Danfoss AK-CC 525A Installation guide

Instructions
AK-CC 525A
115 V
Identication
Principle
Dimensions
084B8017
Connections
AKV info !!
S2:
115 V a.c. spole 115 V a.c. coil 115 V a.c. Spule 115 V c.a. Bobine 115 V c.a. Bobina 115 V c.a. Bobine
AK-CC 525A
Additional information: English Manual RS8HB... www.danfoss.com
RI8RZ102 06-2016
Data communication
Important All connections to the data communication MODBUS and RS 485 must comply
with the requirements for data communication cables. See literature: RC8AC.
System manager / Gateway
Display EKA 163 / 164
L < 15 m
L > 15 m
AK-SM....
AKA 245 version 6.20+ / AK-SM...
! Address: o03 > 0
2 Instructions RI8RZ102 © Danfoss 06/2016 AK-CC 525A
Connections
DI1 DI2
DO1 DO2 DO3 DO4 DO5 DO6 DI3 (od) (ALA) (CoP) (dEF) (FAn) (Lgt) (rHt)
DI1
Digital input signal. The dened function is active when the input is short-circuited/ opened. The function is dened in o02.
DI2
Digital input signal. The dened function is active when the input is short-circuited/ opened. The function is dened in o37.
Pressure transmitter
AKS 32R
Connect to terminal 30, 31 and 32. (Used cable 060G1034: Black=30, Blue=31, Brown=32) The signal from one pressure transmitter can be received by up to 10 controllers. But only if there are no signicant pressure decreases between the evaporators to be controlled.
S2
Pt 1000 ohm sensor
S3, S4, S5
Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of the same type.
S3, air sensor, placed in the warm air before the evaporator S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the conguration)
S5, defrost sensor, placed on the evaporator.
EKA Display
If there is external reading/operation of the controller, display type EKA 163B or EKA 164B can be connected.
RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication module is inserted in the controller. The module can be a LON RS485, DANBUSS or a MODBUS. Terminal 51 = screen Terminal 52 = A (A+) Terminal 53 = B (B-) (For LON RS485 and gateway type AKA 245 the gateway must be version 6.20 or higher.)
MODBUS
For data communication. Terminal 56 = screen Terminal 57 = A+ Terminal 58 = B­(Alternatively the terminals can be connected to an external display type EKA 163A or 164A, but then they cannot be used for data communication. Any data communication must then be carried out by one of the other methods.)
Supply voltage
115 V a.c., 50/60 Hz
DO1
Connection of expansion valve type AKV or AKVA. The coil must be a 115 V a.c. coil.
DO2
Alarm
There is a connection between terminal 7 and 8 in alarm situations and when the controller is without power.
DO3
Refrigeration / Railheat
There is connection between terminal 10 and 11 when the function must be active.
DO4
Defrost
There is connection between terminal 12 and 14 when defrosting takes place.
DO5
Fan
There is connection between terminal 15 and 16 when the fan is on.
DO6
Light
There is connection between terminal 17 and 18 when the light must be on.
DI3
Digital input signal. The signal must have a voltage of 0 / 115 V a.c.. The function is dened in o84.
AK-CC 525A Instructions RI8RZ102 © Danfoss 06/2016 3
Data communication
If data communication is used, it is important that the installation of the data communication cable is performed correctly. See separate literature No. RC8AC…
Electric noise
Cables for sensors, DI inputs and data communication must be kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided
Installation considerations
Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and ultimately lead to a plant breakdown. Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation, for example, could still present problems. Electronic controls are no substitute for normal, good engineering practice. Danfoss will not be responsible for any goods, or plant compo­nents, damaged as a result of the above defects. It is the installer's responsibility to check the installation thoroughly, and to t the necessary safety devices. Special reference is made to the necessity of signals to the controller when the compressor is stopped and to the need of liquid receivers before the compressors. Your local Danfoss agent will be pleased to assist with further advice, etc.
Coordinated defrost via cable connections
Coordinated defrost via data communication
Max. 10
The following controllers can be connected up in this way: EKC 204A, AK-CC 210, AK-CC 250, AK-CC 450, AK-CC 550A,
Refrigeration is resumed when all controllers have “released” the signal for defrost.
The setting of controllers to coordinate their defrosting takes place in the gateway/system manager.
