GP Programmers & Timeswitches
102, 103 and 106 Models, for time control of Domestic Central Heating Systems.
INSTALLATION AND WIRING INSTRUCTIONS
SPECIFICATIONS
Power Supply |
: 220/240Vac, 50/Hz |
Switch Action |
: 1 x SPST, Type 1B |
Switch Rating |
: 220/240Vac, 50/60Hz, 6(2)A. |
Timing Accuracy |
: ± 1 min./month |
Enclosure Rating |
: IP20 |
Pollution Situation |
: Degree 2 |
Max. Ambient Temp. |
: 55°C |
This product complies with the following EC Directives:
Electro-Magnetic Compatibility Directive.
(EMC) (2004/108/EC)
Low Voltage Directive.
(LVD) (2006/95/EC)
Designed to meet BS EN60730-2-7
Dimensions |
: 112mm wide, 135mm high, 69mm deep |
Rated Impulse voltage |
: 2.5kV |
Ball Pressure Test |
: 75°C |
The unit must be installed by a competent electrician and the installation should conform to I.E.E. Regulations. This unit should be wired via full disconnectinaccordancewithBSEN60730-1,e.g.viaaplugandunswitched socket or double pole switch outlet with neon.
INSTALLATION INSTRUCTIONS
1.Loosen the fixing screw in the base of the unit to release the grey plastic Wiring Cover. Ensure the protective tape over the thumbwheel remains in place.
2.Holding the unit clockface downwards, press firmly in the centre of the wallplate and slide it from the module as shown.
3.Fix the Wallplate/Terminal Block to the wall with countersunk No.8 woodscrews or to a steel box to BS 4662. 1970 or a surface mounting steel or moulded box having centres of 23/8" (60.3mm).
4.Referring to the Wiring Diagrams overleaf, connect the unit as shown. Ensure that terminals 3 and 6 are linked where required (Mains Voltage applications) with insulated cable capable of carrying full load current.
5.Ensure all dust and debris have been cleared away from the area, then plug the module firmly into the wallplate ensuring that the hook at the top of the wallplate engages with the slot at the back of the body. Press the module down until it locates solidly.
6.CutacableapertureintheWiringCoverifnecessary;replacetheWiring Cover, and tighten the fixing screw.
7.Switch on Mains and test for correct operation as follows:
i)Remove protective tape from the pre-selector wheel.
ii)Remove the dial cover and rotate the clock dial two complete revolutions to clear the mechanism.
ii)Checkthatallpositionsofthe Selector SwitchandTappetsoperate correctly. (See instructions in User Booklet.)
8.Replace the dial cover. Finally leave the USER INSTRUCTIONS with the Householder.
9.If the unit is to be left turned o and is in a dusty atmosphere, protect the pre-selector wheel by re-a xing the protective tape.
Pre-Selector Wheel
Selector Switch
Plug-in Replacement
Module
Wallplate/Terminal Block
Wallplate/
Terminal Block
Plug-in Module
IMPORTANT: Remove tape prior to putting unit into service.
1
INTERNAL WIRING MODEL 102 |
|
|||
W |
|
|
|
|
OFF |
|
|
|
|
HW |
|
|
|
|
1 |
2 |
3 |
5 |
6 |
Terminals |
|
|
|
|
|
|
|
|
|
|
|
|
L |
||
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
N |
||
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
Water |
Heating |
|
|
|
Mains |
|||||
Output |
Output |
|
|
|
Supply |
|
NOTE: Terminals 3 and 6 MUST be linked externally |
|
(except when voltage free switch contacts are required). |
|
TYPICAL EXTERNAL CIRCUITS |
102 Terminals |
102 Terminals |
1 |
2 |
3 |
|
5 |
6 |
1 |
2 |
3 |
5 |
6 |
|
|
|
Link |
|
L |
|
|
Link |
L |
|
|
|
|
|
|
|
|
|
|
||
|
Room |
|
|
|
N |
|
Room |
|
|
N |
|
|
|
|
|
|
|
|
|
||
Com |
Stat |
|
|
|
|
Com |
Stat |
|
|
|
|
N |
|
|
|
Mains |
|
N |
|
|
Mains |
|
|
|
|
Supply |
|
|
|
Supply |
||
|
|
|
|
|
|
|
|
|
||
|
Call |
|
|
|
|
|
Call |
HP2 spring return |
|
|
|
|
|
|
|
|
|
|
zone valve |
|
|
|
|
L |
N |
|
|
C |
Brown |
L |
N |
Blue |
|
|
|
|
|
|
|||||
|
|
|
Pump |
|
1 |
2 |
|
|
|
|
|
|
|
|
|
|
|
Motor |
|
Grey |
|
|
|
|
|
|
|
Cylinder Stat L641A |
|
|
||
|
|
|
|
|
|
Orange |
|
|
|
|
|
|
L |
N |
Boiler |
|
To Boiler & Pump |
L |
N |
1) Typical domestic gas or oil fired system with |
2) Fully pumped system with cylinder stat in HW |
