Danfoss AK-CC 210A Installation guide [da]

INSTRUCTIONS
AK-CC 210A 084B8530
084R8045
t
= 0 - +55°C
amb
230 V a.c., 50/60 Hz
2.5 VA
10 V < U < 256 V
084R8045
CE (250 V a.c.) UL *** (240 V a.c.)
DO1. Refrigeration * 8 (6) A
DO2. Defrost * 8 (6) A
DO3. Refrigeration 2 * 6 (3) A
DO4. Alarm, light, rail heat, fan or comp. fan *
* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be kept. ** Gold plating ensures make function with small contact loads *** UL-approval based on 30000 couplings
4 (1) A Min. 100 mA**
10 A Resistive 5FLA, 30LRA
10 A Resistive 5FLA, 30LRA
6 A Resistive 3FLA, 18LRA 131 VA Pilot duty 4 A Resistive 131 VA Pilot duty
Koordineret afrimning Coordinated defrost
Data communication
Type: Pt 1000 (1000 Ω /0°C ) /
Ptc 1000 (TYPE) / NTC-M2020 (5000 Ω / 25°C)
LON RS485
MOD-bus
RI8RE3ML 10-2016
o61 — Electrical connections - Conexão elétrica
1 2
3 4
*)
*)
*)
*)
5
*) DI1, DI2: AU: Guld, Gold, Or, Oro l = max. 15 m
*)
*)
2 Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A
Indstil:
Dansk
1 Åbn parameter r12 og stop reguleringen
2 Vælg elforbindelse ud fra tegningerne side 2
3 Åbn parameter o61 og indstil elforbindelsesnummeret heri
4 Vælg derefter et sæt af forudindstillinger fra tabellen til højre
5 Åbn parameter o62 og indstil nummeret for sættet af forudindstil-
linger
6 Åbn parameter r12 og start reguleringen
7 Se oversigten over fabriksindstillinger igennem. — Foretag de nød-
vendige ændringer i de respektive parametre
Hjælpeskema til indstillinger (quick-setup)
Sæt af forudindstillinger (o62) 1 2 3
Temperatur (SP) 4°C 2°C -24°C Max. temp. indstilling (r02) 6°C 4°C -22°C Min. temp. indstilling (r03) 2°C 0°C -26°C Alarmgrænse høj (A13) 10°C 8°C -15°C Alarmgrænse lav (A14) -5°C -5°C -30°C Interval imellem afrimn. (d03) 6 h 6h 12h Afrimningsføler: 0=time,1=S5, 2=S4 (d10) 0 1 1
DI1 konfiguration (o02) 10 10 10
Afr. stop
på tid
8 Ved netværk. Indstil adressen i o03 og send derefter adressen til
gatewayen/systemenheden med indstillingen o04.
Sæt 1-3: Indstillingerne i de grå felter bliver ændret
Parametre Variant af AK-CC Min.­Funktion Koder 1 2 3 4 5 Normal drift
Temperatur (setpunkt) --- -50.0°C 50.0°C 2.0°C
Termostat
Differens *** r01 0.1 K 20.0 K 2.0 K Max. begrænsning af setpunktsindstilling *** r02 -49.0°C 50.0°C 50.0°C Min. begrænsning af setpunktsindstilling *** r03 -50.0°C 49.0°C -50.0°C Justering af temperaturvisning r04 -20.0 K 20.0 K 0.0 K Temperaturenhed (°C/°F) r05 °C °F °C Korrektion af signalet fra S4 r09 -10.0 K 10.0 K 0.0 K Korrektion af signalet fra S3 r10 -10.0 K 10.0 K 0.0 K Manuel service, Stop regulering, Start regulering (-1, 0, 1) r12 -1 1 0 Referenceforskydning under natdrift r13 -20.0 K 20.0 K 0.0 K Definition og evt. vægtning af termostatfølere - S4% (100%=S4, 0%=S3) Aktivering af referenceforskydning r40 r39 OFF ON OFF Værdi for referenceforskydning (aktiveres via r39 eller DI) r40 -50.0 K 50.0 K 0.0 K
Alarm
Forsinkelse på temperaturalarm A03 0 min 240 min 30 min Forsinkelse på døralarm *** A04 0 min 240 min 60 min Forsinkelse på temperaturalarm efter afrimning A12 0 min 240 min 90 min Høj alarmgrænse *** A13 -50.0°C 50.0°C 8.0°C Lav alarmgrænse *** A14 -50.0°C 50.0°C -30.0°C Alarm forsinkelse DI1 A27 0 min 240 min 30 min Alarm forsinkelse DI2 A28 0 min 240 min 30 min Signal til alarmtermostaten. (100%=S4, 0%=S3) A36 0% 100% 100%
Kompressor
Min. ON-tid c01 0 min 30 min 0 min Min. OFF-tid c02 0 min 30 min 0 min Forsinkelsestid for indkobling af compr. 2 c05 0 sec 900 sec 5 sec Kompressorrelæ 1 skal koble modsat (NC-funktion) Forsinkelsestid for indkobling af kompressor 2 under afrimning c92 0 s 30 s 5 s
