For a large print version of these instructions
please call Marketing on 01234 364 621.
®
Certification Mark
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed
material. All trademarks in this material are property of the respective companies. Danfoss and the
Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2
Installation Instructions
Please Note:
This product should only be installed by a qualifi ed
electrician or competent heating installer, and
should be in accordance with the current edition of
the IEEE wiring regulations.
Product specifi cation
Specifi cation
Power supply230 ± 15% Vac, 50 Hz
Switching action 1 x SPST, Type 1B
Switch rating264 Vac, 50/60Hz, 3(1)A
Timing Accuracy±1 min./month
Power ReserveMinimum 14 days
Enclosure RatingIP30
Max. Ambient Temperature45°C
Dimensions, mm (W, H, D) 103 x 137 x 48
Specifi cation
Design standardEN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test75°C
3
Installation
NB. For FRU units - go straight to point 6 below.
1. Loosen the fi xing screw in the base of the unit to release
the Wiring Cover.
2. Holding the unit face downwards, press fi rmly in the
centre of the wallplate and slide it apart and lift it from
the module.
3. Fix the wallplate and terminal block to the wall, or
plaster box, as required. Ensure that the screw heads
do not protrude beyond the vertical centre rib of the
wallplate, or this will prevent the module correctly
locating onto the wallplate.
Screw fi xing holes
(screwheads MUST
NOT protrude
above centre rib)
Installation
Vertical centre rib
4
Wallplate & Terminals
4. Surface cables can only enter from below the unit. Cut
an appropriate cable aperture in the wiring cover. If the
wallplate is mounted on a plaster box, cables can enter
from the rear below the terminal block.
5. Electrical connections are simplifi ed by using a Wiring
Centre. However, if this is not used, the wallplate
terminal identifi cation is as shown.
WaterHeating
ONON
123 56
COM
Mains Supply
(via 3 amp fuse)
NL
If the system being controlled is 230Vac then terminals
3 and L must be linked with insulated cable capable
of carrying full load current. Whilst the unit does not
require an earth connection, a terminal is provided on
the wallplate for earth continuity purposes.
6. Referring to the wiring diagrams on page 6-9, connect
the unit as shown.
7. Find out from the user whether the unit is required
to operate in 24-hour mode (factory preset) or
weekday/weekend mode (5/2 day). To convert to 5/2
day mode remove the small two-way connector from
the pins towards the left of the recess on the rear of
the module, then press the SELECT/ADVANCE/+/-
buttons all at the same time to RESET the unit.
8. Ensure all dust and debris are cleared from the area.
Plug the module into the wallplate by locating it onto
the wallplate and, when fl ush with it, sliding it down,
ensure the hook at the top of the wallplate engages
with the slot at the back of the module.
Installation
9. Before setting the programme, check the unit and circuit.
Set the rocker switch to WATER & HEATING. Press the SELECT button until the bar in the display lines up with
the word ON. Adjust the remote thermostats to check the
system operates correctly.
5
10. Then press the SELECT button until the bar lines up
with the word OFF and check the system does not
operate.
11. Set the rocker switch to WATER ONLY. Press the SELECT button until the bar in the display lines up
with the word ON and check that the water circuit only
operates.
12. When the circuit check has been completed, replace
the wiring cover and tighten the fi xing screw. Cut
any cable aperture in the wiring cover which may be
necessary to accommodate surface mounted cables.
13. Finally set time of day and programmes required,
Wiring
Wiring
noting that the unit is supplied with a pre-set
programme, as stated on Page 14.
6
2, 102E5, 102E7
Typical Gravity DHW with Pumped Heating
1
COM
CALL
L N
2
3
LINK
ROOM
' STAT
N
BOILER
TERMINALS
5
L N
6
102E5
TERMINALS
L
MAINS
N
PUMP
TERMINALS
SUPPLY
FUSED
3 AMP
Typical domestic gas or oil-fi red central heating system
with gravity hot water and pumped heating. (If a room
thermostat is not used, wire pump live directly to terminal 2
of the 102E5).
Wiring
7
Typical Heating and Hot Water control system using
3-port mid-position valve
ROOM
' STAT
CALL
WHITE
OR
BROWN
N
2
CYL.
