2.2Outdoor Unit .........................................................................................102
Table of Contentsiv
Safety CautionsSiMT041509E
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
Caution ItemsThe caution items are classified into Warning and Caution. The Warning items are
especially important since they can lead to death or serious injury if they are not followed
closely. The Caution items can also lead to serious accidents under some conditions if they
are not followed. Therefore, be sure to observe all the safety caution items described below.
PictogramsThis symbol indicates the item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates the prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates the action that must be taken, or the instruction.
The instruction is shown in the illustration or near the symbol.
1.1Warnings and Cautions Regarding Safety of Workers
Warning
Do not store the equipment in a room with successive fire sources (e.g.,
naked flame, gas appliance, electric heater).
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for repair.
Working on the equipment that is connected to the power supply may cause an
electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas is discharged during the repair work, do not touch
the discharged refrigerant gas.
The refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at
the welded section, evacuate the refrigerant gas completely at a wellventilated place first.
If there is gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it may
cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area.
The refrigerant gas may generate toxic gases when it contacts flames.
Be sure to discharge the capacitor completely before conducting repair
work.
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
A charged capacitor may cause an electrical shock.
v
SiMT041509ESafety Cautions
Warning
Do not start or stop the air conditioner operation by plugging or
unplugging the power cable plug.
Plugging or unplugging the power cable plug to operate the equipment may
cause an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when working
at a high place (more than 2 m).
Insufficient safety measures may cause a fall accident.
In case of R-32 / R-410A refrigerant models, be sure to use pipes, flare
nuts and tools for the exclusive use of the R-32 / R-410A refrigerant.
The use of materials for R-22 refrigerant models may cause a serious accident
such as a damage of refrigerant cycle as well as an equipment failure.
Do not mix air or gas other than the specified refrigerant (R-32 / R-410A /
R-22) in the refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner by splashing water.
Washing the unit with water may cause an electrical shock.
Be sure to provide the earth / grounding when repairing the equipment in
a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when
cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools.
The use of inappropriate tools may cause injury.
Be sure to check that the refrigerating cycle section has cooled down
enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
vi
Safety CautionsSiMT041509E
Caution
Use the welder in a well-ventilated place.
Using the welder in an enclosed room may cause oxygen deficiency.
Checking the area
Before beginning work, conduct safety checks to minimise the risk of ignition. When repairing
the refrigerating system, take the following precautions before work.
Work procedure
Work shall be conducted under a controlled procedure so as to minimise the risk of working in
the presence of R-32 or vapour.
General working area
All maintenance staff and others working in the local area shall be instructed on the nature of
work being carried out.
Work in confined spaces shall be avoided.
The area around the workspace shall be sectioned off. Ensure that the conditions within the
area have been made safe by control of flammable materials.
Checking for presence of refrigerant
The working area shall be checked with an appropriate refrigerant detector before and during
work, to ensure the technician is aware of potentially flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with R-32, i.e. nonsparking, adequately sealed or intrinsically safe.
Fire extinguishing equipment
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be made available at hand. Prepare a dry powder
fire extinguisher adjacent to the working area.
2
or CO
No ignition sources
During work on a refrigeration system which involves exposing any piping work that contains or
has contained R-32, any sources of ignition shall not be used in a manner that may lead to the
risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be
kept at a safe distance from the site of installation, repairing, or removing space. Before starting
work, the area around the equipment shall be examined to make sure that there are no
flammable hazard or ignition risks. No Smoking signs shall be displayed.
Ventilated area
Ensure that the working area is open or that it is adequately ventilated before work.
Adequate ventilation shall be maintained during the entire period of work.
The ventilation should disperse any released refrigerant and preferably discharge it into the
external atmosphere.
vii
SiMT041509ESafety Cautions
Checking the refrigeration equipment
Where electrical components are to be changed, the new components shall be fit for the
purpose and have the correct specifications.
The manufacturer's maintenance and service guidelines shall be followed at all times.
If there are any unclear points, consult the manufacturer's technical department for assistance.
