Danfoss AK-CC 210B User guide

User Guide
Controller for temperature control
AK-CC 210B, SW 1.0x
ADAP-KOOL® Refrigeration Control System
www.danfoss.com
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
84B8255
84B8256
Contents
Introduction .........................................................................................................2
Operation ..............................................................................................................3
Applications .........................................................................................................6
Survey of functions ............................................................................................8
Operation ........................................................................................................... 17
Menu survey ...................................................................................................... 18
Ordering ............................................................................................................. 20
Connections ...................................................................................................... 21
Data ...................................................................................................................... 22
Introduction
The AK-CC 210B is dedicated for “plug-in cabinets” in supermarkets.
Principle
The AK-CC 210B controls the temperature in the cabinet based on the measurement from a single sensor – Sair. This sensor can be placed in the cold airflow after the evaporator or in the warm airflow before the evaporator, depending on the construction and usage of the cabinet.
Danfoss
Sair
A measurement of the defrost temperature can be obtained directly through the use of an S5 sensor or indirectly through the use of the Sair measurement.
Relays: the first 3 relays are dedicated for Refrigeration, Defrost and Light, respectively. The usage of relay 4 is selected by the application setting, and can be Alarm, Fan, Rail heat, Condenser fan or Compressor 2.
The different applications are described on page 6.
Advantages
• Many applications in the same unit
• The controller has integrated refrigeration-technical functions, so that it can replace a whole collection of thermostats and timers
• Buttons and seal imbedded in the front
• Alarm monitoring of condenser temperature with compressor stop protection.
• Sealed relays for use with R290 refrigerants
• Can control two compressors
• Easy to remount data communication
• Quick set-up
• Two temperature references
• Digital inputs for various functions
• Clock function with super cap back-up
• Factory calibration that will guarantee a better measuring accuracy than stated in the standard EN ISO 23953-2 without subsequent calibration (Pt 1000 ohm sensor)
Sair
S
air
S
Danfoss
Sair
S
Sair
Sair
Danfoss
84B8257
2 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Tc - Condenser temp.
timet1 t2 t3 t4 t5 t6
84B8259
ompressor run enabled
time
Operation
Operation - Sensors
One thermostat sensor – Sair – can be connected to the controller, and the relevant application defines the placement. It can be placed in the air before the evaporator or in the airflow after the evaporator. The latter is mainly used where there is a risk of too low temperature at the products.
Sair
Sair
Defrost sensor
The best signal concerning the evaporator’s temperature is obtained from a defrost sensor mounted directly on the evaporator. Here the signal may be used by the defrost function, so that the shortest and most energy-saving defrost can take place.
If a defrost sensor is not required, defrost can be stopped based on time, or Sair can be selected.
Condenser temperature sensor
A condenser temperature sensor – Sc – can be used for monitoring the temperature on the condenser. Depending on settings, alarms can be generated and other actions, including safety stop of compressor, can be initiated based on this temperature.
Condenser temperature alarms and actions
An alarm warning can be activated when the temperature gets above a set Condenser Alarm limit and a critical alarm can be activated at a higher Condenser Block Alarm limit. At this critical level, different actions can be initiated e.g. turning off the light in the cabinet, turning off the compressor, or both. The wanted action is defined by parameter "P92".
Compressors can be permanently stopped if a defined number of critical alarms occur within a defined time period. If the number of events exceeds the setting in parameter "P94" within a period defined in "P93", the last event will always include a compressor stop, together with other actions defined in "P92". This state requires a manual reset before the compressor can start again.
Condenser Block Alarm (A54)
Condenser Alarm (A37)
Di.
(A78)
Delay (A55)
S5
Sc
Danfoss
84B8258
2x Di. (A78)
Danfoss
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 3
Time Period (P93)
Events in period (P94)12345
Manual reset
C
Danfoss
84B8260
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Control of two compressors
This control is used for controlling two compressors of the same size. The principle for control is that one of the compressors connects at ½ the differential of the thermostat, and the other at the full differential. When the thermostat cuts in, the compressor with the fewest operating hours is started. The other compressor will only start after a set time delay, so that the load will be divided between them. The time delay has a higher priority than the temperature. When the air temperature has dropped by half the differential, one of the compressors will stop, while the other will continue working and not stop until the required temperature is achieved. The compressors used must be of a type that is capable of starting up against a high pressure.
Change of temperature reference
In an impulse appliance, for example, used for various product groups the temperature reference is changed easily with a contact signal on a digital input. The signal changes the normal thermostat setpoint by a predefined value. At the same time the high and low alarm limits will be displaced with the same value.
Night setback
The thermostat reference can be displayed with an offset at night. The alarm limit value will be changed with the same value as the night offset. The change will only be applied for positive night offset.
Digital inputs
There are two digital inputs, both of which can be used for the following functions:
- Case cleaning
- Door contact function with alarm
- Starting a defrost
- Coordinated defrost (DO2 only)
- Night setback
- Change-over between two temperature reference
- Report state of digital input via data communication
Case cleaning function
This function makes it easy to steer the refrigeration appliance through a cleaning phase. Via three pushes on a switch you change from one phase to the next phase. The first push stops the refrigeration – the fans keep working. ”Later”: The next push stops the fans ”Still later”: The next push restarts refrigeration The different situations can be followed on the display.
On the network, a cleaning alarm is transmitted to the system unit. This alarm can be ”logged” so that proof of the sequence of events is provided.
- + + °C
1 ÷ + Fan
2 ÷ ÷ Off
3 + + °C
Door contact function
In cold rooms and frost rooms the door switch can switch the light on and off, start and stop the refrigeration and give alarm if the door has remained open for too long.
Defrost
Depending on the application, you may choose between the following defrost methods: Natural: Here the fans are kept operating during defrost Electric: The heating element is activated Hot gas: The defrost output is used to control a solenoid that lets
the hot gas flow through the evaporator. The compressor is kept running to generate hot gas.
