Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
For any inquiries, contact your local distributor.
PCH0601
HE AT R ECL A IM V EN T IL A T ION
Combined Air Conditionin g and V entilation
for Energy Efficiency and Com fort
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an
outdoor unit with anti-corrosion treatment.
The air conditioners manufactured
by Daikin I ndustries have
received IS O 9001 certification for
quality assurance.
Certificate Number.
JMI-0107
JQA-0495
JQA-1452
All Daikin Industries locations
and subsidiaries in J apan have
received environmental
management system s tandard
ISO 14001 certification.
Daikin Industries, Ltd.
Domestic Group
Certificate Number. EC99J2044
Dealer
The specifications, designs, and information in this brochure are subject to change without notice.
About ISO 14001
ISO 14001 is the standard defined by the
International Organization for Standardization (I SO)
relating to environmental management s ystems.
Our group has been acknowledged by an
internationally accredited compliance organisation
as having an appropriate programme of
environmental protection procedures and activities
to meet the requirements of I SO 14001.
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c
All rights reserved
Printed in Japan 05/06/003 Y.K.
Printed on 100% recycled paper with soy ink.
Page 2
Daikin's HRV (Heat Reclaim Ventilation) recovers heat energy lost through ventilation
and holds down room temperature changes caused by ventilation, thereby maintaining a
comfortable and clean environment. This also curbs the load on the air conditioning
system and conserves energy.
In addition, the HRV is interlocked to Daikin's VRV system, SkyAir and other air
conditioning systems and automatically switches over ventilation mode, further increasing
the effects of energy conservation. HRV operation has been centralized on the air
conditioner remote controller allowing total control over air conditioning and ventilation
with a simple configuration.
V A M -G J S e rie s R e le a s e d!
9 M od e ls t o C ho o s e F ro m !
Improved Enthalpy Efficiency
Improved Enthalpy Efficiency
Higher External Static Pressure
Higher External Static Pressure
Enhanced Energy Saving Functions
Enhanced Energy Saving Functions
1
2
For models: VAM150/250/350/650/800/1000/2000GJVE
1
For models: VAM150/350/500GJVE
2
Daikin air conditioner
Indoor unit
LCD remote controller
for indoor unit
• Operating mode signal
• Filter cleaning signal
• Failure detection signal
Model Lineup
Model SeriesModel Series
• ON/OFF signal
• Cooling/Heating mode signal
• Set temperature signal
• Ventilation signal
• Humidifier ON/OFF signal
InterlockingInterlocking
HRV
Air flow rate (m3/h)
150 250 350 500 650 800 1000 1500 2000
VAM-GJ
Page 3
F e a t u r e s o f D a ik in H RV
V A M -G J S e rie s
This series provides higher enthalpy efficiency,
due to the greatly enhanced performance of the
new ultra-thin film element. Furthermore,
improved external static pressure offers more
2
flexibility for installation. Along with these three
improvements, Daikin’s exclusive function
—nighttime free cooling operation—contributes
to energy conservation and more comfortable
space.
Enthalpy efficiency dr astically impr oved!
Enthalpy efficiency dr astically impr oved!
Introduction of ultra-thin film element significantly increases enthalpy efficiency!
Enthalpy efficiency improved
Adoption of the ultra-thin film element leads to highly improved enthalpy efficiency.
Achieving higher enthalpy efficiency
VAM-FA
Previous model
VAM-GJ
Model
Ultra-thin film element
1
Outdoor air
1
1
Exhaust air
For models: VAM150/250/350/650/800/1000/2000GJVE
1
For models: VAM150/350/500GJVE
2
1
58
FA
66
GJ
58
FA
For models: VAM150/250/350/650/800/1000/2000GJVE
1
66
64
62
60
58
56
Cooling: Enthalpy efficiency (%)
Return air
Supply air
I
m
1
(For ultra high cooling operation)
64
GJ
61
GJ
6501501000
61
FA
VAM650GJ
p
rov
e
(Air flow type)
d
Higher external static pressure
Higher external static pressure
External static pressure has been significantly increased by adopting a new type of fan.
High external static pressure design adopting efficient fan performance
2
2
I
m
pro
ved
Improvements to the fan, including the use of multi-arc blades and optimized fan sizes, help boost efficiency.
Comparison of external static pressure
(For ultra high operation)
High external static
pressure is realized
even below the
rated air flow!
300
250
VAM350GJVE
Exchange efficiency
90
80
70
40m
60
50
30m
(%)
!
