. At the bottom of the display there is access to a number of general functions, such as “time table”, “manual operation”, “log function”, “alarms”, and “service” (conguration).
Network linking
The controller can be linked up into a network together with other controllers in an ADAP-KOOL® refrigeration control system. After the setup operation can be performed at a distance with, say, our software program type AKM.
Users
The controller comes supplied with several languages, one of which can be selected and employed by the user. If there are several users, they may each have their choice of language. All users must be assigned a user prole which either gives access to full operation or gradually limits the operation to the lowest level that only allows you “to see”. Language selection is part of the service tool settings. If the language selection is not available in the service tool for the current regulator, English texts will be displayed.
External display
An external display can be tted in order for P0 (Suction) and Pc (Condensing) readings to be displayed. A total of 4 displays can be tted and with one setting it is pos­sible to choose between the following readings: suction pressure, suction pressure in temperature, S3, S4, Ss, Sd, condenser pres­sure, condenser pressure in temperature and S7.
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 5
Light-emitting diodes
A number of light-emitting diodes makes it possible to follow the signals that are received and transmitted by the controller.
Log
From the log function you can dene the measurements you wish to be shown. The collected values can be printed, or you may export them to a le. You can open the le in Excel.
If you are in a service situation you can show measurements in a trend function. The measurements are then made realtime and displayed instantly.
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4
DO5 Alarm
DO6
DO7
DO8 Service Pin
Slow ash = OK Quick ash = answer from gateway Constantly ON = error Constantly OFF = error
Flash = active alarm/not cancelled Constant ON = Active alarm/cancelled
Alarm
The display gives you an overview of all active alarms. If you wish to conrm that you have seen the alarm you can cross it o in the acknowledge eld. If you want to know more about a current alarm you can click on it and obtain an information display on the screen.
A corresponding display exists for all earlier alarms. Here you can upload information if you need further details about the alarm history.
Trouble-shooting
The controller contains a function that continuously follows a number of measurements and deals with them. The result indicates whether the function is OK or whether an error may be expected within a given period of time (“the trip down the rollercoaster has started”). At this time an alarm is transmitted about the situation – no error has appeared as yet, but it will come. One example may be slow clogging-up of a condenser. When the alarm comes the capacity has been reduced, but the situation is not serious. There will be time to plan a service call.
Alarm
Error
6 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650

2. Design of a controller

This section describes how the controller is designed.
The controller in the system is based on a uniform connection platform where any deviations from regulation to regulation is determined by the used top part with a specic software and by which input and output signals the relevant application will require. If it is an application with few connections, the controller module (top part with belonging bottom part) may be sucient. If it is an application with many connections it will be necessary to use the controller module plus one or more extension modules.
This section will give you a survey of possible connections plus assistance in selecting the modules required by your actual application.
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 7