4 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Start of defrost
A defrost can be started in different ways: Interval: Defrost is started at fixed time intervals, e.g. every eighth hour Refrigeration time: Defrost is started at fixed refrigeration time intervals. In other words, a low need for refrigeration will ”postpone” the coming defrost. Schedule: Here defrost can be started at fixed times of the day and night. However, max. 6 times. Contact: Defrost is started with a contact signal on a digital input. Network: The signal for defrost is received from a system unit via the data communication. S5 temp In 1:1 systems the efficiency of the evaporator can be followed. Icing-up will start a defrost. Manual: An extra defrost can be activated from the controller’s lower-most button. (Though not for application 4).
All the mentioned methods can be used at random – if just one of them is activated a defrost will be started.
Coordinated defrost
There are two ways in which coordinated defrost can be arranged. Either with wire connections between the controllers or via data communication.
Max. 15
Wire connections
One of the controllers is defined to be the controlling unit and a battery module may be fitted in it so that the clock is ensured back-up. When a defrost is started, all the other controllers will follow suit and likewise start a defrost. After the defrost, the individual controllers will move into waiting position. When all are in waiting position there will be a change-over to refrigeration. (If just one in the group demands defrost, the others will follow suit).
Defrost via data communication
All controllers are fitted with a data communication module, and via the override function from a gateway the defrost can be coordinated.
Defrost on demand
1. Based on refrigeration time
When the aggregate refrigeration time has passed a set time, a defrost will be started.
2. Based on temperature
The controller will constantly follow the temperature at S5. Between two defrosts, the S5 temperature will become lower the more the evaporator ices up (the compressor operates for a longer time and pulls the S5 temperature further down). When the temperature passes a set allowed variation, the defrost will be started. This function can only work in 1:1 systems.
Service request alarm
The controller will register the accumulated on-time in days, and a limit can be set to activate a “service request alarm” to indicate that inspection and cleaning of the fan and condenser is imminent. After doing so, the Runtime counter can be reset and a new period initiated.
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 5
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Extra module
• The controller can afterwards be fitted with an insertion module if the application requires it.
The controller has been prepared with plug, so the module
simply has to be pushed in.
- Battery module The module guarantees voltage to the controller if the supply
voltage should drop out for more than four hours. The clock function can thus be protected during a power failure.
- Data communication If you require operation from a PC, a data communication
module has to be placed in the controller.
External display
If it is necessary to indicate the temperature on the front of
the refrigeration appliance, a display type EKA 163A can be mounted. The extra display will show the same information as the controller's display, but does not incorporate buttons for operation. If operation from the external display is needed a display type EKA 164A must be mounted.
Applications
AK-CC 210B is developed for refrigerated plug-in cabinets with one or 2 compressors. 3 sensors can be connected; Sair, S5 (Defrost termination), and Sc (Condenser temperature). The first 3 relays are used for compressor on-off, defrost, and light while relay 4 is configurable via “o61” application setting. The relay can be configured for 5 different applications:
1. Alarm relay
2. Evaporator fan control
3. Rail Heat Control
4. Condenser fan control
5. Second compressor control
DI1, and DI2 are flexible Dry Contact inputs that can be configured for multiple functions via “o02” or “o37” (see settings page 12-13).
6 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
84B8250
Sair
S5 Sc DI1DI2
84B8252
Sair
S5 Sc
DI1DI2
84B8254
Sair
S5 Sc
DI1DI2
84B8251
Sair
S5 Sc
DI1DI2
84B8253
Sair
S5 Sc
DI1DI2 *)
Application dependent connections
13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12
230 V
13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12
1
13 14 15 16 17 18 19 20
Danfoss
1 2 3 4 5 6 7 8 9 10 11 12
2
Danfoss
230 V
3
13 14 15 16 17 18 19 20
Danfoss
1 2 3 4 5 6 7 8 9 10 11 12
4
Danfoss
230 V
13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12
1
2
230 V
230 V
5
Danfoss
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 7
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Survey of functions
Function Para-
Normal display
Normally the temperature value from the thermostat sensor Sair is displayed. Display air (u56)
Thermostat Thermostat control Setpoint
Regulation is based on the set value plus a displacement, if applicable. The value is set via a push on the centre button. The set value can be locked or limited to a range with the settings in r02 and r 03. The reference at any time can be seen in ”u28 Temp. ref”.
Differential
When the temperature is higher than the reference + the set differential, the com­pressor relay will be cut in. It will cut out again when the temperature comes down to the set reference.
Setpoint limitation
The controller’s setting range for the setpoint may be narrowed down, so that much too high or much too low values are not set accidentally - with resulting damages.
To avoid a too high setting of the setpoint, the max. allowable reference value must be lowered.
To avoid a too low setting of the setpoint, the min. allowable reference value must be increased.
Correction of the display’s temperature showing
If the temperature at the products and the temperature received by the controller are not identical, an offset adjustment of the shown display temperature can be carried out.
Temperature unit
Here you set whether the controller display is to show temperature values in °C or in °F.
Correction of signal from Sair
Compensation possibility through long sensor cable
Start / stop of refrigeration
With this setting refrigeration can be started, stopped or a manual override of the outputs can be allowed. Start / stop of refrigeration can also be accomplished with the external switch func­tion connected to a DI input. Stopped refrigeration will give a ”Standby alarm”.
Night setback value
The thermostat’s reference will be the setpoint plus this value when the controller changes over to night operation. (Select a negative value if there is to be cold ac­cumulation.)
Activation of reference displacement
When the function is changed to ON, the thermostat reference will be displaced by the value in r40. Activation can also take place via input DI1 or DI2 (defined in o02 or o37).
Ref. Dif.
meter
Parameter by operation via data communication
Cutout °C
r01 Differential
r02 Max cutout °C
r03 Min cutout °C
r04 Disp. Adj. K
r05 Temp. unit
°C=0. / °F=1
r09 Adjust Sair
r12 Main Switch
1: Start 0: Stop
-1: Manual control of outputs allowed
r13 Night offset
r39 Th. offset
Value of reference displacement
The thermostat reference and the alarm values are shifted the following number of degrees when the displacement is activated. Activation can take place via r39 or input DI
8 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
r40 Th. offset K
Night setbck (start of night signal)
Forced cool. (start of forced cooling)
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Alarm Alarm settings
The controller can give alarm in different situations. When there is an alarm, all the light-emitting diodes (LED) will flash on the controller front panel, and the alarm relay will cut in.
