Flow controller with integrated control valve (PN 16)
AHQM - return and flow mounting
Description
DN 15-32 DN 40, 50 DN 50-100
AHQM is a self-acting flow controller with
integrated control valve primarily for use in
district heating systems or in secondary district
heating systems as well. The controller closes
when set max. flow is exceeded.
In combination with Danfoss electrical actuators
AMV(E) can be controlled by ECL electronic
controllers.
The controllers have a control valve with
adjustable flow restrictor, connection neck for
electrical actuator, and an actuator with one
control diaphragm.
Controllers are used together with Danfoss
electrical actuators:
• DN 15-32 with
- AMV(E) 10
- AMV(E) 13 with spring return function
- AMV(E) 130, AMV(E) 140
- AMV(E) 130H, AMV(E) 140H with manual
operation
• DN 40-100 with
- AMV(E) 435
- AMV(E) 25 SD spring return function
(spring down)
AHQM, DN 15-32 combined with AMV(E) 13 has
been approved according to DIN EN 14597.
Main data:
• DN 15-100
• k
1,0 -90 m3/h
VS
• Flow range 0,035-38 m
3
/h
• PN 16
• Flow restrictor ∆p
- 0,12 bar for DN 15-20
:
b
- 0,14 bar for DN 25-32
- 0,2 bar for DN 40, 50
- 0,3 bar for DN 65-100
• Temperature:
- Circulation water / glycolic water up to 30%:
2 … 120 °C
• Connections:
- Ext. thread (weld-on, thread and flange
tailpieces)
- Flange
Ordering
Example AHQM controller:
Flow controller with integrated
control valve, DN 15, kVS 1,6; PN
16; flow restrictor Δp 0,12 bar;
T
120 °C; ext. thread
max
- 1× AHQM DN 15 controller
Code No.: 003L3594
Option:
- 1× Weld-on tailpieces
Code No.: 003H6908
Electrical actuator AMV(E) must be
ordered separately.
FunctionFlow controller with integrated control valve
Flow volume causes the pressure drop across the
adjustable flow restrictor. Resulting pressures
are being transferred through external impulse
tubes or control drains within valve body to
the actuator chambers and act on control
diaphragm. The flow restrictor diff. pressure
is controlled and limited by means of built-in
spring for flow rate control.
Settings
Flow setting
Flow setting is being done by the adjustment of
the flow restrictor position. The adjustment can
be performed on the basis of flow adjustment
diagram (see relevant instructions) and/or by the
means of heat meter.
Dimensions
DN 15 -32
DN
L
H24313949
H157597284
D (ISO 228/1)G ¾AG 1AG 1¼ A G 1¾A
Valve weightkg0,510,671,472,23
Additionally the electrical actuator will operate
from zero to set max. flow according to the load.