The following checks shall be applied to any installation work involving R-32:
•The amount of charge is in accordance with the size of the room where the refrigerant
containing parts are installed;
•The ventilation machinery and outlets are operating adequately and are not obstructed;
•If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for
the presence of refrigerant;
•Marking on the equipment is visible and legible. Markings and signs that are illegible shall
be corrected;
•Refrigeration pipes or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, or the
refrigerant containing components are constructed of materials which are inherently
resistant to corrosion or are suitably protected against corrosion.
Checking electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. In case there is any fault that could endanger safety, no
electrical supply shall be connected to the circuit until the fault is satisfactorily dealt with.
Initial safety checks shall include:
•that capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
•that no live electrical components and wiring are exposed while charging, recovering or
purging the system;
•that the equipment is earthed at all times.
Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon before the removal of any sealed covers, etc. If it is absolutely
necessary to have power supplied to equipment during servicing, continuously operating leak
detection shall be installed at the most dangerous point of the system in order to warn of a
potentially hazardous situation.
Particular attention shall be paid to the following: ensure that working on electrical components
does not alter the casing in such a way that affects the level of protection including damage to
cables, excessive number of connections, terminals different from the original specification,
damage to seals, incorrect fitting of glands, etc.
Ensure that the equipment is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the
purpose of preventing the ingression of flammable atmospheres. Replacement parts shall be in
accordance with the manufacturer's specifications.
The use of silicon sealant may inhibit the effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to be isolated before working on them.
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance load to the circuit without ensuring that
this will not exceed the permissible voltage and current for the equipment in use.
Only intrinsically safe components can be worked on in the presence of a flammable
atmosphere.
The test apparatus shall be of correct rating.
Replace components only with parts specified by the manufacturer. Using other parts may
result in ignition of the refrigerant leaked into the atmosphere.
Wiring
Check that wiring is not subject to wear, corrosion, excessive pressure, vibration, sharp edges
or any other adverse environmental effects. The check shall also take into account the effects of
ageing or continuous vibration from sources such as compressors or fans.
viii
Safety CautionsSiMT041509E
Detecting of R-32
Under no circumstances shall potential sources of ignition be used in the search for or detection
of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.
Leak detection methods
The following leak detection methods can be applied for systems containing R-32.
Electronic leak detectors shall be used to detect R-32, but the sensitivity may not be adequate
or may need re-calibration (detection equipment shall be calibrated in a refrigerant-free area).
Ensure that the detector is not a potential source of ignition and that it is suitable for the
refrigerant used. Leak detection equipment shall be set to the percentage of the lower
flammability limit (LFL) of the refrigerant and calibrated to fit the refrigerant employed. The
appropriate percentage of gas (maximum 25%) shall be confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode
the copper piping work.
If a leak is suspected, all naked flames shall be removed or extinguished.
If a refrigerant leakage which requires brazing is found, all of the refrigerant shall be recovered
from the system, or isolated (by means of shut off valves) in a part of the system remote from
the point of the leakage. Oxygen free nitrogen (OFN) shall then be purged through the system
both before and during the brazing process.
Removal and evacuation
When breaking the refrigerant circuit to make repairs or any other purpose, conventional
procedures may be used. However, flammability must be taken into consideration. The
following procedure shall be adhered to:
•Remove refrigerant;
•Purge the circuit with inert gas;
•Evacuate the inert gas;
•Purge again with inert gas;
•Carry out cutting or brazing of the circuit.
The refrigerant shall be recovered into the correct recovery cylinders. The system shall be
cleaned with OFN to render the unit safe. (= Flushing) This process may need to be repeated
several times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved through breaking the vacuum by filling the system with OFN until the
working pressure is achieved, then venting the OFN into the atmosphere, and finally pulling the
system down to vacuum again. This process shall be repeated until no refrigerant remains
within the system. After the last OFN charge is finished, the system shall be vented down to
atmospheric pressure to enable work. This operation is especially important if brazing
operations on the piping work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and that there is
ventilation available.
