The AB-QM temperature control valve provides
pressure independent regulation of flow while
also providing flow limiting system balance. The
valve internally contains a unique differential
pressure regulator which automatically adjusts
to normal changes in system pressure from
valves opening and closing or changing of pump
speed. As a result of maintaining a constant
pressure for the temperature control valve, valve
authority is maintained at 100%. This allows
for precise interaction with the temperature
controller and unparalleled system operation
as indicated by assuring the highest possible
coil log mean temperature difference (∆T). The
valve is easily set and adjusted to provide the
precise flow required for each terminal unit.
Design calculation and commissioning effort
normally required for it's control and balance
valves are virtually eliminated because of the
built in automatic pressure control regulator. A
wide selection of actuators are available for the
AB-QM providing further control features for
the valve, making it an ideal selection for the
simplest of two position control strategies to the
precision required for modulating control and
variable speed pump optimization.
Features:
• AB-QM maintains a stable flow through its
range of operation unaffected by changes
in system differential pressure period. 100%
valve authority allows lower pump head
than traditional valves and reduces energy
consumption which increases ∆T
• Three required valve functions; temperature
control, balance and flow limitation in one
compact valve design
• Flow parameter is the only consideration,
reducing valve selection engineering
• Constant flow regulation limitation through
independent pressure balancing
• User adjustable flow setting for maximum
flow limitation
• Maintains linear characteristic of flow when
installed with a Danfoss proportional actuator.
Actuator options with equal percentage flow
characteristics.
Benefits:
• Flow will match the load
• Eliminate coil over flows
• Reduced installation time and materials
• Simple flow setting procedure; reduced time
involved for field commissioning
• Valve allows maximum coil and system
differential temperature drops for optimum
efficiency
• Operation costs reduced as much as 90 % or
more when properly applied with variable
speed pumping
• "Plug and Play" for quick setup for balancing
allowing immediate start up of unit
• Commissioning accomplished without use of
specialized equipment
• Compact design allows installations in areas
with limited space such as stand alone fan
coils
Data sheet Pressure Independent Control Valve AB‑QM,
½” thru 2”
2½” thru 4”
5” thru 10” Valve Size
Technical Data:
Nominal Diameter½” LF½” HF¾” HF1” HF1¼” H F1½” 2”
Max flow (GPM)1.257.51217.53355
Setting range
Diff. pressure (PSI)
1)
2), 3)
2.3-605-604.4-60
20 -100 %40 -100 %
Connection Male NPSM
Control valve
characteristic
Control valve
accuracy
Linear
± 5% of set point
Max. differential
pressure
90 psi (6.2 bar)
(across the valve)
Max. close off
pressure (regardless
232 psi (16 bar)250 psi (17.2 bar)
of actuator)
Medium
temperature
15 °F to 250 °F (−10 °C to 120 °C)
Allowable FluidWater and secondary refrigerant additives such as glycol
LeakageClass 4, metal to metal
Nominal Diameter 2 ½”3”4”5"6”8”10" 2 ½” HF 3” HF 4” HF 5" HF 6" H F 8" HF 10" H F
Max flow (GPM)85120165395 640 830 1,2351101762604858301,100 1,60 0
Setting range
Diff. pressure (PSI)
Connection ANSI Flange (ANSI Standard B16.1)
1)
2), 3)
4.4-608.7– 60
ISO Flange &
Gasket (ISO
Flange EN
1092-2)
40 -100 %
ANSI Flange (ANSI Standard B16.1)
ISO Flange &
Gasket (ISO
Flange EN
1092-2)
Connection ratingANSI Class 125
Control valve
characteristic
Control valve
accuracy
Linear
± 5% of set point
Max. differential
pressure
90 psi (6.2 bar)
(across the valve)
Max. close off
pressure (regardless
232 psi (16 bar)
of actuator)
Medium
temperature
15 °F to 250 °F (−10 °C to 120 °C)
Allowable FluidWater and secondary refrigerant additives such as glycol
LeakageClass 4, metal to metal
1)
Factory se tting of the valve is done at 100%.
2)
Regardless of t he flow limitations valve can mo dulate till 0.1% of the nomina l flow.
