Daikin VKM50GMV1, VKM80GMV1, VKM100GMV1, VKM50GV1, VKM80GV1 Installation manuals

...
Total Heat Exchanger
INSTALLATION MANUAL
English
HRV (Heat Reclaim Ventilation) -with DX Coil-
MODELS (Ceiling mounted duct type)
With DX coil & Humidifier With DX coil
VKM50GMV1 VKM50GV1 VKM80GMV1 VKM80GV1 VKM100GMV1 VKM100GV1
HRV
HRV;Heat Reclaim Ventilation
Please read this installation manual carefully and install the unit properly to keep it at full capacity for a long time. Please provide some necessary parts, for example round hoods, air suction/discharge grilles etc., before the installation of the unit.
HRV;Wärmerückgewinnungslüftung
Lesen Sie dieses Installationshandbuch bitte sorgfältig durch, und installieren Sie die Einheit korrekt, so daß sie ihre Leistungsfähigkeit noch lange Zeit behält. Einige erforderliche Teile wie z. B. Rundkappen, Luftansaug-/Lufausblasgitter müssen bereits vor der Installation der Einheit vorhanden sein.
HRV;Ventilation avec récupération de chaleur
Veuillez lire attentivement ce Manuel d’installation et installer correctement l’appareil de manière à ce qu’il puisse être utilisé pendant une longue période de temps sans aucun dérangement. Veuillez vous procurer certains éléments nécessaires, tels que des capuchons de formes arrondies, des grilles d’aspiration/évacuation d’air.,avant l’installation de cette unité.
HRV;Ventilación con recuperación de calor
Por favor lea cuidadosamente el manual de instalacion e instale correctamente la unided para que pueda conservar su plena capacidad durante un largo periodo. Por favor, antes de proceder a la instalacion de la unidad, proporcione las piezas necesarias, por ejemple tapas redondas, rejillas de aspiracion y de impulsion de aire, etc.
HRV;Ventilazione per recupero del calore
Leggere attentamente questo mauale ed installare correttamente l’unit in modo da farla funzionare a lungo al massimo delle sue capacita. Prima dell’installazione, è opportuno disporuno delle partinec-essarie, come ganci arrotondati, griglie di aspirazione/di mandata, ecc.
HRV;
Αερισìüò ìε ανÜκτηση θερìüτηταò
ÄιαβÜστε προσεκτικÜ το παρüν εγχειρßδιο εγκατÜστασηò και εγκαταστÞστε σωστÜ τη ìονÜδα για να διατηρÞσετε την πλÞρη απüδοσÞ τηò για πολý καιρü. Προìηθεìτεßτε ìερικÜ απαραßτητα εξαρτÞìατα π.χ. κυκλικÜ καλýììατα, εσχÜρεξ αναρρüφησηò/κατÜθλιψηò κ.τ.λ. πριν εγκαταστÞσετε τη ìονÜδα.
HRV;Hergebruik van warmte
Lees eerst zorgvuldig deze installatiehandleiding en installeer de unit op de juiste manier, zodat deze gedurende lange tijd zijn volledige vermogen kan leveren. Zorg dat alle componenten aanwezig zijn, zoals ronde kappen, luchtaan-en afvoerroosters etc. voordat u de unit gaat installeren.
HRV;Ventilação de Recuperação Térmica
Leia atentamente este manual e instale correctamente esta unidade para que esta funcione inteiramente durante um longo período de tempo. Adquira algumas peças necessárias, por exemplo, tampas redondas, grelhas de aspiração/exaustão, etc., antes da instalação da unidade.
HRV;
Вентиляция с реãенерацией тепла
Внимательно ознаêомьтесь с данным рóêоводством и óстановите блоê надлежащим образом, чтобы он работал на полнóю мощность в течение долãоãо времени. Перед óстановêой блоêа подãотовьте необходимые детали, например êолпаê оêрóãлой формы, решетêи всасывания/выпóсêа воздóха и т.п.
Deutsch
Français
Español
Italiano
ΕλληνικÜ
Nederlands
Рóссêий
DAIKIN.TCF.009
KEMA
59277-KRQ/ECM95-4303
Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome,
Kita-ku, Osaka, 530-8323 Japan
Yoshiaki Hirata
Manager Quality Control Department
Sakai, 1st of Feb. 2005
VKM50GMV1, VKM50GV1
VKM80GMV1, VKM80GV1
DAIKIN INDUSTRIES, LTD.
VKM100GMV1, VKM100GV1
EN60335-2-40,
3P155750-1
With DX coil &Humidifier VKM50GMV1
VKM80GMV1 VKM100GMV1
With DX coil VKM50GV1
VKM80GV1 VKM100GV1
CONTENTS
1 SAFETY CONSIDERATIONS ........................................ 1
2 BEFORE INSTALLATION............................................... 2
3 SELECTING INSTALLATION SITE ................................ 3
4 PREPARATIONS BEFORE INSTALLATION................... 4
5 THE METHOD OF INSTALLATION................................ 4
6 DRAIN PIPING AND WATER SUPPLY WORK .............. 5
7 REFRIGERANT PIPING WORK .................................... 6
8 DUCT CONNECTION .................................................... 7
9 ELECTRIC WIRING WORK ........................................... 8
10 WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER ...................................... 9
11 FIELD SETTING AND TEST RUN............................... 13
12 WIRING DIAGRAM ...................................................... 16

1 SAFETY CONSIDERATIONS

Please read these “SAFETY CONSIDERATIONS” carefully before installing HRV and be sure to install it correctly.
The safety precautions listed here are divided into two catego­ries. In either case, important safety information is listed which must be read carefully.
WARNING ............. Failure to observe a warning may
result in death or serious injury.
CAUTION
After completing the installation, make sure that the unit oper­ates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store this installation manual along with the operation manual for future reference.
Ask your dealer or qualified personnel to carry out installation work. Do not try to install the machine yourself Improper installation may result in water leakage, electric shocks or fire.
Installation should be done following the installation manual and no changes should be made to the unit. Incorrect installation may cause leaking, electric shocks, or fire. Injuries may result if the HRV falls.
Install the unit on a foundation strong enough to withstand the weight of the unit. A foundation of insufficient strength may result in the equip­ment falling and causing injuries.
Do not allow exhaust air to enter the outside air intake vent. This may cause the air of the room to become contaminated, harming the health.
Locate the outside air intake vent so that it does not take in exhaust air which contains combustion air, etc. Incorrect installation may cause a loss of oxygen in the room, leading to serious accidents.
Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this installation manual. An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire. Insufficient power supply capacity or incorrect wiring may cause electrical shocks or fire.
............... Failure to observe a caution may result
in injury or damage to the equipment. These too might lead to serious injury depending on the circumstances.
WARNING
.
HRV(Heat Reclaim Ventilation) -with DX Coil-
Use only accessories and manufacturer-specified parts
Total Heat Exchanger
Installation
manual
when installing. The use of parts other than specified may cause drop of the unit, water leakage, electric shock, fire or other accidents.
Be sure to ground. Do not connect the ground wire to gas or water pipes, light­ning rod or a telephone ground wire. Incomplete grounding may result in electric shocks.
Make sure that all wiring is secured, the specified wires are used, and no external forces act on the terminal connections or wires. Improper connections or installation may result in overheat­ing or fire.
When wiring the power supply and connecting the remote controller wiring and transmission wiring, position the wires so that the electric parts box lid can be securely fastened. Improper positioning of the electric parts box lid may result in electric shocks, fire or the terminals overheating.
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage. Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
If the refrigerant gas leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant gas comes into contact with fire.
After completing the installation work, check that the refriger­ant gas does not leak. Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
Do not directly touch any refrigerant which has leaked out of refrigerant piping connections, etc. This may cause frostbite.
CAUTION
Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in elec­tric shocks or fire.
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)
While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation. Improper drain piping may result in water leakage and prop­erty damage.
Install the two outdoor ducts with down slope to prevent rain­water from entering the unit. If this is not done completely, water may enter the building, may damage furniture, and cause electric shocks and fire.
Insulate the two outdoor ducts and the supply air duct to pre­vent condensation. If this is not done completely, water may enter the building, may damage furniture, etc.
Insulate the duct and the wall electrically when a metal duct is to be penetrated through the metal lattice and wire lattice or metal lining of a wooden structure wall. Inproper duct work may cause electric shocks or fire.
Do not install the unit in the following locations:
a. Place subjected to high temperature or direct flame.
May result in fire or overheating.
b. Where a mineral oil mist or an oil spray or vapor is pro-
duced, for example in a kitchen. This may cause fire.
English 1
c. Place such as machinery plant and chemical plant
where gas, which contains noxious gas or corrosive components of materials such as acid, alkali organic sol­vent and paint, is generated. Place where combustible gas leakage is likely. Copper piping and brazed joints may corrode, causing refrigerant to leak or poisoning and fire due to leaked gas.
d. Place such as bathroom subjected to moisture.
Electric leak or electric shocks and other failure can be caused.
e. Locations below freezing point.
Using the unit at temperatures below 0°C may cause the drain pan the supply and discharge piping, the humidify­ing element, the solenoid valves, and other parts to freeze, which can cause accidents.
f. Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equip­ment.
Make sure the temperature and humidity near the unit and the air suction/discharge air grille is within limit dictated by the usage conditions. Do not install in refrigerated truck or other locations with low temperatures or near heated pools. This may cause fires or short circuits.
Make sure that a snow protection measure is taken. If no pro­tection snow may enter through the outdoor ducts, and cause damaging furniture and electric shock and fire.

