Danfoss ABV, ABV-NO, ABV-NC Data sheet

Data Sheet
ABV Thermo-Hydraulic Actuator Electronic Actuator
Applications:
Ordering:
Low voltage, 24 volt thermo-hydraulic actuator
Normally open or Normally closed versions
Built-in manual operation
Built in stem travel limiting
ABV is recommended for ow temperature control as well as ON/OFF control in hot water systems. Applications include heat exchangers, zone control for mixed loop systems, and storage tanks Use with type RAV, VMT, and KOVM 3-way valve
ABV
Typ e Code No. Without Power
Actuator position
ABV-NO 082F0002 Normally open Port A- AB Port B-AB
ABV-NC 082F0052 Normally closed Open Closed
Valve Ordering No. Style Pipe size Cv Connection type
065F8960
VMT
KOVM
065F8961 3/4” 5.9
065F1242 1” 9.4 Male NPT unions
013U3017
013U3015
013U3020 2.34
2-way
3-way 1/2”
Used on ow temperature or oor heating systems
Installed on KOVM (port position
without power)
Closed Open
1/2” 3.3
1.75
Double solder unions
Female NPT
Compression ttings
Specications:
Supply voltage 24 V ~ +30%, -15%
Frequency 50-60 Hz
Control signal 2-point (ON/OFF)
Consumption 9VA
Time for full spindle travel < 9 min
Max. permissible spindle travel ABV-NO: 4mm
ABV-NC: 2.2mm
Ambient temperature 32-140°F (0-60°C)
Weight 0.6 lb
Actuator mounted onto 2-way: RAV, VMT / 3-way: KOVM
Mounted orientation Any orientation, except upside down
Stem force 18 lbf (80N)
VDLEA 222 © Danfoss 03/14
1
Data Sheet ABV Thermo-Hydraulic Actuator / Electronic Actuator
Electrical Connections:
Mechanical Connection:
Manual Control:
1-5/16” (34 mm)
outside diameter
RAV / VMT
/ KOVM
ABV has a collar that is marked with arrows indicating settings for manual and automatic operation.
Manual Operation Return to Automatic Operation
Lift collar up. Rotate base counter clockwise until right arrow ( ) aligns with A on the collar.
For the ABV-NC, the valve can be opened manually by turning the collar in a counterclockwise direction as indicated. Likewise when tted with ABV-NO, the valve can be manually closed by turning the collar in a clockwise direction
2
VDLEA 222 © Danfoss 03/14
Lift collar up. Rotate base clockwise until triangle ( ) aligns with A on collar.
Push collar down.
Data Sheet ABV Thermo-Hydraulic Actuator / Electronic Actuator
Automatic control settings:
Operation:
The ABV when mounted to the VMT has the unique ability of provide automatic control with or with­out stem travel limitation. When the collar is raised, the scale setting is exposed.
A
With the right triangle ( , AUTO) set to “A” on the collar’s scale, there will be a full ow rate through the valve, i.e. the entire travel of the valve stem and 100% of the valve’s Cv. If the triangle ( ) is set to any other position along the collar’s scale, the maximum stem travel will be reduced resulting in a reduced ow rate and Cv value.
Normally closed actuator
RAV/ VMT
Normally open actuator
KOVM
VDLEA 222 © Danfoss 03/14
3
Data Sheet ABV Thermo-Hydraulic Actuator / Electronic Actuator
Dimensions:
RAV VMT KOVM
A
B
C
H
L
A
B
C
H
L
Size Typ e H L
1/2”
3/4” 4.4” 4.2” B 2.0”
RAV
4.4” 3.7” A 2.8”
1” 4.9” 4.9” C 3.6”
1/2”
3/4” 4.4” 4.8”
VMT
4.4” 4.1”
1” 4.9” 5.7”
A
B
C
G
A
D
E
F
AB
KOVM
B
L
L D E F G
1/2” KOVM 2.3” 1.1” 1.1” 1.0” 4.6”
Typical specication:
The electronic actuator shall be a 2-wire thermo-wax actuator powered by 24 volts AC. The signal to the actuator shall be ON/ OFF. The actuator shall have manual operator and integrated Cv limitation for control in hot water
Danfoss can accept no responsibility for possible errors in printed materials and reserves the right to alter its products without notice. All trademarks in this material are property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss Inc.
Toronto, ON Toll Free: 866-375-HVAC (4822) Tel.: 905-285-2050, Fax: 905-285 -2055 www.na.heating.danfoss.com
systems. The applications for the actuator shall be for linear actuation for 2-way and 3-way valves for normally open or normally closed applications. The electronic actuator shall be an ABV thermo-wax actuator.