Danfoss AB‑QM DN 10-250 Data sheet

Data sheet
Pressure independent balancing and control valve AB‑QM DN 10‑250
The AB‑QM valve equipped with an actuator is a control valve with full authority and an automatic balancing function / f low limitation. Typical applications are: Temperature control with permanent automatic balancing on terminal units (chillers, air‑handling units, fan coils, induction units, radiation panels and heat exchangers).
Description
The precise flow control performance of the AB-QM with a Danfoss actuator provides increased comfort and lower Total Cost of Ownership because of savings made on:
• Efficient energy transfer and minimal pumping costs since there are no overflows at partial loads because of the exact pressure independent flow limitation.
• Smaller pump investments and lower energy consumption as the pump head needed is lower than in the traditional setup. With the built in test plugs it is easy to troubleshoot and find the optimal setpoint for the pump.
• Reduced movements of the actuator since the built-in differential pressure controller ensure the pressure fluctuations do not influence the room temperature.
• Achieving a stable temperature in a room leading to a lower average temperature at the same comfort level.
• Minimal flow complaints, as the valve performs as designed.
• Minimal blockage complains, as the membrane design makes AB-QM less susceptible to blockage than a cartridge type construction.
• Trouble-free segmentation of the building project. When sections of a project are finished they can normally not be handed over to the customer with a fully functional HVAC installation. However the AB-QM with a Danfoss actuator will automatically control the flow, even when other parts of the installation are still unfinished. It’s not needed to adjust the AB-QM after finalisation of the project.
• Commissioning costs, the costs are close to zero because of a convenient setting procedure without the need for flow charts, calculations or measuring equipment. The AB-QM valves can be set to a precise design value even when the system is up and running.
• Halved mounting costs as the AB-QM valve covers two functions, Balancing & Control
© Danfoss | 2018.06
VD.A7.F7.02 | 1
Data sheet AB‑QM DN 10‑250
Control performance
Applications
- variable flow systems
The AB-QM has a linear control characteristic. The AB-QM is pressure independent which means that the control characteristic is independent from the available pressure and is not influenced by a low authority. The flow limitation on the AB-QM is achieved by limiting the stroke and the Danfoss actuators calibrate to the stroke of the valves. This means that the AB-QM keeps its linear characteristic independent of the setting or differential pressure.
Because of the predictable characteristic the actuators on the AB-QM can be used to change the response from linear to logarithmic (equal percentage). That makes the AB-QM suitable for all applications, including AHUs, where the equal percentage characteristic is needed to get a stable control loop. The actuators can be switched from linear to logarithmic by changing a DIP switch setting on the actuator.
100 %
a
t
s
n
o
c
s
For any given 100 % setting
LIN setting stays constant at any available pressure
0
G
O
L
y
a
t
s
g
n
i
t
t
e
s
0 10 V
e
r
u
s
s
e
r
p
e
l
b
a
il
a
v
a
y
n
a
t
a
t
n
Air handling unit (AHU) / fan coil unit (FCU)
An AB-QM with a Danfoss actuator is used as a control valve for terminal units, like an AHU (Air Handling Unit), FCU (Fan Coil Unit) or radiation panel. The AB-QM ensures and control the required flow on every terminal unit and maintains hydronic balance in the system.
Because of the integrated differential pressure controller the control valve always has 100 % authority and therefore offers always stable control. At partial load there is no overflow, contrary to conventional solutions, because the AB-QM will always limit the flow to exactly what is needed. By installing the AB-QM the whole system is divided in completely independent control loops.
There is a full range of Danfoss actuators available for the AB-QM, suitable for every control strategy. Actuators are available for On/Off, 0-10 Volt, 4-20 mA or floating point.
Radiation panel
2 | © Danfoss | 2018.06
VD.A7.F7.02
Data sheet AB‑QM DN 10‑250
Applications
- constant flow systems
Easy implementation
In constant flow system with FCUs or in a one pipe heating system the AB-QM can be installed as an automatic balancing valve in every riser. The AB-QM limits the flow to the set value, thus automatically achieving hydronic balance in the system.
There are numerous applications in which AB‑QM can be used. Every time you need an automatic flow limiter or a control valve you can take advantage of the cost‑saving properties of the AB‑QM. That includes systems with (floor) heating/cooling, concrete core activation or radiation panels.
