Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed
material. All trademarks in this material are property of the respective companies. Danfoss and the
Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Installation Instructions
Please Note:
This product should only be installed by a quali ed
electrician or competent heating installer, and should be
in accordance with the current edition of the IEEE wiring
regulations.
Product speci cation
Speci cation
Power supply230 Vac ± 15%, 50 Hz
Switching action 1 x SPST, Type 1B
Switch rating264 Vac, 50/60Hz, 3(1)A
Timing Accuracy±1 min./month
Power ReserveMinimum 14 days
Enclosure RatingIP30
Max. Ambient Temperature45°C
Dimensions, mm (W, H, D) 102 x 136 x 47
Speci cation
Design standardEN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test75°C
3
Installation
NB. For FRU units - go straight to point 6.
1. Loosen the xing screw in the base of the unit to release the
Wiring Cover.
2. Holding the unit face downwards, press rmly in the
centre of the wallplate and slide it apart and lift it from the
module.
3. Fix the wallplate and terminal block to the wall, or plaster
box, as required. Ensure that the screw heads do not
protrude beyond the vertical centre rib of the wallplate,
Installation
or this will prevent the module correctly locating onto the
wallplate.
Screw xing holes
(screwheads MUST
NOT protrude above
centre rib)
Vertical centre rib
4
Wallplate & Terminals
4. Surface cables can only enter from below the unit. Cut
an appropriate cable aperture in the wiring cover. If the
wallplate is mounted on a plaster box, cables can enter
from the rear below the terminal block.
5. Electrical connections are simpli ed by using a Wiring
Centre. However, if this is not used, the wallplate terminal
identi cation is as shown.
LOAD
ONSPARECOMNL
123 5 6
Mains Supply
(via 3 amp. fuse)
If the system being controlled is 230 Vac then terminals
3 and L must be linked with insulated cable capable of
carrying full load current. Whilst the unit does not require
an earth connection, a terminal is provided on the wallplate
for earth continuity purposes.
6. Referring to the wiring diagrams on page 6-9, connect the
unit as shown.
7. Find out from the user whether the unit is required to
operate in 24-hour mode (factory preset) or weekday/
weekend mode (5/2 day). To convert to 5/2 day mode
remove the small two-way connector from the pins towards
the left of the recess on the rear of the module, then press
the SELECT/ADVANCE/+/- buttons all at the same time to
RESET the unit.
8. Ensure all dust and debris are cleared from the area. Plug
the module into the wallplate by locating it onto the
wallplate and, when ush with it, sliding it down, ensure
the hook at the top of the wallplate engages with the slot
at the back of the module.
Installation
9. Before setting the programme, check the unit and circuit.
Press the SELECT button until the bar in the display lines up
with the word ON. Adjust the remote thermostats to check
the system operates correctly.
5
10. Then press the SELECT button until the bar lines up with
the word OFF and check the system does not operate.
11. When the circuit check has been completed, replace the
wiring cover and tighten the xing screw. Cut any cable
aperture in the wiring cover which may be necessary to
accommodate surface mounted cables.
12. Finally set time of day and programmes required, noting
that the unit is supplied with a pre-set programme, as
stated on Page 14.
Wiring
Wiring
6
103, 103E5
Typical Gravity DHW with pumped heating
COM
L N
1
ROOM
' STAT
23
LINK
CALL
N
BOILER
TERMINALS
56
L N
103E5
TERMINALS
L
MAINS
SUPPLY
N
FUSED
3 AMP
PUMP
TERMINALS
Typical control of Pump for Central Heating on a Solid
Fuel System
3
LINK
5
6
103E5
TERMINALS
L
MAINS
SUPPLY
N
FUSED
3 AMP
COM
1
ROOM
' STAT
2
CALL
N
Wiring
L N
PUMP
TERMINALS
7
Typical Heating Only system, Boiler and Pump
control
1
COM
L N
ROOM
' STAT
23
LINK
CALL
N
BOILER
TERMINALS
56
L N
103E5
TERMINALS
L
MAINS
SUPPLY
N
FUSED
3 AMP
PUMP
TERMINALS
Typical control of Low Voltage System requiring
voltage free contacts
1
2
3
56
103E5
TERMINALS
Wiring
COM
LOW
VOLTAGE
ROOM
' STAT
CALL
L
N
MAINS
SUPPLY
FUSED
3 AMP
8
LOAD
LOW
VOLTAGE
SUPPLY
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.