Refrigeration is resumed when all controllers have “released” the signal for defrost.
4 Instructions RI8RZ102 © Danfoss 06/2016 AK-CC 525A
Operation (only external)
External display
The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.
Light-emitting diodes (LED)
The LED’s on the external display will light up when the relevant relay is activated. o = Refrigeration
o = Defrost o = Fan running
The light-emitting diodes will ash when there is an alarm. In this situation you can download the error code to the display and cancel/sign for the alarm by giving the top button a brief push.
The buttons
When you want to change a setting, the upper and the lower buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the col­umn with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value, save the new value by once more pushing the middle button.
Examples
Set menu
1. Push the upper button until a parameter "cfg" is shown
2. Push the upper, middle or the lower button and nd that parameter you want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to freeze the value.
Get a good start
With the following procedure you can start regulation very quick­ly:
cFg (System settings) 1 Open parameter r12 and stop the regulation (in a new and not
previously set unit, r12 will already be set to 0 which means stopped regulation.)
2 Select the min. range for the pressure transmitter (o20)
3 Select the max. range for the pressure transmitter (o21)
4 Select refrigerant (o30)
5 Factory setting for DO3 = Rail heat. It can be changed (o61)
6 Now select one of the preset settings from the table
Auxiliary schedule for settings (quick-setup)
Preset settings (o62) 1 2 3 4 5 6
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Sensor signal for thermo­stat. S4% (r15) Alarm limit high (A13)
Alarm limit low (A14)
Sensor signal for alarm funct.S4% (A36) Interval between defrost (d03) Defrost sensor: 0=time, 1=S5, 2=S4 (d10) DI1 cong. (o02)
Sensor signal for display view S4% (017)
Case Room
Defrost stop on Defrost stop on
time S5 time S5
2°C -2°C -28°C 4°C 0°C -22°C
6°C 4°C -22°C 8°C 5°C -20°C
0°C -4°C -30°C 0°C -2°C -24°C
100% 0%
8°C 6°C -15°C 10°C 8°C -15°C
-5°C -5°C -30°C 0°C 0°C -30°C
0% 100% 0%
6 h 6h 12h 8h 8h 6h
0 1 1 0 1 1
- Door function (=2)
0%
7 Open parameter o62 and set the number for the array of preset-
tings. The few selected settings will now be transferred to the menu.
8 For network. Set the address in o03
Cutout alarm relay / receipt alarm/see alarm code
• A short press of the upper button
If there are several alarm codes they are found in a rolling stack. Push the uppermost or lowermost button to scan the rolling
9 Send address to system unit:
• MODBUS: Activate scan function in System unit
• If another data communication card is used in the controller:
- LON RS485: Activate the function o04
stack.
10 Open parameter r12 and start the regulation
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
(Menu groups) 11 Go through the survey of factory settings. The values in the
grey cells are changed according to your choice of settings. Make any necessary changes in the respective parameters.
Reading the temperature at defrost sensor
• A short press of the lower button
Manuel start or stop of a defrost
• Push the lower button for four seconds.
AK-CC 525A Instructions RI8RZ102 © Danfoss 06/2016 5
Menu overview
Password
Temperature PS cFg
in
out
r-
Conguration
Service
od
ALA S2 o30 Refrigerant type
Service
System settings
r12 Main switch
PE
o20 Min. transmitter range
tE o21 Max. transmitter range
A-- rHt / CoP S3 o61 Relay DO3 function
c-- dEF S4 o62 Preset settings
d-- FAn S5 o03 Modbus address
f-- Lgt di1 o04 Service pin (for LON only)
n-- ESc
Menu groups
r12 = service (-1)
Read output status. /
Override output when
Read input status
di2 ESc
o-- Return di3 Return
t-- ESc
See also the following pages.
