Flow controller with integrated control valve (PN 16, 25, 40*)
AFQM, AFQM 6 - return and flow mounting
Description
AFQM 6 DN 40, 50 AFQM DN 65-125 AFQM DN 150-250
AFQM(6) is a self-acting flow controller with
integrated control valve with full authority,
primarily for use in district heating systems. The
controller closes when set max. flow is exceeded.
In combination with Danfoss electrical actuators
AMV(E) can be controlled by ECL electronic
controllers.
The AFQM (6) is pressure independent which
means that the control characteristic is
independent from the available pressure and is
not influenced by a low authority.
The controller has a control valve with adjustable
flow restrictor, connection neck for electrical
actuator and an actuator with one control
diaphragm. Further on control valve can be:
- not pressure relieved (AFQM 6 DN 40-50) or
- pressure relieved (AFQM DN 65-250).
Controllers are used together with Danfoss
electrical actuators:
• AFQM 6 PN 16/25, AFQM PN 16/25 DN 65-125 3)
- AMV(E) 65x
without spring return function and with
manual operation:
- AMV(E) 655
spring return function and manual operation:
- AMV(E) 658 SD
2)
spring return function:
- AMV(E) 659 SD 1)
• AFQM 6 PN 16/25, AFQM PN 16/25 DN 65-125
- AMV(E) 55, 56
• AFQM PN 16 DN 150-250
- AMV(E) 85, 86
1)
DIN approved , according to EN 1457
2)
not DIN approved
3)
For AFQM 6 PN 16/25 and AFQM PN 25/40 controllers ,
produced be fore March 2015, adapter code 0 65B3527 need
to be separately o rdered
Main data:
• DN 40-250
• kVS 20-400 m3/h
• Flow range 2.2-420 m3/h
• PN 16, 25
* PN 40 on special request
• Flow restrictor ∆pb: 0.2 or 0.5 bar
• Temperature:
- Circulation water / glycolic water up to 30 %:
2 … 150 °C for DN 40-125
2 … 140 °C for DN 150-250
• Connections:
- Flange
• AFQM 6 and AFQM PN 25 combined with
AMV(E) 659 SD have been DIN approved
according to EN 14597.
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
Ordering
Example:
Flow controller with integrated
control valve, DN 65, kVS 50,
PN 16, flow restrictor Δpb 0.2 bar,
T
150 °C, flange
max
- 1× AFQM DN 65 controller
Code No.: 003G6056
The controller will be delivered
completely assembled, inclusive
impulse tubes bet ween valve and
actuator. Electrical actuator AMV(E)
must be ordered separately.
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
Pressure temperature diagram
PN 25
PN 16
EN -GJL-2 50
(GG -25)
Maximum allowed operating pressure as a function of medium temperature (according to EN 1092-2)
EN-GJS- 400
(GGG-40.3)
Flow diagram
Sizing and setting diagram
Relation between actual flow and number of revolutions on flow restictor. Values given are approximate.
DN 250 kVS 400
DN 200 kVS 320
DN 150 kVS 280
DN 125 kVS 160
DN 100 kVS 125
DN 80 kVS 80
DN 65 kVS 50
DN 50 kVS 32
DN 40 kVS 20
6 | VD.LR.A8.02
Flow can be adjusted by turning flow restrictor screw
counter-clockwise as shown in this diagram
1 = 360º
Water flow shown at differential pressure across flow
restrictor 0.2 bar (20 kPa) and across the controller
from 0.5 bar (50 kPa) to max. diff. pressure.
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
Flow diagram
Sizing and setting diagram
Relation between actual flow and number of revolutions on flow restictor. Values given are approximate.
DN 250 kVS 400
DN 200 kVS 320
DN 150 kVS 280
DN 125 kVS 160
DN 100 kVS 100
DN 80 kVS 80
DN 65 kVS 50
Flow can be adjusted by turning flow restrictor screw
counter-clockwise as shown in this diagram
1 = 360º
Water flow shown at differential pressure across flow
restrictor 0.5 bar (50 kPa) and across the controller
from 0.5 bar (50 kPa) to max diff. pressure.
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
Sizing
- Directly connected heating
system
Example 1
Motorised control valve (MCV) for mixing circuit
in direct-connected heating systems requires
differential pressure of 0.2 bar (20 kPa) and flow
less than 8000 l/h.
Given data:
Q
= 8.0 m3/h (8000 l/h)
max
∆p
= 0.8 bar (80 kPa)
min
1)
∆p
= 0.1 bar (10 kPa)
circuit
∆p
= 0.2 bar (20 kPa) selected
MCV
Remark:
1)
∆p
corresponds to the r equired pump pressure in the
circuit
heating circuit a nd is not to be considered when sizin g the
AFQM.
