Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed
material. All trademarks in this material are property of the respective companies. Danfoss and the
Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Installation Instructions
Please Note:
This product should only be installed by a quali ed
electrician or competent heating installer, and should be
in accordance with the current edition of the IEEE wiring
regulations.
Product speci cation
Speci cation
Power supply230 Vac ± 15%, 50 Hz
Switching action 1 x SPST, Type 1B
Switch rating264 Vac, 50/60Hz, 3(1)A
Timing Accuracy±1 min./month
Power ReserveMinimum 14 days
Enclosure RatingIP30
Max. Ambient Temperature45°C
Dimensions, mm (W, H, D) 102 x 136 x 47
Speci cation
Design standardEN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test75°C
3
Installation
NB. For FRU units - go straight to point 6.
1. Loosen the xing screw in the base of the unit to release the
Wiring Cover.
2. Holding the unit face downwards, press rmly in the
centre of the wallplate and slide it apart and lift it from the
module.
3. Fix the wallplate and terminal block to the wall, or plaster
box, as required. Ensure that the screw heads do not
protrude beyond the vertical centre rib of the wallplate,
Installation
or this will prevent the module correctly locating onto the
wallplate.
Screw xing holes
(screwheads MUST
NOT protrude above
centre rib)
Vertical centre rib
4
Wallplate & Terminals
4. Surface cables can only enter from below the unit. Cut
an appropriate cable aperture in the wiring cover. If the
wallplate is mounted on a plaster box, cables can enter
from the rear below the terminal block.
5. Electrical connections are simpli ed by using a Wiring
Centre. However, if this is not used, the wallplate terminal
identi cation is as shown.
LOAD
ONSPARECOMNL
123 5 6
Mains Supply
(via 3 amp. fuse)
If the system being controlled is 230 Vac then terminals
3 and L must be linked with insulated cable capable of
carrying full load current. Whilst the unit does not require
an earth connection, a terminal is provided on the wallplate
for earth continuity purposes.
6. Referring to the wiring diagrams on page 6-9, connect the
unit as shown.
7. Find out from the user whether the unit is required to
operate in 24-hour mode (factory preset) or weekday/
weekend mode (5/2 day). To convert to 5/2 day mode
remove the small two-way connector from the pins towards
the left of the recess on the rear of the module, then press
the SELECT/ADVANCE/+/- buttons all at the same time to
RESET the unit.
8. Ensure all dust and debris are cleared from the area. Plug
the module into the wallplate by locating it onto the
wallplate and, when ush with it, sliding it down, ensure
the hook at the top of the wallplate engages with the slot
at the back of the module.
Installation
9. Before setting the programme, check the unit and circuit.
Press the SELECT button until the bar in the display lines up
with the word ON. Adjust the remote thermostats to check
the system operates correctly.
5
10. Then press the SELECT button until the bar lines up with
the word OFF and check the system does not operate.
11. When the circuit check has been completed, replace the
wiring cover and tighten the xing screw. Cut any cable
aperture in the wiring cover which may be necessary to
accommodate surface mounted cables.
12. Finally set time of day and programmes required, noting
that the unit is supplied with a pre-set programme, as
stated on Page 14.
Wiring
Wiring
6
103, 103E5
Typical Gravity DHW with pumped heating
COM
L N
1
ROOM
' STAT
23
LINK
CALL
N
BOILER
TERMINALS
56
L N
103E5
TERMINALS
L
MAINS
SUPPLY
N
FUSED
3 AMP
PUMP
TERMINALS
Typical control of Pump for Central Heating on a Solid
Fuel System
3
LINK
5
6
103E5
TERMINALS
L
MAINS
SUPPLY
N
FUSED
3 AMP
COM
1
ROOM
' STAT
2
CALL
N
Wiring
L N
PUMP
TERMINALS
7
Typical Heating Only system, Boiler and Pump
control
1
COM
L N
ROOM
' STAT
23
LINK
CALL
N
BOILER
TERMINALS
56
L N
103E5
TERMINALS
L
MAINS
SUPPLY
N
FUSED
3 AMP
PUMP
TERMINALS
Typical control of Low Voltage System requiring
voltage free contacts
1
2
3
56
103E5
TERMINALS
Wiring
COM
LOW
VOLTAGE
ROOM
' STAT
CALL
L
N
MAINS
SUPPLY
FUSED
3 AMP
8
LOAD
LOW
VOLTAGE
SUPPLY
Typical control of Heating when provided by
Combination type Boiler
COM
1
ROOM
' STAT
23
CALL
N
INPUT
OUTPUT
56
103E5
TERMINALS
NL
COMBI BOILER
TERMINALS
L
N
MAINS
SUPPLY
FUSED
3 AMP
Typical Heating & Hot Water control system using 3 port
mid-position valve
ROOM
' STAT
WHITE
OR
BROWN
1
BLUE
23
CYL.