Alarm delay (short alarm delay) If one of the two limit values is exceeded, a timer function will commence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes.
Time delay for door alarm
The time delay is set in minutes. The function is defined in o02 or in o37.
Time delay for cooling (long alarm delay) This time delay is used during start-up, during defrost and immediately after a defrost. There will be change-over to the normal time delay (A03) when the temperature has dropped below the set upper alarm limit. The time delay is set in minutes.
Upper alarm limit
Here you set the alarm limit for the high temperature alarm. The limit is set in °C (absolute value). During night condition, the limit value will be changed with the same value as the night offset. The change will only be applied for positive night offset. The limit value will also be changed in connection with reference displacement r39. Regardless, whether this is positive or negative.
Lower alarm limit
Here you set the alarm limit for low temperature alarms. The limit value is set in °C (absolute value). During night condition, the limit will remain unchanged, while a reference displacement r39, will increase or lower the limit with the value given by r40.
Delay of a DI1 alarm
A cut-out/cut-in input will result in alarm when the time delay has been passed. The function is defined in o02.
Delay of a DI2 alarm A cut-out/cut-in input will result in alarm when the time delay has been passed. The function is defined in o37
Condenser alarm limit
Setpoint for the condenser temperature alarm, the warning level without compres­sor stop. The alarm will clear when the condenser temperature is decreased with the value defined in parameter A78.
Condenser block alarm limit
Setpoint for the condenser block alarm. Activation of this alarm can trigger an action – light off, compressor stop or both (see parameter P92) The alarm will clear when the condenser temperature is decreased with 2 times the value defined in parameter A78.
Condenser alarm delay
Delay for the condenser block alarm and potential action. The delay starts when the condenser temperature exceeds the limit in parameter A54.
Condenser alarm difference
Difference band below the condenser alarm temperature settings (A37 and A54) for clearing the alarms.
Compressor Compressor control
The compressor relay works in conjunction with the thermostat. When the thermo­stat calls for refrigeration the compressor relay will be operated.
Running times
To prevent irregular operation, values can be set for the time the compressor is to run once it has been started, and for how long it at least has to be stopped.
The running times are not observed when defrosts start. Min. ON time (in minutes) c01 Min. On time Min. OFF time (in minutes) c02 Min. Off time
Time delay for couplings of two compressors
Settings indicate the time that has to elapse from the first relay cuts in and until the next relay has to cut in.
With data communication the impor­tance of the individual alarms can be defined. Setting is carried out in the “Alarm destinations” menu.
A03 Alarm delay
A04 DoorOpen del
A12 Pulldown del
A13 HighLim Air
A14 LowLim Air
A27 AI.Delay DI1
A28 AI.Delay DI2
A37 Cond Al.Lim
A54 Cond T. Block
A55 Al.Del.Cond
A78 Cond Al.Diff
Reset alarm EKC error
c05 Step delay
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 9
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
The LED on the controller’s front will show whether refrigeration is in progress. Comp Relay
Here you can read the status of the compressor relay, or you can force­control the relay in the ”Manual control” mode
Defrost Defrost control
The controller contains a timer function that is zeroset after each defrost start. The timer function will start a defrost if/when the interval time is passed. The timer function starts when voltage is connected to the controller, but it is dis­placed the first time by the setting in d05. If there is power failure, the timer value will be saved and continue from here when the power returns. This timer function can be used as a simple way of starting defrosts, but it will always act as safety defrost if one of the subsequent defrost starts is not received. The controller also contains a real-time clock. By means of settings of this clock and times for the required defrost times, defrost can be started at fixed times of the day. If there is a risk of power failure for periods longer than four hours, a battery module should be mounted in the controller. Defrost start can also be accomplished via data communication, via contact signals or manual start-up. All starting methods will function in the controller. The different functions have to be set, so that defrosts do not ”come tumbling” one after the other. Defrost can be accomplished with electricity or hot gas. The actual defrost will be stopped based on time or temperature with a signal from a temperature sensor.
Defrost method
Here you set whether defrost is to be accomplished with electricity, gas or "non". During defrost the defrost relay will be cut in.
Defrost stop temperature
The defrost is stopped at a given temperature which is measured with a sensor (the sensor is defined in d10).
The temperature value is set.
Interval between defrost starts
The function is zeroset and will start the timer function at each defrost start. When the time has expired the function will start a defrost. The function is used as a simple defrost start, or it may be used as a safeguard if the normal signal fails to appear. If master/slave defrost without clock function or without data communication is used, the interval time will be used as max. time between defrosts. If a defrost start via data communication does not take place, the interval time will be used as max. time between defrosts. When there is defrost with clock function or data communication, the interval time must be set for a somewhat longer period of time than the planned one, as the interval time will otherwise start a defrost which a little later will be followed by the planned one. In connection with power failure the interval time will be maintained, and when the power returns, the interval time will continue from the maintained value. The interval time is not active when set to 0.
Max. defrost duration
This setting is a safety time so that the defrost will be stopped if there has not already been a stop based on temperature or via coordinated defrost.
Time staggering for defrost cut-ins during start-up
The function is only relevant if you have several refrigeration appliances or groups where you want the defrost to be staggered in relation to one another. The function is furthermore only relevant if you have chosen defrost with interval start (d03). The function delays the interval time d03 by the set number of minutes, but it only does it once, and this at the very first defrost taking place when voltage is connected to the controller. The function will be active after each and every power failure.
Drip-off time
Here you set the time that is to elapse from a defrost and until the compressor is to start again. (The time when water drips off the evaporator).
Delay of fan start after defrost
Here you set the time that is to elapse from compressor start after a defrost and until the fan may start again. (The time when water is “tied” to the evaporator).
d01 Def. method
0 = non 1 = El 2 = Gas
d02 Def. Stop Temp
d03 Def Interval
(0=off)
d04 Max Def. time
d05 Time Stagg.
d06 DripOff time
d07 FanStartDel
10 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Fan start temperature
The fan may also be started a little earlier than mentioned under “Delay of fan start after defrost”, if the defrost sensor S5 registers a lower value than the one set here.
