Danfoss 080Z2171 Installation guide

Installation Guide
080Z2171
EMHS-3-1 Humidistat temp & Humidity
Identication
Specications
Size: 3.3” x 5” x 1.3” (85 x 125 x 35 mm)
Power requirement: 12 V d.c. supplied by the I/O board
Operating environment: Humidity: 0 to 100% RH,
Ambient temperature:
RH Output: 0-5 V d.c.
non-condensing
50°F to 95°F 10°C to 35°C
Installation and Inspection
The 080Z2171 should be mounted on an interior wall or column 5’6” (1.7 m) above the oor line. If column falls in the middle of a gon­dola, the 080Z2171 should be mounted 1’ (30 cm) above the top of the gondola. Additional information can be found on the infor­mation sheet enclosed with the sensor.
1.7 m 1.7 m
© Copyright Danfoss | Produced by ADAP-KOOL® | 2016-03
Installation Guide | 080Z2171 - EHMS-3-1 Humidistat temp & Humidity
RI8RQ202 | 1
Ordering
Description
EMHS-3-1 Humidistat temp &
Part #:
080Z2171
Humidity
Programming Note for AK-SC 255:
For software versions older than 2.030
1. Go to misc. Conguration and setup a conversion factor. Set the min input to 0 V, the max input to 5.0 V, the min out­put to 0% and the max output to 100.0%. Name the conver­sion "emhs3-1" (see g. 1 For details)
2. Setup board and point settings under misc sensor screen. (See g. 2 For details)
For software versions 2.030 And newer, congure the board and points under misc sensor input and select "emhs3-1" as the sensor type.
Fig. 1
Fig. 2
The Product contains electrical components And may not be disposed together with domestic waste. Equipment must be separate collected with Electrical and Elec­tronic waste. According to Local and currently valid legislation.
© Copyright Danfoss | Produced by ADAP-KOOL® | 2016-03
Installation Guide | 080Z2171 - EHMS-3-1 Humidistat temp & Humidity
RI8RQ202 | 2
Loading...