Note: For more application examples please contact your local Danfoss organization.
• No Kv or authority calculations needed. Flow is the only parameter to be considered when designing.
• The AB-QM always fits the application because the maximum setting of the AB-QM corresponds with international standards for flow velocity in pipes.
• The AB-QM can be used for all HVAC applications since it can have a linear or logarithmic characteristic when combined with thermal electric or gear actuators.
• Easy commissioning. No specialized staff or measuring equipment needed.
• Easy trouble shooting.
• Fast start-up because AB-QM valves don’t need to be flushed or de-aired before use.
• Trouble-free segmentation of the building project. The AB-QM will automatically control the flow, even when parts of the installation are still unfinished. It’s not needed to adjust the AB-QM after finalisation of the building project.
• Compact design, essential when only limited space is available. For example in fan-coil units.
VD.A7.F7.02
© Danfoss | 2018.06 | 3
Data sheet AB‑QM DN 10‑250
Ordering
AB‑QM threaded version (with test plugs and without test plugs)
Picture DN
10 LF 150
15 LF 275
15 HF 1,135 003Z1222
20 HF 1,70 0 00 3Z1223
25HF 2,700 003Z1224
32 HF 4,000 003Z1225
Note: AB‑ QM DN 10‑32 acts as a normally ope n valve.
Q
10 275 003 Z1211 00 3Z1201
15 450 003 Z1212 00 3Z1202
20 900
25 1, 700
32 3,200
40 7,500 G 2A 003Z0770
50 12,500 G 2 ½A 003Z0771
nom.
(l/h)
Ext. thread
(ISO 228/1)
G ½A
G ¾A
G 1A
G 1 ¼A
G 1 ½A
Code No. AB‑QM
00 3Z1261
00 3Z1262
00 3Z1213
00 3Z1214
00 3Z1215
AB‑QM (D N 10‑32) can not be upgra ded to AB‑QM with test plugs!
AB‑QM industry pack (with test plugs and without test plugs)
Picture DN
10 LF 150
10 275 00 3Z1711 00 3Z1701
15 LF 275
15 450 003 Z1712 00 3Z1702
20 900 G 1A 00 3Z1713 G 1A 003Z1703
Q
nom.
(l/h)
Ext. thread
(ISO 228/1)
G ½A
G ¾A
Code No. AB‑QM
00 3Z1761
00 3Z1762
Ext. thread
(ISO 228/1)
G ½A
G ¾A
G 1A
G 1 ¼A
G 1 ½A
Ext. thread
(ISO 228/1)
G ½A
G ¾A
Code No.
00 3Z1251
00 3Z1252
003Z1203
00 3Z1204
003Z1205
Code No.
00 3Z1751
00 3Z1752
AB‑QM flanged version
Picture DN
50 12,500
65 20,000 003Z0773
65 HF 25,000 003Z0793
80 28,000 00 3Z0774
80 HF 40,000 003Z0794
100 38,000 0 03Z0775
100 H F 59,000 003Z0795
125 90,000 003Z0705
125 HF 110,000 003Z0 715
150 145,000 0 03Z0706
150 HF 190,000 0 03Z0716
200 200,000 003Z0707
200 HF 270,000 0 03Z 0717
250 300,000 003Z0708
250 HF 370,000 0 03Z0718
Q
(l/h)
nom.
Flange
connection
PN 16
Code No.
003Z0772
Set‑pack (one MSV-S and one AB-QM without test plugs)
Picture DN
15 LF 275
15 450 00 3Z1242
20 900 G 1 A 0 03Z124 3
25 1,70 0 G 1 ¼ A 003Z124 4
32 3,200 G 1 ½ A 003 Z1245
Q
(l/h)
nom.
Ext. thread
(ISO 228/1)
G ¾ A
Code No.
003Z1238
4 | © Danfoss | 2018.06
VD.A7.F7.02
Data sheet AB‑QM DN 10‑250
Ordering (continuous)
Accessories & spare parts
Typ e
Union connection (C W617N ) (1 pc s.)
Tailpiece welding (W. Nr. 1.0308) (1 pc s.)
Tailpiece welding - INOX (W. Nr. 1.4404) (1 pc s.)
