Digital input signal.
The dened function is active when the input is short-circuited/
opened. The function is dened in o02.
DI2
Digital input signal.
The dened function is active when the input is short-circuited/
opened. The function is dened in o37.
Pressure transmitter
AKS 32R
Connect to terminal 30, 31 and 32.
(Used cable 060G1034: Black=30, Blue=31, Brown=32)
The signal from one pressure transmitter can be received by up
to 10 controllers. But only if there are no signicant pressure
decreases between the evaporators to be controlled.
S2
Pt 1000 ohm sensor
S3, S4, S5
Pt 1000 ohm sensor or PTC 1000 ohm sensor. All have to be of the
same type.
S3, air sensor, placed in the warm air before the evaporator
S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the
conguration)
S5, defrost sensor, placed on the evaporator.
EKA Display
If there is external reading/operation of the controller, display type
EKA 163B or EKA 164B can be connected.
RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication
module is inserted in the controller. The module can be a LON
RS485, DANBUSS or a MODBUS.
Terminal 51 = screen
Terminal 52 = A (A+)
Terminal 53 = B (B-)
(For LON RS485 and gateway type AKA 245 the gateway must be
version 6.20 or higher.)
MODBUS
For data communication.
Terminal 56 = screen
Terminal 57 = A+
Terminal 58 = B(Alternatively the terminals can be connected to an external
display type EKA 163A or 164A, but then they cannot be used
for data communication. Any data communication must then be
carried out by one of the other methods.)
Supply voltage
115 V a.c., 50/60 Hz
DO1
Connection of expansion valve type AKV or AKVA. The coil must
be a 115 V a.c. coil.
DO2
Alarm
There is a connection between terminal 7 and 8 in alarm situations
and when the controller is without power.
DO3
Refrigeration / Railheat
There is connection between terminal 10 and 11 when the
function must be active.
DO4
Defrost
There is connection between terminal 12 and 14 when defrosting
takes place.
DO5
Fan
There is connection between terminal 15 and 16 when the fan is
on.
DO6
Light
There is connection between terminal 17 and 18 when the light
must be on.
DI3
Digital input signal.
The signal must have a voltage of 0 / 115 V a.c..
The function is dened in o84.
If data communication is used, it is important that the installation
of the data communication cable is performed correctly.
See separate literature No. RC8AC…
Electric noise
Cables for sensors, DI inputs and data communication must be
kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided
Installation considerations
Accidental damage, poor installation, or site conditions, can give
rise to malfunctions of the control system, and ultimately lead to a
plant breakdown.
Every possible safeguard is incorporated into our products to
prevent this. However, a wrong installation, for example, could still
present problems. Electronic controls are no substitute for normal,
good engineering practice.
Danfoss will not be responsible for any goods, or plant components, damaged as a result of the above defects. It is the installer's
responsibility to check the installation thoroughly, and to t the
necessary safety devices.
Special reference is made to the necessity of signals to the
controller when the compressor is stopped and to the need of
liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further
advice, etc.
Coordinated defrost via
cable connections
Coordinated defrost via
data communication
Max. 10
The following controllers can be connected
up in this way:
EKC 204A, AK-CC 210, AK-CC 250,
AK-CC 450, AK-CC 550A,
Refrigeration is resumed when all
controllers have “released” the signal for
defrost.
The setting of controllers to coordinate
their defrosting takes place in the
gateway/system manager.
Refrigeration is resumed when all
controllers have “released” the signal for
defrost.
The values will be shown with three digits, and with a setting you
can determine whether the temperature is to be shown in °C or in
°F.
Light-emitting diodes (LED)
The LED’s on the external display will light up when the relevant
relay is activated.
o = Refrigeration
o = Defrost
o = Fan running
The light-emitting diodes will ash when there is an alarm.
In this situation you can download the error code to the display
and cancel/sign for the alarm by giving the top button a brief
push.
The buttons
When you want to change a setting, the upper and the lower
buttons will give you a higher or lower value depending on the
button you are pushing. But before you change the value, you
must have access to the menu. You obtain this by pushing the
upper button for a couple of seconds - you will then enter the column with parameter codes. Find the parameter code you want to
change and push the middle buttons until value for the parameter
is shown. When you have changed the value, save the new value
by once more pushing the middle button.