Afrimning
Afrimningsmetode (ingen/EL/GAS) d01 no GAS GAS Afrimnings-stoptemperatur d02 0.0°C 25.0°C 6.0°C Interval mellem afrimningsstarter d03 0 hours 240 hours 8 hours Max. afrimningsvarighed d04 0 min 360 min 45 min Tidsforskydning på afrimningsindkoblingen ved opstart d05 0 min 240 min 0 min Afdrypningstid d06 0 min 60 min 0 min Forsinkelse på ventilatorstart efter afrimning d07 0 min 60 min 0 min Ventilator-starttemperatur d08 -50.0°C 0.0°C -5.0°C Ventilator indkoblet under afrimning
r15 0% 100% 100%
c30 0
d09 0 2 1
værdi
OFF
Max.-
værdi
1
ON
Fabriks-
indstil-
ling
0
OFF
0: stoppet 1: Kører 2: Kører under pump down og afrimning
Afrimningsføler (0=tid, 1=S5, 2=S4) d10 0 2 0 Pump down forsinkelse d16 0 min 60 min 0 min Max. opsummeret køletid imellem to afrimninger d18 0 hours 48 hours 0 hours Behovstyret afrimning - S5 temperaturens tilladte variation ved isopbygning. På central­anlæg vælges 20 (=off) Varighed af -d- i displayet d40 5 min 240 min 30 min
Ventilator
Ventilatorstop ved udkoblet kompressor F01 no yes no Forsinkelse af ventilatorstop F02 0 min 30 min 0 min Ventilatorstop temperatur (S5) F04 -50.0°C 50.0°C 50.0°C
d19 0.0 K 20.0 K 20.0 K
Afr. stop
på S5
Aktuel indstil-
ling
AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016 3
HACCP
Aktuel temperaturmåling til HACCP funktionen h01 Den sidst registrerede spidstemperatur h10 Valg af funktion og føler til HACCP funktionen. 0=ingen HACCP funktion. 1= S4 benyttes (evt. også S3). 2=S5 benyttes Alarmgrænse for HACCP funktionen h12 -50.0°C 50.0°C 8.0°C Forsinkelsestid for HACCP alarmen h13 0 min. 240 min. 30 min. Vælg signal til HACCP funktionen. S4% (100%=S4, 0%=S3) h14 0% 100% 100%
Realtidsur
Seks starttidspunkter for afrimning. Indstilling af timer. 0=OFF Seks starttidspunkter for afrimning. Indstilling af minutter 0=OFF Ur - Timeindstilling *** t07 0 hours 23 hours 0 hours Ur - Minutindstilling *** t08 0 min 59 min 0 min Ur - Indstilling af dato *** t45 1 31 1 Ur - Indstilling af måned *** t46 1 12 1 Ur - Indstilling af år *** t47 0 99 0
Diverse
Forsinkelse af udgangssignaler efter opstart o01 0 s 600 s 5 s Indgangssignal på DI1. Funktion: (0=ikke anvendt, 1=status på DI1. 2=dørfunktion med alarm ved åben. 3=døralarm ved åben. 4=afrimningsstart (pulssignal). 5=ekstern hovedafbryder. 6=natdrift. 7=skift reference (r40 aktiveres). 8=alarmfunktion ved sluttet. 9=alarmfunktion ved åben. 10=møbelrengøring (pulssignal). Netværksadresse o03 0 240 0 On/Off omskifter (Service Pin meddelelse) VIGTIGT! o61 skal indstilles før o04 Adgangskode 1 (samtlige indstillinger) o05 0 100 0 Anvendt følertype (Pt /PTC/NTC) o06 Pt ntc Pt Udlæsning af softwareversion o08 Display step = 0.5 (normal 0.1 ved Pt føler) o15 no yes no Max holdetid efter koordineret afrimning o16 0 min 60 min 20 Vælg signal til displayvisningen. S4% (100%=S4, 0%=S3) Indgangssignal på DI2. Funktion: (0=ikke anvendt, 1=status på DI2. 2=dørfunktion med alarm ved åben. 3=døralarm ved åben. 4=afrimningsstart (pulssignal). 5=ekstern hovedafbryder. 6=natdrift. 7=skift reference (r40 aktiveres). 8=alarmfunktion ved sluttet. 9=alarmfunktion ved åben. 10=møbelrengøring (pulssignal). Konfiguration af lysfunktionen (relæ 4) 1=ON under dagdrift. 2=ON / OFF via datakommunikation. 3=ON følger DI-funktionen, når DI er valgt til dørfunktion eller til døralarm Aktivering af lysrelæ (kun hvis o38=2) o39 OFF ON OFF Kantvarme On-tid under dagdrift o41 0% 100% 100 Kantvarme On-tid under natdrift o42 0% 100% 100 Kantvarme periodetid (On tid + Off tid) o43 6 min 60 min 10 min Møbelrengøring. 0= ingen møbelrengørring 1= kun ventilatorer. 2 Alle udgange er OFF *** o46 0 2 0 Valg af EL-diagram. Se oversigten side 2. * o61 1 5 1 Overfør et sæt af forudindstillinger. Se oversigten på forrige side * o62 0 3 0 Adgangskode 2 (delvis adgang) *** o64 0 100 0 Gem apparatets nuværende indstillinger på programmeringsnøglen. Vælg selv num­mer. Hent et sæt indstillinger fra programmeringsnøglen (tidligere gemt via o65 funktionen) o66 0 25 0 Overskriv regulatorens fabriksindstillinger med de nuværende indstillinger o67 OFF On OFF
