Danfoss 101N0800, 101N0810, 101N0820 Installation guide

Instructions

TOOL4COOL

Compressor Module 101N0800, 12V DC

Flexible control set

Compressor Module 101N0810, 24V DC

 

 

Application Module 101N0820, 12/24V DC

 

 

Battery protection settings 12V DC (± 0.3 V DC, all values)

Application Module 101N0820

Voltage (0.1 steps)

Min. value

Default

Max. value

Cut out

VDC

 

 

9.6

10.4

17

 

 

Cut in diff.

VDC

 

 

0.5

1.3

10

 

 

Battery protection settings 24V DC (± 0.3 V DC, all values)

 

 

Voltage (0.1 steps)

Min. value

Default

Max. value

 

 

Cut out

VDC

 

 

19

21.3

27

 

 

Cut in diff.

VDC

 

 

0.5

1.3

10

 

 

Fig. 1

 

 

 

 

 

 

 

 

Wire Dimensions 12V & 24V DC

 

 

 

 

Size

 

Max. length*

Max. length*

 

 

Cross

AWG

12V operation

24V operation

 

 

section

 

 

 

 

 

 

 

 

[mm2] [Gauge]

[m]

[ft.]

[m]

[ft.]

 

 

2 x 4

11

0.75

2.46

1.5

4.92

 

 

2 x 6

9

1

 

3.28

2

6.60

 

 

2 x 10

7

2

 

6.60

4

13.12

Compressor Modules

 

Fig. 2

*Length between battery and electronic unit

101N0800 & 101N0810

 

 

 

 

 

 

 

 

 

 

Recommended fuses and switches

 

 

 

Fuses

 

 

 

 

12V DC

24V DC

 

 

Application module

 

 

 

30A

15A

 

 

Compressor module

 

 

 

60A

30A

 

 

Main switches

 

 

 

12V DC

24V DC

 

 

Single compressor confi guration

75A

38A

 

 

Twin compressor confi guration

150A

75A

 

 

Fig. 3

 

 

 

 

 

 

 

Available cord sets

 

Packages

1500 mm

3000 mm

 

Single compressor

 

 

I - Pack

105N9553 105N9554

 

communication cable assembly

 

Twin compressor

 

 

I - Pack

105N9555 105N9556

 

communication cable assembly

 

Available cord sets

 

Packages

900 mm

2000 mm

 

12V DC line cord

 

 

I - Pack

105N9560 105N9559

For wiring schemes see page 2.

24V DC line cord

 

 

I - Pack

105N9543 105N9541

Fig. 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operational errors

Error

Error type

code

Can be read out in the software TOOL4COOL®

7

Communication failure

 

(In case of lost communication between the

 

compressor module(s) and the application

 

module, the compressor(s) and fans will be

 

switched off).

6

Thermostat failure

 

(If the NTC thermistor is short-circuit, has no

 

connection or is outside the operating range

 

(-60°C - 100°C), the compressor module(s) will

 

switch off and show a NTC failure).

5

Thermal cut-out of compressor module

 

(If the refrigeration system has been too heavily

 

loaded, or if the ambient temperature is high/

 

extremely low the compressor module(s) will

 

run too hot/too cold.

4

Minimum motor speed error

 

(If the refrigeration system is too heavily lo-

 

aded, the motor cannot maintain minimum

 

speed at approximately 1,850 rpm).

3

Motor start error

 

(The rotor is blocked or the differential pressure

 

in the refrigeration system is too high).

2

Fan error / Fan missing

 

(The evaporator fan loads the electronic unit

 

with more than 18A for a 12V system and 9A for

 

a 24V system under start up. The current load

 

exceeds 16.5A for a 12V system or 8.25A for a

 

24V system under runing conditions).

 

(The condenser fan loads the electronic unit

 

with more than 9A for a 12V system and 9.5A for

 

a 24V system under start up. The current load

 

exceeds 8.5A for a 12V system or 4.25A for a

 

24V system under runing conditions).

1

Battery protection cut-out

 

(The voltage is outside the cut-out setting,

 

compressor(s) and fans will stop).

Fig. 5

 

ENGLISH

The application module 101N0820 is a dual voltage device. This means that the same unit can be used in both 12V and 24V power supply systems. Maximum voltage is 17V for a 12V system and 31.5V for a 24V power supply system. The compressor module 101N0810 is a 24V single voltage device. This means that the unit can only be used with 24V DC power supply systems. The compressor module 101N0800 is a 12V single voltage device. This means that the unit can only be used with 12V DC power supply systems.

