Danfoss AK-CC 550B User guide

User Guide
Controller for appliance control
AK-CC 550B
ADAP-KOOL® Refrigeration control systems
Manua l

Introduction

Application
Advantages
• Energy optimisation of the whole refrigeration appliance
• One controller for several different refrigeration appliances
• Integrated display at the front of the controller
• Quick set-up with predefined settings
• Built-in data communication
• Built-in clock function with power reserve
Principle
The temperature in the appliance is registered by one or two temperature sensors which are located in the air flow before the evaporator (S3) or after the evaporator (S4) respectively. A setting for thermostat, alarm thermostat and display reading determines the influence the two sensor values should have for each indi­vidual function. In addition product sensor S6, which can be optionally placed in the appliance, can be used to register the temperature near the required product in a certain place within the appliance. The temperature of the evaporator is registered with the S5 sensor which can be used as a defrosting sensor. In addition to the outlet to the electronic injection valve of the type AKV, the controller has 5 relay outputs which are defined by the use selected – the individual usage options are described in detail on page 12.
Functions
• Day/night thermostat with ON/OFF or modulating principle
• Product sensor S6 with separate alarm limits
• Switch between thermostat settings via digital input
• Adaptive control of superheat
• Adaptive defrosting based on evaporator performance
• Start of defrost via schedule, digital input or network
• Natural, electric or hot gas defrost
• Stop of defrost on time and/or temperature
• Coordination of defrosting among several controls
• Pulsing of fans when thermostat is satisfied
• Case cleaning function for documentation of HACCP procedure
• Rail heat control via day/night load or dew point
• Door function
• Control of two compressors
• Control of night blinds
• Light control
• Heat thermostat
• Factory calibration that will guarantee a better measuring accuracy than stated in the standard EN ISO 23953-2 without subsequent calibration (Pt 1000 ohm sensor)
• Integrated MODBUS communication with the option of mount­ing a LonWorks / DANBUSS communication card
Contents
Introduction ....................................................................................................... 2
Operation ............................................................................................................ 4
Applications .....................................................................................................12
Survey of functions ........................................................................................ 15
Appliance examples
Operation .......................................................................................................... 27
Menu survey .....................................................................................................29
Connections ..................................................................................................... 34
Data ..................................................................................................................... 36
Ordering ............................................................................................................37
2 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Applications
Here is an overview of the controller’s usage options. A setting will configure input and outputs so that the controller’s operation interface is directed at the selected application. The current settings for the respective uses can be found on page
28.
Application 1-8
These uses are applied to standard appliances or cold storage rooms with one valve, one evaporator and one refrigeration sec­tion. The sensors are used according to standard principles. The output functions change depending on the selected applica­tion.
Application 9
This use is for refrigeration appliances with one valve, two evapo­rators and two refrigeration sections, each with its own tempera­ture measurement. There are shared alarm limits but individual alarm delays for each cooling section. Display for each section. Product sensor S6 cannot be used.
Application 10
This use is for refrigeration appliances with one valve, one evapo­rator and two refrigeration sections. There are separate alarm limits and alarm delays for each cooling section. Display for each section.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 3