The total (available) pressure loss across the
controller is:
∆p
= ∆p
∆p
AFQM,A
AFQM,A
min
= 0.8 bar (80 kPa)
Possible pipe pressure losses in tubes, shut-off
fittings, heatmeters, etc. are not included.
Select controller from flow diagram, page 7,
with the smallest possible kVS value considering
available flow ranges.
kVS = 20 m3/h
The min. required differential pressure across
the selected controller is calculated from the
formula:
p
∆p
∆p
MIN,AFQM
= 0.36 bar (36 kPa)
AFQM,MI N
> ∆p
AFQM,A
Q
max
k
VS
AFQM,MIN
2
p
MCV
2
0.8
20
2.0
0.8 bar > 0.36 bar
Solution:
The example selects AFQM 6 DN 40, kVS value 20,
flow setting range 2.2-11 m3/h.
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
Sizing (continuous)
- Indirectly connected heating
system
Example 2
Motorised control valve (MCV) for indirectly
connected heating system control requires
differential pressure of 0.2 (20 kPa) bar and flow
less than 22.000 l/h.
Given data:
Q
= 22 m3/h (22.000 l/h)
max
∆p
= 0.8 bar (80 kPa)
min
∆p
∆p
= 0.1 bar (10 kPa)
exchanger
= 0.2 bar (20 kPa) selected
MCV
The total (available) pressure loss across the
controller is:
∆p
= ∆p
AFQM,A
∆p
= 0.7 bar (70 kPa)
AFQM,A
min
−∆p
exchanger
= 0.8−0.1
Possible pipe pressure losses in tubes, shut-off
fittings, heatmeters, etc. are not included.
Select controller from flow diagram, page 7,
with the smallest possible kVS value considering
available flow ranges.
kVS = 50 m3/h
The min. required differential pressure across
the selected controller is calculated from the
formula:
∆p
∆p
p
MIN,AFQM
= 0.39 bar (39 kPa)
AFQM,MIN
> ∆p
AFQM,A
Q
AFQM,MIN
2
.max
p
MCV
k
VS
2
22
50
2.0
0.7 bar > 0.39 bar
Solution:
The example selects AFQM DN 65, kVS value 50,
flow setting range 5.6-28 m3/h.
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
18
Design
1. Valve body
2. Control valve insert
3. Adjustable flow restrictor
4. Control valve stem
5. Valve seat
6. Actuator
7. Control diaphragm for flow
control
8. Built-in spring for flow rate
control
9. Excess pressure safety valve
10. Valve insert
11. Pressure relieved valve cone
12. Valve stem
13. Bellows for pressure relief of
valve cone
14. Diaphragm for pressure relief
of valve cone
15. Impulse tube
16. Union nut
17. Upper casing of diaphragm
18. Lower casing of diaphragm
19. Cover
20. Bellows for pressure relieve
of control valve cone
10
19
15
17
4
2
3
1
5
11
13
12
15
16
8
6
7
19
15
17
4
2
20
1
3
5
11
10
13
12
15
16
8
6
9
7
18
AFQM 6 DN 40, 50
AFQM DN 65-125
AFQM DN 150-250
Function
10 | VD.LR.A8.02
Flow volume causes pressure drop across the
adjustable flow restrictor. Resulting pressures
are being transferred through the impulse tubes
to the actuator chambers and act on control
on falling differential pressure to control max
flow.
Additionally the electrical actuator will operate
from zero to set max. flow according to the load.
diaphragm for flow control. The flow restrictor
diff. pressure is controlled and limited by means
of built-in spring for flow control. Control valve
closes on rising differential pressure and opens
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
Settings
Dimensions
Flow setting
Flow setting is being done by the adjustment of
the flow restrictor position. The adjustment can
be performed on the basis of flow adjustment
diagram (see relevant instructions) and/or by the
means of heat meter.
Danf
already on order pro
All trademarks in this material are property of the respec
Data sheet Flow controller with integrated control valve AFQM(6), PN 16, 25, 40*
Dimensions (continuous)
4
H
3
2
H
H
1
1
H
L
AMV(E) 55, 56/AFQM
DN 65-125, PN 16/25
3)
For AFQM 6 PN 16/25 and AFQM PN 25/40 controllers , produced before March 2015, adapter code 0 65B3527 need to be
H
L
AMV(E) 65X/AFQM
DN 65-125, PN 16/25
3)
1
H
L
AMV(E) 85, 86/AFQM
DN 150-250, PN 16
separately ord ered
DN
L
H
H
1
H
2
3
mmPN 16PN 25
Valve weight (kg)
H
4
65290425604640-5258.5
80310425624650-6160.5
100350530634665-93.696
125400530664690-117. 213 9
150480576--455142-
200600652--483219-
250730656--533342-
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessaryeady agreed.
12 | VD.LR.A8.02
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.