u-- Return
ESc
Return
Close each group by pressing ESc (Return)
Parameter / Function Code DO3 function
Normal operation
Temperature (setpoint) - - - -50°C 50°C 2 Thermostat r-­Temperature (setpoint) r00 -50°C 50°C 2 Dierential r01 0.1 K 20 K 2 Max. limitation of setpoint setting r02 -49°C 50°C 50 Min. limitation of setpoint setting r03 -50°C 49°C -50 Adjustment of temperature indication r04 -10 K 10 K 0 Temperature unit (°C/°F) r05 0/°C 1/F 0/°C Correction of the signal from S4 r09 -10 K 10 K 0 Correction of the signal from S3 r10 -10 K 10 K 0 Manual service, stop regulation, start regulation (-1, 0, 1) r12 -1 1 0 Displacement of reference during night operation r13 -50 K 50 K 0 Dene thermostat function
1=ON/OFF, 2=Modulating Denition and weighting, if applicable, of thermostat sensors - S4% (100%=S4, 0%=S3) r15 0 % 100 % 100 Time between melt periods r16 0 hrs 10 hrs 1 Duration of melt periods r17 0 min. 30 min. 5 Thermostat displacement when signal on DI input r40 -50 K 50 K 0 Alarms A--
Delay for temperature alarm A03 0 min. 240 min. 30 Delay for door alarm A04 0 min. 240 min. 60 Delay for temperature alarm after defrost A12 0 min. 240 min. 90 High alarm limit for thermostat A13 -50°C 50°C 8 Low alarm limit for thermostat A14 -50°C 50°C -30 Alarm time delay or signal on the DI1 input A27 0 min. 240 min. 30 Alarm time delay or signal on the DI2 input A28 0 min. 240 min. 30 Signal for alarm thermostat. S4% (100%=S4, 0%=S3) A36 0 % 100 % 100 Compressor c-­Min. ON-time c01 0 min. 30 min. 0 Min. OFF-time c02 0 min. 30 min. 0 Defrost d-­Defrost method: 0=o, 1= EL, 2=Gas d01 0/o 2/gAs 1/EL Defrost stop temperature d02 0°C 50°C 6 Interval between defrost starts d03 0 hrs/O 240 hrs 8 Max. defrost duration d04 0 min. 360 min. 45 Displacement of time on cutin of defrost at start-up d05 0 min. 240 min. 0
r14 1 2 1
(o61=)
1
CoP2rHt
Min.­value
Max.­value
Factory
setting
SW = 1.5x
Actual
setting
6 Instructions RI8RZ102 © Danfoss 06/2016 AK-CC 525A
Drip o time d06 0 min. 60 min. 0 Delay for fan start after defrost d07 0 min. 60 min. 0 Fan start temperature d08 -50 °C 0 °C -5 Fan cutin during defrost
d09 0 2 1 0: Stopped 1: Running (stopped during "fan delay") 2: Running during pump down and defrost
Defrost sensor: 0 =Stop on time, 1=S5, 2=S4 d10 0 2 0 Pump down delay d16 0 min. 60 min. 0 Max. aggregate refrigeration time between two defrosts d18 0 hrs 48 hrs 0/OFF Rail heat during defrost
d27 0 2 2 0=o. 1=on. 2=Pulsating
Max. duration of -d- in display
d40
5 min. 240 min. 30 min.
Fan F-­Fan stop temperature (S5) F04 -50°C 50°C 50 Pulse operation on fans: 0=No pulse operation, 1=At thermostat cuts out only, 2=
F05 0 2 0 Only at thermostat cut outs during night operation
Period time for fan pulsation (on-time + o-time) F06 1 min. 30 min. 5 On-time in % of period time F07 0 % 100 % 100 Injection control function n-­Max. value of superheat reference n09 2°C 20°C 12 Min. value of superheat reference n10 2°C 20°C 3 MOP temperature. O if MOP temp. = 15.0 °C n11 -50°C 15°C 15 Period time of AKV pulsation
n13 3 sec 6 sec 6 Only for trained personnel
Miscellaneous o-­Delay of output signals after start-up o01 0 sec 600 sec 5 Input signal on DI1. Function:
o02 0 15 0 0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation 7=thermostat oset (activate r40). 8=alarm function when closed. 9=alarm function when open. 15=case shut down
Network address (0 = o) o03 0 240 0 On/O switch (Service Pin message)
o04 0/O 1/On 0/O IMPORTANT! o61 must be set prior to o04 (used at LON 485 and DANBUSS only)
Access code 1 (all settings) o05 0 100 0 Used sensor type for S3, S4 and S5: 0=Pt1000, 1=Ptc1000, o06 0/Pt 1/Ptc 0/Pt
Readout of software version o08
Max hold time after coordinated defrost o16 0 min. 360 min. 20 Select signal for display view. S4% (100%=S4, 0%=S3) o17 0 % 100 % 100 Pressure transmitter working range – min. value * o20 -1 bar 5 bar -1 Pressure transmitter working range – max. value * o21 6 bar 200 bar 12 Refrigerant setting:
* o30 0 42 0 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User dened. 14=R32. 15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A. 32=R413A. 33=R422D. 34=R427A. 35=R438A. 36=R513A(XP10). 37=R407F. 38=R1234ze. 39=R1234yf. 40=R448A. 41=R449A. 42=R452A.