Charging procedures
In addition to conventional charging procedures, the following requirements shall be met.
Ensure that the charging equipment to be used is not contaminated by different refrigerants.
Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in
them.
•Cylinders shall be kept upright.
•Ensure that the refrigeration system is earthed before charging the system with refrigerant.
•Label the system when charging is complete (if not already).
•Extreme care shall be taken not to overfill the refrigeration system.
Before recharging, the system shall be tested for leakage with OFN. On completion of charging,
the system shall be tested before commissioning. Follow up leakage test shall be carried out
before leaving the site.
ix
SiMT041509ESafety Cautions
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with
the equipment and all its details. It is recommended to train technicians so that all of the
refrigerant is recovered safely. In case analysis is required before re-using the reclaimed
refrigerant, an oil and refrigerant sample shall be taken before proceeding with
decommissioning. It is essential that electrical power is available before work.
a) Comprehend the equipment and its operation.
b) Isolate the system electrically.
c) Before starting work, ensure that:
• mechanical handling equipment is available if required, for handling refrigerant cylinders;
• protective equipment can be used in compliance with specifications;
• the recovery process is supervised by a competent person at all times;
• recovery equipment and cylinders conform to the appropriate standards.
d) Pump down the refrigerant system, if possible.
e) If vacuum can not be ensured, apply a manifold so that refrigerant can be removed from
various parts of the system.
f)Make sure that the cylinder is situated on the scale before recovery takes place.
g) Start the refrigerant recovery device and operate it in accordance with the manufacturer's
instructions.
h) Do not overfill cylinders. (Do not exceed 80% liquid charge volume).
i)Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)When the cylinders have been filled correctly and the process is completed, make sure
that the cylinders and the equipment are removed from site promptly and all valves on the
equipment are closed.
k) Recovered refrigerant shall not be charged into another refrigeration system before it has
been cleaned and checked.
Labelling
Equipment shall be labelled stating that it has been decommissioned and emptied of refrigerant.
The label shall be dated and signed. Ensure that there are labels on the equipment stating the
equipment contains R-32.
Refrigerant recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended to conduct training so that all refrigerants can be removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are used.
Ensure that the correct number of cylinders for holding the total system charge are available. All
cylinders to be used must be designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be equipped
with a pressure relief valve and associated shut-off valves in good working order. If possible,
empty recovery cylinders shall be cooled in a separate place before recovery is conducted.
The recovery equipment shall be in good working order with instructions concerning the
equipment at hand, and shall be suitable for the recovery of R-32. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be equipped with
leak-free disconnect couplings and in good condition. Before using the recovery device, check
that it has undergone proper maintenance, that it is in satisfactory working order, and that any
associated electrical components are sealed to prevent ignition in the event of a refrigerant
leakage. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, with the relevant Waste Transfer Note attached. Do not mix refrigerants in recovery
units and especially not in cylinders.
If compressors or compressor oil are to be removed, ensure that the refrigerant melted into the
oil has been evacuated to an acceptable level to make certain that R-32 does not remain within
the oil. The evacuation process shall be carried out before returning the compressor to the
supplier. Only electric heating to the compressor body shall be employed to accelerate this
process. Oil drained from the system shall be treated safely.
x
Safety CautionsSiMT041509E
1.2Warnings and Cautions Regarding Safety of Users
Warning
Do not store the equipment in a room with successive fire sources (e.g.,
naked flame, gas appliance, electric heater).
Be sure to use parts listed in the service parts list of the applicable model
and appropriate tools to conduct repair work. Never attempt to modify the
equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires have scratches or deteriorated, be sure
to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same
power outlet with other electrical appliances, since it may cause an
electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow
the local technical standards related to the electrical equipment, the
internal wiring regulations, and the instruction manual for installation
when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause an
electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and
outdoor units.
Make the connections securely and route the cable properly so that there is no
force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that the
terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable may cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
may damage the cable.
Do not mix air or gas other than the specified refrigerant (R-32 / R-410A /
R-22) in the refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and repair
it before charging the refrigerant. After charging refrigerant, make sure
that there is no refrigerant leak.
