Danfoss AK-CC 550A, AK-SM 800 Service guide

Service Guide
Configuration
AK-CC 550A to AK-SM 800
ADAP-KOOL® Refrigeration Control System
Service Guide | AK-CC 550A to AK-SM 800 Configuration
Initial Setup/Checks @ Case Controller
Wiring at AK-SM 850/880
Wiring at AK-CC 550A
LON wiring Modbus
wiring
2. With power applied to AK-CC 550A, set parameter o03 (address) and o61 (application). To set: a. Hold top button in for 5 seconds until ‘r01’ is displayed, then
use top/bottom buttons to scroll to each parameter.
b. Press middle button on parameter to view value, top/bottom
to change to desired value, and middle button again to set.
c. Parameter o03 is unique to each controller, and parameter
o61 is typically set to ‘2’.
For LON wiring, comm card should also be installed behind cover
2 | AX278934146190en-000101
© Danfoss | ADAP-KOOL® | 2018.08