Module survey

• Controller module – capable of handling minor plant require­ments.
• Extension modules. When the complexity becomes greater and additional inputs or outputs are required, modules can be attached to the controller. A plug on the side of the module will transmit the supply voltage and data communication between the modules.
• Top part The upper part of the controller module contains the intelligence. This is the unit where the regulation is dened and where data communication is connected to other controllers in a bigger network.
• Connection types There are various types of inputs and outputs. One type may, for example, receive signals from sensors and switches, another may receive a voltage signal, and a third type may be outputs with relays etc. The individual types are shown in the table below.
Extension module with additional analog inputs
External display for suction pressure etc.
• Optional connection When a regulation is planned (set up) it will generate a need for a number of connections distributed on the mentioned types. This connection must then be made on either the controller module or an extension module. The only thing to be observed is that the types must not be mixed (an analog input signal must for instance not be connected to a digital input).
• Programming of connections The controller must know where you connect the individual input and output signals. This takes place in a later congura­tion where each individual connection is dened based on the following principle:
- to which module
- at which point (”terminals”)
- what is connected (e.g. pressure transmitter/type/
pressure range)
Extension module with additional relay outputs and additional analog inputs.
Controller with analog inputs and relay outputs.
Top part
Extension module with 2x analog output signals
The module with additional relay outputs is also available in a version where the top part is provided with change-over switches so that the relays can be overridden.
8 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
1. Controller
Type Function Application
AK-CH 650 Controller for capacity control of compressors and condensers Extended water chiller control
2. Extension modules and survey of inputs and outputs
Type Analog
inputs
For sensors, pres­sure transmitters etc.
Controller 11 4 4 - - - -
Extension modules
AK-XM 101A 8
AK-XM 102A 8
AK-XM 102B 8
AK-XM 103A 4 4
AK-XM 204A 8
AK-XM 204B 8 x
AK-XM 205A 8 8
AK-XM 205B 8 8 x The following extension module can be placed on the PC board in the controller module.
There is only room for one module. AK-OB 110 2
On/O outputs On/o supply voltage
Relay (SPDT)
Solid state Low voltage
(DI signal)
(max. 80 V)
High voltage (max. 260 V)
Analog outputs
0-10 V d.c. For override of
Module with switches
relay outputs
3. AK operation and accessories
Type Function Application
Operation
AK-ST 500 Software for operation of AK controllers AK-operation
- Cable between PC and AK controller AK - Com port
-
- Cable set + converter between PC and AK controller AK - USB
Accessories Power supply module 230 V / 115 V to 24 V
AK-PS 075 18 VA AK-PS 150 36 VA
Accessories External display that can be connected to the controller module. For showing, say, the suction pressure
EKA 163B Display
EKA 164B Display with operation buttons
- Cable between display and controller
Accessories Real time clock for use in controllers that require a clock function, but are not wired with data communication.
AK-OB 101A Real time clock with battery backup. To be mounted in an AK controller
Cable between zero modem cable and AK controller / Cable between PDA cable and AK controller
AK - RS 232
Forsyning til regulator
Length = 2 m
Length = 6 m
On the following pages there is data specic to each module.
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 9

Common data for modules

Supply voltage 24 V d.c./a.c. +/- 20%
Power consumption AK-__ (controller) 8 VA
AK-XM 101, 102 2 VA
AK-XM 204, 205 5 VA
Analoge indgange Pt 1000 ohm /0°C Resolution: 0.1°C
Pressure transmitter type AKS 32R / AKS 2050 / AKS 32 (1-5 V)
Other pressure transmitter: Ratiometric signal Min. and Max. pressure must be set
Voltage signal 0-10 V
Contact function (On/O) On at R < 20 ohm
On/o supply voltage inputs Low voltage
Relay outputs SPDT
0 / 80 V a.c./d.c.
High voltage 0 / 260 V a.c.
AC-1 (ohmic) 4 A
AC-15 (inductive) 3 A
U Min. 24 V
Accuracy: +/- 0.5°C between -50°C and +50°C +/- 1°C between -100°C and -50°C +/- 1°C between +50°C and +130°C
Resolution:1 mV Accuracy +/- 10 mV Max. connection of 5 pressure transmitters on one module
O at R > 2K ohm (Gold -plated contacts not necessary)
O: U < 2 V On: U > 10 V
O: U < 24 V On: U > 80 V
Max. 230 V Low and high voltage must not be connected to the same output group
Solid state outputs Can be used for loads that are cut in and
out frequently, e.g. : rail heat, fans and AKV valve
Ambient temperature During transport -40 to 70°C
During operation -20 to 55°C ,
Enclosure Material PC / ABS
Density IP10 , VBG 4
Mounting For mounting on panel wall or DIN rail
Weight with screw terminals modules in100- / 200- / controller-series Ca. 200 g / 500 g / 600 g
Approvals EU low voltage directive and EMC require-
ments are complied with
UL 873,
The mentioned data applies to all modules. If data is specic, this is mentioned together with the module in question.
Capacitive load
The relays cannot be used for the direct connection of capacitive loads such as LEDs and on/o control of EC motors. All loads with a switch mode power supply must be connected with a suitable con­tactor or similar.
Max. 240 V a.c. , Min. 48 V a.c. Max. 0.5 A, Leak < 1 mA Max. 1 AKV
0 to 95% RH (non condensing) No shock inuences / vibrations
LVD tested according to EN 60730 EMC tested Immunity according to EN 61000-6-2 Emission according to EN 61000-6-3
UL le number: E31024 for CH UL le number: E166834 for XM
10 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Dimensions
The module dimension is 72 mm. Modules in the 100-series consist of one module Modules in the 200-series consist of two modules Controllers consist of three modules The length of an aggregate unit = n x 72 + 8
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 11

