Daikin FTXS12HVJU, RX09FAVJU, FTXS15HVJU, RXS09DAVJU, RXS12DAVJU Service Manual

...
SiUS04 - 904
Inverter Pair
Wall Mounted Type H-Series
[Applied Models] Inverter Pair : Heat Pump
SiUS04-904
Table of Contents i
Inverter Pair
Wall Mounted Type
H-Series
Heat Pump
Indoor Unit
FTXS09HVJU FTXS12HVJU FTXS15HVJU FTXS18HVJU FTXS24HVJU
Outdoor Unit
RXS09DAVJU RX09FAVJU RXS12DAVJU RX12FAVJU RXS15DVJU RX15FVJU RXS18DVJU RX18FVJU RXS24DVJU RX24FVJU
SiUS04-904
ii Table of Contents
Safety Considerations..................................................................vi
Part 1
List of Functions ...................................................................1
1. Functions....................................................................................................2
Part 2
Specifications .......................................................................4
1. Specifications .............................................................................................5
1.1 SEER 16 Models ......................................................................................... 5
1.2 SEER 13 Models ......................................................................................... 8
Part 3
Printed Circuit Board
Connector Wiring Diagram ..................................................11
1. Printed Circuit Board Connector Wiring Diagram..................................... 12
1.1 FTXS09/12HVJU....................................................................................... 12
1.2 FTXS15/18/24HVJU.................................................................................. 14
1.3 RXS09/12DAVJU, RX09/12FAVJU........................................................... 16
1.4 RXS15/18/24DVJU, RX15/18/24FVJU...................................................... 18
Part 4
Function and Control..........................................................21
1. Main Functions......................................................................................... 23
1.1 Frequency Principle................................................................................... 23
1.2 Power-Airflow Dual Louvers, Wide-Angle Fins and Auto-Swing .............. 24
1.3 Fan Speed Control for Indoor Units........................................................... 25
1.4 Program Dry Function ............................................................................... 26
1.5 Automatic Operation.................................................................................. 27
1.6 Thermostat Control.................................................................................... 28
1.7 NIGHT SET Mode ..................................................................................... 29
1.8 INTELLIGENT EYE ................................................................................... 30
1.9 HOME LEAVE Operation .......................................................................... 31
1.10 Inverter POWERFUL Operation ................................................................ 32
1.11 Other Functions......................................................................................... 33
2. Function of Thermistor ............................................................................. 35
3. Control Specification (09/12 Class)..........................................................36
3.1 Mode Hierarchy ........................................................................................ 36
SiUS04-904
Table of Contents iii
3.2 Frequency Control..................................................................................... 36
3.3 Controls at Mode Changing / Start-up....................................................... 38
3.4 Discharge Pipe Temperature Control........................................................ 40
3.5 Input Current Control................................................................................. 40
3.6 Freeze-up Protection Control .................................................................... 41
3.7 Heating Peak-cut Control .......................................................................... 42
3.8 Fan Control................................................................................................ 42
3.9 Liquid Compression Protection Function 2................................................ 42
3.10 Defrost Control .......................................................................................... 43
3.11 Electronic Expansion Valve Control .......................................................... 44
3.12 Malfunctions .............................................................................................. 47
3.13 Forced Operation Mode ............................................................................ 48
3.14 Additional Functions .................................................................................. 48
4. Control Specification (15/18/24 Class).....................................................49
4.1 Mode Hierarchy ......................................................................................... 49
4.2 Frequency Control..................................................................................... 50
4.3 Controls at Mode Changing / Start-up....................................................... 52
4.4 Discharge Pipe Temperature Control........................................................ 53
4.5 Input Current Control................................................................................. 53
4.6 Freeze-up Protection Control .................................................................... 54
4.7 Heating Peak-cut Control .......................................................................... 54
4.8 Fan Control................................................................................................ 55
4.9 Liquid Compression Protection Function 2................................................ 55
4.10 Low Hz High Pressure Limit ...................................................................... 55
4.11 Defrost Control .......................................................................................... 56
4.12 Electronic Expansion Valve Control .......................................................... 57
4.13 Malfunctions .............................................................................................. 59
4.14 Forced Operation Mode ............................................................................ 61
4.15 Additional Functions .................................................................................. 61
Part 5
Operation Manual ................................................................62
1. System Configuration...............................................................................63
2. FTXS09/12HVJU...................................................................................... 64
3. FTXS15/18/24HVJU................................................................................. 77
Part 6
Service Diagnosis................................................................91
1. Caution for Diagnosis............................................................................... 92
2. Problem Symptoms and Measures .......................................................... 94
3. Service Check Function ...........................................................................95
