Danfoss 102E5 Installation guide

102E5
Electronic mini-programmer for
controlling hot water and heating
(Including Factory Replacement Units FRU)
Danfoss Heating
Installation and User Guide
Installation
Product specifi cation 3
Installation 4-6
Wiring 6-9
Replacement 10-11
User
Your programmer 12
Setting the clock 13
Factory preset programmes 14
Setting the programme - 24 hour 15
Setting the programme - 5/2 day 16
Running the programme 17
Temporary user overrides 18
Battery backup 19
Contact details 20
INDEX
For a large print version of these instructions please call Marketing on 01234 364 621.
®
Certification Mark
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2
Installation Instructions
Please Note:
This product should only be installed by a qualifi ed electrician or competent heating installer, and should be in accordance with the current edition of the IEEE wiring regulations.
Product specifi cation
Specifi cation
Power supply 230 ± 15% Vac, 50 Hz
Switching action 1 x SPST, Type 1B
Switch rating 264 Vac, 50/60Hz, 3(1)A
Timing Accuracy ±1 min./month
Power Reserve Minimum 14 days
Enclosure Rating IP30
Max. Ambient Temperature 45°C
Dimensions, mm (W, H, D) 103 x 137 x 48
Specifi cation
Design standard EN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5kV
Ball Pressure Test 75°C
3
Installation
NB. For FRU units - go straight to point 6 below.
1. Loosen the fi xing screw in the base of the unit to release the Wiring Cover.
2. Holding the unit face downwards, press fi rmly in the centre of the wallplate and slide it apart and lift it from the module.
3. Fix the wallplate and terminal block to the wall, or plaster box, as required. Ensure that the screw heads do not protrude beyond the vertical centre rib of the wallplate, or this will prevent the module correctly locating onto the wallplate.
Screw fi xing holes (screwheads MUST NOT protrude above centre rib)
Installation
Vertical centre rib
4
Wallplate & Terminals
4. Surface cables can only enter from below the unit. Cut an appropriate cable aperture in the wiring cover. If the wallplate is mounted on a plaster box, cables can enter from the rear below the terminal block.
5. Electrical connections are simplifi ed by using a Wiring Centre. However, if this is not used, the wallplate terminal identifi cation is as shown.
Water Heating
ON ON
123 56
COM
Mains Supply
(via 3 amp fuse)
NL
If the system being controlled is 230Vac then terminals
3 and L must be linked with insulated cable capable of carrying full load current. Whilst the unit does not require an earth connection, a terminal is provided on the wallplate for earth continuity purposes.
6. Referring to the wiring diagrams on page 6-9, connect the unit as shown.
7. Find out from the user whether the unit is required to operate in 24-hour mode (factory preset) or weekday/weekend mode (5/2 day). To convert to 5/2 day mode remove the small two-way connector from the pins towards the left of the recess on the rear of the module, then press the SELECT/ADVANCE/+/- buttons all at the same time to RESET the unit.
8. Ensure all dust and debris are cleared from the area. Plug the module into the wallplate by locating it onto the wallplate and, when fl ush with it, sliding it down, ensure the hook at the top of the wallplate engages with the slot at the back of the module.
Installation
9. Before setting the programme, check the unit and circuit. Set the rocker switch to WATER & HEATING. Press the SELECT button until the bar in the display lines up with the word ON. Adjust the remote thermostats to check the system operates correctly.
5
10. Then press the SELECT button until the bar lines up with the word OFF and check the system does not operate.
11. Set the rocker switch to WATER ONLY. Press the SELECT button until the bar in the display lines up with the word ON and check that the water circuit only operates.
12. When the circuit check has been completed, replace the wiring cover and tighten the fi xing screw. Cut any cable aperture in the wiring cover which may be necessary to accommodate surface mounted cables.
13. Finally set time of day and programmes required,
Wiring
Wiring
noting that the unit is supplied with a pre-set programme, as stated on Page 14.
6
2, 102E5, 102E7
Typical Gravity DHW with Pumped Heating
1
COM
CALL
L N
2
3
LINK
ROOM ' STAT
N
BOILER TERMINALS
5
L N
6
102E5 TERMINALS
L
MAINS
N
PUMP TERMINALS
SUPPLY FUSED 3 AMP
Typical domestic gas or oil-fi red central heating system with gravity hot water and pumped heating. (If a room thermostat is not used, wire pump live directly to terminal 2 of the 102E5).