All modules must be protected

from direct splash water. Max. ambient temperature is 55°C.

The modules have a built-in thermal protection which is actuated and stops the compressor operation if the electronic unit temperature becomes too high (100°C/212°F on the PCB). The application module can be connected to a PC through the Secop One Wire/LIN Gateway communication interface (11) on the MMI terminal (I/C/+). Communication gateway modules incl. communication cables can be ordered at Secop. The PC interface allows making different settings and reading out several measurements by using the software tool TOOL4COOL® supplied by Secop (must be ordered separately). The application module can also be connected to any modbuscompatible device (12) on the MMI terminal (I/C/+). For detailed information please see the specfic

Operating Instructions literature.

Installation (Fig. 6, page 2)

Connect the terminal plug from the compressor module (B) to the compressor(s) (10) and connect the compressor module(s) to the application module

(A). The application module will automatically detect whether a twin or a single confi guration is used. For connecting the application module with the compressor module(s) cables supplied by Secop (D) can

be used (Fig. 4 ). Mount the electronic unit on the compressor and fi x it with the two screws (1).

Power supply (Fig. 6, page 2)

All modules must always be connected directly to the battery poles (2). Connect the plus to + and the minus to -, otherwise the modules will not work. The modules are protected against reverse battery connection. For protection during installation, fuses

(3) should be mounted in the + cable as close as possible to the modules. Each module must have its own fuse. Recommended fuses and switches (4) are shown in Fig. 3. The wire dimensions in Fig. 2 must be observed.Avoid extra junctions in the power supply system to prevent voltage drop from affecting the battery protection setting. Special supply cables

(C) can be ordered as accessories (Fig 4). When using the compressor module 101N0800 (12V) the application module must also be applied with 12V DC. When using compressor module 101N0810 (24V) the application module must also be applied with 24V DC.

Battery protection (Fig. 1)

The compressor stops and starts again according to the chosen voltage limits measured on the + and - terminals of the modules. The standard settings for the power supply systems are shown in Fig. 1. Other settings are set through the communication interface.

Thermostat (Fig. 6, page 2)

The thermostat is connected between the terminals C and T. Either a NTC (electrical thermostat) (8) or a mechanical thermostat can be connected (7). Another NTC (9) can also be connected between the terminals C and T1 to obtain another temperature. Three different thermostat modes can be chosen in the software – “Auto” (both NTC and mechanical),

“NTC” or “Mechanical”. Standard setting is “Auto”. In case of using a NTC the set point in the range

between -25º C and 40 º C is set with the software and the temperature can also be seen by using the interface. When using the “Auto” setting in the software it is not possible to obtain NTC failures, so it is recommended to set the thermostat mode to “NTC” when using a NTC.

Speed selection

Speed can be set through the Secop One Wire/LIN Gateway communication interface (11). With factory settings, the compressor will run with 2,500 rpm for the fi rst 30 sec. and then step up to 4,000 rpm when the thermostat is switched on.

Other fi xed compressor speeds and start speeds in the range between 2,500 and 4,000 rpm can be obtained when changing the speed settings in the software.

A start delay in the range from 2-240 sec. (factory setting 4 sec.) after thermostat cut-in can also be chosen.

Fan (Fig. 6, page 2)

An evaporator fan (200W) (5) can be connected between the terminals C and Fe and a condenser fan (100W) (6) between + and Fc . Connect the plus to + and the minus to Fc.

Connecting Fe with Fc can destroy the unit.

If fans are used without adapting the software settings, the fans will run but no error signal will be sent in case of fan failure.

It is also possible to set a start delay on the fans in the range from 0-240 sec. Factory settings for the evaporator fan is 6 sec. and for the condenser fan 0 sec. Fan speed can be adjusted through the interface from 40-100%.

Error handling

If the compressor modules records an operational error, the error can be read out in the software. Error codes are defi ned as shown in Fig. 5.

August 2011

compressors.danfoss.com - DEHC.EI.100.V3.02 / 520N0775

1/2

Danfoss 101N0800, 101N0810, 101N0820 Installation guide

Fig. 6

- single compressor

Fig. 6

- twin compressor confi guration

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

2/2

Designed and manufactured by Secop for DANFOSS - DEHC.EI.100.V3.02 / 520N0775

August 2011

Loading...