Service
Statuskoder er vist på side 5 S0-S32 Temperaturen målt med S5 føleren *** u09 Status på DI1 indgangen. 1=sluttet u10 Temperaturen målt med S3 føleren *** u12 Status på natdrift (on eller off) 1=sluttet *** u13 Temperaturen målt med S4 føleren *** u16 Termostattemperaturen u17 Aflæse den øjeblikkelige reguleringsreference u28
Status på DI2 udgangen. 1=sluttet u37 Temperaturen der udlæses på displayet u56 Målt temperatur til alarmtermostaten u57 Status på relæet til køling ** u58 Status på relæet til ventilator ** u59 Status på relæet til afrimning ** u60 Status på relæet til kantvarme ** u61 Status på relæet til alarm ** u62 Status på relæet til lys ** u63 Status på relæet til kompressor 2 ** u67 Status på relæet til kompressorblæser ** u71
t01-t06 0 hours 23 hours 0 hours
t11-t16 0 min 59 min 0 min
1 2 3 4 5
h11 0 2 0
o02 0 10 0
o04 OFF ON OFF
o17 0% 100% 100%
o37 0 10 0
o38 1 3 1
o65 0 25 0
*) Kan kun indstilles, når reguleringen er stoppet (r12=0) **) Kan styres manuelt, men kun når r12 = -1 ***) Med adgangskode 2 begrænses adgangen til disse menuer
SW = 1.1x
4 Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A
Knapperne
LED
Indstille en menu
1. Tryk på den øverste knap til der vises en parameter
2. Tryk på øverste eller nederste knap og find hen til den parameter, du vil indstille
3. Tryk på den midterste knap indtil vær­dien for parameteren vises
Indstille temperaturen
1. Tryk på den midterste knap til tempera­turværdien vises
2. Tryk på øverste eller den nederste knap
og find den nye værdi
3. Tryk på den midterste knap for at af-
slutte indstillingen.
Lysdiode = køling = afrimning = ventilator i gang
Blinker hurtigt ved alarm
4. Tryk på øverste eller nederste knap og find den nye værdi
5. Tryk igen på den midterste knap for at
Aflæse temperaturen ved afrimningsføleren
• Kort tryk på den nederste knap
HACCP
Funktionen er aktiv
fastlåse værdien.
Manuel start eller stop af en afrimning
Udkoble alarmrelæ / se alarmkode
• Kort tryk på den øverste knap
• Tryk på den nederste knap i 4 sekunder. (Dog ikke ved application 4)
Se HACCP registrering
1. Langt tryk på den midterste knap til h01 vises
2. Vælg ønsket h01 - h10
3. Se værdien ved kort tryk på den midter­ste knap.
Visning af fejlkode Visning af alarmkode Visning af statuskode
E 1 Fejl i regulator A 1 Høj-temperatur alarm S0 Der reguleres E 6 Batteriet skal skiftes + kontroller ur A 2 Lav-temperatur alarm S1 Venter på at den koordinerede afrimning
E 25 S3 føler fejl A 4 Dør-alarm S2 ON-tid Kompressor E 26 S4 føler fejl A 5 Max. Hold time S3 OFF-tid kompressor E 27 S5 føler fejl A 15 DI 1 alarm S4 Afdrypningstid
A 16 DI 2 alarm S10 Køling stoppet af hovedafbryder A 45 Standby mode S11 Køling stoppet af termostat A 59 Møbelrengøring S14 Afrimningssekvens. Afrimer A 60 HACCP alarm S15 Afrimningssekvens. Ventilatorforsinkelse
Fabriksindstilling Hvis du får behov for at vende tilbage til de fabriksindstillede værdier, kan det ske således:
- Afbryd forsyningsspændingen til regulatoren
- Hold den øverste og nederste knap inde samtidig med at du igen tilslutter forsyningsspændingen.