Operation

Liquid injection
Liquid injection in the evaporator is controlled by an electronic injection valve of the type AKV. The valve functions as both expan­sion valve and solenoid valve. The valve opens and closes using signals from the controller. The function contains an adaptive algorithm which independently adjusts the valve’s opening so that the evaporator constantly sup­plies optimum refrigeration.
Superheat is measured via
• Pressure sensor P0 and temperature sensor S2 For this use a correct measurement of superheat is achieved under all conditions which ensures a very robust and precise control. The signal from one pressure transmitter can be used by several controllers, but only if there is no significant pressure difference between the evaporators in question.
There are two parallel settings for superheat:
1. Dry expansion, which does not allow liquid flow (normal state)
2. Flooded evaporator, which allows liquid flow. This type of
control requires that the controller receives an on/off signal from (for example) a tank in the suction line. A level switch in the tank will register when the high limit is exceeded. When this happens, the controller will switch to dry expansion, and then back to flooded when the liquid level has dropped. The function is defined in setting o02, o37 or o84.
Warning
Accidental actuation may allow liquid throughput to the compressor. It is the installer’s responsibility to ensure that signal loss to the controller will not result in liquid throughput to the compressor.
Danfoss accepts no responsibility for damage resulting from inadequate installation.
Temperature control
The temperature in the appliance is registered by one or two temperature sensors which are located in the air flow before the evaporator (S3) or after the evaporator (S4) respectively. A setting for the thermostat, alarm thermostat and display reading deter­mines how much the two sensor values should influence each individual function, e.g. 50% will produce an equal value from both sensors.
The actual temperature control can take place in two ways: as an ordinary ON/OFF regulation with a differential, or as a modulat­ing control there the temperature variation will not be nearly as great as in ON/OFF control. There is however a limit to the use of a modulating control as it can only be used in central plant. In a decentralised plant the thermostat function with ON/OFF control should be selected. In a central plant the thermostat function may either be selected for ON/OFF control or modulating control.
Temperature monitoring
Just as is possible for the thermostat, the alarm monitoring can be set with a weighting between S3 and S4 so that you can decide how much the two sensor values should influence the alarm monitoring. Minimum and maximum limits can be set for alarm temperature and time delays. A longer time delay can be set for high temperature alarms. This delay is active after defrosting, appliance cleaning, appliance shutdown and start-up.
4 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Thermostat bands
Thermostat bands can be used beneficially for appliances where different product types are stored which require different tem­perature conditions. It is possible to change between the two different thermostat bands via a contact signal on a digital input. Separate thermostat and alarm limits can be set for each thermo­stat band – also for the product sensor.
Night setback of thermostat value
In refrigeration appliances there may be big load differences between the shop’s opening and closing hours, especially if night lids/blinds are used. The thermostat reference may be raised here without it having any effect on the product temperature. Change-over between day and night operation can take place, as follows:
• via an external switch signal.
• via a signal from the data communication system.
Product sensor
A separate optional product sensor S6, which may be placed in the appliance, can also be used and which can register and monitor the temperature in the warmest part of the appliance. There are separate alarm limits and time delays for the product sensor. The function is not available in application 9.
Appliance cleaning
This function makes it easy for the shop’s staff to carry out a cleaning of the appliance according to a standard procedure. Appliance cleaning is activated via a signal – as a rule via a key switch placed on the appliance. Appliance cleaning is carried out via three phases: 1 - at the first activation the refrigeration is stopped, but the fans
keep on operating in order to defrost the evaporators. ”Fan” is shown on the display.
2 - at the second activation the fans are also stopped and the
appliance can now be cleaned. ”OFF” is shown on the display.
3 - At the third activation refrigeration is recommenced. The
display will show the actual appliance temperature, (o97 setting).
Documentation When appliance cleaning is activated a cleaning alarm is trans­mitted to the normal alarm recipient. A later processing of these alarms will document that the appliance has been cleaned as often as planned.
Alarm monitoring There are no temperature alarms during appliance cleaning.
Appliance shut-down
The function closes the AKV valve and all outputs are switched off. The cooling appliance is stopped like the “Main switch”, but this happens without an “A45 standby alarm”. The function can be enabled by a switch on the DI input or via a setting through data communication.
- + + °C
1 ÷ + Fan
2 ÷ ÷ Off
3 + + °C
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 5
Defrost
Depending on the application you may choose between the fol­lowing defrost methods: Natural: Here the fans are kept operating during the defrost Electric: The heating element is activated Hotgas: Here the solenoid valves are controlled so that the hotgas can flow through the evaporator
Defrost sequence
1) Pump down
2) Defrost
3) Waiting position after defrost
4) Draining (drain delay. Hotgas only)
5) Drip off
6) Delay of fan
Hot gas defrost (application 6 only)
This type of connection can be used on systems with hotgas defrost, but only in small systems in, say, supermarkets – the functional content has not been adapted to systems with large charges Relay 2 is used for suction valve Relay 4’s change-over function can be used by the bypass valve and/or the hotgas valve. If the valves PMLX and GPLX are used, the delay time “d23” will have to be properly set. During hot gas defrosting, it is not possible to start a manual defrosting cycle with a touch on the controller’s lower button. A manual defrost can be started with a signal on a DI input.
Hot gas application
Drip tray heating element
It is possible to control a heating element in the drip tray for hot gas defrosting. When defrosting is commenced, the heating element is activated. The heating element remains activated until a set time after defrosting has ended by time or temperature.
Start of defrost
A defrost can be started in different ways Interval: Defrost is started at fixed time intervals, say, every
eighth hour. An interval must ALWAYS be set to a "higher" value than the period set between two defrostings when a schedule or network signal is used.
Refrigeration time: Defrost is started at fixed refrigeration time
intervals, in other words, a low need for refrigeration will ”postpone” the defrost
Schedule: Here defrost can be started at fixed times of the
day and night. However, max. 6 times Contact: Defrost is started with a contact signal on a digital input Network: The signal for defrost is received from a system unit via the data communication Adaptive defrost: Here defrosting is started based on intelligent
registering of evaporator performance. Manual: An extra defrost can be activated from the controller’s
lower-most button (however not by hot gas defrost). Or
it can be started via a parameter setting. All the mentioned methods can be used at random – if just of them is activated a defrost will be started.
Stop of defrost
Defrosting can be stopped by either:
• Time
• Temperature (with time as safety).
Compressor
If the defrosting method is set to “Hotgas,” the compressor will be “On” during the defrost cycle.
Fans
The fans can be stopped or operated during defrosting. They can also run and then be stopped at a set temperature. The temperature signal is obtained from the defrost stop temperature.
6 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Coordinated defrost
There are two ways in which coordinated defrost can be arranged. Either with wire connections between the controllers or via data communication
Wire connections The digital input DI2 is connected between the current controllers. When one controller starts a defrost all the other controllers will follow suit and likewise start a defrost. After the defrost the indi­vidual controllers will move into waiting position. When all are in waiting position there will be a change-over to refrigeration.
Coordination via data communication Here the system unit handles the coordination. The controllers are gathered in defrosting groups and the system unit ensures that defrosting is started in the group according to a weekly schedule. When a controller has completed defrosting, it sends a message to the system unit and then goes into a waiting position. When every controller in the group is in a waiting position, refrigeration is again permitted in all the individual controllers.
Defrost on demand
1 Based on refrigeration time
When the aggregate refrigeration time has passed a fixed time, a defrost will be started. (The function is not activated if the adaptive defrosting has been set to 2, 3 or 4.)
Adaptive defrosting:
This function assesses the need for defrosting on the basis of the airflow through the appliance. It may even start a defrost and may even cancel a scheduled defrost. The following functions can be selected: 0 Off 1 Monitoring
A value is calculated for the evaporator air flow here.
An alarm will be triggered in the case of icing up or flash gas.
2 Adaptive day (can replace one defrost per day).
This setting can be used if the appliance does not have a blind or
lid during the day, and blinds or lids are used at night.
A value is calculated for the day evaporator air flow.
The evaporator is monitored during the day only, and the next
scheduled defrost is carried out if required.
If the function does not require a defrost at the time of the
scheduled defrost during the day, the defrost will not be carried
out.
All scheduled defrosts are carried out during the night.
3 Adaptive day and night (can replace defrosting both day and night).
This setting can be used if the appliance has a door or a sliding
door, or it is completely uncovered both day and night.
The setting is also recommended for rooms.
A value is calculated for the evaporator air flow.
The evaporator is monitored, and the next scheduled defrost will
be carried out as required.
If the function does not require a defrost at the time of the
scheduled defrost, the defrost will not be carried out.
Max. 10
System manager
4 Full adaptive (can start an extra defrost).
This setting can be used if the appliance has a door or a sliding door, or it is completely uncovered both day and night. The setting is also recommended for rooms. A value is calculated for the evaporator air flow. The evaporator is monitored, and a defrost will be carried out as required regardless of schedules. All scheduled defrosts will also be carried out, so it is recommended to incorporate as few scheduled ones as possible.
Adaptive defrosting requires the following connections:
- Expansion valve type AKV
- Temperature signal from both S3 and S4
- Temperature signal from the condensing pressure Pc which is distributed via the network from a system manager. The value should show the pressure in front of AKV valve.On plants where each part is not representative is the signal from system man­ager not be used. Here, the controller uses a constant.
NOTE. The S3 and S4 sensors must be placed in the air flow/chan-
nel immediately before/after the evaporator.
Note The function "Adaptive defrost” should only be activated when the evaporator runs under normal operational conditions.
Min. time between defrosts
There is a 2 hours minimum time between defrosts. This avoids that planned defrosts in accordance with the weekly schedule or DI signal are carried out immediately after a defrost on demand has been carried out. The time applies from when a defrost on demand has been completed to when a planned defrost is again permitted. The defrost on demand will not start defrosting with a shorter interval than the 2 hours either.
Melting function
This function will stop the air flow in the evaporator from being re­duced by frost created by uninterrupted operation for a long time. The function is activated if the thermostat temperature has remained in the range between -5°C and +10°C for a longer period than the set melting interval. The refrigeration will then be stopped during the set melting period. The frost will be melted
Real-time clock
The controller has a built-in real-time clock which can be used to start defrosts. This clock has a power reserve of four hours. Expires the power reserve, the alarm E6 will occur. If this happens, the clock must be checked / reset. If the controller is equipped with data communication, the clock
will automatically be updated from the system unit. so that the air flow and hence the evaporator’s capacity will be greatly improved.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 7
Control of two compressors (application 5)
The two compressors must be of the same size. When the control­ler demands refrigeration it will first cut in the compressor with the shortest operating time. After the time delay the second compressor will be cut in.
When the temperature has dropped to ”the middle of the differen­tial”, the compressor with the longest operation time will be cut out. The running compressor will continue until the temperature has reached the cutout value. Then it will cut out. When the tempera­ture again reaches the middle of the differential, a compressor will again be started. If one compressor cannot maintain the temperature within the differential, the second compressor will also be started. If one of the compressors has run on its own for two hours, the compressors will be changed over so that operational time is bal­anced.
The two compressors must be of a type that can start up against a high pressure. The compressors’s settings for ”Min On time” and ”Min Off time” will always have top priority during normal regulation. But if one of the override functions is activated, the ”Min On time” will be disregarded.
Railheat
It is possible to pulse-control the power to the rail heat in order to save energy. Pulse control can either be controlled according to day/night load or dew point.
Pulse control according to day and night
Various ON periods can be set for day and night operation. A period time is set as well as the percentage part of the period in which the rail heat is ON.
Pulse control according to dew point
In order to use this function a system manager of the type AK-SM is required which can measure dew point and distribute the cur­rent dew point to the appliance controllers. For this the rail heat’s ON period is controlled from the current dew point. Two dew point values are set in the appliance control:
• One where the effect must be max. i.e.100%. (o87)
• One where the effect must be min. (o86). At a dew point which is equal to or lower than the value in 086, the effect will be the value indicated in o88. In the area between the two dew point values the controller will manage the power to be supplied to the rail heat.
During defrosting
During defrosting rail heat will be active, as selected in setting d27.
Rail heat
Dew point
8 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Fan
Pulse control
To obtain energy savings it is possible to pulse control the power supply to the fans at the evaporators. Pulse control can be accomplished in one of the following ways:
- during the thermostat’s cutout period (cold room)
- during night operation and during the thermostat’s cutout pe-
riod (appliance with night lid) (The function is not current when r14=2, i.e. modulating regulation).
A period of time is set as well as the percentage of this period of time where the fans have to be operating.
Cutout of fans during plant breakdowns
If the refrigeration in a breakdown situation stops, the temperature in the cold room may rise quickly as a result of the power supply from large fans. In order to prevent this situation the controller can stop the fans if the temperature at S5 exceeds a set limit value.
Light function
The function can be used for controlling the light in a refrigeration appliance or in a cold room. It can also be used for controlling a motorised night blind.
The light function can be defined in three ways:
- the light is controlled via a signal from a door contact. Together
with this function there is a time delay so that the light is kept on
for a period of 2 minutes after the door has been closed.
- the light is controlled via the day/night function
- the light is controlled via the data communication from a system
unit.
Here there are two operational options if data communication
should fail:
- The light can go ON
- The light can stay in its current mode.
The light load must be connected to the NC switch on the relay. This ensures that the light remains on in the appliance if power to the controller should fail. The light is switched off when "r12" (Main switch) is set to off (see o98). The light is switched off when the appliance cleaning function is activated.
Period time
Night blind
Motorised night blind can be controlled automatically from the controller. The night blinds will follow the status of the light function. When the light is switched on, the night blinds opens and when the light is switched off, the night blinds close again. When the night blinds are closed, it is possible to open them using a switch signal on the digital input. If this input is activated, the night blinds will open and the refrigeration appliance can be filled with new products. If the input is activated again, the blinds close again. When the night blind function is used, the thermostat function can control with different weighting between the S3 and S4 sensors. A weighting during day operation and another when the blind is closed. (The S4% night setting is not affected by the night blind function.) A night blind is open when the appliance cleaning function is activated. A setting can define that the night blind is open when "r12" (Main switch) is set to off (see o98). When the night blind rolls down, the fan will be stopped for 2 minutes. The night blind can thereby roll down to the correct position.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 9
Digital inputs
There are two digital inputs DI1 and DI2 with contact function and one digital input DI3 with high voltage signal. They can be used for the following functions:
- Readout of contacts position via data communication
- Door contact function with alarm
- Starting a defrost
- Main switch - start/stop of cooling
- Night setback
- Thermostat bands switch
- General alarm monitoring
- Case cleaning
- Appliance shutdown
- Forced cooling
- Override of night blinds
- Allow flooded evaporator
- Coordinated defrost (DI2 only)
- Forced closing of valve (DI3 only)
- Refrigerant leak alarm (DI1 and DI2 only)
Forced closing
The AKV valves can be closed with an external signal ( "Forced closing"). The function must be used in connection with the compressor’s safety circuit, so that there will be no injection of liquid into the evaporator when the compressor is stopped by the safety con­trols. (However not at low pressure – LP). If a defrost cycle is in progress, the forced closing status will not be re-established until the defrost is completed. Otherwise, the defrost cycle is stopped immediately once the signal is received. The function is defined in o90. The signal can be received from the DI3-input or via the data com­munication. During a forced closing the fans can be defined to be stopped or in operation.
Door contact
The door contact function can via the digital inputs be defined for two different applications:
Alarm monitoring
The controller monitors the door contact and delivers an alarm message if the door has been opened for a longer period than the set alarm delay.
Alarm monitoring and stop of refrigeration
When the door is opened the refrigeration is stopped, i.e. the injection, the compressor and the fan are stopped and light switch on. If the door remains open for a longer time than the set restart time, refrigeration will be resumed. This will ensure that refrigeration is maintained even if the door is left open or if the door contact should be defective. If the door remains open for a longer period than the set alarm delay an alarm will also be triggered.
Heating function (App. 8 only)
The heating function is used to prevent the temperature becoming too low, e.g. in a cutting room, etc. The limit for when the heating function cuts off is set as an offset value under the current cutout limit for the refrigeration thermostat. This ensures that refrigeration and heating do not occur simultaneously. The difference for the heating thermostat has the same value as for the refrigeration thermostat. To prevent that the heating thermostat cuts in during short-term drops in air temperature a time delay can be set for when to change from refrigeration to heating.
Refrigeration
Neutral zone
Heat
10 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Data communication
The controller has fixed built-in MODBUS data communication.
If there is a requirement for a different form of data communication, a Lon RS 485 / DANBUSS module can be inserted in the controller. The connection must then be to terminal RS 485.
(To use a Lon RS 485 module and gateway type AKA 245 the module must be Version 6.20 or higher.)
Display
The controller has one plug for a display. Here display type EKA 163B or EKA 164B (max. length 15m) can be connected. EKA 163B is a display for readings. EKA 164B is both for readings and operation. The connection between display and controller may be with a cable which has a plug at both ends.
If the distance between display and controller is greater than 15 m, the connection must take another form. An extra module must also be mounted in the controller if data communication is used. The built-in MODBUS data communication is used so that the display connection and the data communication to the other controllers must take place via a module. The module can be: Lon RS 485 / DANBUSS or MODBUS. When a display is to be connected to the built-in MODBUS, the display can advantageously be changed to one of the same type, but with Index A (version with screw terminals). The controllers address must be set higher than 0 in order for the display to be able to communicate with the controller. If connection of two displays is required, one must be connected to the plug (max. 15 m) and the other must then be connected to the fixed data communication. (In application 9 and 10, the MODBUS display will show values for the B section.)
! Address o03 > 0
Important
All connections to the data communication MODBUS / DANBUSS and RS 485 must comply with the requirements for data communication cables. See literature: RC8AC.
Override
The controller contains a number of functions which can be used together with the override function in the master gateway/system manager.
Function via data communication Function in gateway/system manager Used parameters in AK-CC 550B
Start of defrosting Defrost control / Time schedule / Defrost group --- Def start
Coordinated defrost Defrost control / Defrost group --- HoldAfterDef / - - - DefrostState
Prevent defrost start --- Disable Def
Day/Night schedule Day/Night control / Time schedule / Light zone --- Night setback
Light control Day/Night control / Time schedule O39 light Remote
Forced closing Forced Close / Injection ON / AKC ON --- Forced cl.
Forced cooling --- Forced cool
Railheat link to dew point / Enhanced railheat --- Dew point
P0 optimization P0 Optimization The controller supports P0 optimization
Adaptive defrost / Adaptive defrost. System manager only - - - Tc TempMean, MC Def.start
Flooded evaporator (Currently only via on/off + Boolean function in the
AK-SM)
Appliance shutdown - - - Case shutdown
- - - Flood evap
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 11

