Danfoss AK-CC 550A, AK-SM 800 Service guide

Service Guide
Configuration
AK-CC 550A to AK-SM 800
ADAP-KOOL® Refrigeration Control System
Service Guide | AK-CC 550A to AK-SM 800 Configuration
Initial Setup/Checks @ Case Controller
Wiring at AK-SM 850/880
Wiring at AK-CC 550A
LON wiring Modbus
wiring
2. With power applied to AK-CC 550A, set parameter o03 (address) and o61 (application). To set: a. Hold top button in for 5 seconds until ‘r01’ is displayed, then
use top/bottom buttons to scroll to each parameter.
b. Press middle button on parameter to view value, top/bottom
to change to desired value, and middle button again to set.
c. Parameter o03 is unique to each controller, and parameter
o61 is typically set to ‘2’.
For LON wiring, comm card should also be installed behind cover
2 | AX278934146190en-000101
© Danfoss | ADAP-KOOL® | 2018.08
Service Guide | AK-CC 550A to AK-SM 800 Configuration
Setup at System Manager
*This section is detailed with the assumption that an existing program is in place including cases and addresses.
1. At system manager, press Menu button and select ‘2’ for Network Nodes
2. Confirm proper channel (Modbus or LON) is enabled at top of screen. (refer to 1st page for information on how to check which channel you are using if needed). Once confirmed, highlight and select line ‘Press for complete rescan’.
3. Once rescan is complete, navigate to Config Status tab to confirm case controller is online (will need to know address).
© Danfoss | ADAP-KOOL® | 2018.08
AX278934146190en-000101 | 3
Service Guide | AK-CC 550A to AK-SM 800 Configuration
Downloading setpoints to AK-CC 550A
1. In AK-SM 800, navigate to Configuration->Control->Refrigeration->Circuits->Setup­>Download.
*If prompted at any point to ‘retrieve configuration from device’, select ‘No’.
2. Select addresses of case controllers to be downloaded, so that check mark appears next to address. Then scroll to top of screen and select ‘Press to download to selection’. Controller will timestamp each address after download completes successfully.
Checks for offline AK-CC 550A
1. Wiring a. Comm wiring polarity. LON wiring is not polarity sensitive, but
MODBUS wiring is polarity sensitive.
b. Is comm loop distance > 1200m? If so, repeater should be
added.
c. Is there an EOL resistor at end of loop (120 ohms).
2. Case Controller a. If using LON comm, has comm card been installed? b. Does address in AK-CC 550A match address assigned in AK-
SM 800?
3. System Manager a. Are there >120 case controllers in the program of the system
manager? If so, limit has been exceeded. Some controllers will need to be moved to another system manager.
b. Check Duplicates tab under Network Nodes to ensure
multiple controllers have not been assigned an identical address by mistake.
4 | AX278934146190en-000101
© Danfoss | ADAP-KOOL® | 2018.08
Service Guide | AK-CC 550A to AK-SM 800 Configuration
Other Potential Issues
1. Mismatch. If AK-CC 550A status screen shows ‘Mismatch’, then controller firmware or application differs from selection in AK­SM 800. To correct: a. Go to Network Nodes-> Scan Status and Locate Address. Note
Model listed for address. Model will confirm firmware version and application of device. In example below, ‘-019’ indicates a v1.9 firmware version, and ‘B’ indicates application 2 (A = 1, B = 2, etc).
b. Go to Configuration->Refrigeration->Circuits. Under ‘Type’
tab, locate case in list and verify model matches description from Scan Status screen (a). This will also require you to verify selected part # is correct (084B8036 in example below). Part # is printed on case controller.
c. If type is not a match, verify whether this is because of part #,
application, or firmware. i. For application, verify whether selection in AK-SM 800
is wrong or AK-CC 550A. If in AK-CC 550a, go to case controller and change parameter o61 to correct value. Then rescan. If AK-SM 800 selection is wrong, press +/- key on case controller type and select correct option from list.
ii. For part # or firmware, press +/- key on case controller type
and select correct option from list.
iii. If required part # or firmware is not listed, call or other tech
support resource.
© Danfoss | ADAP-KOOL® | 2018.08
AX278934146190en-000101 | 5
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
6 | AX278934146190en-000101
© Danfoss | ADAP-KOOL® | 2018.08