Instructions
AK-CC 525A
115 V
Identication
Principle
Dimensions
084B8017
Connections
AKV info !!
S2:
Insulate sensor
Fühler isolieren
Capteur isolés
Isolér føleren
Sensores aislados
115 V a.c. spole
115 V a.c. coil
115 V a.c. Spule
115 V c.a. Bobine
115 V c.a. Bobina
115 V c.a. Bobine
AK-CC 525A
Additional information: English Manual RS8HB... www.danfoss.com
RI8RZ102 06-2016
Data communication
Important All connections to the data communication MODBUS and RS 485 must comply
with the requirements for data communication cables. See literature: RC8AC.
System manager
/ Gateway
Display EKA 163 / 164
L < 15 m
L > 15 m
AK-SM....
AKA 245 version 6.20+ /
AK-SM...
! Address: o03 > 0
2 Instructions RI8RZ102 © Danfoss 06/2016 AK-CC 525A
Connections
DI1 DI2
DO1 DO2 DO3 DO4 DO5 DO6 DI3
(od) (ALA) (CoP) (dEF) (FAn) (Lgt)
(rHt)
DI1
Digital input signal.
The dened function is active when the input is short-circuited/
opened. The function is dened in o02.
DI2
Digital input signal.
The dened function is active when the input is short-circuited/
opened. The function is dened in o37.
Pressure transmitter
AKS 32R
Connect to terminal 30, 31 and 32.
(Used cable 060G1034: Black=30, Blue=31, Brown=32)
The signal from one pressure transmitter can be received by up
to 10 controllers. But only if there are no signicant pressure
decreases between the evaporators to be controlled.
S2
Pt 1000 ohm sensor
S3, S4, S5
Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of the
same type.
S3, air sensor, placed in the warm air before the evaporator
S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the
conguration)
S5, defrost sensor, placed on the evaporator.
EKA Display
If there is external reading/operation of the controller, display type
EKA 163B or EKA 164B can be connected.
RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication
module is inserted in the controller. The module can be a LON
RS485, DANBUSS or a MODBUS.
Terminal 51 = screen
Terminal 52 = A (A+)
Terminal 53 = B (B-)
(For LON RS485 and gateway type AKA 245 the gateway must be
version 6.20 or higher.)
MODBUS
For data communication.
Terminal 56 = screen
Terminal 57 = A+
Terminal 58 = B(Alternatively the terminals can be connected to an external
display type EKA 163A or 164A, but then they cannot be used
for data communication. Any data communication must then be
carried out by one of the other methods.)
Supply voltage
115 V a.c., 50/60 Hz
DO1
Connection of expansion valve type AKV or AKVA. The coil must
be a 115 V a.c. coil.
DO2
Alarm
There is a connection between terminal 7 and 8 in alarm situations
and when the controller is without power.
DO3
Refrigeration / Railheat
There is connection between terminal 10 and 11 when the
function must be active.
DO4
Defrost
There is connection between terminal 12 and 14 when defrosting
takes place.
DO5
Fan
There is connection between terminal 15 and 16 when the fan is
on.
DO6
Light
There is connection between terminal 17 and 18 when the light
must be on.
DI3
Digital input signal.
The signal must have a voltage of 0 / 115 V a.c..
The function is dened in o84.
AK-CC 525A Instructions RI8RZ102 © Danfoss 06/2016 3