2 BEFORE INSTALLATION

The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them!
After carrying in the unit, protect it with packing materials to pre­vent it from scratching until installation work is done.
[1] Decide upon a line of transport.
[2] Leave the unit inside its packaging while moving, until reach-
ing the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit.
Hold the unit by the hanger brackets (4) when opening the crate and moving it, and do not lift it holding on to any other part (especially the refrigerant piping, the drain piping, the water supply piping, and the duct connecting flange).
Be sure to check the type of R410A refrigerant to be used before installing the unit. (Using an incorrect refrigerant will prevent normal operation of the unit.)
For the installation of an outdoor unit, refer to the installa­tion manual attached to the outdoor unit.
2. 1 PRECAUTIONS
Be sure to instruct customers how to properly operate the unit (especially maintenance of air filter, and operation proce­dure) by having them carry out operations themselves while looking at the manual.
Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories. Also in vehicles or vessels.
2. 2 ACCESSORIES
Check the following accessories are included with your unit.
Duct con-
Name
Quantity 4 pcs. 24 pcs.
Shape
Name
Quantity
Shape
Name
Quantity
Shape
necting flange
Half-union joint (Copper piping joint)
VKM-GMV1:1 pc. VKM-GV1: 0 pc.
Water sup­ply piping insulation cover
VKM-GMV1: 1 pc. VKM-GV1: 0 pc.
I.D.: φ15
M4 tapping screw (For connecting duct)
Flare nut (Copper piping joint)
VKM-GMV1:1 pc. VKM-GV1: 0 pc.
Sealing material
1 pc.
Water supply piping with strainer
VKM-GMV1: 1 pc. VKM-GV1: 0 pc.
Refrigerant piping
insulation cover
1 set
I.D.: φ35 I.D.: φ26
Clamp
VKM-GMV1: 8 pcs. VKM-GV1: 6 pcs.
(Other)
• Installation manual
• Operation manual
2. 3 OPTIONAL ACCESSORIES
This unit can be made a part of two different systems: as part of the combined operation system used together with VRVII SYSTEM Air Conditioners, and as the independent system using only the HRV. An operating remote controller is required for this unit when using the unit as an independent system. Select a suitable remote controller from below table accord­ing to customer request and technical materials.
Ta bl e
Remote controller type BRC1A62, BRC1D527
NOTE) 1 If you use the remote controller which is not listed in above table, please consult your dealer. NOTE) 2 We recommend the remote controller “BRC1D527” espe­cially when the unit is used as independent system. Because it displays the ventilation mode and can be selected ventila­tion fan mode with the button.
When installing the unit, have ready the round shape hood, the air discharge grille and the air suction grille, and other parts needed for the installation. Consult your Daikin dealer when selecting optional accesso­ries.
2 English
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED.
a.
Items to be checked after completion of work
Items to be checked
Are the indoor and outdoor unit fixed firmly?
Is the outdoor duct installed to outside with down slope?
(Refer to page 8 Fig. 16)
Is the gas leak test finished?
Is the unit fully insu­lated?
Does drainage flow smoothly?
Does the power sup­ply voltage corre­spond to that shown on the name plate?
Are wiring and piping correct?
Is the unit safely grounded?
Is wiring size accord­ing to specifications?
Is something blocking the air outlet or inlet of either the indoor or outdoor units?
Are refrigerant piping length and additional refrigerant charge noted down?
Is water supplied with the water supply pip­ing connected?
Please check all items listed in the SAFETY CONSIDER­AT I ON S above once again.
b.
Items to be checked at time of delivery
Items to be checked Check
Did you explain about operations while showing the operation manual to your customer?
Did you hand the operation manual and warranty over to your customer?
c.
Points for explanation about operations
The items with WARNING and CAUTION marks in the operation manual are the items pertaining to possibilities for bodily injury and material damage in addition to the general usage of the product. Accordingly, it is necessary that you make a full explanation about the described contents and also ask your customers to read the operation manual.
If not properly done, what is likely to occur
The units may drop, vibrate or make noise.
Condensate water may drip.
It may result in insuffi­cient cooling.
Condensate water may drip.
Condensate water may drip.
The unit may malfunc­tion or the compo­nents burn out.
The unit may malfunc­tion or the compo­nents burn out.
Dangerous at electric leakage.
The unit may malfunc­tion or the compo­nents burn out.
It may result in insuffi­cient cooling.
The refrigerant charge in the system is not clear.
Not humidified.
Check

3 SELECTING INSTALLATION SITE

CAUTION
When moving the unit during or after unpacking, make sure to lift it by holding its hanger brackets. Do not exert any pres­sure on other parts, especially the refrigerant piping, drain piping, water supply piping and duct connecting flange.
If you think the humidity inside the ceiling might exceed 30°C and RH80%, reinforce the insulation on the inter-unit piping. Use glass wool or polyethylene foam as insulation so that it is no thicker than 10mm and fits inside the ceiling opening.
Use glass wool or polyethylene form of 10mm or more thick which fit into ceiling opening as insulation material.
(1) Select an installation site where the following conditions
are fulfilled and that meets with your customer’s approval.
Install in a place which has sufficient strength and stabil­ity. (Beams, ceiling, and other locations capable of fully supporting the weight of the unit.) Insufficient strength is dangerous. It may also cause vibration and unusual operating noise.
Where piping between indoor and outdoor units is possi­ble within the allowable limit. (Refer to the installation manual for the outdoor unit.)
Where nothing blocks air passage.
Where condensate can be properly drained.
Install in a location where the air around the unit or taken into the humidifier will not drop below 0°C.
Do not install the unit directly against a ceiling or wall. (If the unit is in contact with the ceiling or wall, it can cause vibration.)
Where sufficient clearance for maintenance and service can be ensured. (Refer to Fig. 1)
Unit (mm)
600
Electric parts box
l
Select the H dimension such that a downward slope of at least 1/100 is ensured as indicated in “6 DRAIN PIPING AND WATER SUPPLY WORK”.
[PRECAUTION]
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise. Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the electric noise.
The bellows may not be able to be used in some disc­tricts, so exercise caution. (Contact your local govern­ment office or fire department for details.)
When discharging exhaust air to a common duct, the Building Standard Law requires the use of fire-proof materials, so attach a 2m copper plate standing duct.
(2)
Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight of the unit or not. If there is a risk, reinforce the ceiling before installing the unit.
(Installation pitch is mentioned as follow. Refer to it to check for points requiring reinforcing.)
or more
Maintenance space
minimum hight
H
20 or more
Fig. 1
English 3