Tailpieces for soldering (CW614N) (2 nuts, 2 gaskets, 2 soldering plugs
Shut-off & protection piece (max. closing pressure 16 bar) Shut-off - plastic (max. closing pressure 1 bar) 003Z0240
Handle AB-QM (necessar y accessory if installing valve without actuator)
Adapter for AB-QM DN 10, G ½ internal thread for AB- QM, G 3/8 internal thread (1 pcs.) Adapter for AB-QM DN 15, G ¾ internal thread for AB-QM, G ¾A ex ternal thread (1 pcs.) Adapter for AB-QM DN 20, G 1 internal thread for AB -QM, G 1A external thread (1 pcs.) Adapter for AB-QM DN 25, G 5/4 internal thread for AB-QM, G 5/4A external thread (1 pcs.) Adapter AMV(E) 25/35 (AB-QM DN 40-100, 2nd. generation) Adapter AME 435 for AB-QM DN 40-100 (1st. generation) Locking ring AB- QM DN10-32 (5 pcs.) Stroke limiter - TWA (5 pcs. in a bag) Adapter AME 13 SU for AB-QM (1st. generation) Adapter AME 13 SU for AB-QM (2nd. generation) Adapter for ABNM A5 Spacer AMI 140 Stem heater for AB-QM DN 40-100 / AME 15 QM Stem heater for AB-QM DN 40-100 / AME 435 QM Stem heater for AB-QM DN 125, 150 / AME 55 QM
To pipe To val ve
R / DN 10 003Z0231 R / D N 15 003Z0232 R / DN 20 003Z0233
R 1 DN 25 003Z0234
R 1 / DN 32 0 03Z0235
R 1/
R 2
Weld.
Weld.
12×1 mm DN 10
15×1 mm DN 15 06 5Z7017
Comments
Code No.
DN 40
DN 50 DN 15 003Z0226 DN 20 003Z0227 DN 25 003Z0228 DN 32 003Z0229
DN 40 DN 50
DN 15 DN 20 DN 25 DN 32 DN 40 DN 50
DN 10 -32
DN 40 -100 DN 125-15 0 DN 200 -250
003Z0279
003Z0278
003Z0270
003Z0276
00 3Z1271
00 3Z1272
003Z1273
00 3Z1274
00 3Z1275
00 3Z1276
065 Z7016
003Z1230
003Z0695
003Z0696
003Z0697
003Z3954
003Z3955
003Z3956
003Z3957
003Z0694
06 5Z0313
00 3Z1236
00 3Z1237
003Z3959
003Z3960
082 F1072
003Z0257
06 5B2171
065Z0 315
065Z7022
VD.A7.F7.02
Typ e
AB-QM heating insul. cap DN 10
AB-QM heating insul. cap DN 15 003Z4731
AB-QM heating insul. cap DN 20 003Z4732
AB-QM heating insul. cap DN 25 003Z4733
AB-QM heating insul. cap DN 32 003Z4734
AB-QM heating insul. cap DN 40 003Z4735
AB-QM heating insul. cap DN 50 003Z4736
Typ e Comments Code No.
Refrig. insulation ABQM DN 15_ABNM/T WA-Z DN 15 003Z4787
Refrig. insulation ABQM DN 20_ ABNM/TWA-Z DN 20 003Z478 8
Refrig. insulation ABQM DN 25_ ABNM/TWA-Z DN 25 003Z478 9
Refrig. insulation ABQM DN 32_ABNM/ TWA-Z DN 32 0 03Z4790
Typ e
Set of needle plug (1 pcs.)
Set of ext. plug (1 pcs.)
Set of measuring needle (1 pcs.)
Elbow test plug extension (1 pcs.)
Straight test plug extension (1 pcs.)
Straight plug extension set (1 pcs.)
Code No.
003Z4730
Code No.
003Z0100
003 Z0106
003 Z0107
003Z3944
003Z3945
003Z3946
© Danfoss | 2018.06 | 5
Data sheet AB‑QM DN 10‑250
Ordering (continuous)
Closing point (measure)
for DN 10‑32
Information regarding safety function is relevant only for AB‑QM valves.