Fan cut-in during defrost
Here you can set whether fan is to operate during defrost. 0: Stopped (Runs during pump down) 1: Running (stopped during "fan delay") 2: Running during pump down and defrost. After that it is stopped.
Defrost sensor Here you define the defrost sensor. 0: None, defrost is based on time 1: S5 2: Sair
Pumpdown delay
Set the time where the evaporator is emptied of refrigerant prior to the defrost.
Defrost on demand – aggregate refrigeration time
Here the refrigeration time allowed without defrosts is set. If the time is passed, a defrost will be started. With setting = 0 the function is cut out.
Defrost on demand – S5 temperature
The controller will follow the effectivity of the evaporator, and via internal calcula­tions and measurements of the S5 temperature it will be able to start a defrost when the variation of the S5 temperature becomes larger than required. Here you set how large a slide of the S5 temperature can be allowed. When the value is passed, a defrost will start.
The function can only be used in 1:1 systems when the evaporating temperature will become lower to ensure that the air temperature will be maintained. In central systems the function must be cut out.
With setting = 20 the function is cut out
Max. duration of -d- in the display
Controls the readout of "-d-" after defrost, so that "-d-" is shown until the temperature is ok, the set delay has expired, or a temperature alarm becomes active.
If you wish to see the temperature at the defrost sensor, push the controller’s lower­most button.
If you wish to start an extra defrost, push the controller’s lowermost button for four seconds. You can stop an ongoing defrost in the same way.
The LED on the controller’s front will indicate whether a defrost is going on. Defrost Relay
d08 FanStartTemp
d09 FanDuringDef
d10 DefStopSens.
d16 Pump dwn del.
d18 MaxTherRunT
d19 CutoutS5Dif.
d40 Disp. D del.
Defrost temp.
Def Start Here you can start a manual defrost
Here you can read the defrost relay status or you can force-control the relay in “Manual control” mode.
Hold After Def Shows ON when the controller is operating with coordinated defrost.
Defrost State Status on defrost 1= pump down / defrost
Fan Fan control Fan stopped at cut-out compressor
Here you can select whether the fan is to be stopped when the compressor is cut out.
Delay of fan stop when compressor is cut out
If you have chosen to stop the fan when the compressor is cut out, you can delay the fan stop when the compressor has stopped. Here you can set the time delay.
Fan stop temperature
The function stops the fans in an error situation, so that they will not provide power to the appliance. If the defrost sensor registers a higher temperature than the one set here, the fans will be stopped. There will be re-start at 2 K below the setting. The function is not active during a defrost or start-up after a defrost. With setting +50°C the function is interrupted.
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 11
F01 Fan stop CO
(Yes = Fan stopped)
F02 Fan del. CO
F04 FanStopTemp.
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
The LED on the controller’s front will indicate whether the fan is running. Fan Relay
Internal defrosting schedule/clock function
(Not used if an external defrosting schedule is used via data communication.) Up to six individual times can be set for the defrost start throughout the day.
Defrost start, hour setting t01-t06 Defrost start, minute setting (1 and 11 belong together, etc.)
When all t01 to t16 equal 0 the clock will not start defrosts.
Real-time clock
Setting the clock is only necessary when there is no data communication. In the event of a power failure of less than four hours, the clock function will be saved. When mounting a battery module the clock function can preserved longer. There is also a date indication used for registration of temperature measurements.
Clock: Hour setting t07
Clock: Minute setting t08
Clock: Date setting t45
Clock: Month setting t46
Clock: Year setting t47
Miscellaneous Miscellaneous Delay of output signal after start-up
Start-up after a power failure the controller’s functions can be delayed so that over­loading of the electricity supply network is avoided. Here you can set the time delay.
Digital input signal - DI1
The controller has a digital input 1 which can be used for one of the following functions: Off: The input is not used
1. Status display of a contact function
2. Door function: When the input is open it signals that the door is open. The refrigeration and the fans are stopped. When the time setting in “A4” is passed, an alarm will be given and refrigeration will be resumed.
3. Door alarm: When the input is open it signals that the door is open. When the time setting in “A4” is passed, there will be an alarm.
4. Defrost: The function is started with a pulse signal. The controller will register when the DI input is activated. The controller will then start a defrost cycle. If the signal is to be received by several controllers it is important that ALL connections are mounted the same way (DI to DI and GND to GND).
5. Main switch: Regulation is carried out when the input is short-circuited, and regulation is stopped when the input is put in pos. OFF.
6. Night operation: When the input is short-circuited, there will be regulation for night operation.
7. Reference displacement when DI1 is short-circuited. Displacement with “r40”.
8. Separate alarm function: Alarm will be given when the input is short-circuited.
9. Separate alarm function: Alarm will be given when the input is opened. (For 8 and 9 the time delay is set in A27)
10. Case cleaning: The function is started with a pulse signal. Cf. also description on page 4.
If the controller is built into a network with data communication, it must have an address, and the master gateway of the data communication must then know this address. These settings can only be made when a data communication module has been mounted in the controller and the installation of the data communication cable has been finished. This installation is mentioned in a separate document “RC8AC”.
The address is set between 1 and 60 (119), gateway determined. o03 The address is sent to the gateway when the menu is set in pos. ON
IMPORTANT: Before you set o04, you MUST set o61. Otherwise you will be transmit­ting incorrect data.
Access code 1 (Access to all settings)
If the settings in the controller are to be protected with an access code you can set a numerical value between 0 and 100. If not, you can cancel the function with setting 0. (99 will always give you access).
t11-t16
Here you can read the fan relay status, or force-control the relay in “Manual control” mode.
o01 DelayOfOutp.
o02 DI 1 Config.
Definition takes place with the numerical value shown to the left.
(0 = off)
DI state (Measurement) The DI input’s present status is shown here. ON or OFF.
