Daikin FDYM60CV1M, FDYM30CV1M, FDYB60CV1M, RY30CV1M, FDYM40CV1M User & Installation Manual

...
INSTALLATION MANUAL
R22 Split Series
Models
FDYM30CV1M FDYB30CV1M RY30CV1M FDYM40CV1M FDYB40CV1M RY40CV1M FDYM60CV1M FDYB60CV1M RY60CV1M FDYM71CV1M FDYB71CV1M RY71CV1M FDYM80CV1M RY80CV1M FDYM90CV1M FDYB90CV1M RY90CV1M FDYM90CV1M FDYB90CV1M RY90CY1M FDYM100CV1M RY100CV1M FDYM125CV1M FDYB125CV1M RY125CV1M FDYM125CV1M FDYB125CV1M RY125CY1M FDYM140CV1M FDYB140CV1M RY140CY1M FDYM160CV1M FDYB160CV1M RY160CY1M
R22 Split series
Manuel d’installation
Série split R22
Руководство По Установке
Cерия R22 с раздельной установкой
Kurulum Kılavuzu
R22 Split serisi
English
Français
Русский
Türkçe
i
Model A B C D E F G H I J K L M N O FDYM30CV1M
31 741 702 662 10 765 72 261 411 351 225 211 232 212,8 114
FDYB30CV1M (1,2) (29,2) (27,6) (26,1) (0,4) (30,1) (2,8) (10,3) (16,2) (13,8) (8,9) (8,3) (9,1) (8,4) (4,5) FDYM40CV1M 31 881 842 802 10 905 72 261 411 351 225 211 232 212,8 114
FDYB40CV1M (1,2) (34,7) (33,1) (31,6) (0,4) (35,6) (2,8) (10,3) (16,2) (13,8) (8,9) (8,3) (9,1) (8,4) (4,5) FDYM60CV1M 31 1041 1002 962 10 1065 72 261 411 351 225 211 232 212,8 114
FDYB60CV1M (1,2) (41,0) (39,4) (37,9) (0,4) (41,9) (2,8) (10,3) (16,2) (13,8) (8,9) (8,3) (9,1) (8,4) (4,5) FDYM71CV1M 31 1176 1137 1097 10 1200 72 261 411 351 225 211 232 212,8 114
FDYB71CV1M (1,2) (46,3) (44,8) (43,2) (0,4) (47,2) (2,8) (10,3) (16,2) (13,8) (8,9) (8,3) (9,1) (8,4) (4,5)
OUTLINE AND DIMENSIONS
Indoor Unit
All dimensions are in mm/(in)
J
I
K
L
E
A
H
O
MN
F
G
D
C
B
Model A B C D E F G H I J K L M N
FDYM80CV1M
371,7 1007 959 920 410,0 295 600 339 121 213 64,0 100,0 239 214,0
(14,6) (39,6) (37,8) (36,2) (16,1) (11,6) (23,6) (13,3) (4,8) (8,4) (2,5) (3,9) (9,4) (8,4)
FDYM90CV1M 359 999 956 917 408,5 378 541 256 173 306 70,5 160,5 248 220,0 FDYB90CV1M (14,1) (39,3) (37,6) (36,1) (16,1) (14,9) (21,3) (10,1) (6,8) (12,0) (2,8) (6,3) (9,8) (8,7)
FDYM100CV1M
371,2 1312 1264 1225 562,5 315 638 401 183 233 217,0 169,2 251 237,8
(14,6) (51,7) (49,8) (48,2) (22,1) (12,4) (25,1) (15,8) (7,2) (9,2) (8,5) (6,7) (9,9) (9,4)
FDYM125CV1M 359 1115 1072 1033 466,5 378 541 256 173 306 128,5 160,5 248 220,0 FDYB125CV1M (14,1) (43,9) (42,2) (40,7) (18,4) (14,9) (21,3) (10,1) (6,8) (12,0) (5,1) (6,3) (9,8) (8,7) FDYM140CV1M 359 1369 1326 1287 593,5 378 541 256 173 306 255,5 160,5 248 220,0 FDYB140CY1M (14,1) (53,9) (52,2) (50,7) (23,4) (14,9) (21,3) (10,1) (6,8) (12,0) (10,1) (6,3) (9,8) (8,7) FDYM160CV1M 359 1569 1526 1487 693,5 378 541 256 173 306 355,5 160,5 248 220,0 FDYB160CV1M (14,1) (53,9) (60,1) (58,5) (27,3) (14,9) (21,3) (10,1) (6,8) (12,0) (14,0) (6,3) (9,8) (8,7)
Indoor Unit
61,0 (2,40)
24,5 (0,96)
E
E
24,5 (0,96)
61,0 (2,40)
15,0 (0,59)
474,0 (18,66)
15,0
(0,59)
K
K
40,0
(1,57)
B C
D
AA
F
MN
L
J
G
H
40,0
(1,57)
40,0 (1,57)
I
156,0
(6,14)
40,0
49,0 (1,93)
39,0 (1,54)
40,0 (1,57)
142,0 (5,59) 143,0 (5,63)
26,0 (1,12)
41,0 (1,61)
90,5
(3,56)
100,0
(3,94)
187,5 (7,38)
All dimensions are in mm/(in)
ii
Outdoor Unit
All dimensions are in mm/(in)
Dimension A B C D E F G H I J K L M N O RY30CV1M 700 521 250 485 175 36 95 93 86 68 441 130 111 15 18
RY40CV1M (27,5) (20,5) (9,8) (19,1) (6,8) (1,4) (3,7) (3,6) (3,3) (2,6) (17,3) (5,1) (4,3) (0,5) (0,7)
30
(1,2)
(0,1)
3
(0,7)
19
(2,6)
