Danfoss AK-CC 210B User guide

User Guide
Controller for temperature control
AK-CC 210B, SW 1.0x
ADAP-KOOL® Refrigeration Control System
www.danfoss.com
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
84B8255
84B8256
Contents
Introduction .........................................................................................................2
Operation ..............................................................................................................3
Applications .........................................................................................................6
Survey of functions ............................................................................................8
Operation ........................................................................................................... 17
Menu survey ...................................................................................................... 18
Ordering ............................................................................................................. 20
Connections ...................................................................................................... 21
Data ...................................................................................................................... 22
Introduction
The AK-CC 210B is dedicated for “plug-in cabinets” in supermarkets.
Principle
The AK-CC 210B controls the temperature in the cabinet based on the measurement from a single sensor – Sair. This sensor can be placed in the cold airflow after the evaporator or in the warm airflow before the evaporator, depending on the construction and usage of the cabinet.
Danfoss
Sair
A measurement of the defrost temperature can be obtained directly through the use of an S5 sensor or indirectly through the use of the Sair measurement.
Relays: the first 3 relays are dedicated for Refrigeration, Defrost and Light, respectively. The usage of relay 4 is selected by the application setting, and can be Alarm, Fan, Rail heat, Condenser fan or Compressor 2.
The different applications are described on page 6.
Advantages
• Many applications in the same unit
• The controller has integrated refrigeration-technical functions, so that it can replace a whole collection of thermostats and timers
• Buttons and seal imbedded in the front
• Alarm monitoring of condenser temperature with compressor stop protection.
• Sealed relays for use with R290 refrigerants
• Can control two compressors
• Easy to remount data communication
• Quick set-up
• Two temperature references
• Digital inputs for various functions
• Clock function with super cap back-up
• Factory calibration that will guarantee a better measuring accuracy than stated in the standard EN ISO 23953-2 without subsequent calibration (Pt 1000 ohm sensor)
Sair
S
air
S
Danfoss
Sair
S
Sair
Sair
Danfoss
84B8257
2 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Tc - Condenser temp.
timet1 t2 t3 t4 t5 t6
84B8259
ompressor run enabled
time
Operation
Operation - Sensors
One thermostat sensor – Sair – can be connected to the controller, and the relevant application defines the placement. It can be placed in the air before the evaporator or in the airflow after the evaporator. The latter is mainly used where there is a risk of too low temperature at the products.
Sair
Sair
Defrost sensor
The best signal concerning the evaporator’s temperature is obtained from a defrost sensor mounted directly on the evaporator. Here the signal may be used by the defrost function, so that the shortest and most energy-saving defrost can take place.
If a defrost sensor is not required, defrost can be stopped based on time, or Sair can be selected.
Condenser temperature sensor
A condenser temperature sensor – Sc – can be used for monitoring the temperature on the condenser. Depending on settings, alarms can be generated and other actions, including safety stop of compressor, can be initiated based on this temperature.
Condenser temperature alarms and actions
An alarm warning can be activated when the temperature gets above a set Condenser Alarm limit and a critical alarm can be activated at a higher Condenser Block Alarm limit. At this critical level, different actions can be initiated e.g. turning off the light in the cabinet, turning off the compressor, or both. The wanted action is defined by parameter "P92".
Compressors can be permanently stopped if a defined number of critical alarms occur within a defined time period. If the number of events exceeds the setting in parameter "P94" within a period defined in "P93", the last event will always include a compressor stop, together with other actions defined in "P92". This state requires a manual reset before the compressor can start again.
Condenser Block Alarm (A54)
Condenser Alarm (A37)
Di.
(A78)
Delay (A55)
S5
Sc
Danfoss
84B8258
2x Di. (A78)
Danfoss
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 3
Time Period (P93)
Events in period (P94)12345
Manual reset
C
Danfoss
84B8260
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Control of two compressors
This control is used for controlling two compressors of the same size. The principle for control is that one of the compressors connects at ½ the differential of the thermostat, and the other at the full differential. When the thermostat cuts in, the compressor with the fewest operating hours is started. The other compressor will only start after a set time delay, so that the load will be divided between them. The time delay has a higher priority than the temperature. When the air temperature has dropped by half the differential, one of the compressors will stop, while the other will continue working and not stop until the required temperature is achieved. The compressors used must be of a type that is capable of starting up against a high pressure.
Change of temperature reference
In an impulse appliance, for example, used for various product groups the temperature reference is changed easily with a contact signal on a digital input. The signal changes the normal thermostat setpoint by a predefined value. At the same time the high and low alarm limits will be displaced with the same value.
Night setback
The thermostat reference can be displayed with an offset at night. The alarm limit value will be changed with the same value as the night offset. The change will only be applied for positive night offset.