4. Troubleshooting ....................................................................................... 98
4.1 Error Codes and Description ..................................................................... 98
4.2 Indoor Unit PCB Abnormality .................................................................... 99
4.3 Freeze-up Protection Control or High Pressure Control.......................... 100
SiUS04-904
iv Table of Contents
4.4 Fan Motor or Related Abnormality .......................................................... 102
4.5 Thermistor or Related Abnormality (Indoor Unit)..................................... 105
4.6 Signal Transmission Error (between Indoor and Outdoor Unit) .............. 106
4.7 OL Activation (Compressor Overload) .................................................... 108
4.8 Compressor Lock .................................................................................... 109
4.9 DC Fan Lock ........................................................................................... 111
4.10 Input Overcurrent Detection .................................................................... 112
4.11 Four-Way Valve Abnormality................................................................... 115
4.12 Discharge Pipe Temperature Control...................................................... 119
4.13 High Pressure Control in Cooling ............................................................ 121
4.14 Position Sensor Abnormality ................................................................... 123
4.15 DC Voltage / Current Sensor Abnormality............................................... 125
4.16 CT or Related Abnormality ...................................................................... 126
4.17 Thermistor or Related Abnormality (Outdoor Unit).................................. 128
4.18 Electrical Box Temperature Rise............................................................. 130
4.19 Radiation Fin Temperature Rise ............................................................. 132
4.20 Output Overcurrent Detection ................................................................. 134
4.21 Refrigerant Shortage ............................................................................... 138
4.22 Over-voltage Detection............................................................................ 142
4.23 Low-voltage Detection............................................................................. 143
5. Check .....................................................................................................144
5.1 How to Check .......................................................................................... 144
Part 7
Removal Procedure ...........................................................153
1. FTXS09/12HVJU.................................................................................... 154
1.1 Removal of Air Filter................................................................................ 154
1.2 Removal of Front Grille ........................................................................... 157
1.3 Removal of Horizontal Blades (Louvers) and Vertical Blades (Fins)....... 160
1.4 Removal of Electrical Box, PCB and Swing Motor .................................. 162
1.5 Removal of Heat Exchanger ................................................................... 168
1.6 Install of Drain Plug ................................................................................. 171
1.7 Removal of Fan Rotor and Fan Motor..................................................... 173
2. FTXS15/18/24HVJU............................................................................... 177
2.1 Removal of the Air Filter / Front Panel .................................................... 177
2.2 Removal of Front Grille ........................................................................... 181
2.3 Removal of Horizontal Blades (Louvers) / Vertical Blades (Fins)............ 184
2.4 Removal of Electrical Box / PCB / Swing Motor ...................................... 187
2.5 Removal of Heat Exchanger ................................................................... 195
2.6 Removal of Fan Rotor / Fan Motor.......................................................... 198
3. RXS09/12DAVJU, RX09/12FAVJU........................................................ 201
3.1 Removal of Panels and Fan Motor.......................................................... 201
3.2 Removal of Electrical Box ....................................................................... 210
3.3 Removal of Reactor and Partition Plate .................................................. 214
3.4 Removal of Sound Blanket...................................................................... 216
3.5 Removal of Four-Way Valve ................................................................... 218
SiUS04-904
Table of Contents v
3.6 Removal of Compressor.......................................................................... 221
3.7 Removal of PCB...................................................................................... 223
4. RXS15/18/24DVJU, RX15/18/24FVJU ..................................................226
4.1 Removal of Panels and Plates ................................................................ 226
4.2 Removal of Fan Motor / Outdoor Fan...................................................... 231
4.3 Removal of PCB / Electrical Box ............................................................. 235
4.4 Removal of the Reactor........................................................................... 244
4.5 Removal of Sound Blanket...................................................................... 246
4.6 Removal of Four-Way Valve ................................................................... 249
4.7 Removal of Electronic Expansion Valve.................................................. 250
4.8 Removal of Compressor.......................................................................... 251
Part 8
Other Considerations ........................................................253
1. Other Considerations .............................................................................254
1.1 Trial Operation......................................................................................... 254
1.2 Jumper Settings ...................................................................................... 255
1.3 Application of Silicon Grease to Power Transistor and Diode Bridge .... 256
Part 9
Appendix............................................................................257
1. Piping Diagrams..................................................................................... 258
1.1 Indoor Units ............................................................................................. 258
1.2 Outdoor Units .......................................................................................... 259
2. Wiring Diagrams..................................................................................... 261
2.1 Indoor Units ............................................................................................. 261
2.2 Outdoor Units .......................................................................................... 262
Safety Considerations SiUS04-904
vi Safety Considerations
1. SAFETY CONSIDERATIONS
Read these SAFETY CONSIDERATIONS carefully before performing any repair work. Comply with these safety symbols without fail.
Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols:
DANGER .............. Indicates an imminently hazardous
situation which, if not avoided, will result in death or serious injury.
WARNING ............ Indicates a potentially hazardous
situation which, if not avoided, could result in death or serious injury.
CAUTION ............. Indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE .................. Indicates situations that may result
in equipment or property-damage accidents only.
1.1 Safety Considerations for Repair
DANGER
• If refrigerant gas leaks during repair or service, ventilate the area immediately. Refrigerant gas may produce toxic gas if it comes into contact with flames. Refrigerant gas is heavier than air and replaces oxygen. In the event of an accident, a massive leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• Do not start or stop the air conditioner operation by plugging or unplugging the power cable plug if a plug is used. Plugging or unplugging the power cable plug to operate the equipment may cause an electrical shock or fire.
• Use parts listed in the service parts list and appropriate tools to conduct repair work. The use of inappropriate parts or tools may cause an electrical shock or fire.
• Disconnect power before disassembling the equipment for repairs. Working on the equipment that is connected to the power supply may cause an electric shock. If it is necessary to supply power to the equipment to conduct repairs or to inspect the circuits, do not touch any electrically charged sections of the equipment.
• The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. Discharge the capacitor completely before conducting repair work. A charged capacitor may cause an electrical shock.
• If refrigerant gas is discharged during repair work, do not touch the discharged refrigerant gas. The refrigerant gas may cause frostbite.
• Use only pipes, flare nuts, tools, and other materials designed specifically for R410A refrigerant systems. Never use tools or materials designed for R22 refrigerant systems on an R410A refrigerant system. Doing so can cause a serious accident or an equipment failure.
• Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections may cause excessive heat generation, fire, or electrical shock.
WARNING
• Prior to disconnecting the suction or discharge pipe from the compressor at the welded section, pump-down the refrigerant gas completely in a well­ventilated place first. If there is refrigerant gas or oil remaining inside the compressor, the refrigerant gas or oil can discharge when the pipe is being disconnected and it may cause an injury.
• Wear a safety helmet, gloves, and a safety belt when working at an elevated height of more than 6.5 ft (2 m). Insufficient safety measures may cause a fall resulting in injury.
• Do not mix air or gas other than the specified refrigerant R410A to the refrigerant system. If air enters the refrigerant systems, it can cause an excessive high pressure resulting in equipment damage and injury.
• When relocating the equipment, check if the new installation site has sufficient strength to withstand the weight of the equipment. If the installation site does not have sufficient strength and the equipment is not properly secured, the equipment may fall and cause injury.
• Securely fasten the outside unit terminal cover (panel). If the terminal cover/panel is not fastened properly, dust or water may enter the outside unit causing fire or electric shock.
• When relocating the system, keep the refrigerant circuit free from substances other than the specified refrigerant (R-410A) such as air. Any presence of air or other foreign substance in the refrigerant circuit can cause an abnormal pressure rise or rupture, resulting in injury.
• If refrigerant gas leaks, locate the leaking point and repair it before charging refrigerant. After charging refrigerant, check for refrigerant leaks. If the leaking point cannot be located and the repair work must be stopped, perform a pump-down and close the service valve to prevent the refrigerant gas from leaking into the room. The refrigerant gas itself is harmless, but it may generate toxic gases if it comes into contact with flames.
SiUS04-904 Safety Considerations
Safety Considerations vii
CAUTION
• Do not repair the electrical components with wet hands. Working on the equipment with wet hands may cause an electrical shock.
• Do not clean the air conditioner by splashing water on it. Washing the unit with water may cause an electrical shock.
• Ground the unit when repairing equipment in a humid or wet place to avoid electrical shocks.
• Turn off the power when cleaning the equipment to prevent internal fans that rotate at high speed from starting suddenly as they can cause injury.
• Let the refrigerant lines cool down before performing any repair work. Working on the unit when the refrigerant lines are hot may cause burns.
• All welding and cutting operations must be done in a well-ventilated place to prevent the accumulation of toxic fumes or possibly oxygen deficiency to occur.
• Check the grounding and repair it if the equipment is not properly grounded. Improper grounding may cause an electrical shock.
• Measure the insulation resistance after the repair.
The resistance must be 1M or higher. Faulty insulation may cause an electrical shock.
NOTE
• Check the drainage of the indoor unit after finishing repair work. Faulty drainage may cause water to enter the room resulting in wet floors and furniture.
• Do not tilt the unit when removing it. The water inside the unit may spill resulting in wet floors and furniture.
• Dismantling of the unit, disposal of the refrigerant, oil, and additional parts, should be done in accordance with the relevant local, state, and national regulations.
