The controller is a self-acting differential pressure
and flow controller primarily for use in district
heating systems. Direct operated, reliable and
high precise controller closes on rising differential
pressure or when set max. flow is exceeded.
The controller has a control valve with adjustable
flow restrictor, an actuator with two control
diaphragms and spring for differential pressure
setting. Differential pressure control and flow
control are independent.
Further on two valve versions are available:
∙ VFQ 22 with metallic sealing cone
∙ VFQ 221 with soft sealing cone
Together with Danfoss intelligent electrical
actuator AMEi 6 intelligent optimization
functions are available:
∙ iSET-intelligent substation efficiency
optimization
∙ iNET-intelligent network balancing
Main data:
∙ DN 65-250
∙ kVS 60-800 m3/h
∙ Flow range 5.6-500 m3/h
∙ PN 16, 25, 40
∙ Setting range: 0.2-1 bar / 0.5-1.5 bar
∙ Flow restrictor ∆pb: 0.2 bar or 0.5 bar
∙ Temperature: – Circulation water / glycolic
water up to 30%: 2 … 150°C
∙ Connections: – Flange
Ordering
Example 1:
Differential pressure controller,
return mounting, DN 65, kVS 60,
PN 16, metallic sealing, setting
range 0.5-1.5 bar, flow restrictor
Δpb 0.2 bar, T
Motorised control valve (MCV) for mixing circuit
in direct-connected heating system requires
differential pressure of 0.5 bar (50 kPa) and flow
less than 25.000 l/h.
Given data:
Q
= 25 m3/h (25.000 l/h)
max
p
= 1 bar (100 kPa)
min
1)
p
= 0.1 bar (10 kPa)
circuit
p
= 0.5 bar (50 kPa) selected
MCV
2)
p
= 0.2 bar (20 kPa)
b
Remark:
1)
∆p
corresponds to the r equired pump pressure in t he heating
circuit
circuit and is not to b e considered when sizing the AFPQ (4).
2)
pb is differe ntial pressure over flow restri ctor.
The differential pressure set value is:
p
p
= p
set value
set value
MCV
= 0.5 bar (50 kPa)
The total pressure loss across the controller is:
p
= p
AFPQ
p
= 0.5 bar (50 kPa)
AFPQ
min
− p
= 1 – 0.5
MCV
Q
max
Possible pipe pressure losses in tubes, shut-off
fittings, heatmeters, etc. are not included.
kv value is calculated according to formula:
Q
k
v
max
25
bAFPQ
2.00.5
kv = 45.6 m3/h
Solution:
The example selects AFPQ 2 (return mounting)
or AFPQ 24 (flow mounting) DN 65, kVS value 60,
with differential pressure setting range 0.2-1 bar,
flow setting range 5.6-28 m3/h.
Flow volume causes pressure drop across the
adjustable flow restrictor. Resulting pressures
are being transferred through the impulse tubes
to the actuator chambers and act on control
diaphragm for flow control. The flow restrictor
diff. pressure is controlled and limited by means
of built-in spring for flow control. Control valve
closes on rising differential pressure and opens
on falling differential pressure to control max
flow.
SettingsDifferential pressure setting
Differential pressure setting is being done by the
adjustment of the setting spring for diff. pressure
control. This is done by rotating the differential
pressure setting nut. Set differential pressure
should be checked by observing the pressure
indicators.
Pressure changes from flow and return pipes are
being transferred through the impulse tubes
to the actuator chambers and act on control
diaphragm for diff. pressure control. The diff.
pressure is controlled by means of setting spring
for diff. pressure control. Control valve closes
on rising differential pressure and opens on
falling differential pressure to maintain constant
differential pressure.
Controller is equipped with two excess pressure
safety valves, which protect control diaphragms
for flow and diff. pressure control from too high
differential pressure.
Flow setting
Flow setting is being done by the adjustment of
the flow restrictor position. The adjustment can
be performed on the basis of flow adjustment
diagram (see relevant instructions) and/or by the
means of heat meter.