Danfoss ABNM A5 Data sheet

Data Sheet
Actuator ABNM A5 0-10 V Proportional
For Use with RA2000 Valves
Application
The ABNM A5 0-10V thermal actuator is designed for use with RA2000 Thermostatic Radiator Valves in heating and cooling applications.
Features include:
• Safety function of normally closed (NC) actuator during power failure
• Low power consumption 1W
• Removalable plug-in cable
• Simple snap-on installation
• Actuator orintation in any installation position
• First-Open function (NC versions)
• Compact size, small dimensions
• 24V AC power source
• Position indicator
• Noiseless and maintenance-free
Control is done by a 0-10 V signal, which is provided either by a 3rd party room thermostat or, in most cases, by a central direct digital control (DDC) system. The actuator converts the 0-10 VDC signal into a proportional actuator travel to the RA2000 or RA-C series of valves.
Suitable applications for the ABNM A5 actuator can include fan coil units, chilled ceiling applica­tions, radiant oor heating or radiator valves. It is not recommended that the ABNM A5 actuator be used on low pressure steam applications due to the increased temperature environment that the actuator is exposed to.
Ordering
Spare Parts
Typ e
ABNM A5, for RA2000
Mounting base adapter VA78
Cables Code no.
3 feet (1 meter) 082F1081 16 feet (5 meters) 082F1082 32 feet (10 meters) 082F1083
Supply
voltage
24 V AC 4 mm NC 0 - 10 VDC 082F1111
Stem
Travel
Description Code no.
Position during
power loss
Input
Signal
Code no.
VDSKA422 © Danfoss 03/2016
1
Data Sheet Actuator ABNM A5 for RA2000 Valves, 0-10 V Proportional
Function
Technical Specications
The actuator mechanism of the ABNM actuator uses a positive temperature coecient (PTC) resistor heated wax element and a compression spring. The wax element is heated by applying the operating voltage and moves the integrated piston. The force generated by this movement is transferred to valve spindle and thus opening or
Version NC “normally closed”
In case of the normally closed version, valve is closed when de-energized. Valve is opened steadily upon switching on the power supply, set­ting control signal to 10 V and after expiry of the
dead time. closing the valve. The actuator provides active regulation in a dened range (see characteristic curve between 0.5 V and 9.5 V). The function display (all-round display) of the ABNM shows at the rst glance whether the valve
Power
ON
is “open” or “closed”.
First open function
In its delivery condition ABNM is partly open due to the rst open function (lling). This enables
Function display for NC versions extends
proportionally with actuator opening from 0 mm
to 5-6 mm. heating/cooling operation during the construc-
tion phase even when the electric wiring is not yet complete. During the later electrical start-up, the rst open function is unlocked by applying the power supply for more than 6 minutes.
Operating voltage
24 V AC 50/60 Hz
(-10% to +20%) Max. inrush current < 300 mA for max. 2 min. Operating power 1 W
1)
Control voltage 0-10 V DC Input resistance 100 kΩ Actuator travel 4 mm Actuating linear force 100 N ± 5% Closing (NC) or opening (NO) time when de-energized 3-5 min. Travel speed 30 s/mm Calibration time (including First Open for NC) > 6min.
2)
2)
Delay when energizded (heat up time) 2-3 min. Fluid temperature 32 to 212°F (0 to 100° C)
2)
Storage temperature -13 to 149°F (-25 to 65°C) Ambient temperature 32 to 140°F (0 to 60° C) Suitable applications Hot or chilled water
3)
Degree/class of protection NEMA 3 (IP54
/III safety extra-Iow voltage) Connecting cable 3 x 0.22 mm², halogen free Mounting Adapter (included) VA 78 Weight 0.24 lb (111 g) Housing material Polyamid / white
1)
Measured with precision power meter LMG95.
2)
Measured at ambient temperature 68°F (20°C). Due to thermal working principle of ac tuator some parameters vary
with ambient temperature. At higher ambient temperatures actuator opening is faster and closing slower. At lower ambient temperatures actuator closing will be faster and opening slower.
2
VDSKA422 © Danfoss 03/2016
Data Sheet Actuator ABNM A5 for RA2000 Valves, 0-10 V Proportional
24 V AC/DC
L1 L2 0 - 10
100%
Flow (%)
0 1 2 3 4 5 6 7 8 9 10
U (V)
Characteristic Curves
Electrical Connections
80%
LIN versions
LOG versions
60%
40%
20%
0%
Control characteristics of LOG and LIN versions.
V DC
GND Blue
Transformer
Rule-of-the-thumb formula for dimensioning transformer: P
transformer
= 6 W x number of ABNM actuators
Red
Black
Calculation of max. cable length (copper cable):
L = K x A / n
A: Conductor cross-section in mm
2
n: Number of ABNM actuators K: Constant for copper (269 m/mm2) L: Cable length in m
VDSKA422 © Danfoss 03/2016
3
Data Sheet Actuator ABNM A5 for RA2000 Valves, 0-10 V Proportional
Installation
1) Full mount the adapter to the valve body.
2) Tighten the Allen screws on the adapter.
3) Align the actuator head to the adapter and push down.
4) There should be an audible to indicate the actuator is fully mounted to the adapter.
First Open Function
Fully push the cable plug into the actuator.
Presentation of First Open Function (Unlock NC version).
4
VDSKA422 © Danfoss 03/2016
Data Sheet Actuator ABNM A5 for RA2000 Valves, 0-10 V Proportional
61.5 mm 44.3 mm
51.1 mm 5 mm
Dimensions
53 mm
2.1 in (53mm)
0.3 in
(7mm)
2.0 in (51.1mm)
2.4 in (61.5mm)
1.7 in (44.3mm)
Danfoss can accept no responsibility for possible errors in printed materials and reser ves the right to alter its products without notice. All trademarks in this material are proper ty of the respective companies. Danfoss and Danfoss logotype are trademark s of Danfoss A/S. All rights reser ved.
Danfoss
Toronto, ON Tel.: 866-375-4822, Fax: 416-352-5981 www.na.heating.danfoss.com
VDSKA422 © Danfoss 03/2016