1.2 Safety Considerations for Users
DANGER
• Never attempt to modify the equipment. Doing so can cause electrical shock, excessive heat generation, or fire.
• If the power cable and lead wires have scratches or have become deteriorated, have them replaced. Damaged cable and wires may cause an electrical shock or fire.
• Do not use a joined power cable or an extension cord, or share the same power outlet with other
electrical appliances as it may cause an electrical shock or fire.
• Use an exclusive power circuit for the equipment. Insufficient circuit amperage capacity may cause an electrical shock or fire.
WARNING
• Do not damage or modify the power cable. Damaged or modified power cables may cause an electrical shock or fire. Placing heavy items on the power cable or pulling the power cable may damage the cable.
• Check the unit foundation for damage on a continual basis, especially if it has been in use for a long time. If left in a damaged condition, the unit may fall and cause injury. If the installation platform or frame has corroded, have it replaced. A corroded platform or frame may cause the unit to fall resulting in injury.
• If the unit has a power cable plug and it is dirty, clean the plug before securely inserting it into a power outlet. If the plug has a loose connection, tighten it or it may cause electrical shock or fire.
CAUTION
• After replacing the battery in the remote controller, dispose of the old battery to prevent children from swallowing it. If a child swallows the battery, see a doctor immediately.
• Never remove the fan guard of the unit. A fan rotating at high speed without the fan guard is very dangerous.
• Before cleaning the unit, stop the operation of the unit by turning the power off or by pulling the power cable plug out from its receptacle. Otherwise an electrical shock or injury may result.
• Do not wipe the controller operation panel with benzene, thinner, chemical dust cloth, etc. The panel may get discolored or the coating can peel off. If it is extremely dirty, soak a cloth in a water-diluted neutral detergent, squeeze it well, and wipe the panel clean. Then wipe it with another dry cloth.
Safety Considerations SiUS04-904
viii Safety Considerations
SiUS04-904
List of Functions 1
Part 1
List of Functions
1. Functions....................................................................................................2
SiUS04-904 Functions
2 List of Functions
1. Functions
SEER 16:
Category Functions
FTXS09/12HVJU
RXS09/12DAVJU
FTXS15/18/24HVJU
RXS15/18/24DVJU
Category Functions
FTXS09/12HVJU
RXS09/12DAVJU
FTXS15/18/24HVJU
RXS15/18/24DVJU
Basic Function
Inverter (with Inverter Power Control) Health & Air
Cleaning
Air-Purifying Filter
Operation Limit for Cooling (°FDB)
(°)
14~
115
**
(°)
14~
115
**
Photocatalytic Deodorizing Filter
Operation Limit for Heating (°FWB)
5~645~
64
Air-Purifying Filter with Photocatalytic Deodorizing Function

PAM Control 
Titanium Apatite Photocatalytic Air-Purifying Filter
——
Compressor Oval Scroll Compressor
Swing Compressor  Air Filter (Prefilter) 
Rotary Compressor Wipe-clean Flat Panel 
Reluctance DC Motor  Washable Grille
Comfortable Airflow
Power-Airflow Louvers Filter Cleaning Indicator
Power-Airflow Dual Louvers  Good-Sleep Cooling Operation
Power-Airflow Diffuser Timer 24-Hour ON/OFF Timer 
Wide-Angle Louvers  Night Set Mode 
Horizontal Louvers operate vertically: Auto-Swing (Up and Down)

Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) 
Vertical Fins operate horizontally: Auto­Swing (Right and Left)
Self-Diagnosis (Digital, LED) Display 
3-D Airflow Wiring Error Check
Comfort Airflow Mode
Anticorrosion Treatment of Outdoor Heat Exchanger

Comfort Control
Auto Fan Speed 
Indoor Unit Quiet Operation Flexibility
Multi-Split / Split Type Compatible Indoor Unit
Night Quiet Mode (Automatic)
Outdoor Unit Quiet Operation (Manual)  Flexible Voltage Correspondence
INTELLIGENT EYE  High Ceiling Application
