Danfoss 102, 103, 106 Installation guide

GP Programmers & Timeswitches
102, 103 and 106 Models, for time control of Domestic Central Heating Systems.
INSTALLATION AND WIRING INSTRUCTIONS
Power Supply : 220/240Vac, 50/Hz Switch Action : 1 x SPST, Type 1B Switch Rating : 220/240Vac, 50/60Hz, 6(2)A. Timing Accuracy : ± 1 min./month Enclosure Rating : IP20 Pollution Situation : Degree 2 Max. Ambient Temp. : 55°C Designed to meet BS EN60730-2-7 Dimensions : 112mm wide, 135mm high, 69mm deep
Rated Impulse voltage : 2.5kV
Ball Pressure Test : 75°C
The unit must be installed by a competent electrician and the installation should conform to I.E.E. Regulations. This unit should be wired via full disconnect in accordance with BS EN60730-1, e.g. via a plug and unswitched
socket or double pole switch outlet with neon.
INSTALLATION INSTRUCTIONS
1. Loosen the fi xing screw in the base of the unit to release the grey plastic Wiring Cover. Ensure the protective tape over the thumbwheel remains in place.
2. Holding the unit clockface downwards, press fi rmly in the centre of the wallplate and slide it from the module as shown.
3. Fix the Wallplate/Terminal Block to the wall with countersunk No.8 woodscrews or to a steel box to BS 4662. 1970 or a surface mounting steel or moulded box having centres of 2
4. Referring to the Wiring Diagrams overleaf, connect the unit as shown. Ensure that terminals 3 and 6 are linked where required (Mains Voltage applications) with insulated cable capable of carrying full load current.
5. Ensure all dust and debris have been cleared away from the area, then plug the module fi rmly into the wallplate ensuring that the hook at the top of the wallplate engages with the slot at the back of the body. Press the module down until it locates solidly.
6. Cut a cable aperture in the Wiring Cover if necessary; replace the Wiring Cover, and tighten the fi xing screw.
7. Switch on Mains and test for correct operation as follows:
i) Remove protective tape from the pre-selector wheel. ii) Remove the dial cover and rotate the clock dial two complete
revolutions to clear the mechanism.
ii) Check that all positions of the Selec tor Switch and Tappets operate
correctly. (See instructions in User Booklet.)
8. Replace the dial cover. Finally leave the USER INSTRUCTIONS with the Householder.
9. If the unit is to be left turned off and is in a dusty atmosphere, protect the pre-selector wheel by re-affi xing the protective tape.
3
/8" (60.3mm).
This product complies with the following EC Directives:
Electro-Magnetic Compatibility Directive.
(EMC) (2004/108/EC)
Low Voltage Directive.
(LVD) (2006/95/EC)
Pre-Selector Wheel
Selector Switch
Plug-in Replacement Module
Wallplate/Terminal Block
Wallplate/ Terminal Block
Plug-in Module
IMPORTANT: Remove tape prior to putting unit into service.
1
INTERNAL WIRING MODEL 102 INTERNAL WIRING MODEL 103
W
OFF
HW
12 3 56
Terminals
Water
Heating
Output
Output
NOTE: Terminals 3 and 6 MUST be linked externally
(except when voltage free switch contacts are required).
TYPICAL EXTERNAL CIRCUITS TYPICAL EXTERNAL CIRCUITS
102 Terminals
123
Link
Room Stat
Com
N
Call
L N
Pump
L N Boiler
1) Typical domestic gas or oil fi red system with gravity hot water and pumped heating. (If a
room stat is not requires wire pump L directly to
terminal 2 on the 102).
6
5
Mains
Supply
Supply
102 Terminals
123
L
N
12
2) Fully pumped system with cylinder stat in HW circuit and room stat and 2 port spring return
Room Stat
Com
N
Call
Brown
C
Cylinder Stat L641A
Orange
To Boiler & Pump
zone valve in heating circuit.
HP2 spring return
Link
zone valve
L
Motor
L N
5
N
L
N
Mains
Blue
Grey
Terminals
Output
NOTE: Terminals 3 and 6 should (in most instances) be linked externally.
Exceptions are when control circuits are operating at low voltage (e.g. 24 volts) or for certain
Combination Type Boilers (see Boiler Manufacturers Handbook).
103 Terminals
123
6
L
N
Com
Mains
Supply
N
Call
1) Control of Heating Function only (Mains
Note: If room thermostat is not required join timeswitch terminals 1 and 2 with a
Voltage)
link suitable for full load current).
103 Terminals
123
TIMED
OFF
CONSTANT
12 3 56
103 Terminals
6
Mains
Supply
L
N
123
Low
voltage
room stat
(e.g. warm air gas valves, low voltage
Load
2) Control of Low Voltage Systems
burners).
Room Stat
L N
Link
Load
Terminals
5
103 Terminals
6
5
123
L
N
Mains
Supply
5
Supply
Low voltage supply
5
6
L
N
Mains
6
INTERNAL WIRING MODEL 106
Water
Priority
Terminals
Typical External Circuit
Honeywell 'W' plan or Satchwell 'K' plan.
Fully pumped system with 3 port (2 way) diverter valve.
OFF
Heating
Priority
12 3 56
CALL
SAT
COM
Cylinder Stat
L
N
4
SAT
CALL
COM
Room Stat
If Danfoss Randall HS3 valve is used
connect valve brown and grey to
To boiler & pump
L N
Danfoss Randall can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss Randall reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifi cations already agreed.
Danfoss Ltd
Ampthill Road, Bedford MK42 9ER. Telephone: (01234) 364621 Fax: (01234) 219705 Email: ukheating@danfoss.com Website: www.heating.danfoss.co.uk
2
L N
terminal 2 of 106
Orange not
connected
(make safe)
Link
Com N
Call
L N
Terminals
3) Typical gas or oil fi red heating system with
gravity hot water primary and pumped heating.
Boiler
Room Stat
L N
Pump
Terminals
L
N
Com
Mains
Supply
N
CallRoom
Stat
Input Output N L
Boiler Terminals
4) Typical control of heating when used with combination type boilers.
Mains
Supply
NOTE: Ease of installation can be achieved by using the Danfoss Randall Wiring Centre which is obtainable from most Builders Merchants and Distributors.
IF A WIRING CENTRE IS USED, follow the installation instructions included with the unit and not the wiring diagrams shown on this page.