Input signal on DI2. Function:
o37 0 15 0 (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation 7=thermostat oset (activate r40). 8=alarm function when closed. 9=alarm function when open. 13=coordinated defrost). 15=case shut down
Conguration of light function: 1=Light follows day /night operation, 2=Light control
o38 1 4 1 via data communication via ‘o39’, 3=Light control with a DI-input, 4=As "2", but light switch on if the network cut out for more than 15 minutes.
Activation of light relay (only if o38=2) On=light o39 0/O 1/On 0/O
Rail heat On time during day operations
Rail heat On time during night operations
Rail heat period time (On time + O time)
Selection of DO3 function.: 1=Cooling. 2=Rail heat
o41
o42
o43
0 % 100 % 100
0 % 100 % 100
6 min. 60 min. 10
o61 1 2 0 2 2 Download a set of predetermined settings. * o62 0 6 0 Access code 2 (partial access) *** o64 0 100 0 Replace the controllers factory settings with the present settings o67 0/O 1/On 0/O Input signal on DI3. Function: (high voltage input)
o84 0 15 0 (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation, 7=thermostat oset (activate r40). 14=Refrigeration stopped (forced closing)). 15=case shut down
AK-CC 525A Instructions RI8RZ102 © Danfoss 06/2016 7
Rail heat control:
o85 0 1 0
0=not used, 1=pulse control with timer function (o41 and o42), Time delay from "open door” refrigeration is started o89 0 min. 240 min. 30 Fan operation at stopped cooling (forced closing):
o90 0 3 1 0= Stopped (defrost allowed) 1= Running (defrost allowed) 2= Stopped (defrost not allowed) 3= Running (defrost not allowed)
Light and night blinds dened
o98 0 1 0
0: Light is switch o and night blind is open when the main switch is o 1: Light and night blind is independent of main switch
Conguration of alarm relay
P41 0 127 111
The alarm relay will be activated upon an alarm signal from the following groups: 1 - High temperature alarms 2 - Low temperature alarms 4 - Sensor error 8 - Digital input enabled for alarm 16 - Defrosting alarms 32 - Miscellaneous 64 - Injection alarms The groups that are to activate the alarm relay must be set by using a numerical value which is the sum of the groups that must be activated. (E.g.: a value of 5 will activate all high temperature alarms and all sensor error and will
cancel the relay function). Real time clock t-­Six start times for defrost.
Setting of hours.
t01 ­t06
0 hrs 23 hrs 0
0=OFF Six start times for defrost.
Setting of minutes.