Controller

Function
There are several controllers in the series. The function is determined by the programmed software, but outwardly the controllers are identical – they all have the same connection possibilities:
11 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 digital outputs, with 4 Solid state outputs and 4 relay outputs
Supply voltage
24 V a.c. or d.c. to be connected to the controller. The 24 V must not be retransmitted and used by other controllers as it is not galvanically separated from inputs and outputs. In other words, you must use a transformer for each controller. Class II is required. The terminals must not be earthed. The supply voltage to any extension modules is transmitted via the plug on the right-hand side. The size of the transformer is determined by the power requirement of the total number of modules.
The supply voltage to a pressure transmitter can be taken either from the 5 V output or from the 12 V output depending on transmitter type.
PIN
Data communication
If the controller is to be included in a system, communication must take place via the LON connection. The installation has to be made as mentioned in the separate instructions for LON communication.
Address setting
When the controller is connected to a gateway type AKA 245, the controller’s address must be set between 1 and 119.
Service PIN
When the controller is connected to the data communication cable the gateway must have knowledge of the new controller. This is obtained by pushing the key PIN. The LED “Status” will ash when the gateway sends an acceptance message.
Operation
The conguration operation of the controller must take place from the software programme “Service Tool”. The program must be installed on a PC, and the PC must be connected to the controller via the network plug on the front of the unit.
Light-emitting diodes
There are two rows with LED’s. They mean: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row:
• Software status (slow ash = OK)
• Communication with Service Tool
• Communication on LON
• Alarm when LED ashes
- 3 LED’s that are not used
• “Service Pin” switch has been activated
Address
Power
Comm
DO1 Status
DO2 Service Tool
DO3 LON
DO4
DO5 Alarm
DO6
DO7
DO8 Service Pin
Slow ash = OK Quick ash = answer from gateway Constantly ON = error Constantly OFF = error
Flash = active alarm/not cancelled Constant ON = Active alarm/cancelled
Keep the safety distance!
Low and high voltage must not be connected to the same output group
A small module (option board) can be placed on the bottom part of the controller. The module is described later in the document.
12 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Point
Point 1 2 3 4 5 6 7 8 9 10 11 Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11
Terminal 15: 12 V Terminal 16: 5 V
Terminal 27: 12 V Terminal 28: 5 V
Analog inputs on 1 - 11
Solid state outputs on 12 - 15
Relay or AKV coil fx 230 V a.c.
Signal Signal
S
Pt 1000 ohm/0°C
S1 S2 Saux1 Saux2 SSA SdA
P
AKS 32R
3: Brown
2: Blue
1: Black
P0A P0B PcA
AKS 32
3: Brown
2: Black
1: Red
PcB
U
...
On/O Ext.
Main switch
Day/ Night
Door
DO
AKV
AKV Comp 1 Comp 2 Fan 1 Alarm Light Rail heat Defrost
Option Board
Please see the signal on the page with the module.
24 and 25 used only when "Op­tion board tted"
type
Pt 1000
AKS 32R / AKS 2050 / MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
0 - 5 V 0 - 10 V
Active at:
Closed
/
Open
Active at:
On
/
O
Point 12 13 14 15 16 17 18 19 Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
Signal Module Point
1 (AI 1) 1 - 2 2 (AI 2) 3 - 4 3 (AI 3) 5 - 6 4 (AI 4) 7 - 8 5 (AI 5) 9 - 10 6 (AI 6) 11 - 12 7 (AI 7) 13 - 14 8 (AI 8) 19 - 20
9 (AI 9) 21 - 22 10 (AI 10) 23 - 24 11 (AI 11) 25 - 26
1
12 (DO 1) 31 - 32 13 (DO 2) 33 - 34 14 (DO 3) 35 - 36 15 (DO 4) 37 - 38 16 (DO 5) 39 - 40 - 41
17 (DO6) 42 -43 - 44 18 (DO7) 45 - 46- 47 19 (DO8) 48 - 49 -50
24 -
25 -
Terminal 17, 18, 29, 30: (Cable screen)
Relay outputs on 16 - 19
Terminal
Signal type /
Active at
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 13