200
External static pressure
increased by 80 Pa
(for 60 Hz operation)
External static pressure (Pa)
150
VAM350FAVE
100
External static pressure
increased by71 Pa
50
(for 50 Hz operation)
0
100
200400600
300
Ener gy conser vation and comfor table air space
Ener gy conser vation and comfor table air space
500
Air flow rate
Nighttime free cooling operation
(m3/h)
20m
150
Pipe
length
10m
For models: VAM150/350/500GJVE
2
50Hz,220–240V
60Hz,220V
VAM-GJ Model
VAM-FA Previous model
The partition sheet in the heat exchanger element has been significantly upgraded. It is approximately two-third
thinner than the conventional type, resulting in a great improvement in moisture absorption!
Air conditioning sensible
heat load reduced by
No operation
Not operatingNot operating
Previous element (FA model)Ultra-thin film element
Moisture absorption is less effective
due to the thickness of the partition
sheets. It also limits the effective
area that supply and exhaust air can
be exposed to.
OutdoorIndoor
SA
RA
(unclean
indoor air)
34
Thickness of
the partition sheet
Exhaust air
Outdoor air
(fresh air)
Due to the thinner film…
•Decreases the moisture resistance of the partition sheets
drastically.
•Realizes more space for extra layers in the element, resulting
in increased effective area that supply and exhaust air can be
exposed to.
Moisture absorption increased by approx. 10%!
Sheet structure
Outdoor
SA
RA
(unclean
indoor air)
Indoor
Exhaust air
Outdoor air
(fresh air)
High-humidity air
Supply air
Moisture exchange efficiency is greatly improved by using optimized
thinner films and moisture-absorption materials in the element.
Furthermore, miscellaneous gas barrier properties are maintained by
decreasing the porosity in the moisture-absorption materials.
Thickness of
the partition sheet
Molecule of water
Miscellaneous gas
CO2 molecule, etc.
Exhaust air
Precise, thin-film
material
Low-humidity air
approx. 5%!
Nighttime free cooling operation is an
energy-conserving function that works at
night when air conditioners are off. By
ventilating rooms containing office
equipment that raises the room
temperature, nighttime free cooling
operation reduces the cooling load when
air conditioners are turned on in the
morning. It also alleviates feelings of
discomfort in the morning caused by heat
accumulated during the night.
•Nighttime free cooling operation only works to cool and
if connected to Building Multi or VRV systems.
•Nighttime free cooling operation is set to “off” in the
factory settings, so if you wish to use it, request your
dealer to turn it on.
Indoor
unit
Generated
Heat generated by computers etc., is retained
in the walls and ceiling.
Retained heat
heat
The air conditioning load is large so the temperature
is not reduced quickly.
Exhaust
heat
Indoor
unit
UncomfortableUncomfortable
Nighttime free cooling operation
The indoor accumulated heat is discharged at night. This reduces the air conditioning
load the next day thereby increasing efficiency.
Cold air
Indoor
unit
Exhaust
heat
Generated
heat
Heat is discharged.The load is small so the temperature is rapidly reduced
to a comfortable level.
*Interlocked operation with an air conditioner
Exhaust
heat
Indoor
unit
Comfortable!Comfortable!
Page 4
Air Conditioning Load Reduced by Appr oximately 30%
306 mm
Air Conditioning Load Reduced by Appr oximately 30%
1. Approximately 20% by operating in total heat exchange mode
(in comparison with normal ventilation fans)
2. Another approximately 8% gained by auto-ventilation mode changeover switching
3. Yet another approximately 2% by pre-cool, pre-heat control
• The above values may vary according to weather and other environmental conditions at the location of the machine's installation.
• The above values are based on the following conditions;
Application: Tokyo office building
Building form: 2 floors above ground, 6 floors underground, floor area 2,100 m
Personnel density: 0.25 person/m
Ventilation volume: 25 m3/h
Indoor air conditioning level: summer 25°C 50% RH, intermediate seasons 24°C 50% RH, winter 22°C 40% RH
Operating time: 2745 hours (9 hours per day, approx. 25 days per month)
Calculation method: simulation based on "MICRO-HASP/1982" of the Japan Building Mechanical and Electrical Engineers Association.
2
Interlocking
Annual air conditioning
load reduced by
approx. 30%!
The HRV is interlocked to Daikin's VRV system, SkyAir and other air
conditioning systems and automatically switches over ventilation mode, further
increasing the effects of energy conservation. HRV operation has been
centralized on the air conditioner remote controller allowing total control over air
conditioning and ventilation with a simple configuration.
2
Auto-ventilation Mode Changeover Switching
Automatically switches the ventilation mode (Total Heat Exchange Mode/Bypass Mode) according to the operating
status of the air conditioner.