Examples
Set menu
1. Push the upper button until a parameter "cfg" is shown
2. Push the upper, middle or the lower button and nd that
parameter you want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to freeze the value.
Get a good start
With the following procedure you can start regulation very quickly:
cFg (System settings)
1 Open parameter r12 and stop the regulation (in a new and not
previously set unit, r12 will already be set to 0 which means
stopped regulation.)
2 Select the min. range for the pressure transmitter (o20)
3 Select the max. range for the pressure transmitter (o21)
4 Select refrigerant (o30)
5 Factory setting for DO3 = Rail heat. It can be changed (o61)
6 Now select one of the preset settings from the table
Auxiliary schedule for
settings (quick-setup)
Preset settings (o62)123456
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Sensor signal for thermostat. S4% (r15)
Alarm limit high (A13)
Alarm limit low (A14)
Sensor signal for alarm
funct.S4% (A36)
Interval between defrost
(d03)
Defrost sensor: 0=time,
1=S5, 2=S4 (d10)
DI1 cong. (o02)
Sensor signal for display
view S4% (017)
CaseRoom
Defrost stop onDefrost stop on
timeS5timeS5
2°C-2°C-28°C4°C0°C-22°C
6°C4°C-22°C8°C5°C-20°C
0°C-4°C-30°C0°C-2°C-24°C
100%0%
8°C6°C-15°C10°C8°C-15°C
-5°C-5°C-30°C0°C0°C-30°C
0%100%0%
6 h6h12h8h8h6h
011011
-Door function (=2)
0%
7 Open parameter o62 and set the number for the array of preset-
tings. The few selected settings will now be transferred to the
menu.
8 For network. Set the address in o03
Cutout alarm relay / receipt alarm/see alarm code
• A short press of the upper button
If there are several alarm codes they are found in a rolling stack.
Push the uppermost or lowermost button to scan the rolling
9 Send address to system unit:
• MODBUS: Activate scan function in System unit
• If another data communication card is used in the controller:
- LON RS485: Activate the function o04
stack.
10 Open parameter r12 and start the regulation
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
(Menu groups)
11 Go through the survey of factory settings. The values in the
grey cells are changed according to your choice of settings.
Make any necessary changes in the respective parameters.
Temperature (setpoint) - - --50°C50°C2
Thermostatr-Temperature (setpoint) r00-50°C50°C2
Dierentialr010.1 K20 K2
Max. limitation of setpoint settingr02 -49°C50°C50
Min. limitation of setpoint settingr03 -50°C49°C-50
Adjustment of temperature indicationr04-10 K10 K0
Temperature unit (°C/°F)r05 0/°C1/F0/°C
Correction of the signal from S4r09 -10 K10 K0
Correction of the signal from S3r10 -10 K10 K0
Manual service, stop regulation, start regulation (-1, 0, 1)r12 -110
Displacement of reference during night operationr13-50 K50 K0
Dene thermostat function
1=ON/OFF, 2=Modulating
Denition and weighting, if applicable, of thermostat sensors - S4% (100%=S4, 0%=S3)r150 %100 %100
Time between melt periodsr16 0 hrs10 hrs1
Duration of melt periodsr170 min.30 min.5
Thermostat displacement when signal on DI inputr40-50 K50 K0
AlarmsA--
Delay for temperature alarmA030 min.240 min.30
Delay for door alarmA040 min.240 min.60
Delay for temperature alarm after defrostA120 min.240 min.90
High alarm limit for thermostat A13-50°C50°C8
Low alarm limit for thermostat A14 -50°C50°C-30
Alarm time delay or signal on the DI1 inputA270 min.240 min.30
Alarm time delay or signal on the DI2 inputA280 min.240 min.30
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)A360 %100 %100
Compressorc-Min. ON-timec010 min.30 min.0
Min. OFF-timec020 min.30 min.0
Defrostd-Defrost method: 0=o, 1= EL, 2=Gasd010/o2/gAs1/EL
Defrost stop temperatured020°C50°C6
Interval between defrost startsd030 hrs/O 240 hrs8
Max. defrost durationd040 min.360 min.45
Displacement of time on cutin of defrost at start-upd050 min.240 min.0
Drip o timed060 min.60 min.0
Delay for fan start after defrostd070 min.60 min.0
Fan start temperatured08-50 °C0 °C-5
Fan cutin during defrost
d09021
0: Stopped
1: Running (stopped during "fan delay")
2: Running during pump down and defrost
Defrost sensor: 0 =Stop on time, 1=S5, 2=S4d10020
Pump down delayd160 min.60 min.0
Max. aggregate refrigeration time between two defrostsd180 hrs48 hrs0/OFF
Rail heat during defrost
d27022
0=o. 1=on. 2=Pulsating
Max. duration of -d- in display
d40
5 min.240 min.30 min.