Extension module AK-XM 101A

Function
The module contains 8 analog inputs for sensors, pressure transmitters, voltage signals and contact signals.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
14 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Point
Point 1 2 3 4 Type AI1 AI2 AI3 AI4
Terminal 9: 12 V Terminal 10: 5 V
S
Pt 1000 ohm/0°C
P
AKS 32R
AKS 32
At the top the signal input is the left of the two terminals.
At the bottom the signal input is the right of the two terminals.
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
Signal Signal
type
S1 S2 Saux1
Pt 1000 Saux2 SSA SdA
AKS 32R / P0A
P0B PcA PcB
AKS 2050 /
MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
Terminal 15: 5 V Terminal 16: 12 V
Terminal
11, 12, 13, 14:
(Cable screen)
Point 5 6 7 8 Type AI5 AI6 AI7 AI8
U
...
On/O Ext.
Main switch
Day/ Night
Door
0 - 5 V
0 - 10 V
Active at:
Closed
/
Open
Signal Module Point
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 17 - 18
6 (AI 6) 19 - 20
7 (AI 7) 21 - 22
8 (AI 8) 23 - 24
Terminal
Signal type /
Active at
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 15

Extension module AK-XM 102A / AK-XM 102B

Function
The module contains 8 inputs for on/o voltage signals.
Signal
AK-XM 102A is for low voltage signals. AK-XM 102B is for high voltage signals.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
Light-emitting diodes
They indicate:
• Voltage supply to the module
• Communication with the controller is active (red = error)
• Status of the individual inputs 1 to 8 (when lit = voltage)
AK-XM 102A
Max. 24 V
On/O: On: DI > 10 V a.c. O: DI < 2 V a.c.
AK-XM 102B
Max. 230 V
On/O: On: DI > 80 V a.c. O: DI < 24 V a.c.
16 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Point
DI
AK-XM 102A: Max. 24 V AK-XM 102B: Max. 230 V
Signal Active at
Ext. Main switch
Day/ Night
Comp. safety 1
Comp. safety 2
Closed
(voltage on)
/
Open
(voltage o)
Point 1 2 3 4
Type DI1 DI2 DI3 DI4
Point 5 6 7 8 Type DI5 DI6 DI7 DI8
Signal Module Point Terminal Active at
1 (DI 1) 1 - 2
2 (DI 2) 3 - 4
3 (DI 3) 5 - 6
4 (DI 4) 7 - 8
5 (DI 5) 9 - 10
6 (DI 6) 11 - 12
7 (DI 7) 13 - 14
8 (DI 8) 15 - 16
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 17

Extension module AK-XM 103A

Function
The module contains : 4 analog inputs for sensors, pressure transmitters, voltage signals and contact signals. 4 analog voltage outputs of 0 - 10 V
Supply voltage
The supply voltage to the module comes from the previous module in the row.
Supply voltage to a pressure transmitter can be taken from either the 5 V output or the 12 V output depending on transmitter type.
Galvanic isolation
The inputs are galvanically separated from the outlets. The outlets AO1 and AO2 are galvanically separated from AO3 and AO4.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
Max. load
I < 2.5 mA R > 4 kΩ
18 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Point
Point 1 2 3 4 Type AI1 AI2 AI3 AI4
Terminal 9: 12 V Terminal 10: 5 V
S
Pt 1000 ohm/0°C
P
AKS 32R
AKS 32
At the top the signal input is the left of the two terminals.
At the bottom the signal input is the right of the two terminals.
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
Signal Signal
type
S1 S2 Saux SsA
Pt 1000 SdA
Shr Stw Sgc
P0A P0B PcA PcB Paux Pgc Prec
AKS 32R /
AKS 2050
MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
Terminal 11, 12: (Cable screen)
Galvanic isolation: AI 1-4 ≠ AO 1-2 ≠ AO 3-4
Point 5 6 7 8 Type AO1 AO2 AO3 AO 4
U
...
On/O Ext.
Main switch Day/ Night
Door Level switch
AO
0 - 5 V
0 - 10 V
Active at:
Closed
/
Open
0-10 V
Signal Module Point Terminal Signal type /Active at
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AO 1) 17 - 18
6 (AO 2) 19 - 20
7 (AO 3) 21 - 22
8 (AO 4) 23 - 24
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 19

