Datasheet
6000 Series
Programmable Heat/Cool Thermostats
Features
The 6000 Series of heat/cool thermostats provide
cost e ective control of heating, cooling and heat/
cool systems.
This range of programmable heat/cool thermostats
is available in battery and 230 volt versions and
comprises of three basic model families.
HCW Models
This model, which is designed for use in hydronic
2-pipe change-over systems, operates as a
heating thermostat in the winter and a cooling
thermostat in the summer. Change-over between
heating and cooling is initiated by means of a
water temperature sensor which measures the
temperature of water owing in the distribution
pipe-work. This model o ers 3 speed fan output.
HCM Models
This models is as per the HCW model but without
pipe sensor. Changeover is manually initiated.
HC Models
This model is designed for use in 4-pipe fan coil
systems or in forced air systems and provides
sequence control of one stage of heat and one
stage of cool. Dual set point adjustments ensure
that heat and cool temperatures can be set for
maximum e ciency.
All models are available with 3 speed fan output.
All models:
• Available in battery and 230 volt version.
• Models for heat or cool, selectable at time of
installation.
• Models for 2-pipe change over systems.
• Models for 4-pipe non-changeover systems
and split units.
• Large, easy to read LCD display.
• Simple to use 5/2 day programming.
• Up to 4 time and temperature events each day,
including o option.
Installer Settings A number of DIL switches on the rear of the thermostat allow the installer to make basic hardware
HCM Model
On/O
Not Used
Not Used
4 events
each day
con gurations. The drawing below details the options.
HCW Model HC Model
Chronoproportional
Not Used
Not Used
2 events
each day
Part No. 042 Issue 06 10/07
On/O
Not Used
Pipe Sensor
Fitted
4 events
each day
Chronoproportional
Not Used
Pipe Sensor
Not Fitted
2 events
each day
On/O
Compressor
Delay On
Not Used
4 events
each day
Chronoproportional
Compressor
Delay O
Not Used
2 events
each day
1
Datasheet
HC6000 Programmable Heat/Cool Thermostats
Software Settings The 6000 Series incorporates a selected range of advanced programming options which the installer
can set at the time of commissioning. Please refer to the table below for details.
Option Description Models Factory Setting Installer Options
1 Keyboard disable All Keyboard enabled Keyboard disabled
Compressor delay timer.
Speci cation
2
Active only if enabled on DIP switch
3 Fan run-on after cooling timer All O 30, 60 or 90 seconds
4 Heat/Cool dead band setting All 2°C 1, 2, 3 or 4°C
5 Thermometer calibration o set All 0 + or - 3°C
Power supply Battery Powered Models:
Temperature Range Heating stage - 5-30°C and O , Cooling stage - 16-37°C and O
Temperature Accuracy ± 0.5°C
Deadzone Adjustment 1, 2, 3 or 4°C
Changeover temperature for HCW water sensor
changeover models
Voltage Rating of Contacts 20-250 Vac, 50/60 Hz
Current Rating of Contacts 10mA - 3 A resistive, 1A inductive
Switching Action Voltage Free SPDT contacts, Type 1B
Time Accuracy ± 1 minute
Memory Retention 230V models: 15 days,
IP Rating IP30
Dimensions (mm) 130 x 100 x 37 (W x H x D)
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5 kV
Ball Pressure Test 75°C
230 Volt Powered Models:
All 2 minutes 3, 4 or 5 minutes
2 x AA alkaline batteries
195-265 Vac, 50/60Hz
Heat - Cool 16°C
Cool - Heat 30°C
Battery model: 1 minute for battery change
Ordering Details
Thermostat Function
1 heat or 1 cool with manual changeover from heat to cool.
(3 speed fan)
1 heat or 1 cool with water temperature changeover from heat
to cool. Pipe sensor included (3 speed fan)
1 heat or 1 cool with auto changeover from heat to cool
(3 speed fan) (Built-in Sensor)
1 heat or 1 cool with auto changeover from heat to cool
(3 speed fan) (Remote Sensor)
Battery Powered Models 230V Powered Models
Type Code No. Type Code No.
HCM6110-3 087N706000 HCM6113-3 087N705600
HCW6110-3 087N706100 HCW6113-3 087N706600
HC6110-3 087N705300 HC6113-3 087N705700
HC6110A-3 087N710300 HC6113A-3 087N710100
2