Quick Warming Function  Chargeless
33ft 33ft
Hot-Start Function  Either Side Drain (Right or Left) 
Automatic Defrosting  Power Selection
Operation
Automatic Operation 
Remote Control
5-Rooms Centralized Controller (Option)

Program Dry Function 
Remote Control Adapter (Normal Open-Pulse Contact) (Option)

Fan Only 
Lifestyle Convenience
New POWERFUL Operation (Non­Inverter)
——
Remote Control Adapter (Normal Open Contact) (Option)

Inverter POWERFUL Operation 
Priority-Room Setting DIII-NET Compatible (Adapter) (Option) 
Cooling / Heating Mode Lock Remote
Controller
Wireless 
HOME LEAVE Operation  Wired (option)
Indoor Unit ON/OFF Switch 
Signal Reception Indicator 
Temperature Display
Note:  : Holding Functions
— : No Functions
15/18 class
** With optional wind baffle
Functions SiUS04-904
List of Functions 3
SEER 13 Functions:
Category Functions
FTXS09/12HVJU
RX09/12FAVJU
FTXS15/18/24HVJU
RX15/18/24FVJU
Category Functions
FTXS09/12HVJU
RX09/12FAVJU
FTXS15/18/24HVJU
RX15/18/24FVJU
Basic Function
Inverter (with Inverter Power Control) Health & Air
Cleaning
Air-Purifying Filter
Operation Limit for Cooling (°FDB)
14~ 115
14~ 115
Photocatalytic Deodorizing Filter
Operation Limit for Heating (°FWB)
5~645~
64
Air-Purifying Filter with Photocatalytic Deodorizing Function

PAM Control 
Titanium Apatite Photocatalytic Air-Purifying Filter
——
Compressor Oval Scroll Compressor
Swing Compressor  Air Filter (Prefilter) 
Rotary Compressor Wipe-clean Flat Panel 
Reluctance DC Motor  Washable Grille
Comfortable Airflow
Power-Airflow Louvers Filter Cleaning Indicator
Power-Airflow Dual Louvers  Good-Sleep Cooling Operation
Power-Airflow Diffuser Timer 24-Hour ON/OFF Timer 
Wide-Angle Louvers  Night Set Mode 
Auto-Swing; Horizontal Louvers operate vertically (Up and Down)

Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) 
Vertical Fins operate horizontally; Auto­Swing (Right and Left)
Self-Diagnosis (Digital, LED) Display 
3-D Airflow Wiring Error Check
Comfort Airflow Mode
Anticorrosion Treatment of Outdoor Heat Exchanger

Comfort Control
Auto Fan Speed 
Indoor Unit Quiet Operation Flexibility
Multi-Split / Split Type Compatible Indoor Unit
Night Quiet Mode (Automatic)
Outdoor Unit Quiet Operation (Manual)  Flexible Voltage Correspondence
INTELLIGENT EYE  High Ceiling Application
Quick Warming Function  Chargeless
33ft 33ft
Hot-Start Function  Either Side Drain (Right or Left) 
Automatic Defrosting  Power Selection
Operation
Automatic Operation 
Remote Control
5-Rooms Centralized Controller (Option)

Program Dry Function 
Remote Control Adapter (Normal Open-Pulse Contact) (Option)

Fan Only 
Lifestyle Convenience
New POWERFUL Operation (Non­Inverter)
——
Remote Control Adapter (Normal Open Contact) (Option)

Inverter POWERFUL Operation 
Priority-Room Setting DIII-NET Compatible (Adapter) (Option) 
Cooling / Heating Mode Lock Remote
Controller
Wireless 
HOME LEAVE Operation  Wired (Option) 
Indoor Unit ON/OFF Switch 
Signal Reception Indicator 
Temperature Display
Note:  : Holding Functions
— : No Functions
15/18 class
SiUS04-904
4 Specifications
Part 2
Specifications
1. Specifications .............................................................................................5
1.1 SEER 16 Models ......................................................................................... 5
1.2 SEER 13 Models ......................................................................................... 8
SiUS04-904 Specifications
Specifications 5
1. Specifications
1.1 SEER 16 Models
60Hz 230V
Note: The data is based on the conditions shown in the table below.
Models
Indoor Units FTXS09HVJU FTXS12HVJU
Outdoor Units
RXS09DAVJU RXS12DAVJU
Cooling Heating Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 8,500 (4,400~9,500) 10,000 (4,400~11,000) 11,500 (4,800~12,000) 11,500 (4,800~13,000)
Moisture Removal Pt/h 2.3 3.2 — Running Current (Rated) A 4.13 4.98 5.51 4.73 Power Consumption Rated
(Min.~Max.)