Total Heat Exchange Mode
(Cooling operation in summer/Heating operation in winter)
Exhaust air
Outdoor air intake
Outdoor air temperature sensor
Heat exchange element
Air exhaust fan
Bypass Mode (“Intermediate” season)
Exhaust air
Air exhaust fan
Heat exchange element
Room temperature sensor
Return air
Air supply fan
Supply air
Indoor air temperature sensor
Return air
Daikin air conditioner
Indoor unit
LCD remote controller
for indoor unit
Pre-cool, Pre-heat Control
• Operating mode signal
• Filter cleaning signal
• Failure detection signal
• ON/OFF signal
• Cooling/Heating mode signal
• Set temperature signal
• Ventilation signal
• Humidifier ON/OFF signal
InterlockingInterlocking
HRV
Outdoor air intake
(Intermediate season)
Compact equipment
Compact equipment
Outdoor air temperature sensor
With a height of just 306 mm, the unit easily fits in limited
spaces, such as above ceilings.
In case of VAM500GJVE
*
Cold climate compatible :
Cold climate compatible :
Standard operation at temperatures down to -15°C
The intermittent operation mode is activated when
outdoor temperature goes down to -10°C or below,
preventing freezing or condensation in the unit. Standard
models can now be used in cold climate regions.
Air supply fan
50
40
30
20
10
Supply air
*
The air cannot be supplied
*
at the same temperature
as the outdoor air because
it is partly heat-exchanged.
50˚CDB
-10
-20
0
-15˚CDB
Reduces air conditioning load by not running the HRV while air is still clean soon after the air conditioner is
turned ON.
56
Page 5
C e nt ra liz e d C o n tr o l o f
Centralized Control System
Centralized Control System
A ir C on d it i o ning a nd V e ntila tion
The operation of the air conditioner using the remote controller is interlocked to the operation of
the HRV, greatly simplifying overall system operation. In addition, installation work associated
with the HRV remote controller is not necessary because operations for air conditioning and
ventilation are completely centralized on the air conditioner remote controller. Also, the use of
such a centralized remote controller allows the user to choose a wide range of control systems
that integrate air conditioning and ventilation. Furthermore, by using a variety of centralized
control equipment, the user can build a large, high-grade centralized control system.
Operations and Control with the Air Conditioning Remote Controller
Operations and Control with the Air Conditioning Remote Controller
• Simultaneous ON/OFF of the HRV and indoor unit air conditioner
• Independent operation of the HRV
• Airflow rate switching (initial setting)
• Ventilation mode switching
• Self-diagnosis functions
• Filter sign display and reset
• Timer settings (simultaneous control with air conditioner)
• Pre-cool, pre-heat control settings (initial setting)
By combining the (optional) centralized control equipment below, the user can achieve a wide range of
comprehensive centralized control systems for air conditioning and ventilation.
Centralized Controller
• One unit can operate and monitor up to 64 groups (128 units) of HRV
and air conditioner units individually or in batch.
• Allows the user to divide connected HRV or air conditioner units into
zones (up to 64) and control any or all of them.
• Two units of this controller can be linked, thereby allowing centralized
control of up to 128 groups (128 units).
• Centralized control from two places is possible using two units of this
controller.
• Ventilation volume and mode can be controlled for Heat Reclaim
Ventilation.
Unified ON/OFF Controller
• One unit can turn ON/OFF up to 16 groups (128 units) of HRV and air
conditioner units individually or in a batch.
• Lamps display operation and failure status of the connected HRV and
air conditioner units.
• Up to 8 units can be linked to allow centralized control of up to 128 units.
(DCS302CA61)
(DCS301BA61)
A Var iety of Control Systems That Can Be Controlled
A Var iety of Control Systems That Can Be Controlled
Using Only the Air Conditioner Remote Controller
Using Only the Air Conditioner Remote Controller
Air conditioner
Group Control
One air conditioner remote controller simultaneously controls up
to 16 air conditioner and HRV units.
Air conditioner
remote controller
Air conditioner
2-Remote-Controller Control
Allows control of air conditioner and HRV units from two places by
connecting two air conditioner remote controllers. (Group control
possible)
Air conditioner
remote controller (No. 2)
Air conditioner
remote controller (No. 1)
Air conditioner
Long-distance Remote Control
Operation control from afar, i.e., a distant control room, is possible
thanks to wiring of up to 500 m. (Group control and 2-remotecntroller control possible)
Up to 500 m
Air conditioner
remote controller
2-remote-controller control possible
Air conditioner
Control with 2 Remote Controllers
(for HRV and Air Conditioner)
System with dual use of the HRV remote controller and air
conditioner remote controller can be achieved. Changes in initial
setting functions are always possible. (Group control possible)
Up to 500 m
HRV remote controller
Air conditioner
remote controller
BRC1C62
Up to 500 m
Up to 500 m
Up to 16
units
Group
control
possible
Group
control
possible
Group
control
possible
HRV
HRV
HRV
HRV
Schedule Timer
• One unit can control the operation of up to 128 HRV and air conditioner
units on a weekly schedule.