afsluttes
S17 Dør åben (åben DI indgang) S20 Nødkøling S25 Manuel regulering af udgange S29 Møbelrengøring S30 Tvangskøling S32 Forsinkelse af udgange ved opstart non Afrimningstemperaturen kan ikke vises. Der
stoppes på tid
-d- Afrimningen er igang PS Password er påkrævet
AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016 5
English
Setting:
1 Open parameter r12 and stop the regulation
2 Select electric connection based on the drawings on page 2
3 Open parameter o61 and set the electric connection number in it
4 Now select one of the preset settings from the table on the right-
hand side
5 Open parameter o62 and set the number for the array of preset-
tings
6 Open parameter r12 and start the regulation
7 Go through the survey of factory settings. Make any necessary
Auxiliary table for settings (quick-setup)
Preset settings (o62) 1 2 3
Temperature (SP) 4°C 2°C -24°C Max. temp. setting (r02) 6°C 4°C -22°C Min. temp. setting (r03) 2°C 0°C -26°C Alarm limit high (A13) 10°C 8°C -15°C Alarm limit low (A14) -5°C -5°C -30°C Interval between defrost (d03) 6 h 6h 12h Defrost sensor: 0=time,1=S5, 2=S4 (d10) 0 1 1 DI1 configuration (o02) 10 10 10
Defrost stop on
time
Defrost stop
changes in the respective parameters.
8 For network. Set the address in o03 and then transmit it to the
gateway/system unit with setting o04.
Array 1-3: The settings in the grey fields will be changed
Function Codes 1 2 3 4 5 Normal operation
Temperature (set point) --- -50.0°C 50.0°C 2.0°C
Thermostat
Differential *** r01 0.0 K 20.0K 2.0 K Max. limitation of setpoint setting *** r02 -49.0°C 50°C 50.0°C Min. limitation of setpoint setting *** r03 -50.0°C 49.0°C -50.0°C Adjustment of temperature indication r04 -20.0 K 20.0 K 0.0 K Temperature unit (°C/°F) r05 °C °F °C Correction of the signal from S4 r09 -10.0 K +10.0 K 0.0 K Correction of the signal from S3 r10 -10.0 K +10.0 K 0.0 K Manual service, stop regulation, start regulation (-1, 0, 1) r12 -1 1 0 Displacement of reference during night operation r13 -20.0 K 20.0 K 0.0 K Definition and weighting, if applicable, of thermostat sensors - S4% (100%=S4, 0%=S3) r15 0% 100% 100% Activation of reference displacement r40 r39 OFF ON OFF Value of reference displacement (activate via r39 or DI) r40 -50.0 K 50.0 K 0.0 K
Alarm
Delay for temperature alarm A03 0 min 240 min 30 min Delay for door alarm *** A04 0 min 240 min 60 min Delay for temperature alarm after defrost A12 0 min 240 min 90 min High alarm limit *** A13 -50.0°C 50.0°C 8.0°C Low alarm limit *** A14 -50.0°C 50.0°C -30.0°C Alarm delay DI1 A27 0 min 240 min 30 min Alarm delay DI2 A28 0 min 240 min 30 min Signal for alarm thermostat. S4% (100%=S4, 0%=S3) A36 0% 100% 100%
Compressor
Min. ON-time c01 0 min 30 min 0 min Min. OFF-time c02 0 min 30 min 0 min Time delay for cutin of comp.2 c05 0 sec 900 sec 5 sec Compressor relay 1 must cutin and out inversely (NC-function) Time delay for cutin of compressor 2 during defrost c92 0 s 30 s 5 s
Defrost
Defrost method (none/EL/GAS) d01 no GAS GAS Defrost stop temperature d02 0.0°C 25.0°C 6.0°C Interval between defrost starts d03 0 hours Max. defrost duration d04 0 min 360 min 45 min Displacement of time on cutin of defrost at start-up d05 0 min 240 min 0 min Drip off time d06 0 min 60 min 0 min Delay for fan start after defrost d07 0 min 60 min 0 min Fan start temperature d08 -50.0°C 0.0°C -5.0°C Fan cutin during defrost 0: Stopped 1: Running 2: Running during pump down and defrost Defrost sensor (0=time, 1=S5, 2=S4) d10 0 2 0 Pump down delay d16 0 min 60 min 0 min Max. aggregate refrigeration time between two defrosts d18 0 hours 48 hours 0 hours Defrost on demand - S5 temperature’s permitted variation during frost build-up. On central plant choose 20 K (=off) Max. duration of -d- in display d40 5 min 240 min 30 min
Fan
Fan stop at cutout compressor F01 no yes no Delay of fan stop F02 0 min 30 min 0 min Fan stop temperature (S5) F04 -50.0°C 50.0°C 50.0°C
Parameters Variant of AK-CC
c30 0
d09 0 2 1
d19 0.0 K 20.0 k 20.0 K
Min.­value
OFF
Max.­value
1
ON
240 hours
Factory setting
0
OFF
8 hours
on S5
Actual
setting
6 Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A
HACCP