Applications

Here is a survey of the controller’s field of application.
A setting will define the relay outputs so that the controller’s interface will be targeted to the chosen application.
On page 28 you can see the relevant settings for the respective wiring diagrams.
S3 and S4 are temperature sensors. The application will determine whether either one or the other or both sensors are to be used. S3 is placed in the air flow before the evaporator. S4 after the evaporator. A percentage setting will determine how the control is to be based. S5 is a defrost sensor and is placed on/in the fins of the evaporator. S6 is a product sensor. DI1, DI2 and DI3 are contact functions that can be used for one of the fol­lowing functions: door function, alarm function, defrost start, external main switch, night operation, change of thermostat reference, appliance cleaning, forced refrigeration or coordinated defrost. DI3 has a 230 V input. See the functions in settings o02, o37and o84.
= O61 setting
General:
The ten uses are all adapted for commercial refrigeration systems in the form of either refrigeration appliances or cold storage rooms. In general all have outputs for:
• AKV valve
• Fan
• Defrost
In addition they have different uses and thereby input and outputs.
Application 1-4
Standard applications. This is for standard use where the vital difference is only different combinations of the following functions/outputs:
• Alarm
• Rail heat
• Compressor
• Light
1
2
3
4
12 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
The following uses have some special functions which in brief are:
Application 5 ”Two-compressor” operation. The two compressors must be of the same size. On start-up (after defrosting, operational stop, etc.) both compressors are started with a set time shift. One compressor starts at half the differential so that an optimum adaptation of compressor capacity takes place for the current load in the appliance/room. There is automatic runtime equalisation between the compressors. For a more detailed description please refer to earlier sections in the manual.
Application 6
Hot gas defrosting. Hot gas defrosting is adapted to commercial appliances/rooms with limited system filling. One relay controls the main valve in the suction line. A changeover relay controls both the hot gas valve and the drain valve. This means that there is no time delay between stops of hot gas and start of draining.
5
6
7
Application 7
Control of night blinds Night blinds follow the status of the light function – when the light is switched on, the night blinds are up and when the light is switched off, the night blinds are down. In addition a digital input provides the option of forced opening of the blinds so that the appliance can be filled with products.
Application 8 Heat thermostat The heat thermostat is typically used if the temperature is to be controlled within narrower limits, e.g. for cutting rooms, etc. The heating thermostat can be set as a difference in relation to the cutout limit for the refrigeration thermostat so that simultaneous refrigeration and heating are avoided.
Application 9 Two refrigeration sections – two defrost outputs This application is for refrigeration appliances with one valve, two evaporators and two refrigeration sections. Alarm monitoring and display readings take place individually via the "S3" sensors in each refrigeration section. There are two individual defrost sensors. There is no product sensor.
8
9
Application 10
Two refrigeration sections – one defrosting output. This application is for refrigeration appliances with one valve, one evaporator and two refrigeration sections. Alarm monitoring and display readings take place individually via the "S3" sensors in each refrigeration section.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 13
10
Connection signs
The controller is provided with signs from the factory indicating application 1. If you employ another use, signs are provided so that you can mount the relevant one.
The number is indicated on the left-hand side of the signs. Use the sign with the current application number. One of the signs applies to both applications 4 and 10.
14 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B