After installation of a data communication module, the controller can be operated on an equal footing with the other controllers in ADAP­KOOL® refrigeration controls.
o04
o05 -
12 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Sensor type
Normally a Pt 1000 sensor with great signal accuracy is used. But you can also use a sensor with another signal accuracy. That may either be a PTC 1000 sensor (1000 ohm) or an NTC sensor (5000 Ohm at 25°C). All the mounted sensors must be of the same type.
Local readout of software version o08 SW version
Display step
Yes: Gives steps of 0.5° No: Gives steps of 0.1°
Max. standby time after coordinated defrost
When a controller has completed a defrost it will wait for a signal which tells that the refrigeration may be resumed. If this signal fails to appear for one reason or another, the controller will itself start the refrigeration when this standby time has elapsed.
Digital input signal - D2
The controller has a digital input 2 which can be used for one of the following func­tions: Off: The input is not used.
1. Status display of a contact function
2. Door function: When the input is open it signals that the door is open. The refrig­eration and the fans are stopped. When the time setting in “A4” is passed, an alarm will be given and refrigeration resumed.
3. Door alarm: When the input is open it signals that the door is open. When the time setting in “A4” is passed an alarm will be given.
4. Defrost: The function is started with a pulse signal. The controller will register when the DI input is activated. The controller will then start a defrost cycle. If the signal is to be received by several controllers it is important that ALL connections are mounted the same way (DI to DI and GND to GND).
5. Main switch: Regulation is carried out when the input is short-circuited, and regu­lation is stopped when the input is put in pos. OFF.
6. Night operation: When the input is short-circuited, there will be regulation for night operation.
7. Reference displacement when DI2 is short-circuited. Displacement with “r40”.
8. Separate alarm function: Alarm will be given when the input is short-circuited.
9. Separate alarm function: Alarm will be given when the input is opened.
10. Case cleaning: The function is started with a pulse signal. Cf. also description on page 4.
11. Not used
12. The input is used for coordinated defrost in conjunction with other controllers of the same type.
Configuration of light function (relay 4 in applications 2 and 6)
1) The relay cuts in during day operation
2) The relay to be controlled via data communication
3) The relay to be controlled by the door switch defined in either o02 or o37 where
the setting is selected to either 2 or 3. When the door is opened the relay will cut in. When the door is closed again there will be a time delay of two minutes before the light is switched off.
Activation of light relay
The light relay can be activated here, but only if defined in o38 with setting 2.
Rail heat during day operation
The ON period is set as a percentage of the time.
Rail heat during night operation
The ON period is set as a percentage of the time.
Rail heat cycle
The period of time for the aggregate ON time + OFF time is set in minutes.
Case cleaning
The status of the function can be followed here or the function can be started manually. 0 = Normal operation (no cleaning) 1 = Cleaning with fans operating. All other outputs are Off. 2 = Cleaning with stopped fans. All outputs are Off. If the function is controlled by a signal at the DI1 or DI2 input, the relevant status can be seen here in the menu.
Selection of application
The controller can be defined in various ways. Here you set which of the 5 applications is required. On page 6 you can see a survey of applications.
This menu can only be set when regulation is stopped, i.e. “r12” is set to 0.
o06 SensorConfig
Pt = 0 PTC = 1
NTC = 2
o15 Disp. Step = 0.5
o16 Max HoldTime
o37 DI2 config.
o38 Light config
o39 Light remote
o41 Railh.ON day%
o42 Railh.ON ngt%
o43 Railh. cycle
o46 Case clean
o61 --- Appl. Mode
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 13
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Transfer a set of presettings to the controller
It is possible to select a quick setting of a number of parameters. It depends on whether an application or a room is to be controlled and whether defrost is to be stopped based on time or based on temperature. The survey can be seen on page 22.
This menu can only be set when regulation is stopped, i.e. “r12” is set to 0.
After the setting, the value will return to 0. Any subsequent adjustment/setting of parameters can be made, as required.
Access code 2 (Access to adjustments)
There is access to adjustments of values, but not to configuration settings. If the set­tings in the controller are to be protected with an access code you can set a numeri­cal value between 0 and 100. If not, you can cancel the function with setting 0. If the function is used, access code 1 (o05) must also be used.
Save as factory setting
With this setting you save the controller’s actual settings as a new basic setting (the earlier factory settings are overwritten).
Runtime readout
Readout of the accumulated controller runtime in days (powered up and main switch on). Can be cleared or adjusted when r12 Main switch is off.
Service alarm request
Days of operation before Service alarm request. Value = 0 disables function
Defines action when Condenser blocked alarm activates
0 = Function disabled, 1 = Turn off Light, 2 = Stop compressor, 3 = Light and comp off, 4 = Stop comp, Rail heat and light off, 5 = Comp, Light and RH off
Period for counting condenser events before permanent stop
Number of hours for counting events. Events that are older than the set period are discarded.
Number of condenser events within period before permanent stop
The period is defined by parameter P93. Value = 0 disables function
Service Service
Temperature measured with Sair sensor u01 Sair temp. Temperature measured with S5 sensor u09 S5 temp. Status on DI1 input. on/1=closed u10 DI1 status Status on night operation (on or off) 1=closed u13 Night Cond. Read the present regulation reference u28 Temp. ref. Status on DI2 output. on/1=closed u37 DI2 status Temperature measured with Sc sensor U09 Sc temp. Temperature shown on display ** Status on relay for cooling u58 Comp1/LLSV ** Status on relay for fan u59 Fan relay ** Status on relay for defrost u60 Def. relay ** Status on relay for rail heat u61 Railh. relay ** Status on relay for alarm u62 Alarm relay ** Status on relay for light u63 Light relay ** Status on relay for compressor 2 u67 Comp2 relay ** Status on relay for condenser fan u71 Condenser fan relay *) Not all items will be shown. Only the function belonging to the selected applica-
tion can be seen.