If the leaking point cannot be located and the repair work must be stopped, be
sure to perform pump-down and close the service valve, to prevent the
refrigerant gas from leaking into the room. The refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such as fan
and other heaters, stoves and ranges.
xi
SiMT041509ESafety Cautions
Warning
When relocating the equipment, make sure that the new installation site
has sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose, then
insert the plug into a power outlet securely.
If the plug has dust or loose connection, it may cause an electrical shock or fire.
Be sure to install the product correctly by using the provided standard
installation frame.
Incorrect use of the installation frame and improper installation may cause the
equipment to fall, resulting in injury.
Be sure to install the product securely in the installation frame mounted
on the window frame.
If the unit is not securely mounted, it may fall and cause injury.
When replacing the coin battery in the remote controller, be sure to
dispose of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending
on the conditions of the installation site, to prevent electrical shocks.
For unitary type
only
For unitary type
only
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If the combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if the parts and wires are mounted and connected properly,
and if the connections at the soldered or crimped terminals are secure.
Improper installation and connections may cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame may cause the unit to fall, resulting in
injury.
xii
Safety CautionsSiMT041509E
Caution
Check the earth / grounding, and repair it if the equipment is not properly
earthed / grounded.
Improper earth / grounding may cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make
sure that the resistance is 1 MΩ or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause the water to enter the room and wet the furniture
and floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
Be sure to install the packing and seal on the installation frame properly.
If the packing and seal are not installed properly, water may enter the room and
wet the furniture and floor.
For unitary type
only
xiii
SiMT041509EUsed Icons
2. Used Icons
The following icons are used to attract the attention of the reader to specific information.
IconType of
Information
WarningA Warning is used when there is danger of personal injury.
Warning
CautionA Caution is used when there is danger that the reader, through
Caution
NoteA Note provides information that is not indispensable, but may
Note:
ReferenceA Reference guides the reader to other places in this binder or
Description
incorrect manipulation, may damage equipment, lose data, get
an unexpected result or has to restart (part of) a procedure.
nevertheless be valuable to the reader, such as tips and tricks.
in this manual, where he/she will find additional information on a
specific topic.
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Lengthm3030