Survey of functions

Function Para-
meter
Normal display
Normally the temperature value from one of the two thermostat sensors S3 or S4 or a mixture of the two measurements is displayed. In o17 the ratio is determined.
Thermostat Thermostat control Set point
Regulation is based on the set value plus a displacement, if applicable. The value is set via a push on the centre button. The set value can be locked or limited to a range with the settings in r02 and r 03. The reference at any time can be seen in "u91 Cutout temp".
Differential
When the temperature is higher than the reference + the set differential, the com­pressor relay will be cut in. It will cut out again when the temperature comes down to the set reference.
Ref. Dif.
Setpoint limitation
The controller’s setting range for the setpoint may be narrowed down, so that much too high or much too low values are not set accidentally - with resulting damages.
To avoid a too high setting of the setpoint, the max. allowable reference value may be lowered.
To avoid a too low setting of the setpoint, the min. allowable reference value may be increased.
Correction of the display’s temperature
If the temperature at the products and the temperature received by the controller are not identical, an offset adjustment of the display temperature can be carried out.
Temperature unit
Set here if the controller is to show temperature values in °C or in °F.
Correction of signal from S4
Compensation possibility due to long sensor cable
Correction of signal from S3 and S3B
Compensation possibility due to long sensor cable
Start / stop of refrigeration
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed. (For manual control the value is set at -1. Then the AKV outlet and the relay outlets can be force-controlled by the respective reading parameters (u23, u58, etc.). Here the read value can be overwritten.) Start / stop of refrigeration can also be accomplished with the external switch func­tion connected to a DI input. Stopped refrigeration will give a ”Standby alarm-A45" (alarm relay not activated)
Night setback value
The thermostat’s reference will be the setpoint plus this value when the controller changes over to night operation. (Select a negative value if there is to be cold ac­cumulation.)
Thermostat function
Here it is defined how the thermostat is to operate. Either as an ordinary ON/OFF ther­mostat or as a modulating thermostat. 1: ON/OFF thermostat 2: Modulating
Parameter by operation via data communication
Display air (u56)
Cutout °C
r01 Differential
r02 Max cutout °C
r03 Min cutout °C
r04 Disp. Adj. K
r05 Temp. unit
°C=0. / °F=1 (Only °C on AKM, whatever the set­ting)
r09 Adjust S4
r10 Adjust S3
r12 Main Switch
1: Start 0: Stop
-1: Manual control of outputs allowed
r13 Night offset
r14 Therm. mode
When operation is ”modulating” the AKV valve will limit the flow of refrigerant so that the temperature variation will be less than for the ON/OFF thermostat. The differential (r01) must not be set lower than 2K for "modulating".
In a decentralised plant you must select the ON/OFF thermostat setting.
Selection of thermostat sensor
Here you define the sensor the thermostat is to use for its control function. S3, S4, or a combination of them. With the setting 0%, only S3 is used (Sin). With 100%, only S4.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 15
r15 Ther. S4 %
Melt function
Only for control of refrigeration (-5 to +10°C). The function ensures that the evapora­tor will not be blocked by frost. Here you set how often the function is to stop the refrigeration and hence transform the frost to water (or ice if there is too much frost).
r16 MeltInterval
Melt period
Here you set how long an on-going melt function is to last. Set point 2
The thermostat’s cutout value when the thermostat band 2 is activated via a digital input.
Correction of signal from S6
Compensation possibility due to long sensor cable
Selection of thermostat sensor S4% during night operation
Here you define the sensor the thermostat is to use for its control function. S3, S4, or a combination of them. With the setting 0%, only S3 is used (Sin). With 100%, only S4.
Heat function
Set the size of the Neutral Zone for changeover from cooling to heating Time delay on transition from refrigeration phase to heating phase.
(there is not time delay on transition from heating phase to refrigeration phase).
Alarm Alarm settings
The controller can give alarm in different situations. When there is an alarm all the light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay will cut in.
Alarm delay (short alarm delay on air temperature) If the upper or the lower alarm limit values are exceeded, a timer function will com­mence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes.
Time delay for door alarm
The time delay is set in minutes. The function is defined in o02 , o37 or in o84.
Time delay for cooling (long alarm delay) This time delay is used during start-up, during defrost, immediately after a defrost. There will be change-over to the normal time delay (A03) when the temperature has dropped below the set upper alarm limit. The time delay is set in minutes.
Upper alarm limit
Here you set when the alarm for high temperature is to start. The limit value is set in °C (absolute value). The limit value will be raised during night operation. The value is the same as the one set for night setback, but will only be raised if the value is positive. In application 9 and 10 the setting is common for both S3 and S3B.
Lower alarm limit
Here you set when the alarm for low temperature is to start. The limit value is set in °C (absolute value). In application 9 and 10 the setting is common for both S3 and S3B.
Upper alarm limit for thermostat 2 (Thermostat band 2)
(Same function as for thermostat 1)
Lower alarm limit for thermostat 2 (Thermostat band 2)
(Same function as for thermostat 1)
Upper alarm limit for S6 temperature at thermostat 1 A22 HighLim1 S6 Lower alarm limit for S6 temperature at thermostat 1 A23 LowLim1 S6 Upper alarm limit for S6 temperature at thermostat 2 (Thermostat band 2) A24 HighLim2 S6 Lower alarm limit for S6 temperature at thermostat 2 (Thermostat band 2) A25 LowLim2 S6 S6 temperature alarm delay
The alarm is activated if one of the relevant alarm limits A22, A23, A24 or A25 is exceeded. The time delay is set in minutes. (Alarms will not activate when the setting is set to the maximum value.)
Delay of a DI1 alarm
A cut-out/cut-in input will result in alarm when the time delay has been passed. The function is defined in o02.
r17 Melt period
r21 Cutout2 temp
r59 Adjust S6
r61 Ther.S4% Ngt
r62 Heat NZ
r63 HeatStartDel
Night setbck (start of nightsignal. 0=Day, 1=Night)
Forced cool. (start of forced cooling)
Forced close (Forced stop of cooling)
With data communication the impor­tance of the individual alarms can be defined. Setting is carried out in the “Alarm destinations” menu via AKM.
A03 Alarm delay
A04 DoorOpen del
A12 Pulldown del
A13 HighLim Air
A14 LowLim Air
A20 HighLim2 Air
A21 LowLim2 Air
A26 Al. Delay S6
A27 AI.Delay DI1
16 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Delay of a DI2 alarm
A28 AI.Delay DI2 A cut-out/cut-in input will result in alarm when the time delay has been passed. The function is defined in o37
Signal to the alarm thermostat
A36 Alarm S4% Here you have to define the ratio between the sensors which the alarm thermostat has to use. S3, S4 or a combination of the two. With setting 0% only S3 is used. With 100% only S4 is used (Setting also applies to a possible B section.)
Time delay on S6 (product sensor) for pull-down (long alarm delay)
A52 PullD del.S6 This time delay is used for start-up, during defrosting, immediately after a defrost and after an appliance clean. A change is carried out to standard time delay (A26) when the temperature has reached below the set upper alarm limit. The time delay is set in minutes.
Alarm delay (short alarm delay on S3B air temperature)
A53 AI.Delay S3B A timer function starts if the top or bottom alarm limit is exceeded. The alarm will first becomes active when the set delay time has been exceeded. The time delay is set in minutes.
Reset alarm Ctrl. Error (EKC error)
Compressor Compressor control
The compressor relay works in conjunction with the thermostat. When the thermostat calls for refrigeration the compressor relay be operated.
Running times
To prevent irregular operation, values can be set for the time the compressor is to run once it has been started. And for how long it at least has to be stopped. The running times are not observed when defrosts start.
Min. ON-time (in minutes) c01 Min. On time
Min. OFF-time (in minutes) c02 Min. Off time
Time delay for couplings of two compressors
Settings indicate the time that has to elapse from the first relay cuts in and until the next relay has to cut in.
The LED on the controller’s front will show whether refrigeration is in progress. u58 comp7/LLSV
Defrost Defrost control
The controller contains a timer function that is zeroset after each defrost start. The timer function will start a defrost if/when the interval time is passed. The timer function starts when voltage is connected to the controller, but it is displaced the first time by the setting in d05. If there is power failure the timer value will be saved and continue from here when the power returns. This timer function can be used as a simple way of starting defrosts, but it will always act as safety defrost if one of the subsequent defrost starts is not received. The controller also contains a real-time clock. By means of settings of this clock and times for the required defrost times, defrost can be started at fixed times of the day. Defrost start can also be accomplished via data communication, via contact signals or manual start-up. All starting methods will function in the controller. The different functions have to be set, so that multiple defrosts are avoided.. Defrost can be accomplished with electricity, hotgas or brine. The actual defrost will be stopped based on time or temperature with a signal from a temperature sensor.
Defrost method
Here you set whether defrost is to be accomplished with electricity, gas, or (none). During defrost the defrost relay will be cut in.
Defrost stop temperature
The defrost is stopped at a given temperature which is measured with a sensor (the sen­sor is defined in d10). The temperature value is set.
c05 Step delay
Here you can read the status of the compressor relay.
d01 Def. method
0 = Off 1 = El 2 = Gas
d02 Def. Stop Temp
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 17
Interval between defrost starts
The function is zeroset and will start the timer function at each defrost start. When the time has expired the function will start a defrost. The function is used as a simple defrost start, or it may be used as a safeguard if the normal signal fails to appear. If master/slave defrost without clock function or without data communication is used, the interval time will be used as max. time between defrosts. If a defrost start via data communcation does not take place, the interval time will be used as max. time between defrosts. When there is defrost with clock function or data communication, the interval time must be set for a somewhat longer period of time than the planned one, as the interval time will otherwise start a defrost which a little later will be followed by the planned one. In connection with power failure the interval time will be maintained, and when the power returns the interval time will continue from the maintained value. The interval time is not active when set to 0.
Max. defrost duration
This setting is a safety time so that the defrost will be stopped if there has not already been a stop based on temperature or via coordinated defrost. (The setting is the defrost time if d10 is set to 0.)
Time staggering for defrost cutins during start-up
The function is only relevant if you have several refrigeration appliances or groups where you want the defrost to be staggered in relation to one another. The function is further­more only relevant if you have chosen defrost with interval start (d03). The function delays the interval time d03 by the set number of minutes, but it only does it once, and this at the very first defrost taking place when voltage is connected to the controller. The function will be active after each and every power failure.
Drip-off time
Here you set the time that is to elapse from a defrost and until the compressor is to start again. (The time when water drips off the evaporator).
d03 Def Interval
(0=off)
d04 Max Def. time
d05 Time Stagg.
d06 DripOff time
Delay of fan start after defrost
Here you set the time that is to elapse from compressor start after a defrost and until the fan may start again. (The time when water is “tied” to the evaporator).
Fan start temperature
The fan may also be started a little earlier than mentioned under “Delay of fan start after defrost”, if the defrost sensor S5 registers a lower value than the one set here.
Fan cut in during defrost
Here you can set whether fan is to operate during defrost. 0: Stopped (Runs during pump down) 1: Running (stopped during "fan delay") 2: Running during pump down and defrost. After that stopped
3: Running but stops at the set d41 temperature
Defrost sensor Here you define the defrost sensor. 0: None, defrost is based on time 1: S5 2: S4 3: Sx. For application 1 to 8 and 10 defrosting is stopped when both S5 and S6 have
reached the set temperature (Both sensors must be located on the evaporator). For application 9 defrosting is stopped individually on the two sections of S5 / S5B
Pumpdown delay
Set the time where the evaporator is emptied of refrigerant prior to the defrost.
Drain delay (only in connection with hotgas)
Set the time where the evaporator is emptied of condensed refrigerant after the defrost.
Defrost on demand – aggregate refrigeration time
Set here is the refrigeration time allowed without defrosts. If the time is passed, a defrost will be started. With setting = 0 the function is cut out.
Delay on stop of heating in the drip tray
The time applies from the time the defrost stops by time or temperature to the time the heating element in the drip tray needs to be disconnected.
Adaptive defrosting
An adaptive defrosting is an extra defrost in addition to the scheduled defrosts or a cancellation of a scheduled defrost. Here the adaptive defrost is set for when it can come into operation if the need arises: 0: Never, 1: Never, but triggers an alarm in the case of icing up 2: Cancellation of day schedule is permitted. Night schedule is carried out 3: Cancellation of day schedule is permitted. Cancellation of night schedule is permitted 4: All schedules are carried out + extra if it is registered that it is required. (Reset: Temporary setting to 0 will reset the recorded values and start a new calculation of the evaporator air flow.)
d07 FanStartDel
d08 FanStartTemp
d09 FanDuringDef
d10 DefStopSens.
d16 Pump dwn del.
d17 Drain del
d18 MaxTherRunT
d20 Drip Tray del
d21 AD mode
18 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Time delay before opening of hot gas valve, so a PMLX valve can close. d23 HotGasInjDel
Define Rail heat during defrost
d27 Railh. at def. 0=off. 1=on. 2=Pulsating
Max. duration of -d- in the display
d40 Disp. d del. Controls the readout of "-d-" after defrost, thus "-d-" is shown until the temperature is ok, set delay has expired, or a temperature alarm will occur.
Fan stop temperature during defrosting
d41 Def fan stop When the defrost stop temperature reaches the set value, the fans will stop. (If d09 is set to 3.)
If you wish to see the temperature at the defrost sensor, push the controller’s lowermost button. (May be changed to another function in o92.)
If you wish to start an extra defrost, push the controller’s lowermost button for four seconds. You can stop an ongoing defrost in the same way
Parameter for cooling function Max. value for the superheat reference (when regulated with dry expansion) Min. value for the superheat reference (when regulated with dry expansion) MOP temperature
If no MOP function is required, select pos. OFF
AKV valve’s time period in seconds
Should only be set to a lower value if it is a decentralised plant and the suction pressure fluctuates a lot and in line with the opening of the AKV valve.
Max. value for the superheat reference when regulating with flooded evapora-
Defrost temp.
Def Start Here you can start a manual defrost
Hold After Def Shows ON when the controller is operating with coordinated defrost.
Disable def. Defrost in progress can be stopped
Defrost State Status on defrost 1= pump down / defrost
n09 Max SH
n10 Min SH
n11 MOP temp
(A value of 15 corresponds to OFF)
n13 AKV Period
P86 Max SH Flood
tor Min. value for the superheat reference when regulating with flooded evaporator P87 Min SH Flood
Fan Fan control Fan stop temperature
The function stops the fans in an error situation, so that they will not provide power to the appliance. If the defrost sensor registers a higher temperature than the one set here, the fans will be stopped. There will be re-start at 2 K below the setting. The function is not active during a defrost or start-up after a defrost. With setting +50°C the function is interrupted.
Pulse operation of fan
0: No pulse operation 1: Pulse operation when the thermostat does not call for refrigeration 2: Pulse operation when the thermostat does not call for refrigeration, but only during night operation
Pulse operation period for fan
Here the overall pulse time is set. The sum of ON-to and OFF time.
ON time for fan
Here the % part of the period the fans are to be in operation is set. The LED on the controller’s front will indicate whether the fan is running.
F04 FanStopTemp.
F05 FanPulseMode
F06 Fan cycle
F07 Fan ON %
u59 Fan Relay
Here you can read the fan relay status, or force-control the relay in “Manual control” mode.
Internal defrosting schedule/clock function
(Not used if an external defrosting schedule is used via data communication.) Up to six individual times can be set for the defrost start throughout the day.
Defrost start, hour setting t01-t06 Defrost start, minute setting (1 and 11 belong together, etc.)
t11-t16
When all t01 to t16 equal 0 the clock will not start defrosts.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 19
Real-time clock:: Setting the clock is only necessary when there is no data communication.
In the event of a power failure of less than four hours, the clock function will be saved. Clock: Hour setting t07
Clock: Minute setting t08
Clock: Date setting t45
Clock: Month setting t46
Clock: Year setting t47
Miscellaneous Miscellaneous Delay of output signal after start-up
After start-up or a power failure the controller’s functions can be delayed so that over­loading of the electricity supply network is avoided. Here you can set the time delay.
Digital input signal - DI1
The controller has a digital input 1 which can be used for one of the following func­tions: Off: The input is not used
1) Status display of a contact function
2) Door function. When the input is open it signals that the door is open. The refrig­eration and the fans are stopped and light switched on. When the time setting in “A04” is passed, an alarm will be given and refrigeration will be resumed (o89).
3) Door alarm. When the input is open it signals that the door is open. When the time setting in “A04” is passed, there will be alarm.
4) Defrost. The function is started with a pulse signal. The controller will register when the DI input is activated. The controller will then start a defrost cycle.
5) Main switch. Regulation is carried out when the input is short-circuited, and regula­tion is stopped when the input is put in pos. OFF.
6) Night operation. When the input is short-circuited, there will be regulation for night operation.