' STAT
SAT
GREY
3
LINK
1
COM
BLUE
MID-POSITION VALVE
COM
CALL
RED OR
ORANGE
5
L N
6
102E5
TERMINALS
L
N
BOILER &
PUMP
TERMINALS
MAINS
SUPPLY
FUSED
3 AMP
Wiring
8
The above control system is available as the Danfoss
Randall 102E5 HEATSHARE pack, which also includes
the TW room thermostat, AT cylinder thermostat, HS3 midposition valve and a WB12 wiring box.
Typical Heating and Hot Water control system using
2-port zone valves
CALL
D.H.W
VALVE
1
COM
CYL.
' STAT
SAT
2
COM
N
N
3
LINK
ROOM
' STAT
CALL
HEATING
VALVE
N
L N
5
6
102E5
TERMINALS
L
MAINS
N
BOILER &
PUMP
TERMINALS
SUPPLY
FUSED
3 AMP
The above control system is available as the Danfoss
Randall 102E5 HEATPLAN pack, which also includes the
TW room thermostat, AT cylinder thermostat, two 22mm
HPP zone valves and a WB12 wiring box.
Wiring
9
should be terminated
required where these discon-
An additional terminal block is
nected leads (or pairs of leads)
MAINS SUPPLY
(via 3 amp fuse)
COM
-2,314,756
Replacement
10
Heating
DANFOSS RANDALL
102E5Water
ON
ON
1235 (N)6 (L)ABC
12356
RANDALL 102, 102E,
102E7
RANDALL 3020P, 306042-1,7635
(8)
Air ‘Stat
(8)
Boiler
RANDALL MKII R645-31,267
HORSTMANN
CORAL 423 & 424
24-NL,1,356
HORSTMANN
DIAMOND 423
24-NL,1,356
HORSTMANN
DIAMOND 424
25-N,1,3L4,6
POTTERTON 42324-NL,1,356
SANGAMO S409 F1
& F4
1,34-N,2L
SANGAMO (Early
model) S410 Form 4
Replacement
32 -NL1 4
SMITHS IND.
CENTROLLER 100
54 -123
SMITHS IND.
CENTROLLER 60
SMITHS IND.
32-NL1,4
CENTROLLER 10
54 -123 6
SMITHS IND.
CENTROLLER 70
31-N4,L2
SWITCHMASTER
320, 350
SWITCHMASTER 60031-NL24
2A/S-N,1,3LA/S,5
VENNER VENOTROLVS,F-N,A,ML,L1T,P0
VENNER VENOTROL
80 (Air ‘Stat)
25-N,1,3L
VENNER VENOTROL
80 (Air ‘Stat Linked)
11
User Instructions
Your programmer
Your 102E5 mini-programmer allows you to switch your
heating and hot water on and off at times that suit you.
The 102E5 can provide 3 ON periods and 3 OFF periods
each day and can offer either 24 hour control (same
programme for each day of the week) or 5/2 day control
(one set of programmes for weekdays and a different set
for weekends).
Overview
12
-
+
PROGRAMME
Before you start
Open the fl ap on the front of
the unit.
Press all four buttons
(SELECT / ADVANCE / + / -) at the same time
This will reset the unit, reinstate
the preset programmes and set
the time to 12:00pm on Monday.
-
+
PROGRAMME
Setting the clock
Press PROGRAMME once
Use + and – buttons to set the
correct time (press and hold to
change in 10 min increments).
When time is correct press
PROGRAMME again.
In 24 hour mode this will take you
straight to programming mode,
where you can select your own ON
and OFF times.
-
+
+
PROGRAMME
-
PROGRAMME
Setting the time & the programme
In 5/2 day mode this fi rst will allow you to programme the
correct DAY. To do this:
use the + or – buttons to select the correct day
press PROGRAMME again to enter programming
mode
13
Factory Presets
The unit is supplied with the following preset programme
which will be active after the unit has been reset.
Mon-Fri or All
days in 24hr mode
1st ON6.30am7.30am
1st OFF8.30am10.00am
2nd ON12.00pm12.00pm
2nd OFF12.00pm12.00pm
3rd ON5.00pm5.00pm
3rd OFF10.30pm10.30pm
NB. 2nd ON and 2nd OFF are set to the same time.
(5/2day mode only*)
Sat-Sun*
These 2 times are ignored by the programme therefore
the heating will just come on once in the morning and
once in the evening. If you want the heating to come on
in the middle of the day set the 2nd ON and 2nd OFF to
the times you require.