Max. Interunit Height Differencem 2020
Chargeless m 1010
Amount of Additional Charge of
Refrigerant
Indoor UnitFTKM18PVMKFTKM24PVMK
Front Panel Color (Mancel No.) White (N95)White (N95)
Airflow Rate
Fan
Air Direction ControlRight, Left, Horizontal, DownwardRight, Left, Horizontal, Downward
Air FilterRemovable, Washable, Mildew ProofRemovable, Washable, Mildew Proof
Running Current (Rated) A 0.45 - 0. 43 - 0.41 / 0.45 - 0.430.70- 0.67 - 0.64 / 0.70 - 0.67
Power Consumption (Rated)W5985
Power Factor (Rated) %59.6 - 59.7 - 60.0 / 59.6 - 59.755.2 - 55.2 - 55.3 / 55.2 - 55.2
Temperature Control Microcomputer ControlMicrocomputer Control
Dimensions (H × W × D) mm 340 × 1,050 × 259 340 × 1,050 × 259
Packaged Dimensions (H × W × D)mm342 × 1,160 × 429342 × 1,160 × 429
Weight (Mass) kg1515
Gross Weight (Gross Mass)kg2121
Sound
H
M16.5 (583)17.7 (625)
L12.6 (445)13.7 (484)
SL10.9 (385)12.2 (431)
Type Cross Flow FanCross Flow Fan
Motor Output W 4848
SpeedSteps5 Steps, Quiet, Auto5 Steps, Quiet, Auto
H / M / L / SL dB(A)48 / 42 / 35 / 3251 / 45 / 37 / 34
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2YC40BXD2YC40BXD
Motor OutputW1,3001,300
Type FW68DA FW68DA
ChargeL0.650 0.650
Type R-32 R-32
Chargekg1.12 1.40
H
SL62.0 (2,189)61.4 (2,168)
TypePropellerPropeller
Motor OutputW 128128
Heat Insulation Both Liquid and Gas Pipes
Max. Interunit Piping Lengthm30
Max. Interunit Height Differencem 20
Chargelessm 10
Amount of Additional Charge of
Refrigerant
Indoor UnitFTKM28PVMK
Front Panel Color (Mancel No.) White (N95)
Airflow Rate
Fan
Air Direction ControlRight, Left, Horizontal, Downward
Air FilterRemovable, Washable, Mildew Proof
Running Current (Rated) A 0.74- 0.71 - 0.68 / 0.74 - 0.71
Power Consumption (Rated)W91
Power Factor (Rated) %55.9 - 55.7 - 55.8 / 55.9 - 55.7
Temperature Control Microcomputer Control
Dimensions (H × W × D) mm 340 × 1,200 × 259
Packaged Dimensions (H × W × D)mm342 × 1,310 × 429
Weight (Mass) kg18
Gross Weight (Gross Mass)kg25
Sound
Pressure
Level
Outdoor UnitRKM28PVMK
Casing ColorIvory White
Compressor
Refrigerant
Oil
Refrigerant
Airflow Rate
Fan
Running Current (Rated)A10.3 - 9.8 - 9.4 / 10.3 - 9.8
Power Consumption (Rated) W2,219
Power Factor (Rated)%97.9 - 98.4 - 98.4 / 97.9 - 98.4
Starting Current A10.7
Dimensions (H × W × D) mm695 × 930 × 350
Packaged Dimensions (H × W × D) mm762 × 1,004 × 475
Weight (Mass)kg49
Gross Weight (Gross Mass)kg56
Sound
Pressure
Level
Drawing No. 3D093406
Indoor UnitFTKM28PVMK
Outdoor UnitRKM28PVMK
Liquidmmφ 6.4
Gasmmφ 15.9
Drainmm—
H
M20.6 (727)
L16.3 (576)
SL14.5 (512)
Type Cross Flow Fan
Motor Output W 64
SpeedSteps5 Steps, Quiet, Auto
H / M / L / SL dB(A)54 / 49 / 42 / 39
Type Hermetically Sealed Swing Type
Model 2YC40BXD
Motor OutputW1,300
Type FW68DA
ChargeL0.650
Type R-32
Chargekg1.60
H
SL61.4 (2,168)
TypePropeller
Motor OutputW 128
HdB(A) 57
kW8.21 (1.9 ~ 9.4)
Btu/h28,000 (6,500 ~ 32,000)
kcal/h7,060 (1,640 ~ 8,070)
W 2,310 (310 ~ 3,030)
W/W3.55 (6.16 ~ 3.10)
g/m 20
25.2 (890)
m³/min
(cfm)
m³/min
(cfm)
79.0 (2,789)
The data are based on the conditions shown in the table below.