7) Thermostat band changeover. Switch to thermostat 2 (r21) when the input is short­circuited.
8) Separate alarm function. Alarm will be given when the input is short-circuited.
9) Separate alarm function. Alarm will be given when the input is opened. (For 8 and 9 the time delay is set in A27)
10) Case cleaning. The function is started with a pulse signal. See also description on page 5.
11) Forced refrigeration at hotgas defrost when the input is short-circuited.
12) Night cover open / closed. Activated by pulse signal.
13,14) Not used
15) Appliance shutdown when the input is short-circuited.
20) Refrigerant leak alarm when the input is open.
21) Switch to operation with flooded evaporator when the input is short-circuited
If the controller is built into a network with data communication, it must have an address.
o01 DelayOfOutp.
o02 DI 1 Config.
Definition takes place with the nu­merical value shown to the left.
(0 = off)
DI state (Measurement) The DI input’s present status is shown here. ON or OFF.
The address is set between 0 and 240, depending on the system unit and the selected data communication. If the system unit is gateway type AKA 245, the version must be
6.20 or higher.
The address is sent to the gateway when the menu is set in pos. ON IMPORTANT: Before you set o04, you MUST set o61. Otherwise you will be transmit­ting incorrect data.
(The function is not used when the data communication is MODBUS)
Access code 1 (Access to all settings)
If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 100. If not, you can cancel the function with setting 0. (99 will always give you access).
Sensor type for S3, S4, S5
Normally a Pt 1000 sensor with great signal accuracy is used. But you can also use a sensor with another signal accuracy. That may either be a PTC 1000 sensor. All the mounted sensors S3-S5 must be of the same type.
Max. standby time after coordinated defrost When a controller has completed a defrost it will wait for a signal which tells that the refrigeration may be resumed. If this signal fails to appear for one reason or another, the controller will itself start the refrigeration when this standby time has elapsed. If the standby time expires, the alarm A5 is sent.
Select signal for the display S4%
Here you define the signal to be shown by the display. S3, S4, or a combination of the two. With setting 0% only S3 is used. With 100% only S4.
Pe. Working range for pressure transmitter - min. value
20 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
o03
o04
o05 Acc. code
o06 SensorConfig
Pt = 0 PTC = 1
o16 Max HoldTime
o17 Disp. S4%
o20 MinTransPres
Pe. Working range for pressure transmitter - max. value
Refrigerant setting (only if "r12" = 0) Before refrigeration is started, the refrigerant must be defined. You may choose be­tween the following refrigerants 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=Userdefined. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=R513A. 37=R407F. 38=R1234ze. 39=R1234yf. 40=R448A. 41=R449A. 42=R452A.
Warning: Wrong selection of refrigerant may cause damage to the compressor.
Other refrigerants: Here Setting 13 is selected and then three factors -Ref.Fac a1, a2 and a3 - via system unit or a AK software program.
Digital input signal - D2
The controller has a digital input 2 which can be used for one of the following func­tions: Off: The input is not used.
1) Status display of a contact function
2) Door function. When the input is open it signals that the door is open. The refrig­eration and the fans are stopped. When the time setting in “A04” is passed, an alarm will be given and refrigeration resumed. (o89).
3) Door alarm. When the input is open it signals that the door is open. When the time setting in “A04” is passed an alarm will be given.
4) Defrost. The function is started with a pulse signal. The controller will register when the DI input is activated. The controller will then start a defrost cycle. If the signal is to be received by several controllers it is important that ALL connections are mounted the same way (DI to DI and GND to GND).
5) Main switch. Regulation is carried out when the input is short-circuited, and regula­tion is stopped when the input is put in pos. OFF.
6) Night operation. When the input is short-circuited, there will be regulation for night operation.
7) Thermostat band changeover. Switch to thermostat 2 (r21) when the input is short-circuited.
8) Separate alarm function. Alarm will be given when the input is short-circuited.
9) Separate alarm function. Alarm will be given when the input is opened. (For 8 and 9 the time delay is set in A28)
10) Case cleaning. The function is started with a pulse signal. See also description on page 5.
11) Forced refrigeration at hotgas defrost when the input is short-circuited.
12) Night cover open / closed. Activated by pulse signal.
13) The input is used for coordinated defrost in conjunction with other controllers of the same type
14) Not used
15) Appliance shutdown when the input is short-circuited.
20) Refrigerant leak alarm when the input is open.
21) Switch to operation with flooded evaporator when the input is short-circuited
Configuration of light function
1) Light is controlled via day/night status
2) Light is controlled via data communication and "Light remote o39"
3) Light is controlled by door contact, defined in either o02, o37 or o84 where the set­ting is selected to either 2 or 3. When the door is opened the relay will cut in. When the door is closed again there will be a time delay of two minutes before the light is switched off.
4) As "2" but if there are any 15-minute network errors, the light will switch on and the night blind will open.
Activation of light relay via data communication
The light relay can be activated here, but only if defined in o38 with setting 2 or 4.
Rail heat during day operation
The ON period is set as a percentage of the time
Rail heat during night operation
The ON period is set as a percentage of the time
Rail heat cycle
The period of time for the aggregate ON time + OFF time is set in minutes
Case cleaning
The status of the function can be followed here or the function can be started manu­ally. 0 = Normal operation (no cleaning) 1 = Cleaning with fans operating. All other outputs are Off. 2 = Cleaning with stopped fans. All outputs are Off. If the function is controlled by a signal at the DI1, DI2 or DI3 input, the relevant status can be seen here in the menu.
o21 MaxTransPres
o30 Refrigerant
o37 DI2 config.
o38 Light config
o39 Light remote
o41 Railh.ON day%
o42 Railh.ON ngt%
o43 Railh. cycle
o46 Case clean
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 21
Selection of application
The controller can be defined in various ways. Here you set which of the 10 applica­tions is required. On page 12 you can see a survey of applications.
This menu can only be set when regulation is stopped, i.e. “r12” is set to 0.
Transfer a set of pre-settings to the controller
An option exists to select quick settings for a number of parameters. This is based on whether an appliance or a room needs to be controlled or whether the defrosting must be stopped by time or by temperature. The overview can be seen on page 27.
This menu can only be set when the control is stopped, i.e. When "r12" is set at 0.
On setting the value will fall back to 0. A subsequent adjustment/setting of param­eters can be carried out as required.
Access code 2 (Access to adjustments)
There is access to adjustments of values, but not to configuration settings. If the set­tings in the controller are to be protected with an access code you can set a numeri­cal value between 0 and 100. If not, you can cancel the function with setting 0. If the function is used, access code 1 (o05) must also be used.
Save as factory setting
With this setting you save the controller’s actual settings as a new basic setting (the earlier factory settings are overwritten).
o61 Appl. Mode
o62 -
o64 Acc. code 2
o67 -
Digital input signal - DI3 (high voltage input)
The controller has a digital input 3 which can be used for one of the following func­tions: Off: The input is not used.
1) Status display of 230 V signal
2) Door function. When the input is 0 V it signals that the door is open. The refrigera­tion and the fans are stopped. When the time setting in “A04” is passed, an alarm will be given and refrigeration resumed. (o89)
3) Door alarm. When the input is 0 V it signals that the door is open. When the time setting in “A04” is passed an alarm will be given.
4) Defrost. The function is started with a pulse signal. (puls on 230 V)
5) Main switch. Regulation is carried out when the input is 230 V, and regulation is stopped when the input is 0 V.
6) Night operation. When the input is 230 V, there will be regulation for night opera-
tion.
7) Thermostat band changeover. Switch to thermostat 2 (r21) when the input is 230 V.
8) Not used.
9) Not used.
10) Case cleaning. The function is started with a pulse signal (pulse on 230 V). See also description on page 5.
11) Forced refrigeration at hotgas defrost when the input is 230 V.
12) Night cover open / close. Activated by pulse signal (pulse on 230 V)
13) Not used
14) Cooling stopped with the function "Forced closing" when input is 230 V.
15) Case shutdown when input is 230 V.
21) Switch to operation with flooded evaporator when the input is 230 V
Rail heat control
The rail heat can be controlled in several ways: 0: The function is not used 1: Pulse control is used with a timer function following the day/night operation (o41 and o42) 2: Pulse control is used with a dew point function. This function requires that a signal is received about the dew point value. The value is measured by a system manager and sent to the controller via the data communication.
Dew point value where the rail heat is minimum
This function is discussed earlier in the manual.
Dew point value where the rail heat is maximum
This function is discussed earlier in the manual.
Lowest permitted rail heat effect
Here the % part of the effect to be achieved when the dew point value is minimum.
Start of refrigeration when door is open
If the door has been left open, refrigeration must be started after a set time. That time can be set here.
Defrosting and fan operation for "Forced Closing"
You can set whether fans should be operational or stopped if the function "Forced closing" is activated here. 0: The fans will be stopped and defrosting will be permitted. 1: The fans will run and defrosting will be permitted. 2: The fans will be stopped and defrosting will not be permitted. 3: The fans will run and defrosting will not be permitted.
o84 DI3 config.
o85 Railh. mode
o86 DewP Min lim
o87 DewP Max lim
o88 Rail Min ON%
o89 DoorInjStart
o90 Mode forcedCl
22 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Alternative display
A reading can be displayed by pressing the lower button on the controller. This read­ing is set from the factory so that the defrosting stop temperature is displayed. A different setting will give the following reading: 1: (Defrost stop temperature = factory setting) 2: S6 temperature (not application 9) 3: S3A temperature (one S3B will be shown via MODBUS display) 4: S4 Temperature
Display of temperature during normal operation
1: Air temperature. Weighted S3 + S4 2: Product temperature S6 (not in application 9)
Light and night blinds definition
0: Light is switched off and night blinds are open when the main switch is off 1: Light and night blinds are independent of main switch.
Configuration of alarm relay
The alarm relay will be activated upon an alarm signal from the following groups: 0 - Relay not used 1 - High temperature alarms 2 - Low temperature alarms 4 - Sensor error 8 - Digital input enabled for alarm 16 - Defrosting alarms 32 - Miscellaneous 64 - Injection alarms The groups that are to activate the alarm relay must be set by using a numerical value which is the sum of the groups that must be activated. (E.g.: a value of 5 will activate all high temperature alarms and all sensor error. 0 will cancel the relay function)
Service Service
Temperature measured with S5 sensor u09 S5 temp. Status on DI1 input. on/1=closed u10 DI1 status Read the duration of the ongoing defrost or the duration of the last completed
defrost. Temperature measured with S3 sensor u12 S3 air temp Status at the day-/night operation (night operation: on/off) u13 Night Cond. Temperature measured with S4 sensor u16 S4 air temp Thermostat temperature u17 Ther. air Read the ongoing cutin time for the thermostat or the duration of the last com-
pleted cutin Read the temperature at the S2 sensor u20 S2 temp. Read superheat u21 Superheat Read the control’s actual superheat reference u22 SH ref. Read the valve’s actual opening degree u23 AKV OD % Read the evaporating pressure u25 Evap.press Pe Read the evaporating temperature u26 Evap.temp Te Read the temperature at the S6 sensor u36 S6 temp Status on DI2 input. on/1=closed Air temperature. Weighted S3 + S4 u56 Display air Measured temperature for alarm thermostat * Status on relay for cooling u58 Comp1/LLSV * Status on relay for fan u59 Fan relay * Status on relay for defrost u60 Def. relay * Status on relay for railheat u61 Railh. relay * Status on relay for alarm u62 Alarm relay * Status on relay for light u63 Light relay * Status on relay for valve in suction line u64 SuctionValve * Status on relay for compressor 2 u67 Comp2 relay
* Temperature measured with S5B sensor
* Temperature measured with S3B sensor
* Status on relay for hot gas
* Status on relay for heating element in drip tray
* Status on relay for night blinds
* Status on relay for defrost B
* Status on relay for heat function
* Readout of the actual rail heat effect in %
o92 Displ menu 2
o97 Disp. Ctrl.
o98 Light MS = Off
P41 Al.Rel. Conf.
Case shutdown
u11 Defrost time
u18 Ther runtime
u37 DI2 status
u57 Alarm air
u75 S5 temp. B
u76 S3 air temp. B
u80 Hotgas valve
u81 Drip tray
u82 Blinds relay
u83 Def. relay B
u84 Heat relay
u85 Rail DutyC %
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 23
Readout of which thermostat used for regulation: 1= Thermostat 1, 2= Thermostat 2
Status on input DI3 (on/1 = 230 V)
Readout of the actual cutin value for the thermostat
Readout of the actual cut out value for the thermostat
Status on function "Adaptive defrost" 0: Off. Function is not activated and is zero set 1: Sensor error S3/S4 are reversed. 2: Tuning is in progress 3: Normal 4: Light build-up of ice 5: Medium build-up of ice 6: Heavy build-up of ice
Number of defrosts carried out since the initial power up or since the resetting of the function
Number of defrosts skipped since the initial power up or since the resetting of the function
Measured temperature for alarm thermostat for B section
Air temperature. Weighted S3 + S4 temp. for B section
*) Not all will be displayed. Only the function belonging to the selection application is displayed.
u86 Ther. band
u87 DI3 status
u90 Cutin temp.
u91 Cutout temp.
U01 AD state
U10 Acc.defrost
U11 Acc.def.skip
U34 Alarm air B
U35 Display air B
24 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Operating status (Measurement)
The controller goes through some regulating situations where it is just waiting for the next point of the regulation. To make these “why is nothing happening” situations
Ctrl. state:
(Shown in all menu displays) visible, you can see an operating status on the display. Push briefly (1s) the upper button. If there is a status code, it will be shown on the display. The individual status codes have the following meanings:
Normal regulation S0 0 Waiting for end of the coordinated defrost S1 1 When the compressor is operating it must run for at least x minutes. S2 2 When the compressor is stopped, it must remain stopped for at least x minutes. S3 3 The evaporator drips off and waits for the time to run out S4 4 Refrigeration stopped by main switch. Either with r12 or a DI-input S10 10 Refrigeration stopped by thermostat S11 11 Defrost sequence. Defrost in progress S14 14 Defrost sequence. Fan delay — water attaches to the evaporator S15 15 Refrigeration stopped due to open ON input or stopped regulation (forced closing) S16 16 Door is open. DI input is open S17 17 Melt function in progress. Refrigeration is interrupted S18 18 Modulating thermostat control S19 19 Emergency cooling due to sensor error *) S20 20 Regulation problem in the injections function S21 21 Start-up phase 2. Evaporator being charged S22 22 Adaptive control S23 23 Start-up phase 1. Signal reliability from sensors is controlled S24 24 Manual control of outputs S25 25 No refrigerant selected S26 26 Case cleaning S29 29 Forced cooling S30 30 Delay on outputs during start-up S32 32 Heat function r36 is active S33 33 Appliance shutdown S45 45 Operation with flooded evaporator S48 48
Other displays:
The defrost temperature cannot be displayed. There is stop based on time non Defrost in progress / First cooling after the defrost where the temperature is still
-d-
above the thermostat band. Password required. Set password PS Regulation is stopped via main switch OFF
*) Emergency cooling will take effect when there is lack of signal from a defined S3 or S4 sensor. The regulation will continue with a registered average
cutin frequency. There are two registered values – one for day operation and one for night operation.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 25
Fault message
In an error situation the LED’s on the front will flash and the alarm relay will be activated. If you push the top button in this situation you can see the alarm report in the display. There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation. A-alarms will not become visible until the set time delay has expired. E-alarms, on the other hand, will become visible the moment the error occurs. (An A alarm will not be visible as long as there is an active E alarm). Here are the messages that may appear:
Code / Alarm text via data communication
A1/--- High t.alarm
A2/--- Low t. alarm
A4/--- Door alarm
A5/--- Max hold time
A10/--- Inject prob.
A11/--- No Rfg. sel.
A13/--- High temp S6 Temperature alarm. High S6 1
A14/--- Low temp S6 Temperature alarm. Low S6 2
A15/--- DI1 alarm DI1 alarm 8
A16/--- DI2 alarm DI2 alarm 8
A45/--- Standby mode Standby position (stopped refrigeration via r12 or DI input) -
A59/--- Case clean Case cleaning. Signal from DI input -
A70/--- High temp S3B High temperature alarm, B section 1
A71/--- Low temp S3B Low temperature alarm, B-section 2
AA2/ ---Refrig Leak A refrigerant leak detection signal is received 8
AA3/--- CO2 alarm A refrigerant leak detection signal is received and the selected refrigerant is
--- AD fault Error in the adaptive defrost function 16
--- AD Iced Evaporator is iced up. Reduction of air flow 16
--- AD not defr. Defrost of evaporator is not satisfactory 16
--- AD flashgas Flash gas is formed at the valve 16
E1/--- Ctrl. error Faults in the controller 32
E6/--- RTC error Check clock 32
E20/--- Pe error Error on pressure transmitter Pe 64
E24/--- S2 error Error on S2 sensor 4
E25/--- S3 error Error on S3 sensor 4
E26/--- S4 error Error on S4 sensor 4
E27/--- S5 error Error on S5 sensor 4
E28/--- S6 error Error on S6 sensor 4
E34/--- S3 error B Error on S3B sensor 4
E37/--- S5 error B Error on S5B sensor 4
---/--- Max Def.Time Defrost stopped based on time instead of, as wanted, on temperature 16
Data communication
The importance of individual alarms can be defined with a setting. The setting must be carried out in the group "Alarm destinations"
Settings from System manager High 1 X X X X Middle 2 X X X Low 3 X X X Log only X Disabled
Description Alarm relay groups (P41)
High temperature alarm
Low temperature alarm
Door alarm
The ”o16” function is activated during a coordinated defrost
Control problem
No refrigerant selected
CO2
Settings from AKM (AKM destination)
Log Alarm relay Send via
Non High Low-High
Network
1
2
8
16
64
64
8
26 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B