4 PREPARATIONS BEFORE INSTALLATION

(1)
Confirm the positional relationship between the unit and suspension bolts. (Refer to Fig. 2)
Leave space for servicing the unit and include inspection hatches. (Always open a hole on the side of the electric parts box so that the air filters, heat exchange elements, fans, and humidifier elements can easily be inspected and serviced.)
1764 Unit (mm)
1688
(Suspension
Exhaust air to outdoors (EA)
Fresh air from outdoors (OA)
360(If the inspection hatch is 450) 140(If the inspection hatch is 600)
Model A B
VKM50GMV1, VKM50GV1 832 878
VKM80GMV1, VKM80GV1 VKM100GMV1, VKM100GV1
(2)
Make sure the range of the units external static pres­sure is not exceeded.
(See the fan-strength and static performance characteristic drawings as well as the general catalog for the range of the external static pressure setting.)
(3)
Open the installation hole. (Pre-set ceilings)
Once the installation hole is opened in the ceiling where the unit is to be installed, pass refrigerant, drain piping, transmission wiring, and remote controller wiring to the units piping and wiring holes. See 6 DRAIN PIPING AND SUPPLY WATER WORK”,
7 REFRIGERANT PIPING WORK, and 10 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER”.
After opening the ceiling hole, make sure ceiling is level if needed. It might be necessary to reinforce the ceiling frame to prevent shaking. Consult an architect or carpenter for details.
(4)
Install the suspension bolts.
(Use M10 to M12 suspension bolts.) Use a hole-in-anchor, sunken insert, sunken anchor for existing ceilings, or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit. (Refer to Fig. 3)
Note: All the above parts are locally procured.
bolt pitch)
Indoor unit
Return air from room (RA)
Supply air to room (SA)
Electric parts box
Inspection hatches
1214 1262
Ceiling slab
Anchor bolt
Antivibration lifting lug or turn buckle
Suspension bolt
A
B
(Suspension bolt pitch )
Fig. 2
(mm)

5 THE METHOD OF INSTALLATION

CAUTION
Hold underside of the unit or hanger bracket without
〈〈
〈〈
〈〈〈〈
putting force on other parts when unpacking or moving the unit.
〈〈
〈〈As for the parts to be used for installation work, be sure to
〈〈〈〈
use the provided accessories and specified parts desig­nated by our company.〉〉
(1)
(2)
(3)
〉〉
〉〉
〉〉〉〉
〉〉
〉〉〉〉
Install the unit temporarily.
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using nuts and washers (locally pro­cured) from the upper and lower sides of the hanger bracket. (Refer to Fig. 4)
Hanger bracket
Nut Washer
Transportation anchors
If unnecessary, remove the four transportation anchors.
Loosen the screws.
Slide upward and remove the transportation anchors.
Securely tighten the screws as before.
CAUTION
The screws shouldnt be removed from the unit and should be tightened in order to prevent air from escaping. Check that foreign objects such as plastic or paper are not contained in the unit when installing.
Install the unit after checking the indoor (SA/RA) and out­door (EA/OA) in accordance with the figure duct layout precaution label.
Do not turn the unit upside down.
Adjust the height of the unit. (Tighten the double nuts securely.)
Screw
Double nut
Fig. 4
Fig. 3
4 English
(4)
Check the unit is horizontally level.
CAUTION
Use a level to make sure that the unit is level and that the tilt (downward slope) to the drain piping connection is within 1°. (Refer to Fig. 5)
(One thing to watch out for in particular is if it is installed so that the slope is not in the direction of the drain piping, as this might cause leaking.)
Level
1
Drain hole
0 or
less
10 or less
Drain hole
Level
Dact connecting flange
CAUTION
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger (Direct expantion coil).
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets from forming. (Refer to Fig. 7-2)
If converging multiple drain pipes, install according to the procedure shown below. (Install a drain trap for each indoor unit.)
Central drain piping
Horizontal line
Fig. 5
(5)
Tighten the upper nut.
(6)
Attach the accessory duct connecting flanges using the included screws to the outlet and intake holes (a total of four).
When attaching, make sure the alignment markings on the unit match up with the triangle on the each duct connecting flange. (Refer to Fig. 6)
Screws (accessory) (6pcs.×4, total 24pcs.)
Duct connecting flange marking
Unit alignment
(RA is a φ3 indentation)
Duct connecting flange
Fig. 6
Duct connecting flange
6 DRAIN PIPING AND WATER SUPPLY
WORK
(1)
Install the drain piping.
Make sure the drain works properly.
In case of the direct duct connection system, there is negative pressure inside the unit relative to atmo­spheric pressure when the unit is running, so be sure to provide drain frap on the drain outlet. (See Fig. 7-1)
Attached drain hose
Bottom of unit
100mm
or more
(Install with a downward slope of at least 1/100)
Fig. 7-2
CAUTION
Water accumulating in the drain piping can cause the drain to clog.
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe. (pipe size: PT3/4B)
When piping passes indoors, always insulate it all the way to the base of the drain socket.
In areas where freezing may occur, always take steps to prevent the pipes from freezing.
Make sure water doesnt leak from the drain pipes.
Avoid bends and curves in the pipes to prevent them getting clogged.
If you are using central drain piping, follow the procedure outlined in the figure 7-2.
Select central drain pipes of proper size according to the capacity of the connected unit.
Make sure the tip of the drain pipes opens out into a loca­tion where the drainage can be safely processed.
(2)
After piping work is finished, check drainage flows smoothly.
Test the drainage by pouring around 1000cc of water into the drain pan through the inspection hole by removing the maintenance cover (10 screws) or through the outlet duct joint of supply air to room (SA). (Refer to Fig. 8)
Supply air to room (SA)
Duct connecting flange (accessory)
Maintenance cover
Portable pump
(Locally procured)
Fig. 7-1
50 mm
or more
50 mm
or more
Drain piping
Drain outlet
(Locally procured)
Fig. 8
(3)
Make sure that heat insulation work is executed on the
(Figure shows VKM-GMV1)
following 2 spots to prevent any possibility water leak­age due to dew condensation.
Indoor drain piping
Bucket (Locally procured)
Drain outlet
English 5
(4)
Install the water supply piping. 〈〈〈VKM-GMV1 series only〉〉〉〉
CAUTION
When installing the water supply piping, wash the pipes with tap water so that all dirt is removed from them or install a drain valve somewhere along the piping and drain the pipes thoroughly until the water flowing through them is clear. Make sure no cutting oils or detergents get into the pipes.
Connect the water supply piping with strainer (acces­sory), other pipings and valves (locally procured) to the indoor unit as shown in the figure at below.
Water supply piping with strainer
(accessory)
Water supply shut-off valve
(Locally procured) Water supply pipe
(Locally procured)
Cap
(Locally procured)
Drain valve
(Locally procured)
[PRECAUTION]
When installing the water supply piping, do not pass pip­ing in front of the maintenance cover, as this will make it impossible to remove the humidifier element.
Include the water supply piping with strainer (included), a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the inspection hole.
It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type) if you need to get your water supply from public piping.
When using copper piping for the water supply connec­tions, replace the included half-union joints.
(Refer to Fig. 9)
Replacement of joints when using copper connections
Water
Flare nut
(accessory) (accessory)
Half-union joint
supply piping side
Copper piping
Y-shaped
Fig. 9
Use two spanners when attaching or removing pipes to
Exchange the included half-union joint
Remove
strainer
the half-union joints.
Secure the water supply piping without applying pressure
[PRECAUTIONS]
Use pure water (city water, tap water or equivalent) that satisfies the standard regulated by the law of each coun­try for water supply to the humidifier when performing anti-sweat work.
Dirty water may cause valves to clog, dirt to accumulate in water tanks, and resulting in poor humidifier perfor­mance. (Never use water from a cooling tower or warm water for heating.)
Make sure the supply water is between 5°C and 40°C in temperature and 0.02MPa to 0.49MPa (0.2kg/cm
2
5kg/cm2) in pressure. Include a pressure release valve between the humidifier and the strainer if the water pres­sure will be higher than this range.
Use city water or clean water and take steps to prevent condensation from forming.
to
Unit side
Also, if the supply water is hard water, use a water soft­ener because of short life. Life of humidifying element is about 3 years (4,000
hours), under the supply water conditions of hardness: 150mg/l. (Life of humidifying element is about 1 year (1,500 hours), under the supply water conditions of hardness: 400mg/l.) Annual operating hours: 10 hours / day × 26 days / month × 5 month = 1,300 hours
(5)
Insulate all piping that passes indoors.
After checking that the water supply piping connections do no leak, insulate them using the included insulation as shown in Fig. 10. (Tighten both edges with clamping material.)
(Refer to Fig. 10)
Clamp
(accessory)
Insulation (for water supply piping)
(accessory)
Wrap the water supply piping with insulation to prevent con-
Fig. 10
densation from forming.
In areas where freezing may occur, always take steps to pre­vent the pipes from freezing.