Wiring
7
Typical Heating and Hot Water control system using 3-port mid-position valve
ROOM ' STAT
CALL
WHITE OR BROWN
N
2
CYL. ' STAT
SAT
GREY
3
LINK
1
COM
BLUE
MID-POSITION VALVE
COM
CALL
RED OR ORANGE
5
L N
6
102E5 TERMINALS
L
N
BOILER & PUMP TERMINALS
MAINS SUPPLY FUSED 3 AMP
Wiring
8
The above control system is available as the Danfoss Randall 102E5 HEATSHARE pack, which also includes the TW room thermostat, AT cylinder thermostat, HS3 mid­position valve and a WB12 wiring box.
Typical Heating and Hot Water control system using 2-port zone valves
CALL
D.H.W VALVE
1
COM
CYL. ' STAT
SAT
2
COM
N
N
3
LINK
ROOM ' STAT
CALL
HEATING
VALVE
N
L N
5
6
102E5 TERMINALS
L
MAINS
N
BOILER & PUMP TERMINALS
SUPPLY FUSED 3 AMP
The above control system is available as the Danfoss Randall 102E5 HEATPLAN pack, which also includes the TW room thermostat, AT cylinder thermostat, two 22mm HPP zone valves and a WB12 wiring box.
Wiring
9
should be terminated
required where these discon-
An additional terminal block is
nected leads (or pairs of leads)
MAINS SUPPLY
(via 3 amp fuse)
COM
- 2,3 1 4,7 5 6
Replacement
10
Heating
DANFOSS RANDALL
102E5 Water
ON
ON
1 2 3 5 (N) 6 (L) A B C
123 56
RANDALL 102, 102E,
102E7
RANDALL 3020P, 3060 4 2 - 1,7 6 3 5
(8)
Air ‘Stat
(8)
Boiler
RANDALL MKII R6 4 5 - 3 1,2 6 7
HORSTMANN
CORAL 423 & 424
2 4 - N L,1,3 5 6
HORSTMANN
DIAMOND 423
2 4 - N L,1,3 5 6
HORSTMANN
DIAMOND 424
2 5 - N,1,3 L 4,6
POTTERTON 423 2 4 - N L,1,3 5 6
SANGAMO S409 F1
& F4
1,3 4 - N,2 L
SANGAMO (Early
model) S410 Form 4
Replacement
32 - NL1 4
SMITHS IND.
CENTROLLER 100
54 - 123
SMITHS IND.
CENTROLLER 60
SMITHS IND.
3 2 - N L 1,4
CENTROLLER 10
54 - 123 6
SMITHS IND.
CENTROLLER 70
3 1 - N 4,L 2
SWITCHMASTER
320, 350
SWITCHMASTER 600 3 1 - N L 2 4
2 A/S - N,1,3 L A/S,5
VENNER VENOTROL V S,F - N,A,M L,L1 T,P 0
VENNER VENOTROL
80 (Air ‘Stat)
2 5 - N,1,3 L
VENNER VENOTROL
80 (Air ‘Stat Linked)
11
User Instructions
Your programmer
Your 102E5 mini-programmer allows you to switch your heating and hot water on and off at times that suit you.
The 102E5 can provide 3 ON periods and 3 OFF periods each day and can offer either 24 hour control (same programme for each day of the week) or 5/2 day control (one set of programmes for weekdays and a different set for weekends).
Overview
12
-
+
PROGRAMME
Before you start
 Open the fl ap on the front of
the unit.
 Press all four buttons
(SELECT / ADVANCE / + / -) at the same time
This will reset the unit, reinstate the preset programmes and set the time to 12:00pm on Monday.
-
+
PROGRAMME
Setting the clock
Press PROGRAMME once
Use + and – buttons to set the
correct time (press and hold to change in 10 min increments).
When time is correct press
PROGRAMME again.
In 24 hour mode this will take you straight to programming mode, where you can select your own ON and OFF times.
-
+
+
PROGRAMME
-
PROGRAMME
Setting the time & the programme
In 5/2 day mode this fi rst will allow you to programme the correct DAY. To do this:
use the + or – buttons to select the correct day
press PROGRAMME again to enter programming
mode
13
Factory Presets
The unit is supplied with the following preset programme which will be active after the unit has been reset.
Mon-Fri or All
days in 24hr mode
1st ON 6.30am 7.30am
1st OFF 8.30am 10.00am
2nd ON 12.00pm 12.00pm
2nd OFF 12.00pm 12.00pm
3rd ON 5.00pm 5.00pm
3rd OFF 10.30pm 10.30pm
NB. 2nd ON and 2nd OFF are set to the same time.
(5/2day mode only*)
Sat-Sun*
These 2 times are ignored by the programme therefore the heating will just come on once in the morning and once in the evening. If you want the heating to come on in the middle of the day set the 2nd ON and 2nd OFF to the times you require.