o62 -
o64 -
o67 -
P48 Unit runtime
P91 CondServ req
P92 Cond action
P93 Cond period
P94 Cond Ev cnt
- - - Night Setback 0=Day 1=Night
u56 Display air
14 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Fault message Alarms
In an error situation the LEDs on the front will flash and the alarm relay will be acti­vated. If you push the top button in this situation you can see the alarm report in the display. If there are more keep on pushing to see them. There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation. A-alarms will not become visible until the set time delay has expired. E-alarms, on the other hand, will become visible the moment the error occurs. (An A alarm will not be visible as long as there is an active E alarm). Here are the messages that may appear: 1 = alarm
A1: High temperature alarm High t. alarm
A2: Low temperature alarm Low t. alarm
A4: Door alarm Door Alarm
A5: Information. Parameter o16 is expired Max Hold Time
A15: Alarm. Signal from DI1 input DI1 alarm
A16: Alarm. Signal from DI2 input DI2 alarm
A45: Standby position (stopped refrigeration via r12 or DI input) (Alarm relay will not be activated)
A59: Case cleaning. Signal from DI1 or DI2 input Case cleaning
A61: Condenser temperature alarm Cond Alarm
A80: Condenser blocked alarm Cond blocked
AA4: Service request alarm Cond ServReq
E1: Faults in the controller EKC error
E6: Fault in real-time clock. Check the battery / reset the clock. -
E27: Sensor error on S5 S5 error
E29: Sair sensor error Sair error
E64: Sc sensor error Sc error
Standby mode
Max. def time
Alarm destinations
The importance of the individual alarms can be defined with a setting (0, 1, 2 or 3)
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 15
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Operating status (Measurement)
The controller goes through some regulating situations where it is just waiting for the next point of the regulation. To make these “why is nothing happening” situations
EKC State:
(Shown in all menu displays) visible, you can see an operating status on the display. Push briefly (1s) the upper but­ton. If there is a status code, it will be shown on the display. The individual status codes have the following meanings:
S0: Regulating 0
S1: Waiting for end of the coordinated defrost 1
S2: When the compressor is operating it must run for at least x minutes. 2
S3: When the compressor is stopped, it must remain stopped for at least x minutes. 3
S4: The evaporator drips off and waits for the time to run out 4
S10: Refrigeration stopped by main switch. Either with r12 or a DI-input 10
S11: Refrigeration stopped by thermostat 11
S14: Defrost sequence. Defrost in progress 14
S15: Defrost sequence. Fan delay — water attaches to the evaporator 15
S17: Door is open. DI input is open 17
S20: Emergency cooling *) 20
S25: Manual control of outputs 25
S29: Case cleaning 29
S32: Delay on outputs during start-up 32
S34: Condenser blocked event active 34
Other displays:
non: The defrost temperature cannot be displayed. There is stop based on time
-d-: Defrost in progress / First cooling after defrost
PS: Password required. Set password
*) Emergency cooling will take effect when there is lack of signal from the Sair sensor. The regulation will continue with a registered average cut-in frequency. There are two registered values – one for day operation and one for night operation.
Warning ! Direct start of compressors * To prevent compressor breakdown, parameter c01 and c02 should be set according to suppliers requirements or in general: Hermetic Compressors c02 min. 5 minutes Semihermetic Compressors c02 min. 8 minutes and c01 min. 2 to 5 minutes (motor from 5 – 15 kW ) * ) Direct activating of solenoid valves does not require settings different from factory (0)
16 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Operation
Display
The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.
Light-emitting diodes (LED) on front panel
The other LEDs on the front panel will light up when the belong­ing relay is activated.
= Refrigeration = Defrost = Fan running
The light-emitting diodes will flash when there is an alarm. In this situation you can download the error code to the display and cancel/sign for the alarm by giving the top knob a brief push.
Defrost
During defrost a –d- is shown in the display. After defrost is finished, the readout of –d- will be continued until one of the following conditions are met:
- The temperature is OK (below the cut-in limit)
- A high temperature alarm becomes active
- The delay set with the d40 parameter expires
- The regulation is stopped with “Main switch”
The buttons
When you want to change a setting, the upper and the lower buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the col­umn with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value, save the new value by once more pushing the middle button.
Examples:
Set menu
1. Push the upper button until a parameter r01 is shown.
2. Push the upper or the lower button and find the parameter you want to change.
3. Push the middle button until the parameter value is shown.
4. Push the upper or the lower button and select the new value.
5. Push the middle button again to freeze the value.
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and select the new value
3. Push the middle button again to conclude the setting.
Reading the temperature at defrost sensor
• Push the lower button shortly
Manual start or stop of a defrost
• Push the lower button for four seconds. (Though not for application 4).
Get a good start
With the following procedure you can start regulation very quickly:
1 Open parameter r12 and stop the regulation (in a new and not
previously set unit, r12 will already be set to 0 which means stopped regulation.)
2 Select application dependent connections based on the
drawings on page 7.
3 Open parameter o61 and set the electric connection number in
it.
4 Now select one of the preset settings from the table on page 20.
5 Open parameter o62 and set the number for the array of
presettings. The few selected settings will now be transferred to the menu.
6 Open parameter r12 and start the regulation
7 Go through the survey of factory settings. The values in the grey
cells are changed according to your choice of settings. Make any necessary changes in the respective parameters.
8 For network. Set the address in o03 and then install on the
system unit by scanning, or for Lon via setting o04.
Cut-out alarm relay / receipt alarm/see alarm code
• Push the upper button shortly. If there are several alarm codes they are found in a rolling stack. Push the uppermost or lowermost button to scan the rolling stack.
