Example 1:
Dierential pressure relief controller;
DN 15; kVS 4,0; PN 16; metallic
sealing; setting range 0,15-1,2 bar;
T
150 °C; ange;
max
- 1× VFG 2 DN 15 valve
Code no: 065B2388
- 1× AFPA actuator
Code no: 003G
- 2× Impulse tube set AF
Code no: 003G1391
Products will be delivered separatly.
1021
The controller is a self-acting dierential pressure
relief controller primarily for use in district
heating systems. The controller is normally
closed and opens on rising dierential pressure.
VFG 2 Valves (metallic sealing cone)
Picture
DNk
(mm)(m3/h)(°C)PN 16PN 25PN 40
154,0
206,3065B2389065B24020 65B2 412
258,0065B2390065B24 03065 B2413
3216065B 2391065B2404065 B2414
4020065B2392065B2405065B2415
5032065B2393065B2406065B2 416
6550065B2394065B2407065 B2417
8080065B2395065B2408065 B2418
100125065B2396065B2409065 B2419
125160065B2397065 B2410065B2420
150280
200320065B2399065B2422
250400065B2400065B2423
VS
T
max
150200
140
1)
The controller has a control valve, an actuator
with one control diaphragm and spring for
dierential pressure setting.
Further on two valve versions are available:
- VFG 2 with metallic sealing cone
- VFG 21 with soft sealing cone
Main data:
∙ D N 15-250
∙ kVS 4,0-400 m3/h
∙ PN 16, 25, 40
∙ Setting range:
- 0,05-0,3 bar / 0,1-0,6 bar / 0,15-1,2 bar /
0,5-2,5 bar / 1-5 bar
∙ Temperature:
- Circulation water / glycolic water up to 30 %:
2 … 140 / 150 / 200 °C
∙ Connections:
- Flange
Connections
065B2388065B24 010 65B 2411
Flanges acc. to
EN 1092-1
065B2398
Code No.
-
065 B2421
DEN-SMT/SI
Impulse tube set AF
150280
250400065B2426
Note: other valves available on special request.
1)
at temperature s above 150 °C (DN 15-125)/140 °C (DN 150-250) only with seal pot s (see Accessories)
10. Control diaphragm for
dierential pressure control
11. Setting spring for di.
pressure control
12. Adjuster for di. pressure
setting, prepared for sealing
13. Stung cone
14. Union nut
15. Compression tting for
impulse tube
16. Upper casing of diaphragm
17. Lower casing of diaphragm
18. Valve body extension
19. Shut o valve for water lling
20. Closing plug
5
13
8
15
17
AFPA / VFG 2 DN 15 - 125
3
6
4
7
2
14
VFG 2 DN 150-250, T
16
15
10
11
12
max
140 °C
92
20
19
VFG 2 DN 150-250, T
max
18
9
2
200 °C
Function
The pressures in front and behind of the control
valve are being transferred through the impulse
tubes to the actuator chambers and act on
control diaphragm for di. pressure control.
Control valve is normally closed. It opens on
rising dierential pressure and closes on falling
dierential pressure to maintain constant
dierential pressure.
SettingsDierential pressure setting
Dierential pressure setting is being done by the
adjustment of the setting spring for dierential
pressure control. The adjustment can be done by
means of spring for dierential pressure setting
and pressure indicators.