7 REFRIGERANT PIPING WORK

〈〈〈〈For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.〉〉〉 〈〈〈〈Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a water leakage can result sometimes. Use insulation that can withstand temperatures of at least 120°C. Improve insulation of refrigerant piping according to the installation environment. Condensation may form on the surface of the insulation.〉〉〉 〈〈〈〈Before refrigerant piping work, check the type of R410A refrigerant is used. (Proper operation is not possible if the types of refrigerant are not the same.)〉〉〉
CAUTION
This product must use a new refrigerant (R410A). Obey the following items.
Use a pipe cutter and flare suitable for the type of refrigerant (R410A).
Apply ester oil or ether oil around the flare portions before connectioning.
Only use the flare nuts included with the unit. Using different flare nuts may cause the refrigerant to leak.
To prevent dust, moisuture or other foreign matter from infiltrating the tube, either pinch the end or cover it with tape.
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
The outdoor unit is charged with refrigerant.
Be sure to use both a spanner and torque wrench together, as shown in the drawing, when connecting or disconnecting pipes to the unit. (Refer to Fig. 11)
Refer to the Tab l e 1 for the dimensions of flare nut spaces.
6 English
Tab l e 1
Pipe
gauge
φ 6.4
Tightening torque
14.2–17.2 N·m8.7 – 9.1
Flare dimen-
sion A (mm)
Flare shape
0
2
0
2
0
45
0
A
90
R0.4-0.8
φ12.7 49.560.3 N·m 16.2 16.6
When connecting the flare nut, coat the flare section (both inside and outside) with ester oil or ether oil, rotate three or four times first, then screw in. (Refer to Fig. 12)
Torque wrench
Ester oil or ether oil
Spanner
Flare nut
Piping union
Fig. 11
Refer to the Tabl e 1 for tightening torque.
Fig. 12
CAUTION
Over-tightening may damage the flare and cause a refrigerant leakage.
If a torque wrench is not available, tighten the nut in the fol­lowing manner. Once work is complete, make sure there is no gas leaking. As the flare nut is tightened with the wrench, the torque will suddenly increase. From that position, tighten the nut to the angle shown on Tab l e 2 ”.
Tab l e 2
Pipe size Further tightening angle
Recommended arm
length of tool
φ 6.4 (1/4”) 60 to 90 degrees Approx. 150mm
φ 12.7 (1/2”) 30 to 60 degrees Approx. 250mm
After the work is finished, make sure to check that there is no gas leak.
After checking the pipe-connection for gas leakage, be sure to insulate the liquid and gas piping. (Refer to Fig. 13)
Gas Piping Insulation Procedure
CAUTION
Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may cause condensation or burns if touched.
Connect refrigerant piping and branching according to the attached installation manuals that come with the outdoor unit.
Model
Gas piping
diameter
Liquid piping
diameter
VKM50GMV1, VKM50GV1 VKM80GMV1, VKM80GV1
φ 12.7 φ 6.4
VKM100GMV1, VKM100GV1
When brazing the refrigerant piping, perform nitrogen replacement first, or perform the brazing (note 2) while feeding nitrogen into the refrigerant piping (note 1), and finally connect the indoor unit using the flare connections.
(Refer to Fig. 14)
Pressure­reducing valve
Taping
hands valve
Nitrogen
Refrigerant piping
Part to be brazed
Nitrogen
Fig. 14
CAUTION
When brazing a pipe while feeding nitrogen inside the pipe, make sure to set the nitrogen pressure to 0.02 MPa
(0.2 kg/cm
2
) or less using the pressure reducing valve.
(This pressure is such that breeze is blown to your cheek.)
Do not use a flux when brazing the refrigerant pipe joints. Use phosphor copper brazer (BCuP-2: JIS Z 3264/B­Cu93P-710/795: ISO 3677) which does not require flux. (Using a flux containing chlorine may cause the piping to corrode. Using a welding flux containing fluorine may cause the refrigerant lubricant to deteriorate, and affect adversely the refrigerant piping system.)
Do not use anti-oxidants or other similar agent when braz­ing the pipe joints. Residue can clog the pipes and may cause breakdown of parts.
Piping insulation material (main unit)
Attach to base
Main unit
Clamp
(accessory)
Insulation for fitting (accessory)
Flare nut connection
Turn seams up
Piping insulation material (locally procured)
Mid sealing pad (accessory)
Wrap over the top of the flare nut connection.

8 DUCT CONNECTION

〈〈〈〈Perform duct work keeping the following things in mind〉〉〉
Do not connect the ducts as shown in Fig. 15.
(a) Exterme bend (b) Multi bend (d) a bend right
(Do not bend the duct over 90˚)
(c) Reduce the
diameter of the duct to be connected.
next to the outlet
Liquid Piping Insulation Procedure
Insulation for fitting (accessory)
Flare nut connection
Turn seams up
Piping insulation material (Locally procured)
Fig. 15
The minimal radius of bends for flexible ducts are as follows.
diameter halfway.)
200-mm duct : 300 mm diameter 250-mm duct : 375 mm diameter
(Do not reduce the duct
To prevent air leakage, wind aluminum tape round the sec­tion after the duct connecting flange and the duct are con­nected. (Refer to Fig. 16)
To prevent short circuit, install the opening of the indoor air
Fig. 13
Gas pipe
Liquid pipe
Piping insulation material (main unit)
Attach to base
Main unit
Clamp
(accessory)
intake as far as from the opening of the exhaust suction.
English 7
Use the duct applicable to the model of unit used (Refer to the installation drawing.)
Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water. Also, provide insula­tion for three ducts (Outdoor ducts and Indoor supply air duct) to prevent dew condensation. (Material : Glass wool of 25 mm thick) (Refer to Fig. 16)
If the level of temperature and humidity inside the ceiling is always high, install a ventilation equipment inside the ceiling.
Insulate the duct and the wall electrically when a metal duct is to be penetrated through the metal lattice and wire lattice or metal lining of a wooden structure wall.
Using flexible or silent ducts can be effective in reducing the air discharge sound of the supply air to room (SA). Select materials keeping in mind the fan strength and operating sound of the unit. Consult your Daikin dealer for selection.
Set the pitch between the exhaust air outlet (EA) and the out­side air intake (OA) to 3 times the duct diameter.
Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly. (We recommend using a deep hood (optional accessory).)
When using a deep hood, make sure the duct from the deep hood (outer wall) to the unit is at least 1m long.
Outdoor duct
Slope:
Aluminum tape (Locally procured)
Over 1/30
Make sure there
Insulation material (Locally procured)
is no slack in the duct.
Duct connecting flange
Aluminum tape
Fig. 16
The change of air discharge grill's location should be exam-
(Locally procured)
ined when the cold draft from air discharge grill is feared. The fan is driving while defrost operation, and the cold air is often blowing.
When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as with the outdoor unit, perform group-linked operation, and make the direct duct connection settings from the remote controller (Mode No. “17 (27)” – FIRST CODE NO. “5” – SECOND CODE NO. “06”) Also, do not connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure, the unit might back up.