Factory preset programmes
Accepting the preset times
If you are happy to use the settings above, you don’t
need to do anything else.
To accept the presets press the PROGRAMME button
until the colon in the display begins to fl ash.
14
Your unit is now in RUN mode.
Programming event times in 24 hour
mode
You can programme your heating and hot water to
come on and go off up to 3 times each day, to suit your
requirements.
Press PROGRAMME until 1
1
(Event 1) shows along the top
of the display.
Use the + and - buttons to set
the time you want your system
to fi rst come on in the morning
Press PROGRAMME again to move to the next step
(Event 2)
Use the + and - buttons to set the time you want your
system to fi rst go off.
Continue using the PROGRAMME and +/- buttons
in this way to set the ON/OFF times for events 3-6
(2nd ON/OFF & 3rd ON/OFF).
NB. It is not possible to programme times out of
sequence.
If you do not press a button at all for 3 or 4 minutes the
unit will automatically return to RUN mode.
Programming the unit - 24 hour mode
15
Programming event times in 5/2 day
mode
You can programme your heating and hot water to come on
and go of up to 3 times each day, to suit your requirements,
with one set of programmes for weekdays and a different
set of programmes for the weekend.
Weekdays (MOTUWETHFR)
Press PROGRAMME until 1
1
(Event 1) shows along the top of
the display and MOTUWETHFR shows along the bottom.
Use the + and - buttons to set the time you want your
system to fi rst come on in the morning
Press PROGRAMME again to move to Event 2
Use the + and - buttons to set the time you want your
system to fi rst go off.
Continue using the PROGRAMME and +/- buttons
in this way to set the ON/OFF times for events 3-6
for weekdays.
Weekend (SASU)
Press PROGRAMME again until
Programming the unit - 5/2 day mode
1 (Event 1) shows along the top
of the display and SASU shows
along the bottom of the display.
Use the PROGRAMME and +/- buttons to set the
ON/OFF times for the weekend.
If at any time you wish to return to the factory preset
programme, press SELECT / ADVANCE / + / - buttons
together at the same time to reset the unit.
16
NB. It is not possible to programme times out of sequence.
Running your programme
y
g
n
A
A
Y
= the unit will come on at the fi rst
The 102E5 will either control your hot water and heating
together, or just your hot water (i.e. during the summer,
when heating is no longer required).
To make your selection use the rocker switch under
the LCD display to select either WATER/HEATING or
WATER ONLY
To run the central heating and/or hot water programme
press the SELECT button.
As you press SELECT a bar on the display will move
between ON, OFF, ALLDAY and AUTO
ON = the hot water/heating will remain on
constantl
constantly
OFF = the hot water/heating will not come on
AUTO = the hot water/heating will come on
and go off according to the programmed times
and go off according to the programmed times
ALLDAY = the unit will come on at the fi rst
programmed ON and will remain on until the last
programmed ON and will remain on until the last programmed OFF
programmed OFF
ON = the hot water/heating will remain on
OFF = the hot water/heatin
will not come o
UTO = the hot water/heating will come on
LLDA
RUN mode
Select the option you require, depending on your
circumstances, time of year, etc.
17
Temporary User Overrides
Sometimes you may need to change the way you use
your heating temporarily, i.e due to unusually cold
weather. The 102E5 has two convenient overrides which
can be selected without affecting the set programme.
Override
buttons
+1HOUR
Press +1HOUR once if you need an extra hour of
operation (a red light will come on).
If the system is off it will come on for an hour. If it is
already on it will add an extra hour so the system
stays on for an extra hour.
To cancel the override press +1HOUR again (red light
will go off).
Override buttons
ADVANCE (does not work when unit set to OFF)
Press the ADVANCE button once to advance to the
next programmed event (a red light will come on).
18
If the system is on it will go off. If it is off it will come
on. The set programme will resume at the next
programmed ON/OFF time
To cancel the override press ADVANCE again (red
light will go off).
Battery backup
In the event of a power cut, the built-in lithium battery
will keep your time and programme settings for up to 15
days.
After 15 days without mains power the unit will switch off
and two dots will show in the display. However all your
programmed on/off times will be remembered.
When the mains power is restored, the unit will need to
be reactivated by pressing the PROGRAMME button,
and the time and day will need to be set (see page 13).