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Lengthm3030
Max. Interunit Height Differencem 2020
Chargeless m 1010
Amount of Additional Charge of
Refrigerant
Indoor UnitFTXM18PVMKFTXM24PVMK
Front Panel Color (Mancel No.) White (N95)White (N95)
Airflow Rate
Fan
Air Direction ControlRight, Left, Horizontal, DownwardRight, Left, Horizontal, Downward
Air FilterRemovable, Washable, Mildew ProofRemovable, Washable, Mildew Proof
Running Current (Rated) A
Power Consumption (Rated)W59658585
Power Factor (Rated) %
Temperature Control Microcomputer ControlMicrocomputer Control
Dimensions (H × W × D) mm 340 × 1,050 × 259 340 × 1,050 × 259
Packaged Dimensions (H × W × D)mm342 × 1,160 × 429342 × 1,160 × 429
Weight (Mass) kg1515
Gross Weight (Gross Mass)kg2121
Sound
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2YC40BXD2YC40BXD
Motor OutputW1,3001,300
Type FW68DA FW68DA
ChargeL0.650 0.650
Type R-32 R-32
Chargekg1.12 1.40
H
SL62.0 (2,189)48.3 (1,705)61.4 (2,168)55.3 (1,953)
TypePropellerPropeller
Motor OutputW 128128
HdB(A) 51515655
m³/min
(cfm)
m³/min
(cfm)
CoolingHeatingCoolingHeating
95.9 - 96.2 - 97.0 /
95.9 - 96.2
20.5 (724)22.2 (784)22.0 (777)22.9 (809)
0.45 - 0.43 - 0.41 /
0.45 - 0.43
59.6 - 59.7 - 60.0 /
59.6 - 59.7
76.9 (2,715)49.8 (1,758)74.2 (2,620)62.5 (2,207)
96.2 - 96.8 - 97.8 /
96.2 - 96.8
RXM18PVMKRXM24PVMK
96.3 - 97.0 - 96.5 /
96.3 - 97.0
0.49 - 0.47 - 0.45 /
0.49 - 0.47
60.3 - 60.1 - 60.2 /
60.3 - 60.1
96.2 - 97.2 - 96.8 /
96.2 - 97.2
97.6 - 97.8 - 97.2 /
97.6 - 97.8
0.70 - 0.67 - 0.64 /
0.70 - 0.67
55.2 - 55.2 - 55.3 /
55.2 - 55.2
97.7 - 98.1 - 97.7 /
97.7 - 98.1
97.2 - 97.0 - 97.2 /
97.2 - 97.0
0.70 - 0.67 - 0.64 /
0.70 - 0.67
55.2 - 55.2 - 55.3 /
55.2 - 55.2
97.3 - 97.3 - 97.8 /
97.3 - 97.3
Note:
The data are based on the conditions shown in the table below.
Heat Insulation Both Liquid and Gas Pipes
Max. Interunit Piping Lengthm30
Max. Interunit Height Differencem 20
Chargelessm 10
Amount of Additional Charge of
Refrigerant
Indoor UnitFTXM28PVMK
Front Panel Color (Mancel No.) White (N95)
Airflow Rate
Fan
Air Direction ControlRight, Left, Horizontal, Downward
Air FilterRemovable, Washable, Mildew Proof
Running Current (Rated) A 0.74 - 0. 71 - 0.68 / 0.74 - 0.710.69 - 0.66 - 0.63 / 0.69 - 0.66
Power Consumption (Rated)W9184
Power Factor (Rated) %55.9 - 55.7 - 55.8 / 55.9 - 55.755.3 - 55.3 - 55.6 / 55.3 - 55.3
Temperature Control Microcomputer Control
Dimensions (H × W × D) mm 340 × 1,200 × 259
Packaged Dimensions (H × W × D)mm342 × 1,310 × 429
Weight (Mass) kg18
Gross Weight (Gross Mass)kg25
Sound
H
M20.6 (727)21.2 (749)
L16.3 (576)16.2 (572)
SL14.5 (512)14.9 (526)
Type Cross Flow Fan
Motor Output W 64
SpeedSteps5 Steps, Quiet, Auto
H / M / L / SL dB(A)54 / 49 / 42 / 3953 / 45 / 38 / 35
Type Hermetically Sealed Swing Type
Model 2YC40BXD
Motor OutputW1,300
Type FW68DA
ChargeL0.650
Type R-32
Chargekg1.60
H
SL61.4 (2,168)55.3 (1,953)
TypePropeller
Motor OutputW 128
HdB(A) 5757
m³/min
(cfm)
m³/min
(cfm)
CoolingHeating
25.2 (890)27.2 (960)
79.0 (2,789)66.8 (2,359)
RXM28PVMK
The data are based on the conditions shown in the table below.
The definitions of temperatures are classified as following.
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
Target temperature
Room thermistor temperature
Set temperature
Room temperature
(R12321)
The temperature of the room is detected by the room temperature thermistor. However, there is
a difference between the temperature detected by room temperature thermistor and the
temperature of lower part of the room, depending on the type of the indoor unit or installation
condition. Practically, the temperature control is done by the target temperature appropriately
adjusted for the indoor unit and the temperature detected by room temperature thermistor.