Actual temperature measurement for the HACCP function h01 Last registered peak temperature h10 Selection of function and sensor for the HACCP function. 0 = no HACCP function. 1 = S4 used (maybe also S3). 2 = S5 used Alarm limit for the HACCP function h12 -50.0°C 50.0°C 8.0°C Time delay for the HACCP alarm h13 0 min. 240 min. 30 min. Select signal for the HACCP function. S4% (100% = S4, 0% = S3) h14 0% 100% 100%
Real time clock
Six start times for defrost. Setting of hours. 0=OFF Six start times for defrost. Setting of minutes. 0=OFF Clock - Setting of hours *** t07 0 hours 23 hours 0 hours Clock - Setting of minute *** t08 0 min 59 min 0 min Clock - Setting of date *** t45 1 31 1 Clock - Setting of month *** t46 1 12 1 Clock - Setting of year *** t47 0 99 0
Miscellaneous
Delay of output signals after start-up o01 0 s 600 s 5 s Input signal on DI1. Function: 0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation 7=change reference (activate r40). 8=alarm function when closed. 9=alarm function when open. 10=case cleaning (pulse signal). Network address o03 0 240 0 On/Off switch (Service Pin message) IMPORTANT! o61 must be set prior to o04 Access code 1 (all settings) o05 0 100 0 Readout of Software version o06 Display step = 0.5 (normal 0.1 at Pt sensor) o15 no yes no Max hold time after coordinated defrost o16 0 min 60 min 20 Select signal for display view. S4% (100%=S4, 0%=S3) o17 0% 100% 100% Input signal on DI2. Function: (0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation 7=change reference (activate r40). 8=alarm function when closed. 9=alarm function when open. 10=case cleaning (pulse signal). Configuration of light function (relay 4) 1=ON during day operation. 2=ON / OFF via data communication. 3=ON follows the DI­function, when DI is selected to door function or to door alarm Activation of light relay (only if o38=2) o39 OFF ON OFF Rail heat On time during day operations o41 0% 100% 100 Rail heat On time during night operations o42 0% 100% 100 Rail heat period time (On time + Off time) o43 6 min 60 min 10 min Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off. *** o46 0 2 0 Selection of EL diagram. See overview page 2 * o61* 1 5 1 Download a set of predetermined settings. See overview previous page. * o62* 0 3 0 Access code 2 (partly access) *** o64 0 100 0 Save the controllers present settings to the programming key. Select your own number. o65 0 25 0 Load a set of settings from the programming key (previously saved via o65 function) o66* 0 25 0 Replace the controllers factory settings with the present settings o67 OFF On OFF
Service
Status codes are shown on page 5 S0-S32 Temperature measured with S5 sensor *** u09
Status on DI1 input. on/1=closed u10 Temperature measured with S3 sensor *** u12 Status on night operation (on or off) 1=closed *** u13 Temperature measured with S4 sensor *** u16 Thermostat temperature u17 Read the present regulation reference u28 Status on DI2 output. on/1=closed u37 Temperature shown on display u56 Measured temperature for alarm thermostat u57 Status on relay for cooling ** u58 Status on relay for fan ** u59 Status on relay for defrost ** u60 Status on relay for railheat ** u61 Status on relay for alarm ** u62 Status on relay for light ** u63 Status on relay for compressor 2 ** u67 Status on relay for compressor fan ** u71
*) Can only be set when regulation is stopped (r12=0) **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited
1 2 3 4 5
h11 0 2 0
t01-t06 0 hours 23 hours 0 hours
t11-t16 0 min 59 min 0 min
o02 1 10 0
o04 OFF ON OFF
o37 0 10 0
o38 1 3 1
SW = 1.1x
AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016 7
The buttons
LED
Set menu
1. Push the upper button until a parameter r01 is shown
2. Push the upper or the lower button and find that parameter you want to change
3. Push the middle button until the parameter value is shown
4. Push the upper or the lower button and select the new value
5. Push the middle button again to enter the value.
Cutout alarm relay / receipt alarm/see alarm code
• Push short the upper button
Set temperature
1. Push the middle button until the temperature value is shown
2. Push the upper or the lower button and
select the new value
3. Push the middle button to select the
setting.
Reading the temperature at defrost sensor
• Push briefly the lower button
Manuel start or stop of a defrost
• Push the lower button for four seconds.