9 ELECTRIC WIRING WORK

Shut off the power before doing any work.
All field supplied parts and materials, electric works must conform to local codes.
Use copper wire only.
All wiring must be performed by an authorized electrician.
See also the “Electrical Wiring Diagram label” attached to the electric parts box lid when laying electrical wiring.
Wire the outdoor unit and remote controller as shown in the electric wiring diagram label. See the “Remote Controller Installation Manual” for details on how to install and lay the wiring for the remote controller.
This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched. If wiring and piping between the outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
Install a wiring interrupter or ground-fault circuit interrupter for the power wiring.
Make sure the ground resistance is no greater than 100Ω . This value can be as high as 500 when using a ground fault circuit interrupter since the protective ground resistance can be applied.
Do not let the ground wire should come in contact with gas pipes, water pipes, lighting rods, or telephone ground wires.
Gas pipes: gas leaks can cause explosions and fire.
Water pipes: cannot be grounded if hard vinyl pipes are used.
Telephone ground and lightning rods: the ground poten­tial when struck by lightning gets extremely high.
Do not turn on the power supply (switch, wiring interrupter or ground fault circuit interrupter) until all other works are done.
SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
Power supply wiring
Model
Field
fuses
Wire Size Wire Size
VKM50GMV1, VKM50GV1
VKM80GMV1, VKM80GV1
15A
H05VV-
U3G
Follow
standards
VKM100GMV1, VKM100GV1
NOTE
If the wiring is in a place where people it can be easily touched by people, install a leak interrupter to prevent electric shock.
When using a ground-fault circuit interrupter, make sure to select one useful also to protection against overcurrent and short-circuit. If you use a leak interrupter which is designed for protect­ing again ground faults, be sure to combine it with a wir­ing interrupter or an load switch that has a fuse.
The length of the transmission wiring and remote control­ler wiring are as follows.
Length of outdoor-indoor transmission wiring max 1000m (total wiring length 2000m)
Length of remote controller wiring between indoor unit and remote controller max 500m
Remote controller wiring
Transmission wiring
Sheathed
local
(2 wire)
wire
0.75-1.25
2
mm
ELECTRICAL CHARACTERISTICS
Units Power supply Fan motor
220-
240V
Voltage
range
Max.
264V
Min.
198V
MCA MFA kW FLA
4.3 15
4.3 15
4.3 15
0.28×2
0.28×2
0.28×2
1.9×2
1.9×2
1.9×2
Model
Hz Volts
VKM50GMV1, VKM50GV1
VKM80GMV1, VKM80GV1
50
VKM50GMV1, VKM50GV1
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)
8 English
10 WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
10. 1 OPENING AND SHUTTING THE ELECTRIC PARTS BOX AND CONNECTING THE WIRING
CAUTION
Be sure to power off before opening the electric parts box.
Remove the electric parts box lid and wire as shown in the figure below.
SS1 is the switch for setting the remote controller. The unit will not run if the settings are changed.
Space for installation of adapter PC board (KRP2A1)
Do not change the switch settings.
Factroy setting
X1M
A1P
A2P
X3M
A3P
NOR. H
SS1
M
Space for installation of adapter PC board (KRP50-2)
Clamp
(accessory)
Resin Clamp parts
10. 2 Connecting power supply wiring and ground wiring
Pass the power supply wiring and the ground wiring through the wiring through-hole into the electrical parts box and secure with the included clamping material after connecting the wires to terminal blocks. (Refer to Fig. 17-1, 17-2)
VKM-GMV1 series
Terminal block (X1M) details
Short-circuit wire
Remove when installing the humidistat (locally procured).
Fig. 17-1
VKM-GV1 series
Terminal block (X1M) details
1
Clamp (accessory)
2
L
N
Grounging terminal
(M4 screws, spring washers, cup washers)
Resin Clamp parts
Power supply wiring Ground wiring
Wiring for the humidistat
Grounging terminal
(M4 screws, spring washers, cup washers)
Transmission wiring Electric parts box lid
See Electrical Wiring Diagram label on the backside of the lid of the electric parts box for electric wiring work.
Be sure to attach the sealing material or putty (locally pro­cured) to hole of wiring to prevent the infiltration of water as well as any insects and other small creatures from outside. Otherwise a short-circuit may occur inside the electric parts box.
When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps. Also, when wiring, make sure the lid on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box lid firmly. When attaching the electric parts box lid, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent damage to them.
Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass through the same locations outside of the unit, separating them by at least 50mm, otherwise electrical noise (external static) could cause mistaken operation or breakage.
Power supply wiring and Ground wiring
NOTE) A3P: VKM-GMV1 series only
CAUTION
through-hole
Power wiring through-hole
L
N
Clamp
Fig. 17-2
Precautions when laying power supply wiring
〈〈〈〈
[PRECAUTIONS]
[1] A circuit breaker capable of shutting down power supply to
the entire system must be installed.
[2] A single switch can be used to supply power to units on the
same system. However branch switches, branch overload circuit interrupter must be selected carefully.
[3] Fit the power supply wiring of each unit with a switch and
fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE
Power supply
(accessory)
VRV Outdoor unit
Resin Clamp parts
Power supply wiring Ground wiring
〉〉〉〉
Power supply wiring Sheathed cable (H05VV-03G)
Transmission wiring Sheathed cable
Switch
Fuse
VRV Indoor unit
VRV Indoor unit
Remote controller
English 9
HRV (VKM)
HRV (VKM)
[4] Use round crimp-style terminals for connecting wires to the
power supply terminal block. If unavailable, observe the following points when wiring.
Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection may cause overheating.)
Use the specified electric wire. Connect the wire securely to the terminal. Lock the wire down without applying excessive force to the terminal. (Tightening torque: 131N·cm ±10 %)
Attach insulation sleeve
Round crimp-style terminal
Electric wire
[5] Tightening torque for the terminal screws.
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
Tightening torque (N·m)
Treminal block for remote controller/ Transmission wiring (X3M)
Power supply terminal block (X1M)
Ground terminal (M4)
0.79 – 0.97
1.18 – 1.44
1.44 – 1.94
〈〈〈〈Precautions when connecting the ground〉〉〉〉
When pulling the ground wire out, wire it so that it comes through the cut out section of the cup washer. (An improper ground connection may prevent a good ground from being achieved.)
Round crimp-style terminal
Cup washer
Spring washer, flat washer
Ground screw
Cut out section
10. 3 Remote power supply wiring, transmission wir­ing, computerised control wire
Pass the remote control wiring, the transmission wiring, and the computerised control wire into the electric parts box through the through-hole and connect to the terminals on the X3M terminal block. After connection, secure with the included cramping material.
(Refer to Fig. 18)
Detail of terminal block (X3M)
P1 P2 F1 F2 T1 T2
REMOTE
TRANSMISSION
CONTRL
WIRING
FORCED
OFF
Clamp
(accessory)
Remote controller wiring Transmission wiring
Fig. 18
[PRECAUTIONS]
Refer to the Remote Controller Installation Manual on how to install and lay the wiring for the remote controller.
Do not, under any circumstances, connect the power wiring to the remote controller or transmission wiring terminal block. Doing so can destroy the entire system.
Connect the remote controller and transmission wiring their respective terminal blocks.
