Differential pressure controller
AFP / VFG 2 (VFG 21), DN 15 - 250
SIBC
VN.CC.F2.02 © Danfoss 01/04 |
1 |
AFP / VFG 2 (VFG 21)
Valves |
Valves VFG 2 (metallic sealing cone) |
|
|
|
|
||
|
DN |
kvs |
tmax. |
|
|
Code No. |
|
|
mm |
m3 /h |
o C |
|
PN 16 |
PN 25 |
PN 40 |
|
15 |
4.0 |
150 |
200* |
065B2388 |
065B2401 |
065B2411 |
|
20 |
6.3 |
150 |
200* |
065B2389 |
065B2402 |
065B2412 |
|
25 |
8.0 |
150 |
200* |
065B2390 |
065B2403 |
065B2413 |
|
32 |
16 |
150 |
200* |
065B2391 |
065B2404 |
065B2414 |
|
40 |
20 |
150 |
200* |
065B2392 |
065B2405 |
065B2415 |
|
50 |
32 |
150 |
200* |
065B2393 |
065B2406 |
065B2416 |
|
65 |
50 |
150 |
200* |
065B2394 |
065B2407 |
065B2417 |
|
80 |
80 |
150 |
200* |
065B2395 |
065B2408 |
065B2418 |
|
100 |
125 |
150 |
200* |
065B2396 |
065B2409 |
065B2419 |
|
125 |
160 |
150 |
200* |
065B2397 |
065B2410 |
065B2420 |
|
150 |
280 |
140 |
- |
065B2398 |
- |
065B2421 |
|
200 |
320 |
140 |
- |
065B2399 |
- |
065B2422 |
|
250 |
400 |
140 |
- |
065B2400 |
- |
065B2423 |
|
150 |
280 |
- |
200* |
|
|
|
|
200 |
320 |
- |
200* |
on request |
|
|
|
250 |
400 |
- |
200* |
|
|
|
* temperatures up to 200 oC only with seal pot (see accessories), mounted in the impulse tube to the flow
Valves VFG 21 (soft sealing cone)
|
|
|
|
|
|
|
|
DN |
kvs |
tmax. |
|
Code No. |
|
|
|
|
|
|
|
|
|
mm |
m3 /h |
oC |
PN 16 |
PN 25 |
PN 40 |
|
|
|
|
|
|
|
|
15 |
4.0 |
150 |
065B2502 |
065B2515 |
065B2525 |
|
|
|
|
|
|
|
|
20 |
6.3 |
150 |
065B2503 |
065B2516 |
065B2526 |
|
|
|
|
|
|
|
|
25 |
8.0 |
150 |
065B2504 |
065B2517 |
065B2527 |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
32 |
16 |
150 |
065B2505 |
065B2518 |
065B2528 |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
40 |
20 |
150 |
065B2506 |
065B2519 |
065B2529 |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50 |
32 |
150 |
065B2507 |
065B2520 |
065B2530 |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
65 |
50 |
150 |
065B2508 |
065B2521 |
065B2531 |
|
|
|
|
|
|
|
|
80 |
80 |
150 |
065B2509 |
065B2522 |
065B2532 |
|
|
|
|
|
|
|
|
100 |
125 |
150 |
065B2510 |
065B2523 |
065B2533 |
|
|
|
|
|
|
|
|
125 |
160 |
150 |
065B2511 |
065B2524 |
065B2534 |
|
|
|
|
|
|
|
|
150 |
280 |
140 |
065B2512 |
- |
065B2535 |
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
200 |
320 |
140 |
065B2513 |
- |
065B2536 |
|
|
|
|
|
|
|
|
250 |
400 |
140 |
065B2514 |
- |
065B2537 |
Actuators |
AFP / AFP-9 Actuators |
|
|
|
Type |
Diff. pressure |
Code No. |
|
(bar) |
||
|
|
|
|
|
|
0.15 - 1.5 |
003G1016 |
|
AFP |
0.1 - 0.7 |
003G1017 |
|
|
0.05 - 0.35 (630 cm2) |
003G1018 |
|
AFP-9 |
1 - 6 |
003G1014 |
|
0.5 - 3 |
003G1015 |
|
|
|
2 |
VN.CC.F2.02 © Danfoss 01/04 |
SIBC
AFP / VFG 2 (VFG 21) DN 15 - 32 (set-point up to 1.5 bar)
SIBC |
VN.CC.F2.02 © Danfoss 01/04 |
<![if ! IE]> <![endif]>set-point. |
|
<![if ! IE]> <![endif]>can be read out from above graphs. It is recommended that Xp does not exceed 50% of the required |
<![if ! IE]> <![endif]>FW503. |
<![if ! IE]> <![endif]>size, corresponding P-band (Xp) |
<![if ! IE]> <![endif]>defined acc. to AGFW Guideline |
<![if ! IE]> <![endif]>After selecting the suitable valve |
<![if ! IE]> <![endif]>Set-point and setting ranges are |