' STAT
N
SAT
GREY
LINK
COM
CALL
RED OR
ORANGE
56
103E5
TERMINALS
BOILER &
PUMP
TERMINALS
L
N
MAINS
SUPPLY
FUSED
3 AMP
Wiring
MID-POSITION VALVE
L N
9
should be terminated
required where these discon-
An additional terminal block is
nected leads (or pairs of leads)
MAINS SUPPLY
(via 3 amp fuse)
MO-
TOR
N
SWITCH
LIVE
LIVE
10
LOAD
Replacement
ONSPARECOM
DANFOSS RANDALL
103E5
1235 (N)6 (L)ABCD
RANDALL 103, 103E, 103E712356
RANDALL 302042-1,7635
RANDALL TSR245-31,267
GRASSLIN 45, 45A, 45E4-321
423NL,15
HORSTMANN 424 EMERALD
& PEARL AUTO RANGE
413NL256
LOAD--NL
HORSTMANN 423 PEARL,
EMERALD & TOPAZ
SANGAMO S254 Form 2S408
LOAD-
SANGAMO S409 Form 82163,N5,L
Form 5, S251 Form 2
SANGAMO S610 F2, S611 F2,
S612 F2, S408 F4, S408 F6,
S253 F2, S255 F2
SANGAMO/RANDALL SET 1425NL
SMITHS IND. MKI, MKIIP3P1P2NL
4,53-126
SMITHS IND.
CENTROLLER 30
4,53-12
SMITHS IND.
CENTROLLER 40
73421891011
LOAD-LINENL
SWITCHMASTER 300124NL3
TOWERCHRON TC
VENNER
VENNERETTE MKIIA
1-423
VENNER
VENNERETTE MKIVA
VENNER VENNERON VEN-
4-132
NERON P
Replacement
11
The text below has been edited and approved by the Plain
English Campaign, who has issued a Crystal Mark to be
displayed with it.
What is a programmer?
... an explanation for householders.
Programmers allow you to set ‘On’ and ‘O ’ time periods.
Some models switch the central heating and domestic hot
water on and o at the same time, while others allow the
domestic hot water and heating to come on and go o at
di erent times.
Set the ‘On’ and ‘O ’ time periods to suit your own lifestyle.
On some programmers you must also set whether you want
the heating and hot water to run continuously, run under the
chosen ‘On’ and ‘O ’ heating periods, or be permanently o .
The time on the programmer must be correct. Some types
have to be adjusted in spring and autumn at the changes
What is a programmer?
between Greenwich Mean Time and British Summer Time.
You may be able to temporarily adjust the heating
programme, for example, ‘Override’, ‘Advance’ or ‘Boost’. These
are explained in the manufacturer’s instructions.
The heating will not work if the room thermostat has switched
the heating o . And, if you have a hot-water cylinder, the
water heating will not work if the cylinder thermostat detects
that the hot water has reached the correct temperature.
Please note: A timeswitch is a single channel programmer. It will
allow you to set your system’s On and O periods.
12
User Instructions
Your timeswitch
Your 103E5 timeswitch controls your hot water and heating
together, turning them on and o at the same times
.
The 103E5 can provide 3 ON periods and 3 OFF periods each day
and can o er either 24 hour control (same programme for each
day of the week) or 5/2 day control (one set of programmes for
weekdays and a di erent set for weekends)
-
+
PROGRAMME
Overview
13
Before you start
Open the ap on the front of
the unit.
Press all four buttons
(SELECT / ADVANCE / + / -) at the same time
This will reset the unit, reinstate the
preset programmes and set the time to
12:00pm on Monday.
-
+
PROGRAMME
Setting the clock
Press PROGRAMME once
Use + and – buttons to set the
correct time
When time is correct press
PROGRAMME again.
Setting the time & the programme
In 24 hour mode this will take you
straight to programming mode,
where you can select your own ON
-
+
+
PROGRAMME
-
PROGRAMME
14
and OFF times.
In 5/2 day mode this will rst allow you to programme the
correct DAY. To do this:
use the + or – buttons to select the correct day
press PROGRAMME again to enter RUN mode
Factory Presets
The unit is supplied with the following preset programme
which will be active after the unit has been reset.