Operation

Display
The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.
Light-emitting diodes (LED) on front panel
The LED’s on the front panel will light up when the relevant relay is activated.
= Refrigeration = Defrost = Fan running
The light-emitting diodes will flash when there is an alarm. In this situation you can download the error code to the display and cancel/sign for the alarm by giving the top button a brief push.
The buttons
When you want to change a setting, the upper and the lower buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the col­umn with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value, save the new value by once more pushing the middle button.
Examples
Set menu
1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and find that parameter you want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to freeze the value.
Get a good start
With the following procedure you can start regulation very quick­ly:
1 Open parameter r12 and stop the regulation (in a new and not
previously set unit, r12 will already be set to 0 which means stopped regulation.)
2 Select electrical connection based on the drawings on page 12
and 13
3 Open parameter o61 and set the electric connection number in
it
4 Now select one of the preset settings from the table on page 27.
5 Open parameter o62 and set the number for the array of preset-
tings. The few selected settings will now be transferred to the menu.
6 Select refrigerant via parameter o30
7 Open parameter r12 and start the regulation
8 Go through the survey of factory settings. The values in the grey
cells are changed according to your choice of settings. Make any necessary changes in the respective parameters.
9 For network. Set the address in o03
10 Send address to system unit:
• MODBUS: Activate scan function in system unit
• If another data communication card is used in the controller:
- LON RS485: Activate the function o04
- DANBUSS: Activate the scanfunction in the system unit
- Ethernet: Use the MAC Address
Cutout alarm relay / receipt alarm/see alarm code
• A short press of the upper button
If there are several alarm codes they are found in a rolling stack. Push the uppermost or lowermost button to scan the rolling stack.
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor (Or product sensor, if selected in o92.)
• A short press of the lower button
Manuel start or stop of a defrost
• Push the lower button for four seconds.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 27
Auxiliary schedule for settings (quick-setup)
Case Room
Defrost stop on
time
Preset settings (o62) 1 2 3 4 5 6
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Sensor signal for thermostat. S4% (r15)
Alarm limit high (A13)
Alarm limit low (A14)
Sensor signal for alarm funct.S4% (A36)
Interval between defrost (d03)
Defrost sensor: 0=time, 1=S5, 2=S4 (d10)
DI1 config. (o02)
Sensor signal for display view S4% (017)
2°C -2°C -28°C 4°C 0°C -22°C
6°C 4°C -22°C 8°C 5°C -20°C
0°C -4°C -30°C 0°C -2°C -24°C
8°C 6°C -15°C 10°C 8°C -15°C
-5°C -5°C -30°C 0°C 0°C -30°C
0% 100% 0%
6 h 6h 12h 8h 8h 6h
0 1 1 0 1 1
Case cleaning (=10) Door function (=2)
Defrost stop
on S5
100% 0%
Defrost stop on
time
0%
Defrost stop
on S5
28 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B