• Can set two ON/OFF operations per day for a period of one week.
(DST301BA61)
Number of units that can
be connected per system
Centralized controller2 units
Unified ON/OFF controller8 units
Schedule timer1 unit
78
Page 6
V a r io us C on t ro l S y s t e m s A c c o rding to
Image of group
control system
A pplic a tion s a nd C ond it i o ns
Major HRV Control Systems
Independent Operation System
Air Conditioning Interlocked Control (VRV, SkyAir) System
System Construction
HRV
Operation
Independent
HRVHRV
of Multiple Units
Main
remote controller
HRV remote controller
Main
remote controller
Simultaneous Operation
Indoor unitHRV
Air conditioner
remote controller
Standard System
Group 1
Air conditioner
remote controller
Group 1
Air conditioner
remote controller
Indoor
unit
Indoor
unit
Group 2
Group 2
Indoor
unit
Air conditioner
remote controller
Indoor
unit
Air conditioner
remote controller
Operation System
Multiple groups Interlocked
HRVHRV
Wiring adaptor
for electrical
appendices
System Characteristics
• Independent operation
of HRV is possible.
• Operation is possible
using 2 HRV remote
controllers.
• Multiple HRV units can
be simultaneously
controlled in batch.
•
HRV remote controller
does not have to be used.
• Up to 16 VRV indoor
units or HRV units can
be connected and
controlled in batch, with
interlocked operation of
HRVs and air
conditioners by using
the air conditioner
remote controller.
• Can control interlocked
operation of multiple
groups of VRV or SkyAir
indoor units.
• When one of the multiple
groups operates, HRVs
are interlocked and
operates simultaneously.
Necessary
Accessories
HRV remote
controller
HRV remote
controller
VRV remote
controller/
SkyAir
remote
controller
VRV remote
controller/
SkyAir
remote
controller
Combined
individual
system
System Construction
Indoor
unit
Air conditioner
remote controller
Indoor
unit
Air conditioner
remote controller
Indoor
unit
Indoor
unit
ON/OFF
controller
HRV LCD
remote
controller
HRV LCD
remote
controller
HRV
HRV
System Characteristics
• Up to 128 VRV, SkyAir and
HRV units can be centrally
controlled over a centralized
(Special adaptor is required to
line
connect the SkyAir to the centralized line.)
• HRV remote controller can
set the individual operation
of each HRV unit.
• Control system can be
expanded depending on its
purposes by combining a
variety of centralized control
equipment.
With only one 450-mm
square inspection
aperture, maintenance
and heat exchange
element replacement can
be performed with ease.
The unit can be
installed upside down
in accordance with
the conditions of the
location.
Maintenance cover
Clean
Fresh-up Operation
The user can select between two fresh-up modes using the remote controller.
S u ppl y ri c h m od e :
Raising the air supply maintains proper room pressure to
prevent back-flow of toilet/kitchen odors or moisture inflow.
Portion of fresh-up
operation
Air exhaust
Air supply
HRV
Normal
ventilation fan
E x h a us t r ic h m o de :
Raising exhaust air decreases room pressure to prevent
the leaking of odors or floating bacteria into other rooms.