10. 4 Wiring for the humidity regulator (locally procured)
Pass into the electric parts box together with the power wire through the power wiring through-hole.
Remove the short-circuit wires (1 and 2) on the X1M terminal block and connect the wiring for the humidity regulator.
Secure with cramping material together with the power wire. (Refer to Fig. 17-1)
Wiring specifications Sheathed wire (2 wire)
Size
Length MAX. 100m
External contact specifications
VKM-GMV1 series only〉〉〉〉
〈 〈
0.75 - 1.25mm
2
Normally closed contact (Current tolerance 10mA – 0.5A)
CAUTION
〈〈〈〈VKM-GMV1 series only〉〉〉〉
If using humidistat, install one per HRV unit. Controlling more than one HRV unit with a single humidity controller may prevent normal humidity operation and cause water leakage, etc.
10. 5 WIRING EXAMPLE
This unit can be used as part of the combined operation sys­tem used together with indoor units (VRVII system air condi­tioners), or as a independent system for processing outside air.
When connecting with a cooling free building multi type and bringing the RA (exhaust gas intake) of this unit directly in from the ceiling, connect to a BS unit identical to the building multi indoor unit (master unit), and use group-linked opera­tion. (See the Engineering Data for details.)
10 English
Combined operation system with VRVII system (connected with HRV units and standard indoor units in a single
〈〈〈〈
circuit
)
〉〉〉〉
Outdoor unit
Electric parts box
IN/D OUT/D
F1 F2 F1 F2
Power supply
220-240V
~
50 Hz
Switch
Fuse
Power supply
220-240V
~
50 Hz
Switch
Fuse
Power supply
220-240V
~
50 Hz
Switch
Fuse
refrigerant
Transmission wiring
Remote controller
Remote controller wiring
Remote controller
HRV A (outside air processing type)
Earth
Earth
RS
P1 P2 F1 F2 T1 T2
Standard indoor unit A
Earth
LN
P1 P2 F1 F2 T1 T2
〈〈〈〈Independent system (connected only with a HRV unit in a single refrigerant circuit)〉〉〉〉
Outdoor unit
Electric parts box
IN/D OUT/D
F1 F2 F1 F2
Power supply
220-240V
~
50 Hz
Switch
Fuse
Power supply
220-240V
~
50 Hz
Switch
Fuse
Transmission wiring
LN
P1 P2 F1 F2 T1 T2
Power supply
220-240V
~
50 Hz
Switch
Fuse
HRV B (outside air processing type)
Remote controller
LN
P1 P2 F1 F2 T1 T2
Earth
NOTE) Standard type ........ VAM series
〈〈〈〈When including a BS unit〉〉〉〉
HRV A (Outside air processing type)
Earth
Power supply
220-240V
~
50 Hz
Remote
Switch
controller
Fuse
Remote controller wiring
LN
P1 P2 F1 F2 T1 T2
HRV B (Outside air processing type)
Outdoor unit
Electric parts box
IN/D OUT/D
F1 F2 F1 F2
Transmission wiring
BS unit
Electric parts box
OUT/D IN/D
F1 F2 F1 F2
RS
P1 P2 F1 F2 T1 T2
Earth
LN
Earth
HRV A (outside air processing type)
P1 P2 F1 F2 T1 T2
HRV C (Outside air processing or standard type) NOTE)
English 11
[PRECAUTIONS]
There is not need to set the indoor unit address when using group control. (It is automatically set when the power is turned on. ) However, since the HRV (outside air processing type) uses two remote control addresses per unit, the number of units which can be group controlled is as follows.
No. of indoor air conditioner units
No. of HRV units
01234567891011121314
877665544332211
[PRECAUTIONS]
Crossover wiring is needed when using group control and 2 remote controllers at the same time.
Connect the indoor unit at the end of the crossover wire (P1, P2) to remote controller 2 (slave).
Max. No. of
Indoor unit 1
Indoor unit 2
indoor units
10. 6 CONTROL BY 2 REMOTE CONTROLLERS (Controlling 1 indoor unit by 2 remote control­lers)
When using 2 remote controllers, one must be set to “MAIN” and the other to “SUB”.
MAIN / SUB CHANGEOVER
(1)
Insert a screw driver into the recess between the upper and lower part of remote controller and, working from the 2 positions, pry off the upper part.
(The remote controller PC board is attached to the upper part of remote controller.)
Upper part of remote controller
Lower part of remote controller
Insert the screwdriver here and gently work off the upper part of remote controller.
(2)
Turn the MAIN/SUB changeover switch on one of the two remote controller PC boards to “S”.
(Leave the switch of the other remote controller set to “M”.)
S
(Factory setting)
S
M
Crossover wire (P1 Remote controller 1
(MAIN)
.
2)
P
Remote controller 2 (SUB)
10. 7 COMPUTERISED CONTROL (FORCED OFF AND ON/OFF OPERATION)
Wire specifications and how to perform wiring Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.
F2 T1 T2
FORCED OFF
Input A
Wire specification Sheathed wire (2 wire)
Gauge
0.75 - 1.25 mm
Length Max. 100 m
External terminal
Actuation
Contact that can ensure the minimum applicable load of 15 V DC, 1 mA.
The following table explains FORCED OFF and ON/OFF OPERATIONS in response to Input A.
FORCED OFF ON/OFF OPERATION
Input ON stops operation (impos­sible by remote controllers.)
Input OFF enables control by remote controller.
2
Input OFF ON turns ON unit.
Input ON OFF turns OFF unit.
Only one remote controller needs to be changed if factory settings have
Remote controller PC board
S
M
How to select FORCED OFF and ON/OFF OPERATION Enter the FORCED OFF and ON/OFF OPERATION selection using the local external start/stop input settings based on
11 FIELD SETTING AND TEST RUN
remained untouched.
10. 8 Central control
〈〈〈〈Wiring Method
(See ‘‘ELECTRIC WIRING WORK’’)
〉 〉
(1) Remove the electric parts box lid.
(2) Add remote controller 2 (slave) to the terminal block for
1
remote controller (P
, P2) in the electric parts box.
(There is no polarity.)
TRANSMISSION
WIRING
FORCED
OFF
T
1P2P1F2F1T2
REMOTE CONTRL
Remote controller wiring terminal block
Remote controller 1 (MAIN)
Remote controller 2 (SUB)
12 English
If control is performed with a central device (central manage­ment controller, etc.), group number needs to be set with the remote controller. See the manual of each central device for detail.
10. 9 FRESH-UP OPERATION BY EXTERNAL INPUT (HRV UNIT)
PURPOSES AND FUNCTIONS
When the operation is interlocked with the local ventilating fan(such as the one for toilet or kitchen), the HRV unit performs the over-supply operation to prevent inflow of the odor from out­side. The flow rate of supply air becomes higher than that of exhaust air. Both the excessive supply mode(Supply Fresh-up)and the excessive exhaust mode (Exhaust Fresh-up) are selectable. In details, contact your dealer.
EXAMPLE OF CONTROL WIRING
Connecting line can be extended up to 50m maximum.
JC
J1 J2 F1 F2
P1P2
HRV unit
P1P2
Remote controller
Local wiring
Operation of HRV unit
Terminal for local connection
Fresh-up Short-circuit
Normal Open circuit
(Terminal for local connection)
Capacity of con­necting terminal
No-voltage nor­mally open contact for micro-current 12V, 1mA
Note:
The connecting wiring between HRV unit and the terminal for local connection can be extended up to 50m maximum.
(3) To make settings for individual units under group control
(when mode No. 27, 28 or 29 is selected), press the TIMER SETTING ON/OFF button to select the unit No.” for which the settings are to be made. (This process is not necessary when settings are made for the entire group.)
(4) Press the top section of the TIMER button to select the
FIRST CODE NO.”
(5) Press the lower section of the TIMER button to select
SECOND CODE NO.”
(6) Press the PROGRAM/CANCEL button once to enter the
settings. (The code display will stop blinking and light up.)
(7) Press the INSPECTION/TRIAL button to return to normal
mode.
UNIT No.
GROUP
11 FIELD SETTING AND TEST RUN
11. 1 Perform field settings with the remote controller.
(1)
Make sure the electric parts box lids are closed on the indoor and outdoor units.
(2)
Depending on the type of installation, make the field settings from the remote controller after the power is turned on, following the Field Settings manual which came with the remote controller.