(However, not application 4)
Light emitting diode = refrigeration = defrost = fan running
Flashes fast at alarm
HACCP
HACCP function is active
See HACCP registration
1. Give the middle button a long push until h01 appears
2. Select required h01-h10
3. See value by giving the middle button a short push
Fault code display Alarm code display Status code display
E 1 Fault in controller A 1 High temperature alarm S0 Regulating
E 6 Change battery + check clock A 2 Low temperature alarm S 1 Waiting for end of the coordinated defrost E 25 S3 sensor error A 4 Door alarm S 2 ON-time Compressor E 26 S4 sensor error A 5 Max. Hold time S 3 OFF-time Compressor E 27 S5 sensor error A 15 DI 1 alarm S 4 Drip-off time
A 16 DI 2 alarm S 10 Refrigeration stopped by main switch A 45 Standby mode S 11 Refrigeration stopped by thermostat A 59 Case cleaning S 14 Defrost sequence. Defrosting A 60 HACCP alarm S 15 Defrost sequence. Fan delay
S 17 Door open (open DI input) S 20 Emergency cooling S 25 Manual control of outputs S 29 Case cleaning S 30 Forced cooling S 32 Delay of output at start-up non The defrost temperature cannot be dis-
played. There is stop based on time
-d- Defrost in progress PS Password required
Factory setting If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you recon nect the supply voltage
8 Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A
Português
Configurações:
1 Abra o parâmetro r12 e pare a regulagem
2 Selecione a conexão elétrica com base nos desenhos na página 2
3 Abra o parâmetro o61 e programe nele o número da conexão
elétrica
4 Agora selecione um dos ajustes predefinidos na tabela à direta
5 Abra o parâmetro o62 e programe o número da matriz
de pré-ajustes.
6 Abra o parâmetro r12 e inicie a regulagem
7 Percorra a pesquisa de ajustes de fábrica. Faça as alterações ne-
cessárias nos parâmetros respectivos.
Tabela auxiliar de ajustes (setup rápido)
Ajustes predefinidos (o62) 1 2 3
Temperatura (SP) 4°C 2°C -24°C
Ajuste de temp. máx. (r02) Ajuste de temp. mín. (r03) Limite de alarme alto (A13) Limite de alarme baixo (A14)
Intervalo entre degelos (d03) 6 h 6h 12h Sensor de degelo: 0=tempo, 1=S5, 2=S4
(d10) DI1 configurações (o02) 10 10 10
Parada
de de­gelo no horário
10°C 8°C -15°C
-5°C -5°C -30°C
Parada de degelo
6°C 4°C -22°C 2°C 0°C -26°C
0 1 1
8 Para rede. Programe o endereço em o03 e inicie a função de
unidade de gateway/sistema com ajuste o04.
Matriz 1-3: As definições dos campos cinzas serão alteradas
Parâmetros Variante da AK-CC
Função
Operação normal
Temperatura (ponto de ajuste) --- -50.0°C 50.0°C 2.0°C
Termostato
Diferencial *** r01 0.0 K 20.0K 2.0 K Limitação máx. do ponto de ajuste *** r02 -49.0°C 50°C 50.0°C Limitação mín. do ponto de ajuste *** r03 -50.0°C 49.0°C -50.0°C Ajuste da indicação de temperatura r04 -20.0 K 20.0 K 0.0 K Unidade de temperatura (°C/°F) r05 °C °F °C Correção do sinal de S4 r09 -10.0 K +10.0 K 0.0 K Correção do sinal de S3 r10 -10.0 K +10.0 K 0.0 K Serviço manual, regulagem da parada, regulagem da partida (-1, 0, 1) r12 -1 1 0 Deslocamento de referência durante operação noturna r13 -20.0 K 20.0 K 0.0 K Definição e pesagem, se aplicável, dos sensores do termostato - S4% (100%=S4, 0%=S3) r15 0% 100% 100% Ativação do deslocamento de referência r40 r39 OFF ON OFF Valor do deslocamento de referência (ativar via r39 ou DI) r40 -50.0 K 50.0 K 0.0 K
Alarme
Atraso do alarme de temperatura A03 0 min 240 min 30 min Atraso do alarme da porta *** A04 0 min 240 min 60 min Atraso do alarme de temperatura após degelo A12 0 min 240 min 90 min Limite de alarme superior *** A13 -50.0°C 50.0°C 8.0°C Limite de alarme inferior *** A14 -50.0°C 50.0°C -30.0°C Atraso de alarme DI1 A27 0 min 240 min 30 min Atraso de alarme DI2 A28 0 min 240 min 30 min Sinal do termostato do alarme. S4% (100%=S4, 0%=S3) A36 0% 100% 100%
Compressor
Tempo mínimo LIGADO c01 0 min 30 min 0 min Tempo mínimo DESLIGADO c02 0 min 30 min 0 min Tempo de atraso de ativação do comp.2 c05 0 sec 900 sec 5 sec O relé do compressor 1 deve ativar e desativar inversamente (função NC) Tempo de atraso de desativação do compressor 2 durante o descongelamento c92 0 s 30 s 5 s
Degelo
Método de degelo (nenhum/EL/GAS) d01 no GAS GAS Temperatura de parada do degelo d02 0.0°C 25.0°C 6.0°C Intervalo entre inícios de degelos d03 0 hours Duração máx. do degelo d04 0 min 360 min 45 min Deslocamento de tempo na ativação do degelo no início de operações d05 0 min 240 min 0 min Tempo de gotejamento d06 0 min 60 min 0 min Atraso da partida do ventilador após degelo d07 0 min 60 min 0 min Temperatura de partida do ventilador d08 -50.0°C 0.0°C -5.0°C Ativação do ventilador durante degelo
Códi-
1 2 3 4 5
gos
c30 0
d09 0 2 1
Valor
mín.