Air exhaust
Air supply
Sick roomFloor area
Portion of
exhaust
operation
Switch box
Access door
HRVHRV
HRV
M o d e l L ine U p
VAM-GJ VE Series
VAM-GJ VE Series
VAM150GJVEVAM250GJVEVAM350GJVE
50Hz,220–240V
60Hz,220V
T
emperatu
Entha
lp
E
nth
alpy
e
250
200
150
100
External static pressure (Pa)
0
Ultra-High
Low
50
y
xcha
r
e
e
xch
an
ge
nge
effi
Exchange efficiency
VAM150GJVE
exc
h
ange efficie
n
ffi
ci
e
ncy
(h
iency
(cool
200
Air flow rate
eating)
in
g)
cy
e
c
High
25010050150
(m3/h)
(%)
90
80
70
60
20m
15m
10m
5m
100
Pipe
length
300
250
200
150
100
External static pressure (Pa)
Low
50
0
50Hz,220–240V
60Hz,220V
100
50
Tem
Enthal
p
y
Enthalpy exc
Ultra-High
150200
p
erature excha
ex
cha
n
ha
ng
High
ge
e ef
Exchange efficiency
VAM250GJVE
n
ge eff
i
ci
e
ncy
e
f
fi
ci
en
cy
(
h
ea
ting
)
f
icien
c
y (
c
oo
ling)
300
250350
Air flow rate
(m3/h)
(%)
90
80
70
60
150
Pipe
length
40m
30m
20m
10m
50Hz,220–240V
60Hz,220V
Tem
p
e
rat
Enth
alpy
Enthalpy exchan
g
300
250
200
150
100
External static pressure (Pa)
50
0
High
Low
100
200400600
Exchange efficiency
VAM350GJVE
ure
e
x
c
ha
n
ge eff
e
xc
hange
e
fficiency (he
e efficiency (cooling)
Ultra-
High
300
Air flow rate
i
ci
500
(%)
90
80
e
ncy
70
ating
)
40m
60
50
30m
20m
150
Pipe
length
10m
(m3/h)
ex. Office
ex. Hospital
Preventing Dust from Falling with Directly Mounted Ducts
OFFDust
W it h C o mp e t i t o rs ' P ro du c ts
When conventional total heat exchange units, which
are independently operated using a dedicated remote
controller, are directly connected by a duct, there is a
possibility of dust falling from the air filter of the indoor
unit when the air conditioner is OFF.
Blowing modeNo dust is blown out.
W it h the H R V
When the HRV is operating independently, the fan in a
interlocked indoor unit continues turning, so dust does
not fall from the air filter.
A sign is displayed on the remote controller when the air filter needs cleaning.
400
350
300
250
200
150
External static pressure (Pa)
100
VAM500GJVEVAM650GJVEVAM800GJVE
50Hz,220–240V
60Hz,220V
Enthal
En
t
halpy excha
50
Low
0
100
Exchange efficiency
Te
mpe
p
y
300700
VAM500GJVE
ra
t
ure
ex
c
ha
nge
e
f
h
a
n
g
400
e
e
f
f
ic
i
en
f
i
ciency
(cooling)
Ultra-High
High
500 600200
fic
i
e
nc
c
y
(
h
ea
e
xc
n
ge ef
(%)
90
80
y
70
t
ing)
60
50
200
Pipe
length
50m
40m
30m
20m
10m
550
500
450
400
350
300
250
200
External static pressure (Pa)
150
100
50
0
50Hz,220–240V
60Hz,220V
Low
T
e
m
E
n
thal
Ent
halp
Ultra-High
y ex
p
e
r
a
p
y
cha
t
u
re
e
e
x
c
h
n
ge efficiency
High
Exchange efficiency
VAM650GJVE
x
cha
n
ge
e
f
f
i
ci
e
n
g
e
ef
fi
c
700 800300200900600100500400
Air flow rate
c
i
e
n
c
y
(
h
e
(coo
li
n
a
n
50Hz,220–240V
60Hz,220V
m
p
e
r
a
x
ch
a
n
Ultra-High
600
t
u
r
g
e eff
Exchange efficiency
VAM800GJVE
e
e
x
c
h
a
n
g
e
e
ff
efficien
i
c
i
e
n
c
y (
h
ea
ti
ien
c
y (co
800
Air flow rate
ng)
o
l
in
g
)
ic
High
(%)
80
70
c
y
60
50
250
Pipe
length
100m
80m
60m
40m
20m
(m3/h)
(%)
90
80
y
70
at
i
n
g)
60
g)
50
60m
50m
40m
30m
20m
10m
200
Pipe
length
(m3/h)
500
400
300
200
Low
External static pressure (Pa)
100
0
200
T
e
E
n
thalpy exchange
En
t
h
a
lp
y e
4001000
1112
Page 8
VAM-GJ VE Ser ies
VAM-GJ VE Ser ies
Dimensions
Dimensions
VAM350GJVEVAM500GJVE
Maintenance space for the heat exchange
elements, the air filters and fans
Control box
VAM1000GJVEVAM1500GJVEVAM2000GJVE
50Hz,220–240V
60Hz,220V
Temperatu
Enthalpy e
Enthalpy exchange efficiency
500
400
300
200
High
100
External static pressure (Pa)
0
Low
2004006008001000 1200
Exchange efficiency
VAM1000GJVEVAM2000GJVE
re
exchange efficienc
xchange
efficienc
y
(heating)
(c
ooling)
Ultra-High
(%)
90
80
y
70
60
250
Pipe
length
100m
80m
60m
40m
700
600
500
400
300
200
External static pressure (Pa)
100
20m
Air flow rate
(m3/h)
0
50Hz,220–240V
60Hz,220V
Enthalpy
High
Low
Temperature exch
Enthalpy exchan
ex
ch
a
nge e
a
nge efficiency
ge
efficiency (heatin
ff
ic
iency
(
c
o
Ultra-High
Exchange efficiency
g)
ol
ing
)
2500150020005001000
Air flow rate
(m3/h)
50Hz,220–240V
(%)
90
Tempe
80
Enthalpy exchange e
60Hz,220V
70
60
50
500
400
300