Menu survey

Parameter
Function
Code 1 2 3 4 5 6 7 8 9 10
Normal operation
Temperature (setpoint) - - - 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 2
Thermostat
Differential r01 1 1 1 1 1 1 1 1 1 1 0.1 K 20 K 2
Max. limitation of setpoint setting
Min. limitation of setpoint setting
Adjustment of temperature indication
Temperature unit (°C/°F)
Correction of the signal from S4
Correction of the signal from S3 and S3B
Manual service, stop regulation, start regulation (-1, 0, 1)
Displacement of reference during night operation
Define thermostat function 1=ON/OFF, 2=Modulating
Definition and weighting, if applicable, of thermostat sen­sors - S4% (100%=S4, 0%=S3)
Time between melt periods
Duration of melt periods
Temperature setting for thermostat band 2 . As differential
r02 1 1 1 1 1 1 1 1 1 1 -49°C 50°C 50
r03 1 1 1 1 1 1 1 1 1 1 -50°C 49°C -50
r04 1 1 1 1 1 1 1 1 1 1 -10 10 0
r05 1 1 1 1 1 1 1 1 1 1 0/°C 1/F 0/°C
r09 1 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
r10 1 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
r12 1 1 1 1 1 1 1 1 1 1 -1 1 0
r13 1 1 1 1 1 1 1 1 1 1 -50 K 50 K 0
r14 1 1 1 1 1 1 1 1 1 1 1 2 1
r15 1 1 1 1 1 1 1 1 1 1 0 % 100 % 100
r16 1 1 1 1 1 1 1 1 1 1 0 hrs 10 hrs 1
r17 1 1 1 1 1 1 1 1 1 1 0 min. 30 min. 5
r21 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 2
use r01
Correction of the signal from S6 r59 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
Definition and weighting, if applicable, of thermostat sen­sors when night cover is on. (100%=S4, 0%=S3)
Heat function
r61 1 1 1 1 1 1 1 1 1 1 0 % 100 % 100
r62 1 0 K 50 K 2
Neutral zone between refrigeration and heat function
Time delay at switch between refrigeration and heat
r63 1 0 min. 240 min. 0
function
Alarms
Delay for temperature alarm
Delay for door alarm
Delay for temperature alarm after defrost
High alarm limit for thermostat 1
Low alarm limit for thermostat 1
High alarm limit for thermostat 2
Low alarm limit for thermostat 2
High alarm limit for sensor S6 at thermostat 1
Low alarm limit for sensor S6 at thermostat 1
High alarm limit for sensor S6 at thermostat 2
Low alarm limit for sensor S6 at thermostat 2
S6 alarm time delay With setting = 240 the S6 alarm will be omitted
Alarm time delay or signal on the DI1 input
Alarm time delay or signal on the DI2 input
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A03 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
A04 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 60
A12 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 90
A13 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
A14 1 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
A20 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
A21 1 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
A22 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
A23 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
A24 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
A25 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
A26 1 1 1 1 1 1 1 1 1 0 min. 240 min. 240
A27 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
A28 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
A36 1 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Delay for S6 (product sensor alarm) after defrost A52 1 1 1 1 1 1 1 1 1 0 min. 240 min. 90
Delay for temperature alarm S3B
A53 1 1 0 min. 240 min. 90
Compressor
Min. ON-time c01 1 1 1 1 0 min. 30 min. 0
Min. OFF-time c02 1 1 1 1 0 min. 30 min. 0
Time delay for cutin of comp.2
c05 1 0 sec 999 sec 5
Defrost
Defrost method: 0=Off, 1= EL, 2= Gas d01 1 1 1 1 1 1 1 1 1 1 0/Off 2/gAs 1/EL
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Displacement of time on cutin of defrost at start-up
Drip off time
Delay for fan start after defrost
Fan start temperature
d02 1 1 1 1 1 1 1 1 1 1 0°C 50°C 6
d03 1 1 1 1 1 1 1 1 1 1 0 hrs/Off 240 hrs 8
d04 1 1 1 1 1 1 1 1 1 1 0 min. 360 min. 45
d05 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 0
d06 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0
d07 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0
d08 1 1 1 1 1 1 1 1 1 1 -50 °C 0 °C -5
EL-diagram page 12 or 13
Min.-value Max.-value
Factory
setting
SW = 2.0x
Actual
setting
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 29
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Fan cutin during defrost
d09 1 1 1 1 1 1 1 1 1 1 0 3 1 0: Stopped 1: Running 2: Running during pump down and defrost 3: Running but stops at the temperature set in d41
Defrost sensor: 0 =Stop on time, 1=S5, 2=S4, 3=Sx
d10 1 1 1 1 1 1 1 1 1 1 0 3 0 (Application 1-8 and 10: both S5 and S6. Application 9: S5 and S5B)
Pump down delay
d16 1 1 1 1 1 1 1 1 1 1 0 min. 60 min. 0
Drain delay (used at hot gas defrost only) d17 1 0 min. 60 min. 0
Max. aggregate refrigeration time between two defrosts
Heat in drip tray. Time from defrosting stops to heating
d18 1 1 1 1 1 1 1 1 1 1 0 hrs 48 hrs 0/OFF
d20 1 0 min. 240 min. 30 in the drip tray is switched off
Adaptive defrost:
d21 1 1 1 1 1 1 1 1 1 1 0 4 0 0=not active, 1=monitoring only, 2=skip allowed day, 3=skip allowed both day and night, 4=own assessment + all schedules
Time delay before opening of hot gas valve d23 1 0 min 60 min 0
Rail heat during defrost 0=off. 1=on. 2=Pulsating
Max. duration of -d- in display d40 1 1 1 1 1 1 1 1 1 1 5 min. 240 min. 30 min.
Temperature limit for fan stop during defrost when d09 is set to 3
Injection control function
Max. value of superheat reference (dry expansion)
Min. value of superheat reference (dry expansion)
d27 1 1 1 1 1 1 1 0 2 2
d41 1 1 1 1 1 1 1 1 1 1 -20°C 20°C 0
n09 1 1 1 1 1 1 1 1 1 1 2°C 20°C 12
n10 1 1 1 1 1 1 1 1 1 1 2°C 20°C 3
MOP temperature. Off if MOP temp. = 15.0 °C n11 1 1 1 1 1 1 1 1 1 1 -50°C 15°C 15
Period time of AKV pulsation
Only for trained personnel
Max. limitation for the superheat reference when regulating with flooded evaporator
Min. limitation for the superheat reference when regulating with flooded evaporator
n13 1 1 1 1 1 1 1 1 1 1 3 sec 6 sec 6
P86 1 1 1 1 1 1 1 1 1 1 1°C 20°C 3
P87 1 1 1 1 1 1 1 1 1 1 0°C 20°C 1
Fan
Fan stop temperature (S5)
Pulse operation on fans: 0=No pulse operation, 1=At
F04 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 50
F05 1 1 1 1 1 1 1 1 1 1 0 2 0 thermostat cuts out only, 2= Only at thermostat cut outs during night operation
Period time for fan pulsation (on-time + off-time) F06 1 1 1 1 1 1 1 1 1 1 1 min. 30 min. 5
On-time in % of period time F07 1 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Real time clock
Six start times for defrost. Setting of hours. 0=OFF
Six start times for defrost. Setting of minutes. 0=OFF
Clock - Setting of hours
Clock - Setting of minute
Clock - Setting of date
Clock - Setting of month
Clock - Setting of year
Miscellaneous
Delay of output signals after power failure
Input signal on DI1. Function: 0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation 7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm function when open. 10=appliance cleaning (pulse signal). 11=forced cooling at hot gas defrost, 12=night cover. 15=appliance
t01 -
1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0
t06
t11 -
1 1 1 1 1 1 1 1 1 1 0 min. 59 min. 0
t16
t07 1 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0
t08 1 1 1 1 1 1 1 1 1 1 0 min. 59 min. 0
t45 1 1 1 1 1 1 1 1 1 1 1 day 31 day 1
t46 1 1 1 1 1 1 1 1 1 1 1 mon. 12 mon. 1
t47 1 1 1 1 1 1 1 1 1 1 0 year 99 year 0
o01 1 1 1 1 1 1 1 1 1 1 0 sec 600 sec 5
o02 1 1 1 1 1 1 1 1 1 1 0 21 0
shutdown. 20=Refrigerant alarm. 21= flooded evaporator at short circuited
Network address
On/Off switch (Service Pin message) IMPORTANT! o61 must be set prior to o04
o03 1 1 1 1 1 1 1 1 1 1 0 240 0
o04 1 1 1 1 1 1 1 1 1 1 0/Off 1/On 0/Off
(used at LON 485 only)
Access code 1 (all settings)
Used sensor type : 0=Pt1000, 1=Ptc1000, o06 1 1 1 1 1 1 1 1 1 1 0/Pt 1/Ptc 0/Pt
Max hold time after coordinated defrost
o05 1 1 1 1 1 1 1 1 1 1 0 100 0
o16 1 1 1 1 1 1 1 1 1 1 0 min. 360 min. 20
30 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Select signal for display view. S4% (100%=S4, 0%=S3)
Pressure transmitter working range – min. value
Pressure transmitter working range – max. value
Refrigerant setting:
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13.
7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User defined. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=R513A. 37=R407F.
38=R1234ze. 39=R1234yf. 40=R448A. 41=R449A. 42=R452A
Input signal on DI2. Function: (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation 7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm function when open. 10=appliance cleaning (pulse signal). 11=forced cooling at hot gas defrost.). 12=night cover, 13=coordinated defrost). 15=appliance shutdown. 20=Refrigerant alarm. 21=
flooded evaporator at short circuited
Configuration of light function: 1=Light follows day /night
operation, 2=Light control via data communication via ‘o39’, 3=Light control with a DI-input, 4=As "2", but light switch on and night cover will open if the network cut out for more than 15 minutes.
Activation of light relay (only if o38=2) On=light
Rail heat On time during day operations
Rail heat On time during night operations
Rail heat period time (On time + Off time)
Appliance cleaning. 0=no appliance cleaning. 1=Fans only. 2=All output Off.
Selection of EL diagram. See overview page 12 and 13
Download a set of predetermined settings. See overview page 27.
Access code 2 (partial access)
Replace the controllers factory settings with the present settings
Input signal on DI3. Function: (high voltage input) (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation,
7=thermostat band changeover (activate r21). 8=Not used. 9=Not used. 10=appliance cleaning (pulse signal).
11=forced cooling at hot gas defrost, 12=night cover.
13=Not used. 14=Refrigeration stopped (forced closing)). 15=appliance shutdown. 21=flooded evaporator
Rail heat control 0=not used, 1=pulse control with timer function (o41 and o42), 2=pulse control with dew point function
Dew point value where the rail heat is minimum
Dew point value where the rail heat is 100% on
Lowest permitted rail heat effect in %
Time delay from "open door” refrigeration is started
Fan operation on stopped refrigeration (forced closing):
0 = Stopped (defrosting permitted) 1 = Running (defrosting permitted) 2 = Stopped (defrosting not permitted) 3 = Running (defrosting not permitted)
Definition of readings on lower button: 1=defrost stop temperature, 2=S6 temperature, 3=S3 temperature , 4=S4 temperature
Display of temperature 1= u56 Air temperature (set automtically to 1 at application 9) 2= u36 product temperature
Light and night blinds defined 0: Light is switch off and night blind is open when the main switch is off 1: Light and night blind is independent of main switch
o17 1 1 1 1 1 1 1 1 1 1 0 % 100 % 100
o20 1 1 1 1 1 1 1 1 1 1 -1 bar 5 bar -1
o21 1 1 1 1 1 1 1 1 1 1 6 bar 200 bar 12
o30 1 1 1 1 1 1 1 1 1 1 0 42 0
o37 1 1 1 1 1 1 1 1 1 1 0 21 0
o38 1 1 1 1 1 1 1 1 1 4 1
o39 1 1 1 1 1 1 1 1 0/Off 1/On 0/Off
o41 1 1 1 1 1 1 1 0 % 100 % 100
o42 1 1 1 1 1 1 1 0 % 100 % 100
o43 1 1 1 1 1 1 1 6 min. 60 min. 10
*** o46 1 1 1 1 1 1 1 1 1 1 0 2 0
* o61 1 1 1 1 1 1 1 1 1 1 1 10 1
* o62 1 1 1 1 1 1 1 1 1 1 0 6 0
*** o64 1 1 1 1 1 1 1 1 1 1 0 100 0
o67 1 1 1 1 1 1 1 1 1 1 0/Off 1/On 0/Off
o84 1 1 1 1 1 1 1 1 1 1 0 21 0
o85 1 1 1 1 1 1 1 0 2 0
o86 1 1 1 1 1 1 1 -10°C 50°C 8
o87 1 1 1 1 1 1 1 -9°C 50°C 17
o88 1 1 1 1 1 1 1 0 % 100 % 30
o89 1 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
o90 1 1 1 1 1 1 1 1 1 1 0 3 1
o92 1 1 1 1 1 1 1 1 1 1 1 4 1
o97 1 1 1 1 1 1 1 1 1 1 1 2 1
o98 1 1 1 1 1 1 1 1 1 1 0 1 0
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 31
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Configuration of alarm relay The alarm relay will be activated upon an alarm signal from the following groups: 0 - Alarm relay not used 1 - High temperature alarms 2 - Low temperature alarms 4 - Sensor error 8 - Digital input enabled for alarm 16 - Defrosting alarms 32 - Miscellaneous 64 - Injection alarms The groups that are to activate the alarm relay must be set by using a numerical value which is the sum of the groups that must be activated. (E.g.: a value of 5 will activate all high temperature alarms and all sensor error.
P41 1 1 1 1 1 0 127 111
32 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
Continued Code 1 2 3 4 5 6 7 8 9 10 Min. Max. Fac. Actual
Service
Temperature measured with S5 sensor
Status on DI1 input. on/1=closed
Actual defrost time (minutes)
Temperature measured with S3 sensor
Status on night operation (on or off) 1=on
Temperature measured with S4 sensor
Thermostat temperature
Run time of thermostat (cooling time) in minutes
Temperature of evaporator outlet temp.
Superheat across evaporator
Reference of superheat control
Opening degree of AKV valve
Evaporating pressure Po (relative)
Evaporator temperature To (Calculated)
Temperature measured with S6 sensor
u09 1 1 1 1 1 1 1 1 1 1
u10 1 1 1 1 1 1 1 1 1 1
u11 1 1 1 1 1 1 1 1 1 1
u12 1 1 1 1 1 1 1 1 1 1
u13 1 1 1 1 1 1 1 1 1 1
u16 1 1 1 1 1 1 1 1 1 1
u17 1 1 1 1 1 1 1 1
u18 1 1 1 1 1 1 1 1 1 1
u20 1 1 1 1 1 1 1 1 1 1
u21 1 1 1 1 1 1 1 1 1 1
u22 1 1 1 1 1 1 1 1 1 1
** u23 1 1 1 1 1 1 1 1 1 1
u25 1 1 1 1 1 1 1 1 1 1
u26 1 1 1 1 1 1 1 1 1 1
u36 1 1 1 1 1 1 1 1 1
(product temperature)
Status on DI2 input. on/1=closed
Air temperature . Weighted S3 and S4
Measured temperature for alarm thermostat
Status on relay for cooling
Status on relay for fan
Status on relay for defrost
Status on relay for railheat
Status on relay for alarm
Status on relay for light
Status on relay for valve in suction line
Status on relay for compressor 2
Temperature measured with S5B sensor
Temperature measured with S3B sensor
Status on relay for hot gas- / drain valve
Status on relay for heating element in drip tray
Status on relay for night blinds
Status on relay for defrost B
Status on relay for heat function
Readout of the actual rail heat effect
1: Thermostat 1 operating, 2: Thermostat 2 operating
Status on high voltage input DI3
Readout of thermostats actual cut in value
Readout of thermostats actual cut out value
Readout of status on the adaptive defrost
u37 1 1 1 1 1 1 1 1 1 1
u56 1 1 1 1 1 1 1 1 1 1
u57 1 1 1 1 1 1 1 1 1 1
** u58 1 1 1 1
** u59 1 1 1 1 1 1 1 1 1 1
** u60 1 1 1 1 1 1 1 1 1
** u61 1 1 1 1 1 1 1
** u62 1 1 1 1 1
** u63 1 1 1 1 1 1 1 1
** u64 1
** u67 1
u75 1
u76 1 1
** u80 1
** u81 1
** u82 1
** u83 1
** u84 1
u85 1 1 1 1 1 1 1
u86 1 1 1 1 1 1 1 1 1 1
u87 1 1 1 1 1 1 1 1 1 1
u90 1 1 1 1 1 1 1 1 1 1
u91 1 1 1 1 1 1 1 1 1 1
U01 1 1 1 1 1 1 1 1 1 1 0: Off. Function is not activated and are zero set 1: Sensor error or S3/S4 are reversed. 2: Tuning is in progress 3: Normal 4: Light build-up of ice 5: Medium build-up of ice 6: Heavy build-up of ice
Number of defrosts carried out since the initial power
U10 1 1 1 1 1 1 1 1 1 1
up or since the resetting of the function Number of defrosts skipped since the initial power up
U11 1 1 1 1 1 1 1 1 1 1
or since the resetting of the function
Measured temperature for alarm thermostat in section B U34
Air temperature in section B U35
1 1
1 1
*) Can only be set when regulation is stopped (r12=0) **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 33