FanF-Fan stop temperature (S5)F04-50°C50°C50
Pulse operation on fans: 0=No pulse operation, 1=At thermostat cuts out only, 2=
F05020
Only at thermostat cut outs during night operation
Period time for fan pulsation (on-time + o-time)F061 min.30 min.5
On-time in % of period timeF070 %100 %100
Injection control functionn-Max. value of superheat referencen092°C20°C12
Min. value of superheat referencen102°C20°C3
MOP temperature. O if MOP temp. = 15.0 °Cn11-50°C15°C15
Period time of AKV pulsation
n133 sec6 sec6
Only for trained personnel
Miscellaneouso-Delay of output signals after start-upo010 sec600 sec5
Input signal on DI1. Function:
o020150
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation
7=thermostat oset (activate r40). 8=alarm function when closed. 9=alarm function
when open. 15=case shut down
o040/O1/On0/O
IMPORTANT! o61 must be set prior to o04
(used at LON 485 and DANBUSS only)
Access code 1 (all settings)o0501000
Used sensor type for S3, S4 and S5: 0=Pt1000, 1=Ptc1000, o060/Pt1/Ptc0/Pt
Readout of software versiono08
Max hold time after coordinated defrosto160 min.360 min.20
Select signal for display view. S4% (100%=S4, 0%=S3)o170 %100 %100
Pressure transmitter working range – min. value*o20-1 bar5 bar-1
Pressure transmitter working range – max. value*o216 bar200 bar12
Refrigerant setting:
o370150
(0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation
7=thermostat oset (activate r40). 8=alarm function when closed. 9=alarm function
when open. 13=coordinated defrost). 15=case shut down
Conguration of light function: 1=Light follows day /night operation, 2=Light control
o38141
via data communication via ‘o39’, 3=Light control with a DI-input, 4=As "2", but light
switch on if the network cut out for more than 15 minutes.
Activation of light relay (only if o38=2) On=lighto390/O1/On0/O
Rail heat On time during day operations
Rail heat On time during night operations
Rail heat period time (On time + O time)
Selection of DO3 function.: 1=Cooling. 2=Rail heat
o41
o42
o43
0 %100 %100
0 %100 %100
6 min.60 min.10
o6112022
Download a set of predetermined settings. *o62 060
Access code 2 (partial access)*** o6401000
Replace the controllers factory settings with the present settingso670/O1/On0/O
Input signal on DI3. Function: (high voltage input)
o840150
(0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation,
7=thermostat oset (activate r40). 14=Refrigeration stopped (forced closing)). 15=case
shut down
0=not used, 1=pulse control with timer function (o41 and o42),
Time delay from "open door” refrigeration is startedo890 min.240 min.30
Fan operation at stopped cooling (forced closing):
o90031
0= Stopped (defrost allowed)
1= Running (defrost allowed)
2= Stopped (defrost not allowed)
3= Running (defrost not allowed)
Light and night blinds dened
o98010
0: Light is switch o and night blind is open when the main switch is o
1: Light and night blind is independent of main switch
Conguration of alarm relay
P410127111
The alarm relay will be activated upon an alarm signal from the following groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input enabled for alarm
16 - Defrosting alarms
32 - Miscellaneous
64 - Injection alarms
The groups that are to activate the alarm relay must be set by using a numerical value
which is the sum of the groups that must be activated.
(E.g.: a value of 5 will activate all high temperature alarms and all sensor error and will
cancel the relay function).
Real time clockt-Six start times for defrost.
Setting of hours.
t01 t06
0 hrs23 hrs0
0=OFF
Six start times for defrost.