Enthalpy exchan
Exchange efficiency
VAM1500GJVE
ra
ture e
x
change effic
f
fi
c
ie
n
g
e efficien
c
y (
Ultra-High
(%)
90
80
ienc
y
ling)
70
at
ing)
60
cy
(he
c
oo
50
200
High
External static pressure (Pa)
100
Low
0
Air flow rate
2500150020005001000
(m3/h)
306
183
132
123
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
600~
68
SA
800
RA
(Maintenance cover)
Heat exchange elements
150~250
247
416
137
Damper plate
(Control box)
Inspection hole
450
Maintenance cover
Supply air fan
823
High efficiency filter
(Optional accessory)
879132132
Air filters
Ceiling hook
4-12X40 oval hole
137
416
247
Exhaust air fan
200
146
123
20
850
20
132
OA
EA
183
Maintenance space for the heat exchange
elements, the air filters and fans
Exhaust air fan
84
Ceiling hook
4-12X40 oval hole
20
OA
416137
850
EA
247
20
197
213
123 132
183
Control box
306
183
132
123
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
600~
68
SA
800
RA
Damper plate
(Maintenance cover)
Heat exchange elements
150~250
247
416
137
(Control box)
Inspection hole
Maintenance cover
Supply air fan
84
450
823
High efficiency filter
(Optional accessory)
879
Air filters
Dimensions
Dimensions
SA: Supply air to room
RA: Return air from room
OA: Fresh air from outdoors (Outdoor air)
EA: Exhaust air to outdoors
VAM150GJVE
Maintenance space for the heat exchange
elements, the air filters and fans
Control box
278
158
121
109
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
600~
150~250
68
SA
551
275
RA
126150
Damper plate
(Maintenance cover)
(Control box)
Heat exchange elements
Maintenance cover
Supply air fan
145
Inspection hole
450
754
High efficiency filter
(Optional accessory)
810
Air filters
Ceiling hook
4-12X40 oval hole
Exhaust air fan
145
97
20
OA
126
275
601
EA
150
20
200
VAM250GJVE
Maintenance space for the heat exchange
elements, the air filters and fans
Control box
121
109
158
278
158
121
109
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
600~
150~250
68
SA
150
551
275
RA
126
Damper plate
(Maintenance cover)
(Control box)
Heat exchange elements
Maintenance cover
Supply air fan
132
Inspection hole
450
754
High efficiency filter
(Optional accessory)
810
Air filters
Ceiling hook
4-12X40 oval hole
Exhaust air fan
132
146
20601
126
275
150
20
200
121109
OA
EA
158
VAM650GJVEVAM800GJVE
Maintenance space for the heat exchange
elements, the air filters and fans
Control box
338
193
149
139
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
600~
68
SA
832
RA
Heat exchange elements
150~250
248
422
162
Damper plate
(Maintenance cover)
(Control box)
Maintenance cover
Supply air fan
137
Inspection hole
450
897
High efficiency filter
(Optional accessory)
973
Air filters
Ceiling hook
4-12X40 oval hole
162
422
248
Exhaust air fan
137
196
139
149
20
OA
882
EA
20
250
193
Maintenance space for the heat exchange
elements, the air filters and fans
Control box
387
235
163
153
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the exchange elements
and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange element.
600~
68
SA
832
RA
Damper plate
(Maintenance cover)
Heat exchange elements
150~250
248
431
153
(Control box)
89
Inspection hole
Maintenance cover
Supply air fan
High efficiency filter
(Optional accessory)
1034
1110
450
Air filters
Ceiling hook
4-12X40 oval hole
153
431
248
Exhaust air fan
89
263
246
163 153
2020
OA
882
EA
235
1314
Page 9
VAM1000GJVE
VAM1500GJVE
VAM2000GJVE
Maintenance space for the heat exchange
elements, the air filters and fans
Control box
387
235
1531034
Maintenance space for the heat exchange
elements, the air filters and fans
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the
exchange elements and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange
element.
Enthalpy
Exchange
Efficiency (%)
[50Hz/60Hz]
Sound Level
dB(A)
[50Hz/60Hz]
Low
20
OA
214
308
878
EA
310
20
546
160
214
Casing
Dimensions (HXWXD)
Weight
Air Flow Rate (m3/h)
Ultra-High
[50Hz/60Hz]
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the
330
350
395
exchange elements and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange
element.