Lastly, make sure the customer keeps the Field Settings manual, along with the operating manual, in a safe place.
SECOND CODE NO.
FIRST CODE NO.
11. 1. 1
Field setting
SETTING
Using the remote controller of the VRV-system air conditioner to make HRV unit settings
〈〈〈〈Initial setting〉〉〉〉
Mode No.” 17,18 and 19: Group control of HRV units.
Mode No.” 27, 28 and 29: individual control
〈〈〈〈Operating procedure〉〉〉〉 The following describes the operating procedure and settings.
(1) Press the INSPECTION/TRIAL button for more than four
seconds with the unit in the normal mode to enter the local setting mode.
(2) Use the TEMPERATURE ADJUSTMENT button to select
the desired Mode No.” (The code display will blink.)
Mode No.
FIELD SET MODE
2
6
〈〈〈〈Example〉〉〉〉
When adjusting the ventilation air flow to low setting in the group setting mode, enter the Mode No., “19” FIRST CODE NO., “0” and SECOND CODE NO., 01”.
English 13
■■■■Settings and setting numbers
Mode
FIRST
No.
1
17
(27)
17
(27)
12
(22)
12
(22)
15
(25)
18
(28)
19
(29)
1A
43 45
CORD
01 02 03 04 05 06 07
NO
.
App-
rox.
0
2500
hours
1
OFF2 hours
Nor-
4
mal Not
direct
duct
(Air
5
flow
set-
ting)
Air
flow
5
set­ting
High
6
For-
ced
1
off
No
equ-
5
ipp-
ed
1
No Yes
Indi-
4
cat­ion
No
Indication
7
Supply Exhaust Supply Exhaust
Fresh- upOverall
8
Fan
9
on/off
0
LowLowLowLow
Auto-
2
matic
Off On
Description of setting
Filter cleaning time setting NOTE) 5
Nighttime free cooling operation setting (Time after air condi­tioning is stopped.) NOTE) 5
Fan speed initial setting
Direct duct connec­tion with VRV setting
Setting for cold areas (Fan operation selec­tion for heater thermo OFF) NOTE) 6
Ventilation air flow setting when Nighttime free cooling setting
ON/OFF input from Outside (Set when ON/OFF is to be controlled from outside)
Power faillure automatic reset (Auto Restart)
Humidification on/off when heating thermo is off
Indication of ventilation mode/Not indication
Fresh up air supply/ exhaust setting
External input termi­nal function selection (between J1 and JC) NOTE) 7
KRP50-2 output switching selection (between 1 and 3)
Ventilation air flow setting
Ventilation mode setting
Fresh-up operation Forced fan on Unit no. allocation
SECOND CORD NO.
App-
No
rox.
1250
hours
later
Ultra
high
With
direct
duct
(fan
off)
Air flow set­ting
Ult-
ra-
High
ON/ OFF con-
trol
Equ-
ipp-
ed
No Indi­cat-
ion
alarm
Abno-
rmal
Ex-
change
––––
coun-
ting
4
6
hours
hours
hours
later
later
later
–––––
Not
direct
duct
(Air
flow set-
ting)
Fan
L
–––––
–––––
–––––
–––––
–––––
Indication
–––
–––––
High High
By-
pass
–––––
8
––
With direct duct
–––
(fan
off)
Fan
L
Air flow
incre-
ase
NOTE)
1. The inside the frame indicates the second code no. set when shipped from factory.
2. The settings are applied to the entire group, but if the mode no. inside the parentheses is selected, the settings can be applied to individual indoor units. However, it is only possible to check any changes made to the settings inside the parentheses in individual mode. (For group batch operation, the changes are made but the dis­play remains as it was when shipped from the factory.)
3. Do not set anything not shown above. If the applicable func­tions are not available, they will not be displayed.
4. When returning to normal mode, the remote controller is ini­tialized, so the display might show “88.
5. When Filter cleaning time setting or Nighttime free cooling operation setting is changed, explain set contents to the customer.
6. See below for details on the settings for cold areas. – : operate at the set fan strength
Air conditioner fan Heating thermo off Operation Defrost Stop Oil return Stop
In case of Independent operation
Air conditioner fan Heating thermo off Operation Defrost Stop Oil return Stop
– : operate at the set fan strength L : operate at the weak fan strength
: Stop
S
Defrost operation
In heating operation, freezing of the outdoor unit’s coil increases. Heating capability decreases and the system goes into defrost operation.
The remote controller will read “” until the hot air starts blowing.
It returns to the heating operation again after 6 to 8 minutes (10 at the longest).
During defrost operation, the fans of the unit continues driv­ing (factory setting). The purpose of this is to maintain the amount of ventilation and humidifying.
The change of air discharge grills location should be exam­ined when the cold draft from air discharge grill is feared.
Though the fan can be stopped by the setting of remote controller. Do not stop the fan in the place where no ventilation by stop­ping the fan may cause the influence of diffusion of air which it is dirty and moisture into another room, or the inflow from outside the room. (outflow such as viruses from the sickroom, or smell leakage from the rest room, etc.)
7. See below for details on the external input terminal function.
SECOND CODE NO.
SECOND CODE NO. “04 does not function when in air condi-
tioner linked mode.
01
02
06
Input contact
a
a
a
Fan operation
Operation On Fresh-up operation
Operation On
Operation On
Operation lamp
01 02 04 06
–– –
Stop Stop Stop
Stop Stop Stop
01 02 04 06
–– –– ––
Malfunction code “60” is displayed
Fan strength up (Low to High, High to Ultra-High)
LL
LL Stop Stop Stop Stop
14 English
11. 2 Perform a test run according to the outdoor units installation manual.
(1) Make sure the electric parts box of the unit is closed
before turning on power.
(2) Make a test run following the operation manual of the
outdoor unit.
The operation lamp of the remote controller will flash when an malfunction occurs. Check the malfunction code on the liquid crystal display to identify the point of trouble. An explanation of malfunction codes and the correspond­ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit. If the display shows any of the following, there is a possi­bility that the wiring was done incorrectly or that the power is not on, so check again.
Remote controller display
“” is display
“” is display
“” is display
“” is display
“” is display
No display
There is a short circuit at the FORCED OFF terminals (T1, T2)
The test-run has not be performed.
The power on the outdoor unit is off.
The outdoor unit has not been wired for
power supply.
Incorrect wiring for the transmission wiring and the wiring the remote con­troller wiring or FORCED OFF wiring.
The transmission wiring is cut.
•“MAIN/SUB” setting of the remote
controller is wrong.
The power on the indoor unit and HRV is off.
The indoor unit and HRV has not been wired for power supply.
Incorrect wiring for the remote control­ler wiring and the wiring the transmis­sion wiring or the FORCED OFF wiring.
The remote controller wiring is cut.
Content
11. 3 Next, run the humidifier.
〈〈〈〈VKM-GMV1 series only〉〉〉〉
Check that the water supply piping is connected securely.
(1) (2) Open the water supply shut-off valve. (No water will be
supplied at this time.)
(3) Run the HRV unit in heating mode.
(See the operating manual included with the indoor unit for details on how to run the unit in heating mode.) The water supply will start and the humidifier will begin operation.
(4) After starting heating (humidifying), the sound of the
water supply solenoid valve will be heard every 3 or 4 minutes (a clicking sound), so listening for that clicking sound let the unit run for 30 minutes to make sure that humidifying operation is normal.
CAUTION
If carpentry work is not completed when a test run is fin­ished, tell the customer not to run the humidifier for the pro­tection of indoor unit and HRV until it is completed.
If the humidifier is run, paint, particles generated from adhesive and other materials used for carpentry work may cause HRV to get dirty, causing splash or leakage of water.
English 15
12 WIRING DIAGRAM
Note) 7
Note) 7
Note) 9