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 17
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Menu survey
Function Codes 1 2 3 4 5 Normal operation
Temperature (set point) --- -50.0 °C 50.0 °C 2.0 °C
Thermostat
Differential *** r01 0.1 K 20.0K 2.0 K Max. limitation of setpoint setting *** r02 -49.0 °C 50 °C 50.0 °C Min. limitation of setpoint setting *** r03 -50.0 °C 49.0 °C -50.0 °C Adjustment of temperature indication r04 -20.0 K 20.0 K 0.0 K Temperature unit (°C/°F) r05 °C °F °C Correction of the signal from Sair r09 -10.0 K 10.0 K 0.0 K Manual service, stop regulation, start regulation (-1, 0, 1) r12 -1 1 0 Displacement of reference during night operation r13 -20.0 K 20.0 K 0.0 K Activation of reference displacement r40 r39 OFF ON OFF Value of reference displacement (activate via r39 or DI) r40 -50.0 K 50.0 K 0.0 K
Alarm
Delay for temperature alarm A03 0 min. 240 min. 30 min. Delay for door alarm *** A04 0 min. 240 min. 60 min. Delay for temperature alarm after defrost A12 0 min. 240 min. 90 min. High alarm limit *** A13 -50.0 °C 50.0 °C 8.0 °C Low alarm limit *** A14 -50.0 °C 50.0 °C -30.0 °C Alarm delay DI1 A27 0 min. 240 min. 30 min. Alarm delay DI2 A28 0 min. 240 min. 30 min. Alarm limit for condenser temperature alarm A37 20.0 °C 120.0 °C 60.0 °C Limit for condenser block alarm and comp. stop A54 20.0 °C 140.0 °C 70.0 °C Delay for condenser block alarm A55 0 min. 30 min. 0 min. Difference for clearing condenser alarms A78 1.0 K 30.0 K 10.0 K
Compressor
Min. ON-time c01 0 min. 30 min. 0 min. Min. OFF-time c02 0 min. 30 min. 0 min. Time delay for cut-in of comp.2 c05 0 sec 900 sec 5 sec
Defrost
Defrost method (none/EL/GAS) d01 none GAS none Defrost stop temperature d02 0.0 °C 25.0 °C 6.0 °C Interval between defrost starts d03 0 hours Max. defrost duration d04 0 min. 180 min. 45 min. Displacement of time on cut-in of defrost at start-up d05 0 min. 240 min. 0 min. Drip off time d06 0 min. 60 min. 0 min. Delay for fan start after defrost d07 0 min. 60 min. 0 min. Fan start temperature d08 -15.0 °C 0.0 °C -5.0 °C Fan cut-in during defrost 0: Stopped 1: Running 2: Running during pump down and defrost Defrost sensor (0=time, 1=S5, 2=Sair) d10 0 2 0 Pump down delay d16 0 min. 60 min. 0 min. Max. aggregate refrigeration time between two defrosts d18 0 hours 48 hours 0 hours Defrost on demand - S5 temperature’s permitted variation during frost build-up. On central plant choose 20 K (=off) Max. duration of -d- in display d40 5 min. 240 min. 30 min.
Fan
Fan stop at cut-out compressor F01 no yes no Delay of fan stop F02 0 min. 30 min. 0 min. Fan stop temperature (S5) F04 -50.0 °C 50.0 °C 50.0 °C
Real time clock
Six start times for defrost. Setting of hours. 0=OFF Six start times for defrost. Setting of minutes. 0=OFF Clock - Setting of hours *** t07 0 hours 23 hours 0 hours Clock - Setting of minutes *** t08 0 min. 59 min. 0 min. Clock - Setting of date *** t45 1 31 1 Clock - Setting of month *** t46 1 12 1 Clock - Setting of year *** t47 0 99 0
Miscellaneous
Delay of output signals after start-up o01 0 s 600 s 5 s Input signal on DI1. Function: 0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation 7=change reference (activate r40). 8=alarm function when closed. 9=alarm function when open. 10=case cleaning (pulse signal). Network address o03 0 240 0 On/Off switch (Service Pin message) IMPORTANT! o61 must be set prior to o04
Parameters Variant of AK-CC
d09 0 2 1
d19 0.0 K 20.0 K 20.0 K
t01-t06 0 hours 23 hours 0 hours
t11-t16 0 min. 59 min. 0 min.
o02 0 10 0
o04 OFF ON OFF
Grey marked settings will be changed by the Quick setting function. See table on page 20.
Min.­value
Max.­value
240 hours
Factory
setting
8 hours
SW = 1.0x
Actual
setting
18 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Access code 1 (all settings) o05 0 100 0 Used sensor type (Pt /PTC/NTC) o06 Pt ntc Pt Readout of software version o08 Display step = 0.5 (normal 0.1 at Pt sensor) o15 no yes no Max. hold time after coordinated defrost o16 0 min. 60 min. 20 min. Input signal on DI2. Function: (0 = not used. 1 = status on DI2. 2 = door function with alarm when open. 3 = door alarm when open. 4 = defrost start (pulse-signal). 5 = ext. main switch. 6 = night operation. 7 = change reference (activate r40). 8 = alarm function when closed. 9 = alarm function when open. 10 = case cleaning (pulse signal). 11 = not used. 12 = defrost coordination. Configuration of light function (relay 4) 1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI­function, when DI is selected to door function or to door alarm Activation of light relay (only if o38=2) o39 OFF ON OFF Rail heat On time during day operations o41 0% 100% 100% Rail heat On time during night operations o42 0% 100% 100% Rail heat period time (On time + Off time) o43 6 min. 60 min. 10 min. Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off. *** o46 0 2 0 Selection of EL diagram. See page 7 * o61* 1 5 1 Download a set of predetermined settings. See overview previous page. * o62* 0 2 0 Access code 2 (partly access) *** o64 0 100 0 Replace the controllers factory settings with the present settings o67 OFF On OFF Readout of Unit runtime in days * P48 0 days 999 days 0 days Service Alarm request. Days of operation (Unit runtime) before Service request alarm Value = 0 disables function Defines action when Condenser blocked alarm activates: 0 = Function disabled. 1 = Turn off Light, 2 = Stop compressor. 3 = Light and comp off, 4 = Stop comp, Rail heat and light off. 5 = Comp, Light and RH off Period for counting condenser events before permanent stop P93 0 hours 96 hours 0 hours Number of condenser events within period before permanent stop Value = 0 disables function
Service
Status codes are shown on page 16 Temperature measured with Sair sensor u01 Temperature measured with S5 sensor Status on DI1 input. on/1=closed Status on night operation (on or off) 1=closed Read the present regulation reference Status on DI2 output. on/1=closed Temperature measured with Sc sensor Temperature shown on display Status on relay for cooling Status on relay for fan Status on relay for defrost Status on relay for rail heat Status on relay for alarm Status on relay for light Status on relay for compressor 2 Status on relay for condenser fan
*) Can only be set when regulation is stopped (r12=0) **) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
o37 0 12 0
o38 1 3 1
P91 0 days 960 days 0 days
P92 0 5 0
P94 0 50 0
S0-S34
*** u09
u10
*** u13
u28 u37 U09
u56 ** u58 ** u59 ** u60 ** u61 ** u62 ** u63 ** u67 ** u71
Factory setting If you need to return to the factory-set values, do the following:
- Cut off the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 19
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
Table for Quick settings MT (cooling)
cabinet Preset setting – via o62 1 2 Temperature (SP) 4.0 °C -24.0 °C Max. temp. setting (r02) 6.0 °C -22.0 °C Min. temp. setting (r03) 2.0 °C -26.0 °C Alarm limit high (A13) 10.0 °C -15.0 °C Alarm limit low (A14) -5.0 °C -30.0 °C
LT (frost)
cabinet
Override
The controller contains a number of functions that can be used together with the override function in the master gateway / System Manager.