Fan
External Static
Pressure (Pa)
[50Hz/60Hz]
Ultra-High
Motor Output
Connection Duct Diameter
79/7975/75
79/7975/75
84/8579/79
72/7271/7170/7067/67
72/7271/7170/7067/67High
76/76.574/7477/7774/74.5Low
66/6663/6366/6655/55
66/6663/6366/6655/55High
70/70.566/6670/7059/59.5Low
27-28.5/28.527-29/2931.5-33/3333-35.5/34
26-27.5/27.5 26-27.5/2830-31.5/3031.5-34/32High
20.5-21.5/2121-22/2123-25/2325-28.5/24Low
28.5-29.5/29.5 28.5-30.5/30.5
27.5-28.5/28.5
22.5-23.5/22
27.5-29/29.5 31.5-33/31.5 33-34.5/33.5High
22.5-23/22.5
278X810X551306X879X800mm
2432kg
150/150250/250350/350500/500
150/150250/250350/350500/500High
100/95155/155230/230320/295Low
120/15470/96169/222105/150
106/13154/65141/14566/52High
56/6024/2067/3032/18Low
0.030X20.090X2kW
100 150 200mm
79/7974/74
79/7974/74
82/8280/80.5
33-34.5/34.5 34.5-36/35.5
24.5-26.5/24.5
25.5-28.5/25.5
Galvanized steel plate
Self-extinguishable polyurethane foamInsulation Material
Air to air cross flow total heat (Sensible heat + latent heat) exchangeHeat Exchange System
Specially processed nonflammable paperHeat Exchange Element Material
Multidirectional fibrous fleecesAir Filter
75/7572/72
75/7572/72
78/7872/72
78/7872/72
77/77.574/74.580.5/8175.5/76
67.5/67.565/6570/7065/65
67.5/67.565/6570/7065/65
71.5/7267.5/6872.5/7367/67.5
61/6161/6164/6461/61
61/6161/6164/6461/61
64/64.564/64.568.5/6964/64.5
34-36/3639-40.5/39.5
33-34.5/34 37-39.5/37.5
39.5-41.5/39.5 39.5-41.5/41.5
37.5-39.5/37.5 37.5-39.5/39.5
27.5-29.5/28 35-37.5/34 35-37.5/34.5 35-37.5/36
35-37.5/37.5
33-35.5/35.5 38.5-40/39
27.5-30.5/29.5
338X973X832
455567
40.5-42/41
40.5-42.5/40.5
38.5-40.5/38.5
41-43/42.5
39.5-41/41.5
36-38.5/35.5 36-38.5/35.5 36.5-38/37.5
387X1,111X1,214387X1,111X832
785X1,619X832 785X1,619X1,214
129
Sirroco fanType
650/650800/8001,000/1,000 1,500/1,500
650/650800/8001,000/1,000 1,500/1,500
500/470700/670860/8401,320/1,260
85/125133/170168/192112/150
53/6792/85110/8673/72
35/3872/6185/6056/50
0.140X20.280X20.280X4
250 350
77/77
77/77
79/81
72/72
72/72
75/76
62/62
62/62
66/67
41.5-43.5/42
39-43/40
36-39/39
43-45.5/44
40.5-45/42
37.5-39.5/41
157
2,000/2,000
2,000/2,000
1,720/1,580
116/140
58/32
45/45
163
S pe c ific a t i o ns
-15°C~+50°CDB, 80%RH or lessUnit ambient condition
Maintenance space for the heat exchange
elements, the air filters and fans
Control box
785
214
546
650~
200~300
95
501
SA
1214
499
RA
214
160
Damper plate
(Maintenance cover)
130
254
Inspection hole
Maintenance cover
Supply air fan
High efficiency filter
(Optional accessory)
450
1034
1110
Ceiling hook
4-12X40 oval hole
Exhaust air fan
Heat exchange elements
130
254
546
OA
214501
499
1260
EA
160
214
Note: 1.
Sound level is measured at 1.5m below the center of the body.
2.
Air flow rate can be changed over to Low mode or High mode.
3.
Sound level is measured in an anechoic chamber.
Sound level generally become greater than this value depending on the operating conditions, reflected sound, and peripheral noise.
4.
The sound level at the air discharge port is about 8 dB higher than the unit's sound level.
5.
The specifications, designs and information given here are subject to change without notice.
6.
Temperature Exchange Efficiency is the mean value between cooling and heating.
7.
Efficiency is measured under the following conditions:
Ratio of rated external static pressure has been maintained as follows; outdoor side to indoor side = 7 to 1.
