Danfoss 101N0500 Installation guide

August 2011 compressors.danfoss.com - DEHC.EI.100.G6.02 / 520N0232 1/2
Instructions
Electronic Unit for BD35/BD50F Compressors,
101N0500, 12/24V DC & 100-240V AC 50/60Hz
The electronic unit is a multi voltage device. It can be used in both 12V/24V DC and 100-240V AC 50/60Hz power supply systems. Max. voltage is 17V DC for a 12V DC system and 31.5V DC for a 24V DC power supply system. Max. voltage is 265V AC and min. 85V AC for an AC power supply system. Max. ambient temperature is 55°C. The electronic unit has a built-in thermal protection which is actuated and stops the compressor op­eration if the electronic unit temperature becomes too high (100°C / 212°F on the PCB). Power consumption is limited to 100W. See datasheet BD50F for details.
Installation (Fig. 1)
Connect the terminal plug from the electronic unit to the compressor terminal. Mount the electronic unit on the compressor by snapping the cover over the screw head (1).
Power supply (Fig. 1)
DC: The electronic unit must always be connected directly to the battery poles (2). Connect the plus to + and the minus to -, otherwise the electronic unit will not work. The electronic unit is protected against reverse battery connection. For protection of the installation, a fuse (3) must be mounted in the + cable as close to the battery as possible. It is recommended to use 15A fuses for 12V and 7.5A fuses for 24V circuits. If a main switch (4) is used, it should be rated to a current of min. 20A. The wire dimensions in Fig. 2 must be observed. Avoid extra junctions in the power supply system to prevent voltage drop from af­fecting the battery protection setting. AC: The wires must be connected to the terminal marked L and N on the electronic unit. Nominal voltages from 100 to 240 VAC 50/60Hz. Upper safety cut-out limit = 270V AC and lower limit 80V AC. A 4A fuse (11) must be mounted in the live
(L) cable to protect the installation. If a main switch (12) is used, it should be rated to a current of min. 6A. The wire dimensions must be min. 0.75 mm2 or AWG 18. NB: Earth connection can be used if required. General: Both the AC and the DC power supply can be connected to the electronic unit at the same time. In this case, AC will be preferred power supply source. If the AC power supply is discon­nected or drop below 85V AC on a 12V DC supply system, a time delay of 1 min. will be activated before the compressor continues on DC power supply. If AC power supply is re-established there will be no delay in compressor operation.
Battery protection (Fig. 1)
The compressor stops and restarts again accord­ing to the designated voltage limits measured on the + and - terminals of the electronic unit. The standard settings for 12V and 24V power supply systems appear from Fig. 3. Other settings are optional if a connection which includes a resistor (9) is established between terminals C and P. See manual.
Thermostat (Fig. 1)
The thermostat (7) is connected between the ter­minals C and T. Without any resistor in the control circuit, the compressor will run with a fi xed speed of 2,000 rpm when the thermostat is switched on. Other fi xed compressor speeds in the range be­tween 2,000 and 3,500 rpm can be obtained when a resistor (8) is installed to adjust the current (mA) of the control circuit. Resistor values for various motor speeds appear from Fig. 5.
Fan (optional, Fig. 1)
A fan (5) can be connected between the terminals
+ and F. Connect the plus to + and the minus to F. Since the output voltage between the terminals + and F is always regulated to 12V, a 12V fan must be used for both 12V and 24V power supply systems.
Fig. 1
Optional battery protection settings DC
Fig. 4
ENGLISH
The fan output can supply a continuous current of 0.5A
avg
. A higher current draw is allowed for 2
seconds during start.
Lamp (optional, Fig. 1)
A 12V DC 5 Watt lamp (10) can be connected between the terminals A and C. The output volt­age between the terminals A and C is always regulated to 12V DC. A 12V DC lamp must be
used for both 12V and 24V power supply sys­tems.The lamp output can supply a continuous current of 0.5A
avg
.