65
(3,1)
80
L
KL
N
CN
M
F
E
C
G
H
IJ
A
D
O
B
Dimension A B C D E F G H I J K L M N O RY60CV1M
855 628 328 513 182 44 93 149 101 113 603 126 164 17 49
(33,7) (24,7) (12,9) (20,0) (7,1) (1,7) (3,7) (5,9) (4,0) (4,4) (23,7) (5,0) (6,4) (0,7) (1,9)
RY71CV1M 855 730 328 513 182 44 93 149 101 113 603 126 164 17 47 RY80CV1M (33,7) (28,7) (12,9) (20,2) (7,2) (1,7) (3,7) (5,9) (4,0) (4,4) (23,7) (5,0) (6,4) (0,7) (1,9)
All dimensions are in mm/ (in)
Outdoor Unit
Dimension P Q R S T RY60CV1M
32 3 23 73 75
(1,3) (0,1) (0,9) (2,9) (3,0)
RY71CV1M 32 3 23 73 75 RY80CV1M (1,3) (0,1) (0,9) (2,9) (3,0)
KL
C
M
N
A
D
N
P
FE
C
GH
B
Q
R
O
L
ST
IJ
iii
Outdoor Unit
Model A B C D E F G H J K L M N P
RY90CV1M/ RY90CY1M/
1030 850 400 390 414 827 72 196 91 488 448 141,5 746,5 82
RY100CV1M/ RY125CV1M/
(40,6) (33,5) (15,7) (15,4) (16,3) (32,6) (2,8) (7,7) (3,6) (19,2) (17,6) (5,6) (29,4) (3,2)
RY125CY1M/ RY140CY1M
All dimensions are in mm/(in)
J
H
C
G
E
F
B
D
NM
A
L
K
P
iv
Model A B C D E F G H J K L M N
RY160CY1M
1030 850 400 448 746,5 320 25 50 85 40 141.5 20 60
(40,6) (33,5) (15,7) (17,6) (29,4) (12,6) (1,0) (2,0) (3,3) (1,6) (5,6) (0,8) (2,4)
All dimensions are in mm/(in)
J
H
C
FK
K
B
G
A
LEL
M
D
M
N
1
English
SAFETY PRECAUTIONS
! CAUTION
Please take note of the following important points when installing.
• Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates around the unit, it may cause fire ignition.
• Ensure that the drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.
• Do not overcharge the unit.
This unit is factory pre-charged, Overcharge will cause over-current or damage to the compressor.
• Ensure that the unit’s panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
• Sharp edges and coil surfaces are potential locations which may cause injury hazards. Avoid from being in contact with these places.
• Before turning off the power supply set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is not done,
the unit’s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.
• Do not operate any heating apparatus too close to the air conditioner unit. This may cause the plastic panel to melt or
deform as a result of the excessive heat.
• Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
! WARNING
• Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance.
• All field wiring must be installed in accordance with the national wiring regulation.
• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazard due to insulation failure.
• All electrical wiring must not touch the refrigerant piping or any moving parts of the fan motors.
• Confirm that the unit has been switched OFF before installing or servicing the unit.
• Disconnect from the main power supply before servicing the air conditioner unit.
• DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in the fire hazards.
• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. {Depending on the type and source of the electrical waves, static may be heard even when more than 1m away}.
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit. Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
INSTALLATION MANUAL
Disposal requirements
Dismanteling of the unit, treatment of the refrigerant, oil and other parts shall be done in accordance with local and national regulation.