Extension module AK-XM 204A / AK-XM 204B

Function
The module contains 8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
AK-XM 204B only Override of relay
Eight change-over switches at the front make it possible to override the relay’s function. Either to position OFF or ON. In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They indicate the following: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 204B only):
• Override of relays ON = override OFF = no override
AK-XM 204A AK-XM 204B
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic) AC-15: max. 3 A (Inductive)
AK-XM 204B Override of relay
Keep the safety distance!
Low and high voltage must not be connected to the same output group
20 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Point
DO
Signal Active at
Comp. 1
Comp. 2
Fan 1
Alarm
On
/
O
Point 1 2 3 4 5 6 7 8 Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
Signal Module Point Terminal Active at
1 (DO 1) 25 -26 - 27
2 (DO 2) 28 - 27 - 30
3 (DO 3) 31 - 32 - 33
4 (DO 4) 34 - 35 -36
5 (DO 5) 37 - 38 - 39
6 (DO 6) 40 - 41 - 42
7 (DO 7) 43 - 44 - 45
8 (DO 8) 46 - 47 - 48
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 21

Extension module AK-XM 205A / AK-XM 205B

Function
The module contains: 8 analog inputs for sensors, pressure transmitters, voltage signals
and contact signals.
8 relay outputs.
Supply voltage
The supply voltage to the module comes from the previous module in the row.
AK-XM 205B only Override of relay
Eight change-over switches at the front make it possible to override the relay’s function. Either to position OFF or ON. In position Auto the controller carries out the control.
Light-emitting diodes
There are two rows with LED’s. They mean: Left row:
• Voltage supply to the controller
• Communication active with the bottom PC board (red = error)
• Status of outputs DO1 to DO8
Right row: (AK-XM 205B only):
• Override of relays ON = override OFF = no override
AK-XM 205A AK-XM 205B
max. 10 V
Fuses
Behind the upper part there is a fuse for each output.
Max. 230 V
AC-1: max. 4 A (ohmic) AC-15: max. 3 A (Inductive)
AK-XM 205B Override of relay
Keep the safety distance!
Low and high voltage must not be connected to the same output group
22 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Point
S
Pt 1000 ohm/0°C
Signal Signal
type
S1 S2 Saux1
Pt 1000
Saux2 SSA SdA
Point 1 2 3 4 5 6 7 8 Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
Terminal 9: 12 V Terminal 10: 5 V
Terminal 21: 12 V Terminal 22: 5 V
Terminal 11, 12, 23, 24 :
(Cable screen)
Point 9 10 11 12 13 14 15 16 Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
P
AKS 32R
AKS 32
U
On/O
DO
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
P0A P0B PcA PcB
...
Ext. Main switch
Day/ Night
Door
Comp 1 Comp 2 Fan 1 Alarm Light Rail heat Defrost
AKS 32R / AKS 2050 / MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
0 - 5 V 0 - 10 V
Active at:
Closed
/
Open
Active at:
on
/
O
Signal Module Point
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 13 - 14
6 (AI 6) 15 - 16
7 (AI 7) 17 - 18
8 (AI 8) 19 -20
9 (DO 1) 25 - 26 - 27
10 (DO 2) 28 - 29 - 30
11 (DO 3) 31 - 32 - 33
12 (DO 4) 34 - 35 - 36
13 (DO 5) 37 - 38 - 39
14 (DO6) 40 - 41 - 42
15 (DO7) 43 - 44 - 45
16 (DO8) 46 - 47 - 48
Terminal
Signal type /
Active at
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 23

