Danfoss AHF 005, AHF 010 Fact sheet

Fact Sheet
VLT® Advanced Harmonic Filter AHF 005 and AHF 010
Optimised harmonic performance for VLT® drives rated up to 250 kW.
The VLT® Advanced Harmonic Filter has been specially designed to match the Danfoss drives for unmatched per­formance and design.
Compared to traditional harmonic trap filters, the VLT® Advanced Harmonic Fil­ter offers a smaller foot print and higher harmonic reduction.
The filter is available in two variants,
AHF 005 and AHF 010. When con­nected at the input to a Danfoss VLT® drive the harmonic current distortion generated back to the mains is reduced to 5% or 10% Total Harmonic Current Distortion (THiD) at full load.
With efficiency exceeding 98 % the pas­sive filters AHF 005 and AHF 010 offer cost-effective and very robust harmonic solutions specifically for power ranges up to 250 kW.
As stand-alone options the advanced harmonic filters feature a compact housing that is easily integrated into existing panel space. This makes them well-suited for retrofit applications with limited adjustments of the drive.
Line Voltage
n 380 – 415 V AC (50 and 60 Hz) n 440 – 480 V AC (60 Hz) n 600 V AC (60 Hz) n 500 – 690 V AC (50 Hz)
Filter current
n 10 A-480 A
(380-415 V AC, 50 and 60 Hz)
n 10 A-436 A (440-480 V AC, 60 Hz) n 15 A-395 A, (600 V AC, 60 Hz) n 15 A-395 A (500-690 V AC, 50 Hz) n Modules can be paralleled for higher
power
Enclosure IP rating
n IP20*
* An IP21/NEMA 1 upgrade kit is available
for the IP20 unit. Order separately.
Perfect
match for industrial automation, highly dynamic applications and safety installations
Feature Benefit
Reliable Maximum uptime
– 100% factory tested – Based on proven and tested filter concept
Energy saving Lower operation costs
– High efficiency – Electrically matched to the individual
VLT® frequency converters
Design Compact and aesthetic enclosure
– Innovative coil design – Side-by-side mounting – Optimised for mounting in panels
– Easy commissioning – Low commissioning costs – Enclosure size and colour matches – Danfoss look and feel
– Low failure rate
– Low running expenses
– Smaller footprint – Less wall space needed
drives.danfoss.com
Accessories
The following accessories are available:
n IP21/NEMA 1 kit n IP21/NEMA 1 kit with capacitor
disconnect feature
n Backplate for IP
20 enclosures
Harmonic Calculation Software
With VLT® Motion Control Tool MCT 31, you can determine whether harmonics will have a detrimental effect on an installation incorporating frequency converters.
MCT 31 calculates system harmonic distortion. Then it estimates the benefits of implementing harmonic mitigation, using filters available from Danfoss. Furthermore the software provides quick indication of whether the installation complies with the most recognised harmonic norms and recommendations.
Download the MCT 31 software free of charge at: www.danfoss.com
Specifications
AHF 010 AHF 005
THiD* at: – 40% load – 70% load – 100% load
Efficiency* at 100% load >98.5% True power factor* at:
– 40% load – 70% load – 100% load
Ambient temperature 45° C without derating
Cooling
* Measured at balanced grid without pre-distortion
Norms and recommendations Compliance
IEEE519
IEC61000-3-2 (up to 16 A) AHF 005 and AHF 010 IEC61000-3-12 (between 16 and 75 A) AHF 005 and AHF 010 IEC61000-3-4 (above 75 A) AHF 005 and AHF 010
~ 12% ~ 11% < 10%
~ 81% ~ 96% > 99%
For enclosures rated IP20, back channel cooling is built in.
AHF 005 is compliant under all conditions AHF 010 is compliant dependent on grid and load conditions
~ 7% ~ 6% < 5%
~ 80% ~ 95% > 98%
Enclosures
AHF current rating
380-415 V/
50 Hz
AHF
AHF
005
133
171 204
251 304
325 381 480
010
[A] [A] [A] [A] [A] [A] [A] [A] [A] [A] Type
10
10
14
14
22
22
29
29
34
34
40
40
55
55
66
66
82
82
96
96
133
171 204
251 304 325 381
480
380-415 V/
60 Hz
AHF
005
10 14
22 29
34 40 55
66 82
96
133
171 204
251
304 325 381 480
AHF
010
10 14
22 29
34 40 55
66 82
96
133
171 204
251 304 325 381
480
440-480 V/
60 Hz
AHF
005
10 14
19 25
31 36 48
60 73
95
118
154 183
231
291 355 380 436
AHF
010
10 14
19 25
31 36 48
60 73
95
118
154 183
231 291 355 380
436
600/
60 Hz
AHF
AHF
005
109 128
155 197
240 296
010
X1
X2
15 20 24
29 36
50 58
77 87
15 20 24
29 36
50 58
77
87 109 128
155 197 240
296 366 395
500-690 V/
50 Hz
AHF
005
15 20 24
29 36
50 58
77
87 109 128
155 197
240 296
AHF
010
15 20 24
29 36
50 58
77
87 109 128
155 197 240
296 366 395
Dimensions
Enclosure type Height
X1 347 190 206 X2 451 230 248 X3 605 378 242 X4 634 378 333 X5 747 418 333 X6 778 418 400 X7 900 468 450 X8 900 468 515
(*1)
: Maximum dimension. The exact dimension depends on fan concept.
For the exact dimensions, refer to the Design Guide Advanced Harmonic Filters.
(*1)
[mm] Width [mm] Depth [mm]
AHF
enclo-
sure
X3
X4
X5
X6
X7
X8
DKDD.PFP.653.A2.02 © Copyright Danfoss Drives | 2019.02
Loading...