Connections

Overview of outputs and applications.
See also electrical diagrams earlier in the manual
DI1
Digital input signal. The defined function is active when the input is short-circuited/ opened. The function is defined in o02.
DI2
Digital input signal. The defined function is active when the input is short-circuited/ opened. The function is defined in o37.
Pressure transmitter
AKS 32R
Connect to terminal 30, 31 and 32. (Used cable 060G1034: Black=30, Blue=31, Brown=32) The signal from one pressure transmitter can be received by up to 10 controllers. But only if there are no significant pressure decreases between the evaporators to be controlled. See drawing page 34.
S2, S6
Pt 1000 ohm sensor
S6, product sensor.
S3, S4, S5
Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of the same type.
S3, air sensor, placed in the warm air before the evaporator S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the configuration)
S5, defrost sensor, placed on the evaporator
Application DO1 DO2 DO3 DO4 DO5 DO6 DI1 DI2 DI3 AI1 AI2 AI3 AI4 AI5 AI6 AI7
1
2
3
4
5
6
7
8
9
10
• •
• •
• •
• •
• •
suction
Blinds
heat
hotgas
2 1
• •
• •
• •
• •
• •
RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication module is inserted in the controller. The module can be a LON RS485, DANBUSS or a MODBUS. Terminal 51 = screen Terminal 52 = A (A+) Terminal 53 = B (B-) (For LON RS485 and gateway type AKA 245 the gateway must be version 6.20 or higher.)
RJ45
For data communication, but only if a TCP/IP module is inserted in the controller. (OEM specific)
MODBUS
For data communication. Terminal 56 = screen Terminal 57 = A+ Terminal 58 = B­(Alternatively the terminals can be connected to an external display type EKA 163A or 164A, but then they cannot be used for data communication. Any data communication must then be carried out by one of the other methods.)
Supply voltage
230 V a.c.
DO1
Connection of expansion valve type AKV or AKVA. The coil must be a 230 V a.c. coil.
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S6
P0 S2 S3 S4 S5 S3B S5B
P0 S2 S3 S4 S5 S3B S6
EKA Display
If there is be external reading/operation of the controller, display type EKA 163B or EKA 164B can be connected.
34 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
DO2
Alarm
There is a connection between terminal 7 and 8 in alarm situations and when the controller is without power.
Rail heat and heating element in drip tray
There is connection between terminal 7 and 9 when heating takes place.
Night blind
There is connection between terminal 7 and 9 when the night blind is up.
Suction line valve
There is connection between terminal 7 and 9 when the suction line must be open.
DO3
Refrigeration, Rail heat, Heat function, Defrost 2
There is connection between terminal 10 and 11 when the function must be active.
Heating element in drip tray
There is connection between terminal 10 and 11 when heating takes place.
DO4
Defrost
There is connection between terminal 12 and 14 when defrosting takes place.
Hot gas / drain valve
There is connection between terminal 13 and 14 during normal operation. There is connection between terminal 12 and 14 when the hot gas valves must open.
DO5
Fan
There is connection between terminal 15 and 16 when the fan is on.
Coordinated defrost via cable connections
DO6
Light relay
There is connection between terminal 17 and 18 when the light must be on.
Rail heat, Compressor 2
There is connection between terminal 17 and 19 when the function must be active.
DI3
Digital input signal. The signal must have a voltage of 0 / 230 V AC. The function is defined in o84.
Data communication
If data communication is used, it is important that the installation of the data communication cable is performed correctly. See separate literature No. RC8AC…
Electric noise
Cables for sensors, DI inputs and data communication must be kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided
Installation considerations
Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and ultimately lead to a plant breakdown. Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation, for example, could still present problems. Electronic controls are no substitute for normal, good engineering practice. Danfoss will not be responsible for any goods, or plant compo­nents, damaged as a result of the above defects. It is the installer's responsibility to check the installation thoroughly, and to fit the necessary safety devices. Special reference is made to the necessity of signals to the controller when the compressor is stopped and to the need of liquid receivers before the compressors. Your local Danfoss agent will be pleased to assist with further advice, etc.
Max. 10
The following controllers can be connected up in this way: EKC 204A, AK-CC 210, AK-CC 250, AK-CC 450, AK-CC 550A,
Refrigeration is resumed when all controllers have “released” the signal for defrost.
Coordinated defrost via data communication
The setting of controllers to coordinate their defrosting takes place in the gateway/system manager.
Refrigeration is resumed when all controllers have “released” the signal for defrost.
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 35

Data

Supply voltage 230 V a.c. +10/-15 %. 5 VA, 50/60 Hz
Sensor S2, S6 Pt 1000
Sensor S3, S3B, S4, S5, S5B
Accuracy
Measuring of Pe
Display LED, 3-digits
External display EKA 163B or 164B. (any EKA 163A or 164A)
Digital inputs DI1, DI2
Digital input DI3 230 V a.c.
Electrical con­nection cable
Solid state output
Relays*
Pt 1000 or PTC 1000 ohm (All must be of the same type)
Measuring range -60 to +120°C
Controller
Pt 1000 sensor
Pressure transmitter
Signal from contact functions Requirements to contacts: Gold plating Cable length must be max. 15 m Use auxiliary relays when the cable is longer
Max.1.5 mm2 multi-core cable
DO1 (for AKV coil)
DO3, DO4 4 (3) A
±1 K below -35°C ±0.5 K between -35 to +25°C ±1 K above +25°C
±0.3 K at 0°C ±0.005 K per grad
AKS 32R
Max. 240 V a.c. , Min. 28 V a.c. Max. 0.5 A Leak < 1 mA Max. 1 pcs. AKV (2 pcs. if EEC coils are used)
CE (250 V a.c.)
AKV info !!
DO2, DO5, DO6 4 (3) A
0 to +55°C, During operations
Environments
Density IP 20
Mounting DIN-rail or wall
Weight 0.4 Kg
Data communication
Power reserve for the clock
Approvals
* DO3 and DO4 are 16 A relays. DO2, DO5 and DO6 are 8 A relays. Max. load must be observed.
-40 to +70°C, During transport
20 - 80% Rh, not condensed
No shock influence / vibrations
Fixed MODBUS
LON RS485
Extension options
The controller cannot be hooked up with a monitor­ing unit type m2.
4 hours
EU Low Voltage Directive and EMC demands re CE­marking complied with LVD tested acc. EN 60730-1, EN 60730-2-1 and EN 60730-2-9 EMC tested acc. EN 61000-6-2 and EN 61000-6-3
TCP/IP
MODBUS
DANBUSS
230 V a.c. coil
AKS 32R info
The signal from one pressure transmitter can be received by up to ten controllers.
36 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B

Ordering

Type Function Code no.
AK-CC 550B Case controller with MODBUS data communication 084B8032
EKA 175
EKA 178B Data communication module MODBUS 084B8571
EKA 176 Data communication module DANBUSS + gateway 084B8583
EKA 176A Data communication module DANBUSS + AK-PI 200 084B8591
EKA 163B External display with plug for direct connection 084B8574
EKA 164B
EKA 163A External display with screw terminals 084B8562
EKA 164A External display with operation buttons and screw terminals 084B8563
Data communication module LON RS 485
External display with operation buttons and plug for direct connections
084B8579
084B8575
Examples of order
Installation Data communication Connection Code no.
MODBUS 084B8032 (AK-CC 550B)
LON 084B8032
DANBUSS 084B8032
MODBUS 084B8032
L
L < 15 m
L
LON / DANBUSS 084B8032
MODBUS / LON / DANBUSS 084B8032
084B8579
084B8583
084B8574 (Display) 084B7299 (Cable, 6 m)
084B8574 (Display) 084B7299 (Cable, 6 m) 084Bxxxx (Data module)
084B8562 (Display) 084Bxxxx (Data module)
L > 15 m
AK-CC 550B User guide RS8GL402 © Danfoss 2018-11 37
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
38 User guide RS8GL402 © Danfoss 2018-11 AK-CC 550B
ADAP-KOOL®
Loading...