Extension module AK-OB 110

Function
The module contains two analog voltage outputs of 0 – 10 V.
Supply voltage
The supply voltage to the module comes from the controller module.
Placing
The module is placed on the PC board in the controller module.
Point
The two outputs have points 24 and 25. They are shown on the earlier page where the controller is also mentioned.
Max. load I < 2,5 mA R > 4 kohm
AO
AO 0 - 10 V
Module
Point 24 25 Type AO1 AO2
1
AO2
AO1
24 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650

Extension module AK-OB 101A

Function
The module is a real time clock module with battery backup.
The module can be used in controllers that are not linked up in a data communication unit together with other controllers. The module is used here if the controller needs battery backup for the following functions
• Clock function
• Fixed times for day/night change-over
• Fixed defrost times
• Saving of alarm log in case of power failure
• Saving of temperature log in case of power failure
Connection
The module is provided with plug connection.
Placing
The module is placed on the PC board inside the top part.
Point
No point for a clock module to be dened – just connect it.
Working life of the battery
The working life of the battery is several years – even if there are frequent power failures. An alarm is generated when the battery has to be replaced. After the alarm there are still several months of operating hours left in the battery.
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 25

Extension module EKA 163B / EKA 164B

Function
Display of important measurements from the controller, e.g. appli-
ance temperature, suction pressure or condensing pressure.
Setting of the individual functions can be performed by using the display with control buttons. It is the controller used that determines the measurements and settings that can occur.
Connection
The extension module is connected to the controller module via a cable with plug connections. You have to use one cable per module. The cable is supplied in various lengths.
Both types of display (with or without control buttons) can be connected to either display output A, B, C or D.
When the controller starts up, the display will show the output that is connected.
- - 1 = output A
- - 2 = output B etc.
EKA 163B EKA 164B
Placing
The extension module can be placed at a distance of up to 15 m from the controller module.
Point
No point has to be dened for a display module – you simply con­nect it.
Module
Point - ­Type - -
1
26 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650

Power supply module AK-PS 075 / 150

Function
24 V supply for controller.
Supply voltage
230 V a.c or 115 V a.c. (from 100 V a.c. to 240 V a.c.)
Placing
On DIN-rail
Eect
Type Output tension Output current Power
AK-PS 075 24 V d.c. 0.75 A 18 VA AK-PS 150 24 V d.c.
(adjustable)
1.5 A 36 VA
Dimension
Type High Width
AK-PS 075 90 mm 36 mm AK-PS 150 90 mm 54 mm
Supply to a controller
Connections
AK-PS 075
AK-PS 150
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 27

Preface to design

Be aware of the following when the number of extension modules is being planned. A signal may have to be changed, so that an additional module may be avoided.
• An ON/OFF signal can be received in two ways. Either as a contact signal on an analog input or as voltage on a low or high­voltage module.
• An ON/OFF output signal can be given in two ways. Either with a relay switch or with solid state. The primary dierence is the per­mitted load and that the relay switch contains a cutout switch.
Mentioned below is a number of functions and connections that may have to be considered when a regulation has to be planned. There are more functions in the controller than the ones mentioned here, but those mentioned have been included in order that the need for connections can be established.

Functions

Clock function
Clock function and change-over between summer time and winter time are contained in the controller. The clock is zeroset when there is power failure. The clock’s setting is maintained if the controller is linked up in a network with a gateway, or a clock module can be mounted in the controller.
Start/stop of regulation
Regulation can be started and stopped via the software. External start/stop can also be connected.
Alarm function
If the alarm is to be sent to a signal transmitter, a relay output will have to be used.
Extra temperature sensors and pressure sensors
If additional measurements have to be carried out beyond the regulation, sensors can be connected to the analog inputs.
Forced control
The software contains a forced control option. If an extension module with relay outputs is used, the module’s top part can be with change-over switches – switches that can override the individual relays into either OFF or ON position.
Data communication
The controller module has terminals for LON data communication. The requirements to the installation are described in a separate document.
28 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650