Digital inputs
There are two digital inputs, both of which can be used for the following functions:
- Case cleaning
- Door contact function with alarm
- Starting a defrost
- Coordinated defrost (DO2 only)
- Night setback
- Change-over between two temperature reference
- Report state of digital input via data communication
Case cleaning function
This function makes it easy to steer the refrigeration appliance through a cleaning phase. Via three pushes on a switch you change from one phase to the next phase. The first push stops the refrigeration – the fans keep working. ”Later”: The next push stops the fans ”Still later”: The next push restarts refrigeration The different situations can be followed on the display.
On the network, a cleaning alarm is transmitted to the system unit. This alarm can be ”logged” so that proof of the sequence of events is provided.
- + + °C
1 ÷ + Fan
2 ÷ ÷ Off
3 + + °C
Door contact function
In cold rooms and frost rooms the door switch can switch the light on and off, start and stop the refrigeration and give alarm if the door has remained open for too long.
Defrost
Depending on the application, you may choose between the following defrost methods: Natural: Here the fans are kept operating during defrost Electric: The heating element is activated Hot gas: The defrost output is used to control a solenoid that lets
the hot gas flow through the evaporator. The compressor is kept running to generate hot gas.
4 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Start of defrost
A defrost can be started in different ways: Interval: Defrost is started at fixed time intervals, e.g. every eighth hour Refrigeration time: Defrost is started at fixed refrigeration time intervals. In other words, a low need for refrigeration will ”postpone” the coming defrost. Schedule: Here defrost can be started at fixed times of the day and night. However, max. 6 times. Contact: Defrost is started with a contact signal on a digital input. Network: The signal for defrost is received from a system unit via the data communication. S5 temp In 1:1 systems the efficiency of the evaporator can be followed. Icing-up will start a defrost. Manual: An extra defrost can be activated from the controller’s lower-most button. (Though not for application 4).
All the mentioned methods can be used at random – if just one of them is activated a defrost will be started.
Coordinated defrost
There are two ways in which coordinated defrost can be arranged. Either with wire connections between the controllers or via data communication.
Max. 15
Wire connections
One of the controllers is defined to be the controlling unit and a battery module may be fitted in it so that the clock is ensured back-up. When a defrost is started, all the other controllers will follow suit and likewise start a defrost. After the defrost, the individual controllers will move into waiting position. When all are in waiting position there will be a change-over to refrigeration. (If just one in the group demands defrost, the others will follow suit).
Defrost via data communication
All controllers are fitted with a data communication module, and via the override function from a gateway the defrost can be coordinated.
Defrost on demand
1. Based on refrigeration time
When the aggregate refrigeration time has passed a set time, a defrost will be started.
2. Based on temperature
The controller will constantly follow the temperature at S5. Between two defrosts, the S5 temperature will become lower the more the evaporator ices up (the compressor operates for a longer time and pulls the S5 temperature further down). When the temperature passes a set allowed variation, the defrost will be started. This function can only work in 1:1 systems.
Service request alarm
The controller will register the accumulated on-time in days, and a limit can be set to activate a “service request alarm” to indicate that inspection and cleaning of the fan and condenser is imminent. After doing so, the Runtime counter can be reset and a new period initiated.
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 5
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Extra module
• The controller can afterwards be fitted with an insertion module if the application requires it.
The controller has been prepared with plug, so the module
simply has to be pushed in.
- Battery module The module guarantees voltage to the controller if the supply
voltage should drop out for more than four hours. The clock function can thus be protected during a power failure.
- Data communication If you require operation from a PC, a data communication
module has to be placed in the controller.
External display
If it is necessary to indicate the temperature on the front of
the refrigeration appliance, a display type EKA 163A can be mounted. The extra display will show the same information as the controller's display, but does not incorporate buttons for operation. If operation from the external display is needed a display type EKA 164A must be mounted.
Applications
AK-CC 210B is developed for refrigerated plug-in cabinets with one or 2 compressors. 3 sensors can be connected; Sair, S5 (Defrost termination), and Sc (Condenser temperature). The first 3 relays are used for compressor on-off, defrost, and light while relay 4 is configurable via “o61” application setting. The relay can be configured for 5 different applications:
1. Alarm relay
2. Evaporator fan control
3. Rail Heat Control
4. Condenser fan control
5. Second compressor control
DI1, and DI2 are flexible Dry Contact inputs that can be configured for multiple functions via “o02” or “o37” (see settings page 12-13).
6 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
84B8250
Sair
S5 Sc DI1DI2
84B8252
Sair
S5 Sc
DI1DI2
84B8254
Sair
S5 Sc
DI1DI2
84B8251
Sair
S5 Sc
DI1DI2
84B8253
Sair
S5 Sc
DI1DI2 *)
Application dependent connections
13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12
230 V
13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12
1
13 14 15 16 17 18 19 20
Danfoss
1 2 3 4 5 6 7 8 9 10 11 12
2
Danfoss
230 V
3
13 14 15 16 17 18 19 20
Danfoss
1 2 3 4 5 6 7 8 9 10 11 12
4
Danfoss
230 V
13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12
1
2
230 V
230 V
5
Danfoss
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 7
Loading...
+ 15 hidden pages