Differential pressure controller with flow limitation and
with integrated control valve (PN 16)
AHPBM-F– flow mounting, fixed setting
Description
AHPBM-F is a self-acting differential pressure
controller with flow limitation primarily for use in
direct-connected district heating systems with mixing loop only. The controller closes on rising
differential pressure or when set max. flow is
exceeded.
It can be combined with Danfoss electrical
actuators AMV(E) and controlled by ECL
electronic controllers.
The controller has a control valve with adjustable
flow restrictor, connection neck for electrical
actuator, and an actuator with one control
diaphragm.
Controllers are used together with Danfoss
electrical actuators:
- AMV(E) 10
- AMV(E) 13 with spring return function
- AMV(E) 130, AMV(E) 140
- AMV(E) 130H, AMV(E) 140H with manual
override knob
AHPBM-F combined with AMV(E) 13 has been
approved according to DIN EN 14597.
Main data:
• DN 15-32
• kvs 1.0-6.3 m3/h
• PN 16
• Fixed ∆p setting:
- 0.12 bar for DN 15-20
- 0.14 bar for DN 25-32
• Temperature:
- Circulation water / glycolic water up to 30%:
2 … 120 °C
• Connections:
- Ext. thread (weld-on, thread and flange
tailpieces)
Ordering
Example:
Differential pressure controller
with flow limitation (fixed setting)
and integrated control valve,
DN 15, kVS 1.6, PN 16, flow restrictor
Δp 0.12 bar, t
- 1× AHPBM-F DN 15 controller
Code No.: 003L3582
Option:
- 1× Impulse tube set AH, 1.5 m
Code No: 003L8152
- 1× Fitting for imp. tube
Code No: 003L5042
- 1× Weld-on tailpieces
Code No.: 003H6908
External impulse tube (AH), nipple
for impulse tube and electrical
actuators AMV(E) must be ordered
separately.
Diff. press. controller with flow limitation and with integrated control valve AHPBM-F (PN 16)
Sizing
- Directly connected heating
system
Example AHPBM-F
(flow mounting only)
Motorised control valve (MCV) for mixing circuit
in direct-connected heating systems requires
differential pressure of 0.12 bar (12 kPa) and flow
less than 600 l/h.
Given data:
Q
= 0.6 m3/h (600 l/h)
max
p
= 0.8 bar (80 kPa)
min
*p
= 0.1 bar (10 kPa)
circuit
p
= 0.12 bar (12 kPa) selected
MCV
* Remark:
p
corresponds to the required pump
circuit
pressure in the heating circuit and is not to be
considered when sizing the AHPBM-F.
The total (available) pressure loss across the
controller is:
p
p
= p
AHPBM-F,A
= 0.8 bar (80 kPa)
AHPBM-F,A
min
Possible pipe pressure losses in tubes, shut-off
fittings, heatmeters, etc. are not included.
Select controller from flow diagram, page 5,
with the smallest possible kVS value considering
available flow ranges.
kVS = 1.6 m3/h
The min. required differential pressure across
the selected controller is calculated from the
formula:
2
Q
max
p
p
p
AHPBM-F,MI N
p
AHPBM-F,A
MINF,-AHPBM
k
VS
2
0.6
MINF,-AHPBM
1.6
0.12
= 0.26 bar (26 kPa)
> p
AHPBM-F,MI N
p
MCV
0.8 bar > 0.26 bar
Solution:
The example selects AHPBM-F DN 15, kVS value
Diff. press. controller with flow limitation and with integrated control valve AHPBM-F (PN 16)
FunctionPressure changes from the flow and return
pipeline are being transferred through the
impulse tube and control drain to the actuator
chambers and act on control diaphragm. Control
valve closes on rising differential pressure and
opens on falling differential pressure to maintain
constant differential pressure. Flow volume is
controlled and limited by means of the flow
restrictor.
Additionally the electrical actuator will operate
from zero to set max. flow according to the load.
Settings
Flow setting
Flow setting is being done by the adjustment of
the flow restrictor position. The adjustment can
be performed on the basis of flow adjustment
diagram (see relevant instructions) and/or by the
means of heat meter.