OFF
240 hours
Valor
máx.
1
ON
Ajuste
de
fábrica
0
OFF
8 hours
0: Parado 1: Funcionando 2: Funcionando durante desac. da bomba e degelo
Sensor de degelo (0=tempo, 1=S5, 2=S4) d10 0 2 0 Atraso de desaceleração da bomba d16 0 min 60 min 0 min Tempo de refrigeração agregado máx. entre dois degelos d18 0 hours 48 hours 0 hours Degelo sob demanda - variação permitida da temperatura do S5 durante acúmulo de geada. Na fábrica central escolha 20 K (=desligado) Duração máx. de -d- no display d40 5 min 240 min 30 min
Ventilador
Parada do ventilador na desativação do compressor F01 no yes no Atraso de parada do ventilador F02 0 min 30 min 0 min Temperatura de parada do ventilador (S5) F04 -50.0°C 50.0°C 50.0°C
d19 0.0 K 20.0 k 20.0 K
no S5
Ajuste
real
AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016 9
HACCP
Medição de temperatura a real da função HACCP h01 Última temperatura de pico registrada h10 Seleção de função e sensor da função HACCP. 0 = sem função HACCP. 1 = S4 usado (talvez também S3). 2 = S5 usado Limite de alarme da função HACCP h12 -50.0°C 50.0°C 8.0°C Tempo de atraso do alarme HACCP h13 0 min. 240 min. 30 min. Seleção de sinal da função HACCP. S4% (100% = S4, 0% = S3) h14 0% 100% 100%
Relógio em tempo real
Seis horários de início de degelo. Ajuste de horas. 0=DESLIGADO Seis horários de início de degelo. Ajuste de minutos. 0=DESLIGADO Relógio - Ajuste de horas *** t07 0 hours 23 hours 0 hours Relógio - Ajuste de minuto *** t08 0 min 59 min 0 min Relógio - Ajuste de data *** t45 1 31 1 Relógio - Ajuste do mês *** t46 1 12 1 Relógio - Ajuste do ano *** t47 0 99 0
Diversos
Atraso dos sinais de saída após o início de operações o01 0 s 600 s 5 s Sinal de entrada em DI1. Função: 0=não usado. 1=status em DI1. 2=função de porta com alarme quando aberto. 3=alarme da porta quando aberto. 4=início de degelo (pressão de pulso). 5=interruptor principal ext.. 6=operação noturna 7=mudar referência (ativar r40). 8=função de alarme quando fe­chado. 9=função de alarme quando aberto. 10=limpeza do expositor (pressão de pulso). Endereço de rede (0=desligado) o03 0 240 0 Interruptor liga/desliga (mensagem de Pino de Serviço) IMPORTANTE! o61 deve ser ajustado antes de o04 Código de acesso 1 (todos os ajustes) o05 0 100 0 Indicador da versão do software o06 Exibir etapa = 0,5 (normal 0,1 no sensor Pt) o15 no yes no Tempo de retenção máx. após degelo coordenado o16 0 min 60 min 20 Seleção de sinal para exibir visão. S4% (100%=S4, 0%=S3) o17 0% 100% 100% Sinal de entrada em DI2. Função: (0=não usado. 1=status em DI2. 2=função de porta com alarme quando aberto. 3=alarme de porta quando aberto. 4=início de degelo (pressão de pulso). 5=interruptor principal ext. 6=operação noturna 7=mudar referência (ativar r40). 8=função de alarme quando fe­chado. 9=função de alarme quando aberto. 10=limpeza do expositor (pressão de pulso). Configuração da função de luz (relé 4) 1=LIGADO durante a operação diurna. 2=LIGADO / DESLIGADO via comunicação de dados. 3=segue a função de DI quando DI estiver selecionado para função de porta ou alarme da porta Ativação do relé de luz (somente se o38=2) o39 OFF ON OFF Tempo de aquecimento do trilho ligado durante operações diurnas o41 0% 100% 100 Tempo de aquecimento do trilho ligado durante operações noturnas o42 0% 100% 100 Intervalo de tempo de aquecimento do trilho (tempo ligado + tempo desligado) o43 6 min 60 min 10 min Limpeza do expositor. 0= sem limpeza do expositor. 1= somente ventiladores. 2= todas as saídas desligadas. Seleção do diagrama EL. Consultar a página de visão geral 2 * o61 1 5 1 Transferir por download um conjunto de ajustes predeterminados. Consultar a próxima página de visão geral. Código de acesso 2 (acesso parcial) *** o64 0 100 0 Salvar os ajustes atuais dos controladores na tecla de programação. Selecionar seu próprio número. Carregar um conjunto de ajustes da tecla programação (salvo anteriormente via função o65) o66 0 25 0 Substituir os ajustes de fábrica dos controladores pelos ajustes atuais o67 OFF On OFF
Serviço de manutenção
Os códigos de status são mostrados na página 5 S0-S32 Temperatura medida com o sensor S5 *** u09