Factory preset programmes
Accepting the preset times
If you are happy to use the settings above, you don’t need to do anything else.
To accept the presets press the PROGRAMME button until the colon in the display begins to fl ash.
14
Your unit is now in RUN mode.
Programming event times in 24 hour mode
You can programme your heating and hot water to come on and go off up to 3 times each day, to suit your requirements.
Press PROGRAMME until 1
1
(Event 1) shows along the top of the display.
Use the + and - buttons to set
the time you want your system to fi rst come on in the morning
Press PROGRAMME again to move to the next step
(Event 2)
Use the + and - buttons to set the time you want your
system to fi rst go off.
Continue using the PROGRAMME and +/- buttons
in this way to set the ON/OFF times for events 3-6 (2nd ON/OFF & 3rd ON/OFF).
NB. It is not possible to programme times out of sequence.
If you do not press a button at all for 3 or 4 minutes the unit will automatically return to RUN mode.
Programming the unit - 24 hour mode
15
Programming event times in 5/2 day mode
You can programme your heating and hot water to come on and go of up to 3 times each day, to suit your requirements, with one set of programmes for weekdays and a different set of programmes for the weekend.
Weekdays (MOTUWETHFR)
Press PROGRAMME until 1
1
(Event 1) shows along the top of the display and MOTUWETHFR shows along the bottom.
Use the + and - buttons to set the time you want your
system to fi rst come on in the morning
Press PROGRAMME again to move to Event 2
Use the + and - buttons to set the time you want your
system to fi rst go off.
Continue using the PROGRAMME and +/- buttons
in this way to set the ON/OFF times for events 3-6 for weekdays.
Weekend (SASU)
Press PROGRAMME again until
Programming the unit - 5/2 day mode
1 (Event 1) shows along the top of the display and SASU shows along the bottom of the display.
Use the PROGRAMME and +/- buttons to set the
ON/OFF times for the weekend.
If at any time you wish to return to the factory preset programme, press SELECT / ADVANCE / + / - buttons together at the same time to reset the unit.
16
NB. It is not possible to programme times out of sequence.
Running your programme
y
g
n
A
A
Y
= the unit will come on at the fi rst
The 102E5 will either control your hot water and heating together, or just your hot water (i.e. during the summer, when heating is no longer required).
To make your selection use the rocker switch under the LCD display to select either WATER/HEATING or
WATER ONLY
To run the central heating and/or hot water programme press the SELECT button.
As you press SELECT a bar on the display will move between ON, OFF, ALLDAY and AUTO
 ON = the hot water/heating will remain on
constantl
constantly
OFF = the hot water/heating will not come on
AUTO = the hot water/heating will come on
and go off according to the programmed times
and go off according to the programmed times
ALLDAY = the unit will come on at the rst
programmed ON and will remain on until the last
programmed ON and will remain on until the last programmed OFF
programmed OFF
ON = the hot water/heating will remain on
OFF = the hot water/heatin
will not come o
UTO = the hot water/heating will come on
LLDA
RUN mode
Select the option you require, depending on your circumstances, time of year, etc.
17
Temporary User Overrides
Sometimes you may need to change the way you use your heating temporarily, i.e due to unusually cold weather. The 102E5 has two convenient overrides which can be selected without affecting the set programme.
Override buttons
+1HOUR
Press +1HOUR once if you need an extra hour of
operation (a red light will come on).
If the system is off it will come on for an hour. If it is
already on it will add an extra hour so the system stays on for an extra hour.
To cancel the override press +1HOUR again (red light
will go off).
Override buttons
ADVANCE (does not work when unit set to OFF)
Press the ADVANCE button once to advance to the
next programmed event (a red light will come on).
18
If the system is on it will go off. If it is off it will come
on. The set programme will resume at the next programmed ON/OFF time
To cancel the override press ADVANCE again (red
light will go off).
Battery backup
In the event of a power cut, the built-in lithium battery will keep your time and programme settings for up to 15 days.
After 15 days without mains power the unit will switch off and two dots will show in the display. However all your programmed on/off times will be remembered.
When the mains power is restored, the unit will need to be reactivated by pressing the PROGRAMME button, and the time and day will need to be set (see page 13).
Battery backup
19
Still having problems?
Call your local heating engineer:
Name:
Tel:
Visit our website:
www.heating.danfoss.co.uk
Email our technical department:
ukheating.technical@danfoss.com
Call our technical department
01234 364 621
(9.00-5.00 Mon-Thurs, 9.00-4.30 Fri)
Danfoss Ltd
Ampthill Road Bedford MK42 9ER Tel: 01234 364621 Fax: 01234 219705
Part No 2467v04 Issue 4 01/15
Loading...