Connections

In principle there are the following types of connections:
Analog inputs ”AI”
This signal must be connected to two terminals. Signals can be received from the following
sources:
• Temperature signal from Pt 1000 ohm temperature sensor
• Contact signal where the input is short­circuited or ”opened”, respectively
• Voltage signal from 0 to 10 V
• Signal from pressure transmitter AKS 32, AKS 32R or AKS 2050 The supply voltage is supplied from the module’s terminal board where there is both a 5 V supply and a 12 V supply. When programming the pressure
transmitter’s pressure range must be set.
ON/OFF voltage inputs ”DI”
This signal must be connected to two terminals.
• The signal must have two levels, either 0 V or ”voltage” on the input. There are two dierent extension modules for this signal type:
- low-voltage signals, e.g. 24 V
- high-voltage signals, e.g. 230 V
ON/OFF output signals ”DO”
There are two types, as follows:
• Relay outputs All relay outputs are with change-over relay so that the required function can be obtained when the controller is without voltage.
• Solid state outputs Reserved for AKV valves, but output can cut an external relay in and out, as with a relay output. The output is only found on the controller module.
When programming the function must be set:
• Active when the output is activated
• Active when the output is not activated.
Analog output signal ”AO”
This signal is to be used if a control signal is to be transmitted to an external unit, e.g. a frequency converter. When programming the signal range must be dened: 0-5 V, 1-5 V, 0-10 V or 2-10 V.
When programming the function must be set:
• Active when the input is without voltage
• Active when voltage is applied to the input.

Limitations

As the system is very exible regarding the number of connected units you must check whether your selection complies with the few limitations there are. The complexity of the controller is determined by the software, the size of the processor, and the size of the memory. It provides the controller with a certain number of connections from which data can be downloaded, and others where coupling with relays can be performed.
The sum of connections cannot exceed 80.
The number of extension modules must be limited so that the
total power will not exceed 32 VA (including controller).
No more than 5 pressure transmitters may be connected to one
controller module.
No more than 5 pressure transmitters may be connected to one
extension module.
Common pressure transmitter
If several controllers receive a signal from the same pressure trans­mitter, the supply to the aected controllers must be wired so that it is not possible to switch o one of the controllers without also switching o the others. (If one controller is switched o, the sig­nal will be pulled down, and all the other controllers will receive a signal which is too low)
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 29

Design of a compressor and condenser control

Procedure:

1. Make a sketch of the system in question
2. Check that the controller’s functions cover the required applica­tion
3. Consider the connections to be made
4. Use the planning table. / Note down the number of connections ./ add up
5. Are there enough connections on the controller module? – If not, can they be obtained by changing an ON/OFF input signal from voltage signal to contact signal, or will an extension mod­ule be required?
6. Decide which extension modules are to be used
7. Check that the limitations are observed
8. Calculate the total length of modules
8. The modules are linked together
10. The connection sites are established
11. Draw a connection diagram or a key diagram
12. Size of supply voltage/transformer
Follow these 12 steps
1

Sketch

Make a sketch of the actual plant.
2

Compressor and condenser functions

AK-CH 650
Application
Regulation of a compressor group x Regulation of a condenser group x Both compressor group and condenser group x Pumpe control x
Regulation of compressor capacity
PI-regulation x Max. number of compressors 6 Max. number of unloaders each compressor 3 Identical compressor capacities x Dierent compressor capacities x Sequentiel operation (rst in / last out) x Speed regulation of 1 or 2 compressors x Run time equalisation x Min. restart time x Min. On-time x Liquid injection in heat exchanger x Liquid injection in suction line x Load shedding (Capacity limitation) x Relay output, which is activated by a request for extra cooling x 0-10 V signal, which shows cutin compressor capacity x
Brine temperature reference
Override via P0 optimisation x Override via “night setback” x Override via "0 -10 V signal" x
Regulation of condenser capacity
Step regulation x
30 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Loading...
+ 84 hidden pages