Mon-Fri or All
days in 24hr mode
1st ON6.30am7.30am
1st OFF8.30am10.00am
2nd ON12.00pm12.00pm
2nd OFF12.00pm12.00pm
3rd ON5.00pm5.00pm
3rd OFF10.30pm10.30pm
N.B. 2nd ON and 2nd OFF are set to the same time. These 2
(5/2day mode only*)
Sat-Sun*
times are ignored by the programme therefore the heating will
just come on once in the morning and once in the evening. If
you want the heating to come on in the middle of the day set
the 2nd ON and 2nd OFF to the times you require.
Accepting the preset times
If you are happy to use the settings above, you don’t need to
do anything else.
To accept the presets press the PROGRAMME button until the
colon in the display begins to ash.
Factory preset programmes
Your unit is now in RUN mode.
15
Programming event times in 24 hour mode
You can programme your timeswitch to come on and go o up to
3 times each day, to suit your requirements.
Press PROGRAMME until 1 (Event
1
1) shows along the top of the
display.
Use the + and - buttons to set the
time you want your system to rst
come on in the morning
Press PROGRAMME again to move to the next step (Event
2)
Use the + and - buttons to set the time you want your
system to rst go o .
Continue using the PROGRAMME and +/- buttons in this
way to set the ON/OFF times for events 3-6 (2nd ON/OFF
& 3rd ON/OFF).
N.B. It is not possible to programme times out of sequence.
If you do not press a button at all for 3 or 4 minutes the unit
will automatically return to RUN mode.
Programming the unit - 24 hour mode
16
Programming event times in 5/2 day mode
You can programme your timeswitch to come on and go of up
to 3 times each day, to suit your requirements, with one set of
programmes for weekdays and a di erent set of programmes for
the weekend.
Weekdays (MOTUWETHFR)
Press PROGRAMME until 1 (Event 1)
1
shows along the top of the display
and MOTUWETHFR shows along
the bottom.
Use the + and - buttons to set the time you want your
system to rst come on in the morning.
Press PROGRAMME again to move to Event 2
Use the + and - buttons to set the time you want your
system to rst go o .
Continue using the PROGRAMME and +/- buttons in this
way to set the ON/OFF times for events 3-6 for weekdays.
Weekend (SASU)
Press PROGRAMME again until 1
(Event 1) shows along the top of the
display and SASU shows along the
bottom of the display.
Use the PROGRAMME and +/- buttons to set the ON/
OFF times for the weekend.
If at any time you wish to return to the factory preset
programme, press SELECT / ADVANCE / + / - buttons together
at the same time to reset the unit.
N.B. It is not possible to programme times out of sequence.
Programming the unit - 5/2 day mode
17
Running your programme
ON
y
O
n
AUTO
s
The 103E5 controls your hot water and heating together, turning
them on and o at the same times.
To run the central heating and hot water programme press the
SELECT button.
As you press SELECT a bar on the display will move between
ON, OFF, ALLDAY and AUTO
OFF = the hot water/heating will not come on
AUTO = the hot water/heating will come on and
ALLDAY = the unit will come on at the rst
RUN mode
ON = the hot water/heating will remain on
= the hot water/heating will remain on
constantly
constantl
FF = the hot water/heating will not come o
= the hot water/heating will come on and
o o according to the programmed time
go o according to the programmed times
LLDAY = the unit will come on at the rst
programmed ON and will remain on until the last
programmed ON and will remain on until the last
programmed OFF
programmed OFF
18
Select the option you require, depending on your
circumstances, time of year, etc.
Temporary User Overrides
Sometimes you may need to change the way you use your
timeswitch temporarily, i.e due to unusually cold weather. The
103E5 has two convenient overrides which can be selected
without a ecting the set programme.
Override
buttons
+1HOUR
Press +1HOUR once if you need an extra hour of
operation
If the system is o it will come on for an hour. If it is already
on it will add an extra hour so the system stays on for an
extra hour.
To cancel the override press +1HOUR again.
ADVANCE (only during AUTO mode)
Press the ADVANCE button once to advance to the next
programmed event.
Override buttons
If the system is on it will go o . If it is o it will come on. The
set programme will resume at the next programmed ON/
OFF time.
To cancel the override press ADVANCE again.
19
Battery backup
In the event of a power cut, the built-in lithium battery will
keep your time and programme settings for up to 15 days.
After 15 days without mains power the unit will switch o
and two dots will show in the display. However all your
programmed on/o times will be remembered.
When the mains power is restored, the unit will need to be
reactivated by pressing the PROGRAMME button, and the
time and day will need to be set (see page 14).
Battery backup
20
212223
Still having problems?
Call your local heating engineer:
Name:
Tel:
For problems relating to your heating controls ...