8.
In conformance with JIS standards (JIS B 8628), operating sound level is based on the value when one unit is operated, with the value converted for an anechoic chamber. This is
transmission sound from the main unit, and does not include sound from the discharge grille. Thus it is normal for the sound to be louder than the indicated value when the unit is
actually installed.
9.
Sound level from the discharge port causes the value to be approximately 8 dB (models with the air flow rate of less than 150 to 500 m3/h) to approximately 11 dB (models with the air
flow rate of 650 m
conditions. Please consider noise countermeasures when installing the unit.
10
.
With large models in particular (1500 and 2000 m3/h models), if the supply air (SA) grille is installed near the main unit, the noise of the main unit may be heard from the discharge
grille via the duct, and this will result in a marked increase in noise. In such cases, if peripheral effects are included (such as reverberation of the floor and walls, combination with
other equipment, and background noise), sound level may be as much as 15 dB higher than the indicated value. When installing a large model, please provide as much separation as
possible between the main unit and the discharge grille. If the equipment and discharge grille are near each other, please consider countermeasures such as the following:
•Use a sound-muffling box, flexible duct and sound-muffling air supply/discharge grilles
•Decentralized installation of discharge grilles
11
.
When installing in a location with particularly low background noise such as a classroom, please consider the following measures to avoid transmission sound from the main unit:
•Use of ceiling materials with high sound insulating properties (high transmission loss)
•Methods of blocking sound transmission, for example, by adding sound insulating materials around the bottom of the sound source.
Alternatively, consider supplementary methods such as installing the equipment in a different location (corridor, etc.)
3
/h or more) greater than the indicated value. Furthermore, fan rotation and noise from the discharge grille may increase depending on the on-site duct resistance
Remark)
1. Be sure to provide the inspection hole (450X450 mm) to inspect the air filters, the
exchange elements and fans.
2. It is possible to install the high efficiency filter on the SA face side of heat exchange
element.
(Control box)
Air filters
350
330
395
1516
Page 10
O ptio n
Installation of Optional Pr oducts
Installation of Optional Pr oducts
Air suction/discharge grille (Field supply)
RA
SA
Branch duct
(Field supply)
SA
Duct
(Field supply)
Option List
Member
HRV remote controller
Centralized
controlling
device
Wiring adaptor for electrical
appendices
For humidifier
Installation box for adaptor PCB
For heater control kit
Controlling device
For wiring
PC Board Adaptor
Installation box for adaptor PCB
Note: 1.
Installation box is necessary for each adaptor marked .
2.
Up to 2 adaptors can be fixed for each installation box.
3.
Only one installation box can be installed for each indoor unit.
Applicable model
Central remote controller
Unified ON/OFF controller
Schedule timer
KRP50-2A90 (Mounted electric component assy of HRV)
BRP4A50
FXK-L
FXKQ-MA
FXD-P
FXD-N
FXDQ-P
FXS-L
FXSQ-M
FXM-L
FXMQ-MA
FXH-L
FXHQ-MA
FXA-L
FXAQ-MA
FXDQ-NA
—
KRP1B3
Note 3
KRP1C93
Note 2, 3
KRP4A93
KRP1B61
KRP1B56
Note 4, 6
—
KRP1B101
4.
Up to 2 installation boxes can be installed for each indoor unit.
5.
Installation box is necessary for second adaptor.
6.
Installation box is necessary for each adaptor.
KRP1B61
Note 5
KRP4A91
Round hood
(Field supply)
OA
FXYB-K
FXYD-KA
KRP1B61—
Note 5
——
KRP1B100
EA
FXL-L
FXLQ-MA
FXN-L
FXNQ-MA
FXUQ-MA
—
KRP1B97
PC board adaptor for heater control kit (BRP4A50)
When the installation of an electric heater is required in a cold region, this adaptor with an internal timer function eliminates the
complicated timer connecting work that was necessary with conventional heaters.
Notes when installing
Examine fully an installation place and
specification for using the electric heater based on
the standard and regulation of each country.
Supply the electric heater and safety production
devices such as a relay and a thermostat, etc of
which qualities satisfy the standerd and regulation
of each country at site.
Use a non-inflammable connecting duct to the
electric heater. Be sure to allow 2m or more
between the electric heater and HRV for safty.
For the HRV units, use a different power supply
from that of the electric heater and install a circuit
breaker for each.
RA
SA
BRP4A50
Temperature thermo. (Field supply)
(OFF when the temperature is at or more than 5°C)
HRV
Heater
control kit
(Field supply)
Indoor Outdoor
EA
OA
Temperature thermo.
(Field supply)
(ON when the temperature
is at or below -10°C)