gravity hot water and pumped heating. (If a |
circuit and room stat and 2 port spring return |
room stat is not requires wire pump L directly to |
zone valve in heating circuit. |
terminal 2 on the 102). |
|
INTERNAL WIRING MODEL 106
Water |
OFF |
|
|
|
|
|
Priority |
|
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
|
|
|
|
|
|
|
Priority |
|
|
|
|
|
1 |
2 |
|
3 |
4 |
5 |
6 |
Terminals |
|
|
|
|
|
|
|
|
|
|
|
|
L |
|
CALL |
|
|
SAT |
|
N |
|
SAT |
|
|
CALL |
|
|
|
|
|
|
|
||
Typical |
COM |
|
|
COM |
|
|
External |
Cylinder Stat |
L |
|
Room Stat |
If Danfoss Randall HS3 valve is used |
|
Circuit |
|
|
|
|
connect valve brown and grey to |
|
|
|
|
|
|
|
terminal 2 of 106 |
|
|
|
N |
|
|
|
To boiler & pump |
Orange not |
|||||||||||
|
|
|
|
|
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L |
N |
|
|
|
|
|
|
|
connected |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Honeywell 'W' plan or Satchwell 'K' plan. |
|
|
|
|
|
|
|
|
|
|
|
(make safe) |
Fully pumped system with 3 port (2 way) diverter valve.
INTERNAL WIRING MODEL 103
TIMED |
OFF |
CONSTANT |
1 |
2 |
3 |
|
|
|
|
|
5 |
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
Terminals |
|
|
|
|
|
|
|
|
|
|
|
|
L |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
N |
||||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
Output |
|
|
|
|
|
|
|
|
|
Mains |
|||||||
|
|
|
|
|
|
|
|
|
|
|
Supply |
NOTE: Terminals 3 and 6 should (in most instances) be linked externally.
Exceptions are when control circuits are operating at low voltage (e.g. 24 volts) or for certain Combination Type Boilers (see Boiler Manufacturers Handbook).
TYPICAL EXTERNAL CIRCUITS
103 Terminals |
|
|
|
|
|
|
|
|
103 Terminals |
|
|
|
|
|
|
|||||||||
1 |
2 |
3 |
|
|
5 |
6 |
|
|
1 |
2 |
3 |
|
|
5 |
6 |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Link |
|
|
|
|
L |
|
|
|
|
|
|
|
|
|
L |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
N |
|
|
|
|
|
|
|
|
|
N |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Com |
|
Mains |
|
Mains |
|
|
|
||
N |
|
Supply |
|
Supply |
Room |
Low |
|
|
|
|
|
Low voltage |
||
|
voltage |
|
||
|
Stat |
|
||
|
room stat |
Load |
supply |
|
|
|
|||
|
Call |
|
|
|
LN
Load
Terminals
1) Control of Heating Function only (Mains |
2) Control of Low Voltage Systems |
Voltage) |
(e.g. warm air gas valves, low voltage |
Note: If room thermostat is not required |
burners). |
join timeswitch terminals 1 and 2 with a |
|
link suitable for full load current). |
|
103 Terminals |
|
|
|
|
103 Terminals |
|
|
|
|
||||||
1 |
2 |
3 |
|
|
5 |
6 |
1 |
2 |
3 |
|
|
|
5 |
6 |
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Link |
|
|
|
|
|
|
|
|
|
L |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
N |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
Com |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
N |
Room |
|
|
|
|
|
|
|
|
|
|
Mains |
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Supply |
|||||||||
|
|
|
|
|
|
|
|
|
Stat |
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
Call |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L |
N |
|
|
|
|
|
L |
|
N |
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Boiler |
|
|
|
Pump |
|
|
|
|
|
|
|
|
|
|||||||||||
|
|
|
Terminals |
|
|
|
Terminals |
|
|
|
|
|
|
|
|
|
|
|
|
|
L |
|
|
|
|
N |
Com |
|
|
|
|
N |
|
|
|
Mains |
|
|
|
|
Supply |
Room |
Call |
|
|
|
Stat |
|
|
|
|
|
Input |
Output |
N |
L |
|
|
Boiler Terminals |
|
|
3) Typical gas or oil fired heating system with |
4) Typical control of heating when used with |
gravity hot water primary and pumped heating. |
combination type boilers. |
NOTE: Ease of installation can be achieved by using the Danfoss Randall Wiring Centre which is obtainable from most Builders Merchants and Distributors.
IF A WIRING CENTRE IS USED, follow the installation instructions included with the unit and not the wiring diagrams shown on this page.
Danfoss Randall can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss Randall reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
|