Installation Guide
AK-CC 460
Identification
Principle
Application 1, 3
1: Sequential operation
3: Cyclic operation
084R8052
AN234086440123en-000301
Dimensions
08 4B8016
Application 2
Speed control
© Danfoss | DCS (vt) | 2019.08
AN234086440123en-000301 | 1
Connections
Appplication 1 and 3
DI1 DI2
Solid state
output
DO1 DO2 DO3 DO4 DO5 DO6 DO7 DI3
Appplication 2
DI1 DI2 AO
DO2 DO3 DO4 DO5 DO6 DO7 DI3
Overview of outputs and applications
Application DO1 DO2 DO3 DO4 DO5 DO6 DO7 DI1 DI2 DI3 AI1 AI2 AI3 AI4 AI5 AI6 AO
1 and 3
2
• • •
• • •
S7 S3 S4 S5 S6
S7 S3 S4 S5 S6 0-10V
Relays
DO1
(for coil)
DO3, DO4 4 (3) A
DO2, DO5,
DO6, DO7
Max. 240 V AC , Min. 28 V AC
Max. 0.5 A
Leak < 1 mA
Max. 1 pcs. coil
CE
(250 V AC)
IBExU approved
4 (3) A
DI1
Digital input signal.
The defined function is active when the input is short-circuited/
opened. The function is defined in o02.
DI2
Digital input signal.
The defined function is active when the input is short-circuited/
opened. The function is defined in o37.
AO
Analogue output (only application 2)
0 - 10 V signal for compressor speed control.
S7, S3, S4, S5, S6
Pt 1000 ohm
S7, brine sensor, placed in the cold inlet before the heat exchanger
S3, air sensor, placed in the warm air before the evaporator
S4, air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be deselected in the
configuration)
S5, defrost sensor, placed on the evaporator
S6, product sensor
2 | AN234086440123en-000301
EKA Display
If there is a need for external reading/operation of the controller,
display type EKA 163B or EKA 164B can be connected.
RS485 (terminal 51, 52, 53)
For data communication, but only if a data communication
module is inserted in the controller. The module can be a LON
RS485, DANBUSS or a MODBUS.
Terminal 51 = screen
Terminal 52 = A (A+)
Terminal 53 = B (B-)
(For LON RS485 and gateway type AKA 245, the gateway must be
version 6.20 or higher.)
RJ45
For data communication, but only if a TCP/IP module is inserted in
the controller. (OEM)
MODBUS
For data communication.
Terminal 56 = screen
Terminal 57 = A+
Terminal 58 = B(Alternatively the terminals can be connected to an external
display type EKA 163A or 164A, but then they cannot be used
© Danfoss | DCS (vt) | 2019.08
for data communication. Any data communication must then be
carried out by one of the other methods.)
Supply voltage
230 V AC, 50/60 Hz
DO1
Compressor 1 (only application 1 and 3)
Connection of relay. The coil must be a 230 V AC coil.
DI3
Digital input signal
Safety circuits compressor 1 and 2
The signal must have a voltage of 0 / 230 V AC
Data communication
If data communication is used, it is important that the installation
of the data communication cable is performed correctly.
See separate literature No. RC8AC…
DO2
Alarm
There is a connection between terminal 7 and 8 in alarm
situations and when the controller is without power.
DO3
Compressor 2
There is connection between terminal 10 and 11 when the
compressor is on.
DO4
Defrost
There is connection between terminal 12 and 14 when
defrosting takes place.
DO5
Fan
There is connection between terminal 15 and 16 when the fan
is on.
DO6
Light relay
There is connection between terminal 17 and 18 when the light
must be on.
DO7
Rail heat
There is connection between terminal 20 and 21 when the rail
heat is on.
Electric noise
Cables for sensors, DI inputs and data communication must be
kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided
Installation considerations
Accidental damage, poor installation, or site conditions, can give
rise to malfunctions of the control system, and ultimately lead to a
plant breakdown.
Every possible safeguard is incorporated into our products to
prevent this. However, a wrong installation, for example, could
still present problems. Electronic controls are no substitute for
normal, good engineering practice.
Danfoss wil not be responsible for any goods, or plant
components, damaged as a result of the above defects. It is the
installer's responsibility to check the installation thoroughly, and
to fit the necessary safety devices.
Special reference is made to the necessity of signals to the
controller when the compressor is stopped and to the need of
liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further
advice, etc.
Coordinated defrost via
max. 10
cable connections The following controllers can be connected
up in this way:
EKC 204A, AK-CC 210, AK-CC 250,
AK-CC 450, AK-CC 460, AK-CC 550, AK-CC 55.
Refrigeration is resumed when all
controllers have “released” the signal for
defrost.
Coordinated defrost via
data communication
The setting of controllers to coordinate
their defrosting takes place in the gateway/
system manager.
Refrigeration is resumed when all controllers
have “released” the signal for defrost.
© Danfoss | DCS (vt) | 2019.08
AN234086440123en-000301 | 3