Humidity Transducer
Identication
The 080Z2167 is compatible with all Danfoss AK255 controllers as well as legacy controllers (AKC55, NC-25).
Specications
Size: 8.45” X 0.7”
Power requirement: 12 Vdc supplied by the I/O board
Operating environment: Humidity: 0 to 100% RH,
Ambient temperature:
RH Output: 0-5Vdc
non-condensing
-40°F to 122°F
Installation and Inspection
The 080Z2167 should be mounted in a sheltered outdoor location, preferably out of direct sunlight. The probe must point downward when suspended from conduit. Note that the 080Z2167 must be unpowered when installing a new sensor or it will continuously read 100%. Interrupt sensor power to restart.
Ordering
Description
Humidity Transducer 080Z2167
Part #:
Danfoss Inc. ELECTRONIC DIVISION Baltimore, MD
© Copyright Danfoss | Produced by ADAP-KOOL® | 2015-06
Installation Guide | 080Z2167 Humidity transducer
RI8RS102 | 1
The Product contains electrical components And may not be disposed together with domestic waste. Equipment must be separate collected with Electrical and Elec­tronic waste. According to Local and currently valid legislation.