1)
Size AB‑Q M: DN 10LF ‑ DN 20 ena bles setting to 120%; DN 25 ‑ 32 enable s setting up to 6 0%
2)
Requires 003Z3960 adapter
3)
Requires spacer 003Z0257
4)
Cable needs to b e ordered as separate cod e nr.
5)
Feedback signal over field bus
The code no. lis ted are for actuators with standard cable lengths when cables are included, others lengths are available referring to da ta sheet for actuators.
For Valve Sizes DN 10 ‑ 32
Typ e Note Power
NovoCon® S
NovoCon® S CO6, Ene rgy, I/O
AME 110 NL 24 VAC
AME 120 NL 24 VAC
AME 110 NLX 24 VAC
AME 13 SU
AME 13 SD
ABNM A5 NC LOG 5 mm stroke
ABNM A5 NC LOG 6.5 mm stroke
ABNM A5 DC NC LOG
ABNM A5 DC NO LOG
ABNM A5 NO LOG
ABNM A5 NC LIN 5 mm stroke
ABNM A5 NC LIN 6.5 mm stroke
ABNM A5 NO LIN 6.5 mm stroke
AMV 110 NL 24 VAC
10.4±0.3
AMV 120 NL 24 VAC
AMV 13 SU
AMV 13 SD
TWA-Z NC
TWA-Z NC
ABN A5 NC 5 mm stroke
ABN A5 NC
ABN A5 NO 5 mm stroke
TWA-Z NO
AMI 140
TWA-Z NC
TWA-Z NC
ABN A5 NC 5 mm stroke
ABN A5 NO 5 mm stroke
TWA-Z NO
AMI 140
BACnet & Modbus communication
BACnet & Modbus communication
2), 3)
3)
4)
6.5 mm stroke
6.5 mm stroke
6.5 mm stroke
4)
2), 3)
3)
1)
Halogen free
1)
cable
5 mm stroke, End-switch
1)
3)
1)
Halogen free cable
1)
3)
4)
4)
4)
1)
4)
4)
4)
4)
4)
4)
4)
4)
4)
4)
24 VAC /DC
24 VAC /DC
24 VAC
24 VAC
24 VAC
24 VAC
24 VDC
24 VDC
24 VAC
24 VAC
24 VAC
24 VAC
24 VAC
24 VAC
24 VAC /DC
24 VAC /DC
24 VAC /DC
24 VAC /DC
24 VAC /DC
24 VAC /DC
24 VAC
230 VAC
230 VAC
230 VAC
230 VAC
230 VAC
230 VAC
Input Signal
On/
Float. Modul. Up Down
Off
Output
Signal
5)
5)
Safety Function
Selectable
Selectable
Code No.
Selectable
003Z8504
Selectable 003Z8503
082H8057
082H8059
082H8060
082H3044
082G3006
08 2F116 0
08 2F116 2
08 2F116 6
08 2F1167
08 2F116 3
08 2F1161
08 2F116 4
08 2F116 5
082H8056
082H8058
082H3043
082G3004
08 2F1262
082F1380
08 2F115 0
082F1154
08 2F1151
08 2F1260
082H8048
08 2F1266
082F1382
08 2F1152
08 2F1153
08 2F1264
082H8049
* Adapter requ ired for 2nd gen valve. Part# 003Z0694 **Available batte ry backup assembly f or safety f unction, AM‑PBU25, 08 2H7090, one per four A ME 435 QM actuators
AB‑QM D N 65‑100 with AME 25 SD has limited flo w to 90% of Q Actuators f or valves DN 40‑100 are
nom
delivered without cables.
6 | © Danfoss | 2018.06
For Valve Sizes DN 40 ‑ 100
Typ e Power
AME 435 QM 24 VAC /DC
AMV 435 24 VAC /DC
AMV 435 230 VAC
AME 25 SU* 24 VAC
AME 25 SD* 24 VAC
AMV 25 SD* 24 VAC
AMV 25 SU* 24 VAC
AMV 25 SD* 230 VAC
AMV 25 SU* 23 0 VAC
Input Signal
On/Off Floating Modulating Up Down
Output Signal
(0 ‑10VD C)
Safety Function
•** •**
Code No.
08 2H017 1
082 H0162
082 H0163
082H3041
082H3038
082H3036
082H3039
082H3037
082H3040
VD.A7.F7.02
Loading...
+ 14 hidden pages