With factory settings, the compressor will run with
a fi xed speed of 4,000 rpm when the thermostat
is switched on.
Other fi xed compressor speeds and start speeds
in the range between 2,500 and 4,000 rpm can
be obtained when changing the speed settings
in the software.
A start delay in the range from 2-240 sec. (factory
setting 4 sec.) after thermostat cut-in can also
be chosen.
Fan (Fig. 1)
An evaporator fan (60W) (6) can be connected
between the terminals + and Fe and a condenser
fan (60W) (5) between + and Fc . Connect the
plus to + and the minus to Fe or Fc.
If both fans are used, the settings in the software
must be adapted, including specifying the voltage
used. The factory setting is no fans and 48V. The
unit has to be restarted when these settings have
been changed.
If fans are used without adapting the software
settings, the fans will run but no error signal will
be sent in case of fan failure.
It is also possible to set a start delay on the fans
in the range from 0-240 sec. Factory settings for
the evaporator fan is 6 sec. and for the condenser
fan 0 sec.
Fan speed can be adjusted through the interface
from 40-100%.
Error handling
If the electronic unit records an operational error,
the error can be read out in the software. Error
codes are defi ned as shown in Fig. 4.
The electronic unit is a single voltage device. This
means that the unit can only be used with 48V DC
power supply systems. Maximum voltage is 60V
DC,
max. ambient temperature is 55°C. The electronic unit has a built-in thermal protection which
is actuated and stops the compressor operation if
the electronic unit temperature becomes too high
(100°C / 212°F on the PCB). It can be connected
to a PC through the Secop One Wire/LIN Gateway
communication interface (9) on the terminals I ,
+ and C. Communication gateway modules incl.
communication cables (max. possible length:
3000 mm) can be ordered at Secop.
The PC interface allows for making different settings and reading out several measurements by
using the software tool TOOL4COOL® supplied
by Secop (must be ordered separately).
Installation (Fig. 1)
Connect the terminal plug from the electronic
unit to the compressor terminal (10). Mount the
electronic unit on the compressor and fi x it with
the two screws (1).
Power supply (Fig. 1)
The electronic unit must always be connected
directly to the battery poles (2). Connect the plus
to + and the minus to -, otherwise the electronic
unit will not work. The electronic unit is protected
against reverse battery connection. For protection
during installation, a fuse (3) must be mounted in
the + cable as close to the battery as possible.
The fuse rating shall be 20A maximum for 48V
circuits.
If a main switch (4) is used, it should be rated to a
current of min. 25A. The wire dimensions in Fig.
2 must be observed.
Avoid extra junctions in the power supply system
to prevent voltage drop from affecting the battery
protection setting. Special supply cables can be
ordered as accessory (Molex type 42816-0212).
Battery protection (Fig. 3)
The compressor is stopped and re-started again
according to the chosen voltage limits measured
on the + and - terminals of the electronic unit. The
standard settings for the power supply systems
are shown in Fig. 3. Other settings are set through
the communication interface.
Thermostat (Fig. 1)
The thermostat is connected between the terminals C and T. Either a NTC (electrical thermostat)
(8) or a mechanical thermostat can be connected
(7). Three different thermostat modes can be
chosen in the software – “Auto” (both NTC and
mechanical), “NTC” or “Mechanical”. Standard
setting is “Auto”. In case of using a NTC the set
point in the range between -25º C and 40 º C is
set with the software and the temperature can
also be seen by using the interface. When using
the “Auto” setting in the software it is not possible
to obtain NTC failures, so it is recommended to
set the thermostat mode to “NTC” when using
a NTC.
Speed selection
Speed can be set through the Secop One Wire/
LIN Gateway communication interface (9).
ENGLISH
Instructions
Electronic Unit for BD350GH Compressor,
101N0720, 48V DC
Fig. 1
Wire Dimensions
Size Max. length*
24V operation
Cross
section
AWG
[mm2]
[Gauge]
[m] [ft.]
2 x 4
2 x 6
2 x 10
11
9
7
1.5
2
4
4.92
6.60
13.12
*Length between battery
and electronic unit
Fig. 2
Fig. 3
Battery protection settings
Voltage (0.1 steps) Min. value Default
Max. value
Cut out VDC 32 36 60
Cut in diff. VDC 0.5 4.0 10.0
Operational errors
Error
code
Error type
Can be read out in the software TOOL4COOL®
6
Thermostat failure
(If the NTC thermistor is short-circuit or has
no connection, the electronic unit will enter
manual mode).
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too heavi ly loaded, or if the ambient tem pe ra ture is
high, the electronic unit will run too hot).
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum
speed at approximately 1,850 rpm).
3
Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high.
2
Fan over-current cut-out
(The fan loads the electronic unit with more
than 1.8A
peak
).
1
Battery protection cut-out
(The voltage is outside the cut-out setting).
Fig. 4