t11 ­t16
0 min. 59 min. 0
0=OFF Clock - Setting of hours t07 0 hrs 23 hrs 0 Clock - Setting of minute t08 0 min. 59 min. 0 Clock - Setting of date t45 1 day 31 day 1 Clock - Setting of month t46 1 mon. 12 mon. 1 Clock - Setting of year t47 0 year 99 year 0 Service u-­Temperature measured with S5 sensor u09 Status on DI1 input. on/1=closed u10 Actual defrost time (minutes) u11 Temperature measured with S3 sensor u12 Status on night operation (on or o) 1=on u13 Temperature measured with S4 sensor u16 Thermostat temperature u17 Run time of thermostat (cooling time) in minutes u18 Temperature of evaporator outlet temp. (S2) u20 Superheat across evaporator u21 Reference of superheat control u22 Opening degree of AKV valve ** u23 Evaporating pressure Po (relative) u25 Evaporator temperature To (Calculated) u26 Status on DI2 output. on/1=closed u37 Display air temperature. Weighted S3 and S4 u56 Measured temperature for alarm thermostat u57
Status on relay for cooling
** u58 Status on relay for fan ** u59 Status on relay for defrost ** u60
Status on relay for railheat
** u61 Status on relay for alarm ** u62 Status on relay for light ** u63 Readout of the actual rail heat eect u85 Status on high voltage input DI3 u87 Readout of thermostats actual cut in value u90 Readout of thermostats actual cut out value u91
*) Can only be set when regulation is stopped (r12=0) **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage
8 Instructions RI8RZ102 © Danfoss 06/2016 AK-CC 525A
Fault message
In an error situation the LED’s on the front will ash and the alarm relay will be activated. If you push the top button in this situation you can see the alarm report in the display. There are two kinds of error reports - it can either be an alarm occurring dur­ing the daily operation, or there may be a defect in the installation. A-alarms will not become visible until the set time delay has expired. E-alarms, on the other hand, will become visible the moment the error occurs. (An A alarm will not be visible as long as there is an active E alarm). Here are the messages that may appear:
Code / Alarm text via data communication
A1/--- High t.alarm High temperature alarm
A2/--- Low t. alarm Low temperature alarm
A4/--- Door alarm Door alarm
A5/--- Max hold time The ”o16” function is activated during
A10/--- Inject prob. Control problem
A11/--- No Rfg. sel. No refrigerant selected
A15/--- DI1 alarm DI1 alarm
A16/--- DI2 alarm DI2 alarm
A45/--- Standby mode
E1/--- Ctrl. error Faults in the controller
E6/--- RTC error Check clock
E20/--- Pe error Error on pressure transmitter Pe
E24/--- S2 error Error on S2 sensor 4
E25/--- S3 error Error on S3 sensor 4
E26/--- S4 error Error on S4 sensor 4
E27/--- S5 error Error on S5 sensor 4
---/--- Max Def.Time Defrost stopped based on time in-
Description
a coordinated defrost
Standby position (stopped refrigera­tion via r12 or DI input)
stead of, as wanted, on temperature
Alarm relay groups (P41)
1
2
8
16
64
64
8
8
-
32
32
64
16
Operating status (Measurement)
The controller goes through some regulating situa­tions where it is just waiting for the next point of the regulation. To make these “why is nothing happening” situations visible, you can see an operating status on the display. Push briey (1s) the upper button. If there is a status code, it will be shown on the display. The indi­vidual status codes have the following meanings:
Normal regulation S0 0
Waiting for end of the coordinated defrost S1 1
When the compressor is operating it must run for at least x minutes.
When the compressor is stopped, it must remain stopped for at least x minutes.
The evaporator drips o and waits for the time to run out S4 4
Refrigeration stopped by main switch. Either with r12 or a DI-input
Refrigeration stopped by thermostat S11 11
Defrost sequence. Defrost in progress S14 14
Defrost sequence. Fan delay — water attaches to the evaporator
Refrigeration stopped due to open ON input or stopped regulation
Door is open. DI input is open S17 17
Melt function in progress. Refrigeration is interrupted S18 18
Modulating thermostat control S19 19
Emergency cooling due to sensor error S20 20
Regulation problem in the injections function S21 21
Start-up phase 2. Evaporator being charged S22 22
Adaptive control S23 23
Start-up phase 1. Signal reliability from sensors is controlled
Manual control of outputs S25 25
No refrigerant selected S26 26
Delay on outputs during start-up S32 32
Case shutdown S45 45
Other displays:
The defrost temperature cannot be displayed. There is stop based on time
Defrost in progress / First cooling after defrost -d-
Password required. Set password PS
Regulation is stopped via main switch OFF
S2 2
S3 3
S10 10
S15 15
S16 16
S24 24
non
Ctrl. state: (Shown in all menu displays)
*) Emergency cooling will take eect when there is lack of signal from a dened S3
or S4 sensor or signal from the pressure transmitter is outside signal range. The regulation will continue with a registered average cutin frequency. There are two registered values – one for day operation and one for night operation.
Data communication
The importance of individual alarms can be dened with a setting. The setting must be carried out in the group "Alarm destinations"
Settings from System manager
Settings from AKM (AKM destination)
Log Alarm relay Send via
Non High Low-High
Network High 1 X X X X Middle 2 X X X Low 3 X X X Log only X Disabled
AK-CC 525A Instructions RI8RZ102 © Danfoss 06/2016 9
10 Instructions RI8RZ102 © Danfoss 06/2016 AK-CC 525A
ADAP-KOOL®
Loading...