W 770 (300~940) 1,070 (290~1,260) 1,290 (300~1,480) 1,000 (310~1,340) Power Factor % 76.9 89.9 93.9 88.2 EER (Rated)
Btu/h·W
11.0 9.3 — COP (Rated) W/W 2.74 3.37 Energy
Efficiency
SEER/HSPF 16.0 8.8 16.0 8.8
Piping Connections
Liquid in (mm) 1/4” (6.4 mm) 1/4” (6.4 mm) Gas in (mm) 3/8” (9.5 mm) 3/8” (9.5 mm)
Drain in (mm) 11/16” (17.5 mm) 11/16” (17.5 mm) Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length ft (m) 65’ (20 m) 65’ (20 m) Max. Interunit Height Difference ft (m) 49’ (15 m) 49’ (15 m) Chargeless ft (m) 33’ (10 m) 33’ (10 m) Amount of Additional Charge of
Refrigerant
oz/ft (kg/ft) 0.22 oz (0.006 kg) 0.22 oz (0.006 kg)
Indoor Units FTXS09HVJU FTXS12HVJU
Front Panel Color White White
Airflow Rate cfm (m³/min)
H 246 (7.0) 253 (7.2) 242 (6.8) 286 (8.1)
M 197 (5.6) 220 (6.2) 195 (5.5) 237 (6.7)
L 148 (4.2) 187 (5.3) 148 (4.2) 187 (5.3)
Fan
Type Cross Flow Fan Cross Flow Fan
Motor Output W 18 18
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.18 0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.6 96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) in (mm) 10-3/4 × 30-7/8 × 7-11/16” (273 × 784 ×195 mm) 10-3/4× 30-7/8 × 7-11/16” (273 × 784× 195 mm) Packaged Dimensions (H×W×D) in (mm) 10-3/16 × 32-13/16 × 12-13/16” (259×818 × 325 mm) 10-3/16 × 32-13/16 × 12-13/16” (259 × 818 × 325 mm) Weight Lbs (kg) 16.6 lbs (7.5 kg) 16.6 lbs (7.5 kg) Gross Weight Lbs (kg) 25.0 lbs (11.3 kg) 25.0 lbs (11.3 kg) Operation Sound H / M / L dBA 38 / 32 / 25 38 / 33 / 28 40 / 33 / 26 39 / 34 / 29
Outdoor Units RXS09DAVJU RXS12DAVJU
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 1YC23NXD 1YC23NXD
Motor Output W 600 600
Refrigerant Oil
Type FVC50K FVC50K
Charge oz (kg) 12.6 oz (0.36 kg) 12.6 oz (0.36 kg)
Refrigerant
Type R-410A R-410A
Charge Lbs (kg) 1.76 Lbs (0.8 kg) 2.20 Lbs (1.0 kg)
Airflow Rate cfm (m³/min)
H 1,120 (31.7) 1,008 (28.5) 1,031 (29.2) 927 (26.3) L 816 (23.1) 813 (23.0) 737 (20.9) 737 (20.9)
Fan
Type Propeller Propeller
Motor Output W 31 31 Running Current (Rated) A 3.93 4.8 5.33 4.6 Power Consumption (Rated) W 730 1,030 1,190 960 Power Factor % 80.4 93.3 97.1 91.7 Dimensions (H×W×D) in(mm) 21-5/8 × 30-1/8 × 11-1/4” (549 × 765 × 286 mm) 21-5/8 × 30-1/8 × 11-1/4” (549× 765 × 286 mm) Packaged Dimensions (H×W×D) in (mm) 25 × 34-5/8 × 14-3/16” (635 × 879 × 360 mm) 25× 34-5/8× 14-3/16” (635× 879× 360 mm) Weight Lbs (kg) 74.0 lbs (33.5 kg) 80.0 lbs (36 kg) Gross Weight Lbs (kg) 86.0 lbs (39 kg) 92.0 lbs (41.7 kg) Operation
Sound
H / L dBA 48 / — 49 / — 49 / — 51 / —
Drawing No. 3D062864A 3D062865A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25 ft (7.5 m)
Specifications SiUS04-904
6 Specifications
60Hz 230V
Note: The data are based on the conditions shown in the table below.
Model
Indoor Units FTXS15HVJU FTXS18HVJU
Outdoor Units
RXS15DVJU RXS18DVJU
Cooling Heating Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 15,000 (3,200~15,000) 18,000 (3,200~21,200) 18,000 (3,200~18,000) 21,600 (3,200~24,000)
Moisture Removal Pt/h 3.4 4.3 — Running Current (Rated) A 5.44 6.88 6.97 8.71 Power Consumption Rated
(Min.~Max.)
