Danfoss Adapters Fact sheet

Tech note
Adapters for non-Danfoss actuators with M30×1,5 thread connection
Ordering
Stem extension Closing measure Code No.
Example:
Closing measure
Stem extension
0,5 mm 10,9 ±0,3 003Z0246 (5 pieces)
1,0 m m 11, 4 ± 0, 3 003Z0247 (5 p ieces)
1,5 mm 11, 9 ±0 ,3 003Z0248 (5 pieces)
2,0 mm 12, 4 ±0 ,3 0 03Z0249 (5 pieces)
1,0 m m 9,4 ±0, 3 003Z0257 (5 pieces)
1,5 mm 8,9 ±0,3 003Z0258 (5 pie ces)
Actuator’s spindle
DEN-SMT/SI
Washer
Opening measure
EN.C6.L4.02 © Danfoss 10/2013
9,4 ±0,3
Closing measure
on AB-QM with
1 mm washer
Basic opening measure: DN 10-20: 12,65±0,3 mm DN 25-32: 14,9±0,3 mm
10,4 ±0,3
Basic closing
measure on AB- QM
11,4 ±0,3
Closing measure
on AB-QM with
steam
1
Data sheet AB-QM - calculation, ow conrmation & pump optimisation
Data for non-Danfoss actuators
Actuator AB-QM DN 10-20 AB-QM DN 25-32
Honeywell
M5410L1506 1,5 mm stem extension 003Z0248 1,5 mm stem extension 003Z0248
M5 410L45 00
M4450A1009T 1,5 mm stem extension 003Z0248
Johnson Controls
VA7450-####-03 (M30 × 1,5 connection !)
Siemens
STA 21(71) 2 mm stem extension 003Z0249
SSA (M30 × 1,5 connection *) No adapters needed No adapters needed
SSD61U 0-10 V No adapters needed, due to 1,5mm min
SSD61.5U 0-10 V (actuator has no DIP switch and works by default in inverse mode)
Sauter
AXT211F110 230 V on/o AXS215SF122 24 V 0-10 V
Theben
CHEOPS control KNX No adapters needed No adapters needed, 7,5mm stroke
1,5 mm stem extension 003Z0248
No adapters needed
+ washer 003Z0257
stroke min pre-setting 70 %
No adapters needed, due to 1,5mm min stroke min pre-setting 70 %
No adapters needed, move DIP switch 2 to ON to decrease stroke to 3,2 mm
1,5 mm stem extension 003Z0248
No adapters needed
Only 60 % of the ow
(3,2 mm travel from actuator)
2 mm stem extension 003Z0249 + washer 003Z0257
Only 60 % of the ow
No adapters needed, due to 1.5mm min stroke min pre-setting 40 % , 5 mm stroke (opens 100 %)
No adapters needed, due to 1.5mm min stroke min pre-setting 40 % , 5 mm stroke (opens 100 %)
No adapters needed, move DIP switch 2 to OFF in order to keep stroke at 4, 5 mm (opens 100 %)
(opens 100 %)
* For modulating version (SSA61) settings on AB-QM DN 10-20 should be at least 70 %, while on AB-QM DN 25-32 at least 35 %. Those settings will allow stroke of 1,5 requested to calibrate (closing and full open position) the actuator.
In order to secure compatibility between valve and actuator it is recommended that actuator supplier is asked to provide exact denition of maximum stroke and lower & upper point relative
to spindle- nut position of the actuator to
be used.
2
EN.C6.L4.02
Produce d by Danfoss A/S © 10/2013
Loading...