Function via data com­munication
Start of defrosting
Coordinated defrost Defrost control
Night setback
Light control
Functions to be used in the gateway’s override function
Defrost control Time schedule
Day/night control Time schedule
Day/night control Time schedule
Used parameter in AK-CC 210B
- - - Def.start
- - - HoldAfterDef u60 Def.relay
- - - Night setbck
o39 Light Remote
Ordering
Type Function Code no.
AK-CC 210B
EKA 178A
EKA 179A
EKA 181C
EKA 183A Programming key 084B8582
EKA 163A External display for AK-CC 210B 084B8562
Refrigeration controller without data communication but prepared for mounting of one module.
Data communication module MODBUS
Data communication module LON RS 485
Battery module that will protect the clock in case of lengthy power failure.
230 V AC 084B8544
084B8564
084B8565
084B8577
20 | BC337220653630en-000201 © Danfoss | DCS (vt) | 2020.10
User Guide | Controller for temperature control AK-CC 210B, SW 1.0x
84B3285
DI1 DI2
230 V
Sair S5 Sc
Connections
Relays
The general uses are mentioned here. See also page 6-7 where the different applications are shown. DO1: Refrigeration. The relay will cut in when the controller demands refrigeration DO2: Defrost. The relay will cut in when defrost is in progress DO3: Light. The relay cuts in when the light has to be switched on. DO4: For either alarm, rail heat, fan, condenser fan or compressor 2.
DO1
EKA
163A
21
22 23 24
DO2 DO3 DO4
Danfoss
Alarm: Cf. diagram. The relay is cut in during normal operation and cuts out in alarm situations and when the controller is dead (de-energised)
Rail heat: The relay cuts in when rail heat is to operate. Fans: The relay will cut in when the fans have to operate. Condenser fan: The relay follows the compressor except
during defrost. Compressor 2: The relay will cut in when refrigeration step 2 has to be cut in.
Power supply
230 V AC
Sensors
Thermostat temperature is measured with Sair. S5 is a defrost sensor and is used if defrost has to be stopped based on temperature. The Sc sensor is used for monitoring and controlling the condenser temperature.
Digital On/Off signals
A cut-in input will activate a function. The possible functions are described in menus o02 and o37.
EKA 163A – External display
Here an external display type EKA 163A or EKA 164A can be connected – please see the Instruction for EKA 16xA (literature no. 084R9970)
Coordinated defrost via cable connections
Data communication
The controller is available in several versions where data communication can be carried out with one of the following systems: MODBUS or LON-RS485. If data communication is used, it is important that the installation of the data communication cable is performed correctly. See separate literature No. RC8AC…
Electric noise
Cables for sensors, DI inputs and data communication must be kept separate from other electric cables:
- Use separate cable trays
- Keep a distance between cables of at least 10 cm
- Long cables at the DI input should be avoided
The following controllers can be connected up in this way: AK-CC 210, AK-CC 250, AK-CC 450, AK-CC 550 and AK-CC55. Max. 10. Refrigeration is resumed when all controllers have “released” the signal for defrost.
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 21
Coordinated defrost via data communication
Data
Supply voltage 230 V AC +10/-15 %. 2.5 V A, 50/60 Hz
Sensors 3 pcs off either
Accuracy
Display LED, 3-digits
External display EKA 163A
Digital inputs
Electrical con­nection cable
Relays*
Environments
Density
Escapement reserve for the clock
Approvals EU Low Voltage Directive and EMC demands re CE-
* DO1 and DO2 are 16 A relays. The mentioned 8 A can be increased up to 10 A, when the
ambient temperature is kept below 50 °C. DO3 and DO4 are 8 A relays. Max. load must be kept. ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings.
Pt 1000 or PTC 1000 or NTC-M2020 (5000 ohm / 25 °C)
Measuring range -60 – 99 °C
±1 K below -35 °C
Controller
±0.5 K between -35 – 25 °C ±1 K above 25 °C
Pt 1000 sensor
±0.3 K at 0°C ±0.005 K per degree
Signal from contact functions. Requirements to contacts: Gold plating Cable length must be max. 15 m Use auxiliary relays when the cable is longer.
Max. 1.5 mm2 multi-core cable
CE (250 V AC)
DO1. Refrigeration
8 (6) A
DO2. Defrost 8 (6) A
UL *** (240 V AC)
10 A Resistive 5FLA, 30LRA
10 A Resistive 5FLA, 30LRA
6 A Resistive
DO3. Fan 6 (3) A
3FLA, 18LRA 131 VA Pilot duty
DO4. Alarm
4 (1) A Min. 100 mA**
4 A Resistive 131 VA Pilot duty
0 – 55 °C, during operations
-40 – 70 °C, during transport 20 – 80% Rh, not condensed No shock influence / vibrations IP 65 from front.
Buttons and packing are imbedded in the front.
4 hours
marking complied with LVD tested acc. EN 60730-1 and EN 60730-2-9, A1, A2 EMC tested acc. EN61000-6-3 and EN 61000-6-2
© Danfoss | DCS (vt) | 2020.10 BC337220653630en-000201 | 22
ADAP-KOOL®
Loading...