W 1,230 (450~1,230) 1,570 (450~2,540) 1,590 (450~1,590) 2,000 (450~2,620) Power Factor % 95.1 96.7 96.7 97.8 EER (Rated)
Btu/h·W
12.2 11.3 — COP (Rated) W/W 3.36 3.17 Energy
Efficiency
SEER/HSPF 17.0 10.1 16.3 9.1
Piping Connections
Liquid in (mm) 1/4” (6.4 mm) 1/4” (6.4 mm) Gas in (mm) 1/2” (12.7 mm) 1/2” (12.7 mm)
Drain in (mm) 11/16” (17.5 mm) 11/16” (17.5 mm) Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length ft (m) 98.4’ (30 m) 98.4’ (30 m) Max. Interunit Height Difference ft (m) 65.6’ (20 m) 65.6’ (20 m) Chargeless ft (m) 33’ (10 m) 33’ (10 m) Amount of Additional Charge of
Refrigerant
oz/ft
(kg/ft)
0.22 oz (0.006 kg) 0.22 oz (0.006 kg)
Indoor Unit FTXS15HVJU FTXS18HVJU
Front Panel Color White White
Airflow Rate cfm (m³/min)
H 519 (14.7) 515 (14.6) 549 (15.5) 609 (17.2)
M 436 (12.3) 459 (13.0) 476 (13.5) 529 (15.0)
L 353 (10.0) 402 (11.4) 402 (11.4) 448 (12.7)
Fan
Type Cross Flow Fan Cross Flow Fan
Motor Output W 43 43
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.18 0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.6 96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) in (mm) 11-7/16 × 41-5/16 ×9-3/8” (291 × 1049 x 238 mm) 11-7/16 × 41-5/16 × 9-3/8” (291× 1049 × 238 mm) Packaged Dimensions (H×W×D) in (mm) 13-1/4 × 45-3/16 × 14-7/16” (337 × 1148 x 367 mm) 13-1/4 × 45-3/16 × 14-7/16” (337 × 1148 × 367 mm) Weight Lbs (kg) 26.5 lbs (12 kg) 26.5 lbs (12 kg) Gross Weight Lbs (kg) 38.0 lbs (17 kg) 38.0 lbs (17 kg) Operation
Sound
H / M / L dBA 45 / 41 / 36 44 / 40 / 35 45 / 41 / 36 44 / 40 / 35
Outdoor Unit RXS15DVJU RXS18DVJU
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2YC32JXD 2YC32JXD
Motor Output W 1,500 1,500
Refrigerant Oil
Model FVC50K FVC50K
Charge oz (kg) 21.8 oz (0.62 kg) 21.8 oz (0.62 kg)
Refrigerant
Model R-410A R-410A
Charge Lbs (kg) 3.75 Lbs (1.7 kg) 3.75 Lbs (1.7 kg)
Airflow Rate cfm (m³/min)
H 1,603 (45.4) 1,367 (38.7) 1,603 (45.4) 1,367 (38.7) L 1,451 (41.1) 1,367 (38.7) 1,451 (41.1) 1,367 (38.7)
Fan
Type Propeller Propeller
Motor Output W 53 53 Running Current (Rated) A 5.3 6.7 6.79 8.50 Power Consumption (Rated) W 1,190 1,530 1,550 1,960 Power Factor % 98.4 99.3 99.3 99.9 Dimensions (H×W×D) in (mm) 28-15/16 × 32-1/2 × 11-13/16” (735 × 826 × 300 mm) 28-15/16 × 32-1/2 × 11-13/16” (735 × 826 × 300 mm) Packaged Dimensions (H×W×D) in (mm) 31-7/16 × 37-15/16 × 15-3/8” (799 × 964 × 391 mm) 31-7/16 × 37-15/16 × 15-3/8” (799 × 964 × 391 mm) Weight Lbs (kg) 117.0 lbs (53 kg) 117.0 lbs (53 kg) Gross Weight Lbs (kg) 133.0 lbs (60 kg) 133.0 lbs (60 kg) Operation
Sound
H / L dBA 51 / — 51 / — 51 / — 51 / —
Drawing No. 3D062866A 3D062868A
Conversion Formulae
kcal/h=kW×860 Btu/h=kW×3414
cfm=m³/min×35.3
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25 ft (7.5 m)
SiUS04-904 Specifications
Specifications 7
60Hz 230V
Note: The data are based on the conditions shown in the table below.
Model
Indoor Units FTXS24HVJU
Outdoor Units
RXS24DVJU
Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 22,000 (3,200~22,000) 24,000 (3,200~25,400)
Moisture Removal Pt/h 6.3 — Running Current (Rated) A 10.30 11.30 Power Consumption Rated
(Min.~Max.)