LED (optional, Fig. 1)
A 10mA light emitting diode (LED) (6) can be connected between the terminals + and D. If the electronic unit records an operational error, the diode will fl ash a number of times. The number of fl ashes depends on what kind of operational error was recorded. Each fl ash will last ¼ second. After the actual number of fl ashes there will be a delay with no fl ashes, so that the sequence for each er­ror recording is repeated every 4 seconds.
24V max.
Voltage
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
24V cut-in
V
22.7
22.9
23.2
23.4
23.7
23.9
24.2
24.5
24.7
25.0
25.2
25.5
25.7
26.0
24V cut-out
V
21.3
21.5
21.8
22.0
22.3
22.5
22.8
23.0
23.3
23.6
23.8
24.1
24.3
24.6
12V max.
Voltage
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
12V cut-in
V
10.9
11.0
11.1
11.3
11.4
11.5
11.7
11.8
11.9
12.0
12.2
12.3
12.4
12.5
10.9
12V cut-out
V
9.6
9.7
9.9
10.0
10.1
10.2
10.4
10.5
10.6
10.8
10.9
11.0
11.1
11.3
9.6
Resistor
(9) kΩ
0
1.6
2.4
3.6
4.7
6.2
8.2 11 14 18 24 33 47 82
220
Number
of
fl ashes
Error type
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded or if the ambient temperature is high, the electronic unit will run too hot).
5
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed 1,850 rpm).
4
Motor start error3
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
Fan over-current cut-out2
(The fan loads the electronic unit with more than 1A
peak
).
1
Battery protection cut-out
(The voltage is outside the cut-out setting).
Fig. 3
24V cut-out
V
22.8
12V cut-in
V
11.7
24V cut - in
V
24.2
12V cut-out
V
10.4
Standard battery protection settings DC
Compressor speed
Electronic
unit
101N0500
Motor
speed
rpm
2,000 2,500 3,000 3,500
Resistor
(8) Ω
(calculated)
0 277 692
1523
Contr.circ.
current
mA
5 4 3 2
Fig. 5
Fig. 2
Wire dimensions DC
*Length between battery and electronic unit
Max length*
24V DC
operation
ft. m
16 5 26 8 39 12 66 20
Size
AWG Cross section
Gauge mm
2
12 2.5 12 4 10 6 8 10
Max length*
12V DC
operation
ft. m
8 2.5 13 4 20 6 33 10
Wire dimensions AC
Cross section min. 0.75 mm2 or AWG 18
2/2 Designed and manufactured by Secop for DANFOSS - DEHC.EI.100.G6.02 / 520N0232 August 2011
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifi cations already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Instructions
Electronic Units for BD Compressors
VDE/UL Approvals for BD Compressors
Approved Compressor - Electronic Unit Combinations
Compressors Electronic Units
Standard EMI High start High speed AEO AEO EMI
101N0210 101N0220 101N0230 101N0290 101N0300 101N0320
BD35F mm 101Z0200
UL UL UL
BD35F inch 101Z0204
UL UL UL
BD35K (R600a) 101Z0211
BD50F mm 101Z1220
UL UL UL UL
BD50F inch 101Z0203
UL UL UL UL
BD80F mm 101Z0280
BD250GH 101Z0400
BD250GH Twin 101Z0500
BD100CN (R290) 101Z0401
Compressors Electronic Units
Solar AC/DC converter Automotive Automotive Telecommunication Extended EMI
101N0400 101N0500 101N0600 101N0630 101N0730 101N0900
BD35F mm 101Z0200
UL VDE/UL
BD35F inch 101Z0204
UL VDE/UL
BD35K (R600a) 101Z0211 BD50F mm 101Z1220
VDE/UL
BD50F inch 101Z0203
VDE/UL
BD250GH (48V) 101Z0402
UL
VDE/UL
= Combination possible, VDE or UL approval
= Combination possible, but no approval
= Combination not possible
Loading...