Setting of minutes.
t11 t16
0 min.59 min.0
0=OFF
Clock - Setting of hourst070 hrs23 hrs0
Clock - Setting of minutet080 min.59 min.0
Clock - Setting of datet451 day31 day1
Clock - Setting of montht461 mon.12 mon.1
Clock - Setting of yeart470 year99 year0
Serviceu-Temperature measured with S5 sensoru09
Status on DI1 input. on/1=closedu10
Actual defrost time (minutes)u11
Temperature measured with S3 sensoru12
Status on night operation (on or o) 1=onu13
Temperature measured with S4 sensoru16
Thermostat temperatureu17
Run time of thermostat (cooling time) in minutesu18
Temperature of evaporator outlet temp. (S2)u20
Superheat across evaporatoru21
Reference of superheat controlu22
Opening degree of AKV valve**u23
Evaporating pressure Po (relative)u25
Evaporator temperature To (Calculated)u26
Status on DI2 output. on/1=closedu37
Display air temperature. Weighted S3 and S4u56
Measured temperature for alarm thermostatu57
Status on relay for cooling
**u58
Status on relay for fan**u59
Status on relay for defrost**u60
Status on relay for railheat
**u61
Status on relay for alarm**u62
Status on relay for light**u63
Readout of the actual rail heat eectu85
Status on high voltage input DI3u87
Readout of thermostats actual cut in valueu90
Readout of thermostats actual cut out valueu91
*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage
In an error situation the LED’s on the front will ash and the alarm relay will be
activated. If you push the top button in this situation you can see the alarm
report in the display.
There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired.
E-alarms, on the other hand, will become visible the moment the error occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:
Code / Alarm
text via data
communication
A1/--- High t.alarmHigh temperature alarm
A2/--- Low t. alarmLow temperature alarm
A4/--- Door alarmDoor alarm
A5/--- Max hold time The ”o16” function is activated during
A10/--- Inject prob.Control problem
A11/--- No Rfg. sel.No refrigerant selected
A15/--- DI1 alarmDI1 alarm
A16/--- DI2 alarmDI2 alarm
A45/--- Standby
mode
E1/--- Ctrl. errorFaults in the controller
E6/--- RTC errorCheck clock
E20/--- Pe errorError on pressure transmitter Pe
E24/--- S2 errorError on S2 sensor4
E25/--- S3 errorError on S3 sensor4
E26/--- S4 errorError on S4 sensor4
E27/--- S5 errorError on S5 sensor4
---/--- Max Def.TimeDefrost stopped based on time in-
Description
a coordinated defrost
Standby position (stopped refrigeration via r12 or DI input)
stead of, as wanted, on temperature
Alarm relay
groups (P41)
1
2
8
16
64
64
8
8
-
32
32
64
16
Operating status(Measurement)
The controller goes through some regulating situations where it is just waiting for the next point of the
regulation. To make these “why is nothing happening”
situations visible, you can see an operating status on
the display. Push briey (1s) the upper button. If there is
a status code, it will be shown on the display. The individual status codes have the following meanings:
Normal regulationS00
Waiting for end of the coordinated defrostS11
When the compressor is operating it must run for at least
x minutes.
When the compressor is stopped, it must remain stopped
for at least x minutes.
The evaporator drips o and waits for the time to run out S44
Refrigeration stopped by main switch. Either with r12 or
a DI-input
Refrigeration stopped by thermostatS1111
Defrost sequence. Defrost in progressS1414
Defrost sequence. Fan delay — water attaches to the
evaporator
Refrigeration stopped due to open ON input or stopped
regulation
Door is open. DI input is openS1717
Melt function in progress. Refrigeration is interruptedS1818
Modulating thermostat controlS1919
Emergency cooling due to sensor errorS2020
Regulation problem in the injections functionS2121
Start-up phase 2. Evaporator being chargedS2222
Adaptive controlS2323
Start-up phase 1. Signal reliability from sensors is
controlled
Manual control of outputsS2525
No refrigerant selectedS2626
Delay on outputs during start-upS3232
Case shutdownS4545
Other displays:
The defrost temperature cannot be displayed. There is
stop based on time
Defrost in progress / First cooling after defrost-d-
Password required. Set password PS
Regulation is stopped via main switchOFF
S22
S33
S1010
S1515
S1616
S2424
non
Ctrl. state:
(Shown in all
menu displays)
*) Emergency cooling will take eect when there is lack of signal from a dened S3
or S4 sensor or signal from the pressure transmitter is outside signal range. The
regulation will continue with a registered average cutin frequency. There are
two registered values – one for day operation and one for night operation.
Data communication
The importance of individual alarms can be dened with a setting. The setting
must be carried out in the group "Alarm destinations"