3)
∆p = (P1–P3) min~max
According suitabili ty and usage especiall y in not oxygen tight syste ms please mind the instructio ns given by the coolant produce r.
Available AB- QM valves with low minimum p in sizes ⁄” to 1⁄”.
Contact Danfoss f or further informati on.
Data sheet Pressure Independent Control Valve AB‑QM,
½” thru 2”
2½” thru 4”
5” thru 10” Valve Size
Application:
The AB-QM is a versatile device that can
be used as an actuated or non-actuated
balance valve / flow limiter. With an actuator
mounted to the AB-QM valve, the assembly is
a pressure independent control valve. Utilizing
a proportioning controller, the AB-QM creates
a robust and stable energy management sub
system using only the required flow and energy
to offset facility heat transfer gains and losses.
The integrated AB-QM differential pressure
regulator virtually eliminates the problem
of fluctuating pressures on control valve
performance. The AB-QM regulator immediately
reacts to all changes in system pressure creating
the stability to make the valve flow and control
predictable and controllers and valves work as
intended. Energy is saved taking advantage of
the greatly reduced amount of flow required
for heat transfer of full valve authority for an
air handling unit (AHU), fan coil, etc. With the
AB-QM the required design flow to the AHU is
met, subsequently simplifying the balancing
of the system. Air handling units react quickly
to changes in the building load and simple
proportional control will not accurately
regulate these systems. Using control integral
action to adjust for this requires skill and extra
commissioning to properly match the required
setting to the applications, sometimes over
several seasons of operation. The AB-QM
differential pressure regulator acts as an extra
sub-master controller and makes tuning the
main controllers easier and less time consuming.
Smaller building HVAC sub-systems such as
fan coil units, or terminal unit heating coils and
newer modern designs such as chilled beams
or radiant cooling panels greatly benefit from
AB-QM application even when applied with
simple thermostatic operation. No pressure
calculations are required, valve authority doesn't
need to be calculated and no calculations
have to be performed to pre-set a balancing
valve. If extra flow is determined to be required
while tuning the installation, it's easy for the
commissioning agent to reset the AB-QM for
any flow up to the rated range of the valve.
The HVAC units and controllers will benefit
from greatly enhanced ability to control, with
no overflow. AB-QM allows hydronic HVAC
systems to achieve the green and sustainable
performance envisioned by their designers and
owners. Owners benefit in significant reductions
in commissioning time, energy cost in operation
from reduced flow and reduced complaints
associated with improper temperatures within
the building.
Minimum Pressure Drop
To verify that an installation functions according
to the design specifications checking the critical
valve in the installation is needed . The critical
valve is the furthest valve away on the branch
or loop and has the lowest available differential
pressure. The AB-QM maintains a constant
differential pressure across temperature control
valve and any excess pressure will automatically
be throttled by the regulator. If there is not
enough differential pressure the valve cannot
reach the set flow. Therefore the critical valve
must have the minimum differential pressure for
the pressure regulator to properly operate, all
prior AB-QM valves will function properly.
Data sheet Pressure Independent Control Valve AB‑QM,
½” thru 2”
2½” thru 4”
5” thru 10” Valve Size
Function
Differential Pressure
Regulator
The AB-QM combines aspects of both a
differential pressure controller for balancing and
a temperature control into a single valve.
P1 Available Pressure
P2 Regulated inlet pressure to temperature
control valve
P3 Exit pressure of valve
Flow enters the valve through the differential
pressure regulator, which maintains a constant
pressure difference across the temperature
control valve orifice. As entering pressure
increases or decreases in reaction to changes
in flow and pump speed in the piping system,
the regulator diaphragm is balanced with the
force of the spring keeping a constant pressure
difference (P2-P3) between the water entering
the temperature control valve and the leaving
side of the valve. As a result the differential
pressure across the temperature control valve
(P2-P3) is at a constant level.
A nominal 5 psi differential is required from P1
to P3 for the valve and flow regulator operation.
The regulator controls the range of system
differential pressure to 60 psi (140 FOH). Under
normal system operation such as in variable
speed pumping, as system flow is reduced,
controlled pump speed reduces the system
differential pressure (head) of the pump. In
constant speed pumping applications reductions
in system flow may result in increased system
differential pressure (head) of the pump.