Status na entrada DI1. on/1=fechado u10 Temperatura medida com o sensor S3 *** u12 Status na operação noturna (ligado ou desligado) 1=fechado *** u13 Temperatura medida com o sensor S4 *** u16 Temperatura do termostato u17 Ler a referência de regulagem presente u28 Status na saída DI2. on/1=fechado u37 Temperatura mostrada no display u56 Temperatura medida do termostato de alarme u57 Status no relé de resfriamento ** u58 Status no relé de ventilador ** u59 Status no relé de degelo ** u60 Status no relé de aquecimento do trilho ** u61 Status no relé de alarme ** u62 Status no relé de luz ** u63 Status no relé do compressor 2 ** u67 Status no relé do compressor ventilador ** u71
*) Pode ser ajustado somente quando a regulagem estiver parada (r12=0) **) Pode ser controlado manualmente, mas somente quando r12=-1 ***) Com código de acesso 2 o acesso a esses menus será limitado
*** o46 0 2 0
* o62 0 3 0
1 2 3 4 5
h11 0 2 0
t01-t06 0 hours 23 hours 0 hours
t11-t16 0 min 59 min 0 min
o02 1 10 0
o04 OFF ON OFF
o37 0 10 0
o38 1 3 1
o65 0 25 0
SW = 1.1x
10 Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A
Os botões
LED
Programar menu
1. Pressione o botão superior até ser mos­trado um parâmetro r01
2. Pressione o botão superior ou inferior e localize o parâmetro que deseja alterar
3. Pressione o botão intermediário até o valor de parâmetro ser mostrado
Ajustar temperatura
1. Pressione o botão intermediário até ser mostrado o valor de temperatura
2. Pressione o botão superior ou inferior e
selecione o novo valor
3. Pressione o botão intermediário nova-
mente para concluir o ajuste.
Diodos emissores de luz (LED)
= Refrigeração = Degelo = Ventilador funcionando
Flashes rápidos em alarme
4. Pressione o botão superior ou inferior e selecione o novo valor
5. Pressione o botão intermediário nova-
Lendo a temperatura no sensor de degelo
• Pressione brevemente o botão inferior
HACCP
Função HACCP está ativo
mente para congelar o valor.
Partida/parada manual de um degelo
Desativar relê de alarme / alarme de recebi­mento / consultar código de alarme
• Pressione brevemente o botão superior
• Pressione o botão inferior durante quatro segundos. (No entanto, não aplicação 4)
Consulte o registro de HACCP
1. Pressione o botão intermediário por mais tempo até h01 aparecer.
2. Selecione o h01-h10 requerido
3. Veja o valor pressionando brevemente o botão intermediário
Exibição do código de falha Exibição do código de alarme Exibição do código de status
E 1
Falhas no controlador
E 6
Falha no relógio em tempo real. Reinicializar o relógio.
E 25
Erro do sensor em S3
E 26
Erro do sensor em S4
E 27
Erro do sensor em S5
A 1
Alarme de alta temperatura
A 2
Alarma de baixa temperatura
A 4
Alarme da porta
A 5
Informação. O parâmetro o16 expirou
A 15
Alarme. Sinal da entrada DI1
A 16
Alarme. Sinal da entrada DI2
A 45
Posição de espera (refrigeração parada via r12 ou entrada DI)
A 59
Limpeza do expositor. Sinal da entrada DI1 ou DI2
A 60
Alarme de alta temperatura da função HACCP
S0 Regulagem
S 1 Aguardando o fim do congelamento
coordenado
S 2 Quando o compressor estiver operando
deve funcionar durante pelo menos x minutos.
S 3 Quando o compressor parar, deve permane-
cer parado durante pelo menos x minutos.
S 4 O evaporador goteja e aguarda o tempo
esgotar
S 10 Refrigeração parada pelo interruptor
principal.
S 11 Refrigeração parada pelo termostato
S 14 Sequência de degelo. Degelo em anda-
mento
S 15 Sequência de degelo. Atraso do ventilador
— água adere ao evaporador
S 17 A porta está aberta. Entrada DI está aberta S 20 Resfriamento de emergência S 25 Controle manual das saídas S 29 Limpeza do expositor S 30 Resfriamento forçado S 32 Atraso de saídas durante início de opera-
ções
não A temperatura de degelo não pode ser
exibida. Há parada baseada no tempo
-d- Degelo em andamento / Primeiro resfria­mento após degelo
PS Senha requerida. Configurar senha
Ajuste de fábrica Se for necessário retornar aos valores dos ajustes de fábrica, pode ser feito desta maneira:
- Desativar a tensão de alimentação para o controlador
- Mantenha os dois botões pressionados ao mesmo tempo ao conectar novamente a tensão de alimen­tação
AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016 11
12 Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A
Loading...