8000 Series Programmable &
Non-Programmable Thermostat s
for Heat/Cool Applications
The 8000 Series is available in heat/cool
versions for conventional heat cool systems with
up to 2 stages of heat and 2 stages of cool.
Versions are also available for heat pump
systems incorporating auxilliary heating
systems. The heat pump models which can
provide up to 3 stages of heat and 2 stages of
cool, also incorporate optional balance point
control which improves efficiency.
All models can be used either with the built-in
sensor, which is standard or with low cost remote
sensors which can be added at time of
installation.
For temperature averaging, up to four sensors
The 8000 Series of advanced heat/cool
thermostats provides sophisticated sequence
control of multi-stage heat/cool systems
including air to air heat pump systems with
auxilliary/emergency heat. All models are
available in programmable and nonprogrammable versions.
The products, which offer 7 day, 5/2 day or 24
hour programming incorporate advanced
programming features which are set up by the
installer at the time of installation. These
features allow a relatively small number of
products to fulfill a wide range of application
demands. This significantly reduces the number
of thermostats that either a wholesaler or
installer need to stock, it also significantly
reduces installation and programming difficulties
by offering a common architecture across the
whole range of models.
In addition to the advanced programming, the
product range also incorporates a service mode
which allows the installer to step through the
heat/cool sequence manually during
commissioning.
can be used in a series/parallel arrangement.
Full details of ordering codes, wiring and
thermostat specification and settings can be
found in the following pages.
●Available in battery, 24 & 230 volt
●Conventional heat /cool versions give
●Heat pump versions give up to 2
●Heat pump version provide both O & B
●Advanced programming allows
●Service mode simplifies
●Up to six time and temperature
●Large easy to read display
versions
up to 2 stages of cool and 2 stages of
heat
stages of cool and 3 of heat, including
emergency heat
reversing valve outputs
configuration to match application
demand
commissioning
changes each day
Installer SettingsHardware Settings
A number of DIL switches on the rear of the unit allow the installer to make some basic hardware settings. The diagram below details the selection options:
ProgrammableNon-Programmable
* unit must be programmed
before this switch is set to
disable
HC models*HP models*HCT models*HPT models*
1
Software Settings
The 8000 Series incorporates a wide range of installer configurable options which are selected
from within an advanced programming mode. A brief description of the options is listed below:
OptionDescriptionFactory settingOther options
1Temperature override timerNext event1,2,3 or 4 hours or disabled
2Fan run-on after cooling timerOff30, 60 or 90 Seconds
3Fan operating mode settingAllSmart fan (LOC)
4Heat / Cool dead-band setting2°C1,3 or 4°C
5Limit maximum heating set-point30°CCan be reduced to 6°C in
adjustment0.5°C steps
6Limit minimum cooling set-point16°CCan be increased to 40°C
adjustmentin 0.5°C steps
7Limit minimum heating set-point6°CCan be increased to 30°C
adjustmentin 0.5°C steps
8Limit maximum cooling set-point40°CCan be reduced to 16°C
adjustmentin 0.5°C steps
9Thermostat calibration0°C±1.5°C
HP8000 Heat-Pump Models Only
ACompressor delay timer2 min Off,2 min On/Off, 6 cycles
bThis option not used
CHeat-pump low cut-off adjustment-9°C-30°C to +15°C in
(Active only if outdoor sensor is1°C steps
detected)
dHeat-pump balance point10°C0°C to 21°C in
adjustment.1°C steps
(Active only if outdoor sensor
is detected)
HC8000 Heat/Cool Models Only
ACooling source type selectionCompressor, CP YESChilled water source
bThermostat cooling stage cycle6 cycles per hour3 cycles per hour
rate per hour setting. (Only
available if ”CP No” is selected
in A above)
CThermostat heating stage6 cycles per hour3 cycles per hour
cycle rate per hour setting.
dHeating stage integral action5%2.5% or 10%
time selection
All Models with Remote Room Sensor/Duct Sensor
6 cycles per hour4 min On/Off, 1 cycle per
hour selection or 4 min On/
Off, 3 cycles per hour
(Only active if a remote room orenableddisabled
duct sensor is detected)
Software version number - please interrogate unit in “Advanced Programming mode”
In addition to advanced programming settings, the thermostat also incorporates a service mode
which allows the installer to manually sequence the heat/cool and fan stages during system
commissioning.
Specification
Temperature rangeHeating, off 6-30oC, (43-86°F ), Cooling, 26-40oC (61-104°F), off
o
Thermal differential< 1
Dead zone options1-4
C (2°F)
o
C (2-10°F), selectable by installer
Programming options*All models can be set for 24hr, 5/2 or 7 day operation by
installer
Programmed events per day*2 or 6 selectable by installer, inc off events for both heat & cool
Vacation programming optionUp to 99 days, heat & cool set points can be set independently
Factory pre-set programmesYes, refer to user manual details
Control ouputPl algorythm with Chrono-proportional output with adjustable
cycle rate
Power supplyBattery powered2 x AA batteries
24V power supply20-30 Vac, 50/60 Hz
230V power supply220/250 Vac, 50/60 Hz
Memory retentionRechargeable battery for real time (48 hours whenfully
charged), non-volatile memory device for all other settings
Fan mode optionsAuto, On or Smart-Fan (fan on during day & Auto during night)
User mode selection
Heat/cool modelsHeat/Cool/Auto/Off and holiday and thermostat mode
Heat pump modelsHeat/Cool/Auto/Off plus emergency heat, holiday and
thermostat mode
Output relay voltage rating10-240 Vac
Output relay current rating2 (1) Amp per relay, min. 10mA
Output relay number & contact typeVaries according to model, refer to installation guide
Installer DIL switch settingsYes, refer to commissioning guide
Installer advanced programming
settingsYes, refer to commissioning guide
Installer service mode optionYes, refer to commissioning guide
Compressor delay timerYes , all compressor stages, adjustable
Reversing valve control, HP modelsYes, selectable “O” or “B” function with SPDT output controls
Heat pump balance point controlYes, programmable high and low balance points (outdoor
sensor required)
Lockable keypadElectronic keypad lock, plus mechanical locking catch on cover
flap
Limitation of high and low set points Both heat and cool ranges can be limited or locked
Limitations of temperature overrideCan be limited to +/- 2oC (3°F) or disabled
Temperature OverrideCan be limited to “next event”, 1, 2, 3, or 4 hrs disables
Max ambient temperature45oC (113°F)
Dimensions (mm)137 wide x 117 high x 25 deep