WIRING DIAGRAM

~
50Hz
220-240V
POWER SUPPLY
Note) 3
TO CONNECTION WIRING AND
CENTRAL REMOTE
Note) 6
INPUT FROM OUTSIDE
Note) 8
Note) 5
INPUT
FROM
OUTSIDE
CONTACT
CAPACITY
EXTERNAL OUTPUT
TERMINALS
Note) 4
ADAPTER PC BOARD FOR WIRING
(OPTIONAL ACCESSORIES)
CONTROLLER UNIT
WIRED REMOTE CONTROLLER
(OPTIONAL ACCESSORIES)
VKM50·80·100GMV13D047684-1
: SHORT CIRCUIT CONNECTOR
,
CONTROL BOX
TERMINAL BLOCK
(POWER SUPPLY)
TERMINAL BLOCK
(CONTROL)(A3P)
TERMINAL BLOCK
(CONTROL)(A1P)
TERMINAL BLOCK
(CONTROL)
X1M
PRINTED CIRCUIT BOARD
PRINTED CIRCUIT BOARD
X2M
X1M,X2M
PRINTED CIRCUIT BOARD
(ADAPTOR FOR WIRING)
X3M
CAPACITOR (M1F, M2F)
FUSE ( B , 10A, 250V)(A1P)
FUSE ( B , 5A, 250V)(A2P)
FUSE ( B , 5A, 250V)(A3P)
CONNECTOR
(RELAYING WIRE)
CONNECTOR
(RELAYING WIRE)
ELECTRONIC EXPANSION
VALVE
FEED WATER SOLENOID
VALVE
Y1E
X17A,X19A
X20A
THERMO SWITCH
(152˚C)(M1F, M2F BUILT-IN)
LIGHT EMITTING DIODE
Y2S
(SERVICE MONITOR-GREEN)(A1P)
LIGHT EMITTING DIODE
(SERVICE MONITOR-GREEN)(A2P)
MAGNETIC RELAY (M1F)(A1P)
MAGNETIC RELAY (M2F)(A1P)
: TERMINAL BLOCK, : TERMINAL, : CONNECTOR,
Notes)
(KRP50-2)
SELECTOR SWITCH
(MAIN/SUB)
OPTIONAL ACCESSORIES
WIRED REMOTE CONTROLLER
ADAPTOR PC BOARD FOR WIRING
SS1
MAGNETIC RELAY (M1D)(A1P)
MAGNETIC RELAY (S1L)
MAGNETIC RELAY (A3P)
MAGNETIC RELAY (A3P)
MOTOR (DAMPER MOTOR)
MOTOR (SUPPLY AIR FAN)
(FOR HUMIDIFIER OPERATION)
MAGNETIC RELAY
(OPERATION/STOP)
MAGNETIC RELAY
Ry1
Ry2
MOTOR (EXHAUST AIR FAN)
THERMISTOR (INDOOR AIR)
THERMISTOR (OUTDOOR AIR)
THERMISTOR
REMOTE CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
SELECTED BY REMOTE CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
AND (2) AS SHOWN IN THE FIGURE RIGHT.
REMOVED.
INSTRUCTION MANUAL.
MANUAL.
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
1.
2. : FIELD WIRING
4. IN CASE USING WIRING ADAPTER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FRESH UP CONTROL OPERATION CAN BE SELECTED BY
6. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE
7. IN CASE INSTALLING A HUMIDISTAT S1H (LOCALLY PROCURED), REMOVE THE SHORT CIRCUIT WIRING BETWEEN (1)
OPTIONAL PARTS
CONNECTOR FOR
CONNECTOR
(ADAPTER POWER
SUPPLY)(A1P)
CONNECTOR
(WIRING ADAPTER FOR
TERMINAL BLOCK
(FOR EXTERNAL OUTPUT)
Tes10
(INLET AIR INTO COIL)
X11A
THERMISTOR
(LIQUID/GAS PIPE OF COIL)
FLOAT SWITCH (HUMIDIFIER)
LIMIT SWITCH
(DAMPER MOTOR)
SELECTOR SWITCH
ELECTRICAL APPENDICES)(A2P)
LOCAL SUPPLIED PARTS
X18A
(FOR ESPECIALLY USE )(A1P)
SELECTOR SWITCH
(HUMIDISTAT INPUT )(A3P)
TRANSFORMER
ARE CHANGED.
8. DO NOT REMOVE THE SHORT CIRCUIT CONNECTORS OF X8A AND X9A, THE UNIT WILL NOT RUN IF THEY ARE
9. SS1 (A3P) HAS ALREADY BEEN SET TO OFF AT FACTORY SET. HUMIDIFYING BECOMES IMPOSSIBLE, IF THE SETTING
HUMIDISTAT
S1H
(220-240V/22V)
TRANSFORMER
(220-240V/22V)
BLK: BLACK RED: RED GRN: GREEN)
CHANGED.
10. SS1(A1P) HAS ALREADY BEEN SET TO “NOR.” AT FACTORY SET. THE UNIT WILL NOT RUN IF THE SETTING ARE
11. SYMBOLS SHOW AS FOLLOWS. (PNK: PINK WHT: WHITE YLW: YELLOW ORG: ORANGE BLU:BLUE
12. USE COPPER CONDUCTORS ONLY.
A1P
A2P
A3P
C1·C2
F1U
F1U
F1U,F2U
R1T
R2T
K7R
HAP
HAP
F2UT
F1UT·
K1R~K3R
K8R
K4R~K6R
M1D
KHR,KHuR
KCR,KFR
M1F
M2F
R3T
S1L
R4T,R5T
S1Q
SS1
SS1
T1R
T2R
16 English
Note) 3
TO CONNECTION WIRING AND
CENTRAL REMOTE
CONTROLLER UNIT
Note) 6
INPUT FROM OUTSIDE
WIRED REMOTE CONTROLLER
(OPTIONAL ACCESSORIES)
VKM50·80·100GV13D048372-1
WIRING DIAGRAM
POWER SUPPLY
~
50Hz
220-240V
Note) 7
Note) 5
INPUT
FROM
OUTSIDE
CONTACT
CAPACITY
EXTERNAL OUTPUT
TERMINALS
Note) 4
ADAPTER PC BOARD FOR WIRING
(OPTIONAL ACCESSORIES)
Note) 8
: SHORT CIRCUIT CONNECTOR
,
CONTROL BOX
: TERMINAL BLOCK, : TERMINAL, : CONNECTOR,
1.
Notes)
MANUAL.
REMOTE CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
SELECTED BY REMOTE CONTROLLER, IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
REMOVED.
CHANGED.
INSTRUCTION MANUAL.
2. : FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
4. IN CASE USING WIRING ADAPTER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FRESH UP CONTROL OPERATION CAN BE SELECTED BY
6. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE
7. DO NOT REMOVE THE SHORT CIRCUIT CONNECTORS OF X8A AND X9A, THE UNIT WILL NOT RUN IF THEY ARE
BLK: BLACK RED: RED GRN: GREEN)
8. SS1(A1P) HAS ALREADY BEEN SET TO NOR. AT FACTORY SET. THE UNIT WILL NOT RUN IF THE SETTING ARE
9. SYMBOLS SHOW AS FOLLOWS. (PNK: PINK WHT: WHITE YLW: YELLOW ORG: ORANGE BLU:BLUE
10. USE COPPER CONDUCTORS ONLY.
(KRP50-2)
OPTIONAL PARTS
TERMINAL BLOCK
(POWER SUPPLY)
TERMINAL BLOCK
(CONTROL)(A1P)
TERMINAL BLOCK
(CONTROL)
CONNECTOR
(RELAYING WIRE)
CONNECTOR
X1M
X2M
X3M
X17A,X19A
PRINTED CIRCUIT BOARD
PRINTED CIRCUIT BOARD
CAPACITOR (M1F, M2F)
FUSE ( B , 10A, 250V)(A1P)
FUSE ( B , 5A, 250V)(A2P)
F1U
C1·C2
F1U
F1UT·
A1P
A2P
(SERVICE MONITOR-GREEN)(A1P)
THERMO SWITCH
(152˚C)(M1F, M2F BUILT-IN)
LIGHT EMITTING DIODE
HAP
F2UT
SELECTOR SWITCH
(RELAYING WIRE)
ELECTRONIC EXPANSION
VALVE
Y1E
X20A
LIGHT EMITTING DIODE
(SERVICE MONITOR-GREEN)(A2P)
MAGNETIC RELAY (M1F)(A1P)
HAP
K1R~K3R
(MAIN/SUB)
OPTIONAL ACCESSORIES
WIRED REMOTE CONTROLLER
ADAPTOR PC BOARD FOR WIRING
SS1
MAGNETIC RELAY (M2F)(A1P)
MAGNETIC RELAY (M1D)(A1P)
MOTOR (DAMPER MOTOR)
MOTOR (SUPPLY AIR FAN)
MOTOR (EXHAUST AIR FAN)
K7R
M1F
M2F
M1D
K4R~K6R
MAGNETIC RELAY
(OPERATION/STOP)
MAGNETIC RELAY
Ry1
Ry2
THERMISTOR (INDOOR AIR)
THERMISTOR (OUTDOOR AIR)
THERMISTOR
(INLET AIR INTO COIL)
THERMISTOR
R1T
R2T
R3T
R4T,R5T
CONNECTOR FOR
CONNECTOR
(ADAPTER POWER
SUPPLY)(A1P)
CONNECTOR
(FOR HUMIDIFIER OPERATION)
TERMINAL BLOCK
(FOR EXTERNAL OUTPUT)
Tes10
(LIQUID/GAS PIPE OF COIL)
LIMIT SWITCH
S1Q
X11A
(DAMPER MOTOR)
SELECTOR SWITCH
(FOR ESPECIALLY USE)(A1P)
SS1
(WIRING ADAPTER FOR
X18A
TRANSFORMER
(220-240V/22V)
TRANSFORMER
(220-240V/22V)
T1R
T2R
ELECTRICAL APPENDICES)(A2P)
English 17
3P130768-1B
EM03A096A
(0504)
FS HT
Loading...