1.2Frequency Principle
Control
Parameters
Inverter PrincipleTo regulate the capacity, a frequency control is needed. The inverter makes it possible to
The frequency of the compressor is controlled by the following 2 parameters:
The load condition of the operating indoor unit
The difference between the room thermistor temperature and the target temperature
The target frequency is adapted by additional parameters in the following cases:
Frequency restrictions
Initial settings
Forced cooling operation
control the rotation speed of the compressor. The following table explains the inverter principle:
PhaseDescription
1The supplied AC power source is converted into the DC power source for the present.
2The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting
in an increase of refrigerant circulation. This leads to a larger amount of heat exchange
per unit.
When the frequency decreases, the rotation speed of the compressor decreases
resulting in a decrease of refrigerant circulation. This leads to a smaller amount of heat
exchange per unit.
13Function and Control
SiMT041509EMain Functions
The following drawing shows a schematic view of the inverter principle:
Refrigerant circulation rate (high)
Amount of heat
exchanged air (large)
Amount of heat
exchanged air (small)
AC
freq=
constant
DC
power
power
50 Hz
freq=variable
60 Hz
Refrigerant circulation rate (low)
Inverter FeaturesThe inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor
temperature and cooling / heating load.
Quick heating and quick cooling
The rotation speed of the compressor is increased when starting the heating (or cooling).
This enables to reach the set temperature quickly.
Even during extreme cold weather, high capacity is achieved. It is maintained even when the
outdoor temperature is 2°C.
Comfortable air conditioning
A fine adjustment is integrated to keep the room temperature constant.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
high f
low f
high speed
low speed
capacity=
variable
Amount of heat
exchanged air (large)
Amount of heat
exchanged air (small)
(R2812)
Frequency LimitsThe following functions regulate the minimum and maximum frequency:
FrequencyFunctions
Low Four way valve operation compensation. Refer to page 35.
High Compressor protection function. Refer to page 36.
Discharge pipe temperature control. Refer to page 36.
Input current control. Refer to page 37.
Freeze-up protection control. Refer to page 38.
Heating peak-cut control. Refer to page 38.
Defrost control. Refer to page 40.
Forced Cooling
Refer to page 92 for detail.
Operation
Function and Control14
Main FunctionsSiMT041509E
1.3Airflow Direction Control
Power-Airflow
Dual Flaps
The large flap sends a large volume of air downward to the floor and provides an optimum
control in cooling, dry, and heating operation.
<Cooling / Dry>
During cooling or dry operation, the flap retracts into the indoor unit. Then, cool air can be blown
far and distributed all over the room.
<Heating>
During heating operation, the large flap directs airflow downward to spread the warm air to the
entire room.
Wide-Angle
Louvers
The louvers, made of elastic synthetic resin, provide a wide range of airflow that guarantees
comfortable air distribution.
Auto-SwingThe following table explains the auto-swing process for cooling, dry, heating, and fan:
Flap (up and down)
Cooling / DryHeatingFan
°
15
50
°
°
25
°
°
60
(R9303)
30
70
40
°
°
75
°
(R9304)
15
°
°
25
°
75
°
70
(R9305)
Louver
(right and left)
°
45
°
45
(R9306)
3-D AirflowAlternative repetition of vertical and horizontal swing motions enables uniform air-conditioning of
the entire room.
When the horizontal swing and vertical swing are both set to automatic operation, the airflow
becomes 3-D airflow. The horizontal and vertical swing motions are alternated and the airflow
direction changes in the order shown in the following diagram.
(1) The louvers move from the right to the left.
(2) The flaps move downward.
(3) The louvers move from the left to the right.
(4) The flaps move upward.
(1)
COMFORT
AIRFLOW
(2)
(3)
The flaps are controlled not to blow the air directly at the people in the room.
CoolingHeating
(4)
(R13554)
Operation
°
10
20
°
(R22374)
75
°
°
80
(R9654)
15Function and Control
Loading...
+ 89 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.