W 2,360 (450~2,360) 2,590 (450~3,320) Power Factor % 97.7 97.9 EER (Rated)
Btu/h·W
9.3 — COP (Rated) W/W 2.72 Energy
Efficiency
SEER/HSPF 15.0 9.2
Piping Connections
Liquid in (mm) 1/4” (6.4 mm) Gas in (mm) 5/8” (15.8 mm)
Drain in (mm) 11/16” (17.5 mm) Heat Insulation Both Liquid and Gas Pipes Max. Interunit Piping Length ft (m) 98.4’ (30 m) Max. Interunit Height Difference ft (m) 65.6’ (20 m) Chargeless ft (m) 33’ (10 m) Amount of Additional Charge of
Refrigerant
oz/ft
(kg/ft)
0.22 oz (0.006 kg)
Indoor Unit FTXS24HVJU
Front Panel Color White
Airflow Rate cfm (m³/min)
H 536 (15.2) 586 (16.6)
M 473 (13.4) 532 (15.1)
L 409 (11.6) 477 (13.5)
Fan
Type Cross Flow Fan
Motor Output W 43
Speed Steps 5 Steps, Quiet, Auto Air Direction Control Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Running Current (Rated) A 0.20 Power Consumption (Rated) W 45 Power Factor % 97.8 Temperature Control Microcomputer Control Dimensions (H×W×D) in (mm) 11-7/16 × 41-5/16 × 9-3/8” (291 × 1049 × 238 mm) Packaged Dimensions (H×W×D) in (mm) 13-1/4×45-3/16×14-7/16” (337 × 1148 × 367 mm) Weight Lbs (kg) 26.5 lbs (12 kg) Gross Weight Lbs (kg) 38.0 lbs (17 kg) Operation
Sound
H / M / L dBA 46 / 42 / 37 46 / 42 / 37
Outdoor Unit RXS24DVJU
Casing Color Ivory White
Compressor
Type Hermetically Sealed Swing Type
Model 2YC45EXD
Motor Output W 1,900
Refrigerant Oil
Model FVC50K
Charge oz (kg) 25.2 oz (0.7 kg)
Refrigerant
Model R-410A
Charge Lbs (kg) 3.75 Lbs (1.7 kg)
Airflow Rate cfm (m³/min)
H 1,752 (49.6) 1,465 (41.5) L 1,529 (43.3) 1,398 (39.6)
Fan
Type Propeller
Motor Output W 53 Running Current (Rated) A 10.1 11.1 Power Consumption (Rated) W 2,315 2,545 Power Factor % 99.7 99.7 Dimensions (H×W×D) in (mm) 28-15/16 × 32-1/2 × 11-13/16” (735 × 826 × 300 mm) Packaged Dimensions (H×W×D) in (mm) 31-7/16 × 37-15/16 × 15-3/8” (799× 948 × 391 mm) Weight Lbs (kg) 121.0 lbs (55 kg) Gross Weight Lbs (kg) 137.0 lbs (62 kg) Operation
Sound
H / L dBA 54 / — 54 / —
Drawing No. 3D062869A
Conversion
Formulae
kcal/h=kW×860 Btu/h=kW×3414
cfm=m³/min×35.3
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25 ft (7.5 m)
Specifications SiUS04-904
8 Specifications
1.2 SEER 13 Models
60Hz 230V
Note: The data are based on the conditions shown in the table below.
Models
Indoor Units FTXS09HVJU FTXS12HVJU
Outdoor Units
RX09FAVJU RX12FAVJU
Cooling Heating Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 8,500 (5,100~8,500) 10,000 (5,100~10,000) 11,500 (5,500~11,500) 11,500 (5,500~11,500)
Moisture Removal Pt/h 2.3 3.2 — Running Current (Rated) A 4.56 5.21 6.00 5.20 Power Consumption Rated
(Min.~Max.)
W 850 (300~850) 1,120 (290~1,220) 1,350 (300~1,350) 1,100 (310~1,190) Power Factor % 81.1 93.4 97.1 92.0 EER (Rated)
Btu/h·W
10.0 8.5 — COP (Rated) W/W 2.62 3.06 Energy
Efficiency
SEER/HSPF 13.0 7.7 13.0 7.7
Piping Connections
Liquid in (mm) 1/4” (6.4 mm) 1/4” (6.4 mm) Gas in (mm) 3/8” (9.5 mm) 3/8” (9.5 mm)
Drain in (mm) 11/16” (17.5 mm) 11/16” (17.5 mm) Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length ft (m) 65’ (20 m) 65’ (20 m) Max. Interunit Height Difference ft (m) 49’ (15 m) 49’ (15 m) Chargeless ft (m) 33’ (10 m) 33’ (10 m) Amount of Additional Charge of
Refrigerant
oz/ft
(kg/ft)
0.22 oz (0.006 kg) 0.22 oz (0.006 kg)
Indoor Units FTXS09HVJU FTXS12HVJU
Front Panel Color White White
Airflow Rate cfm (m³/min)
H 246 (7.0) 253 (7.2) 242 (6.8) 286 (8.1)
M 197 (5.6) 220 (6.2) 195 (5.5) 237 (6.7)
L 148 (4.2) 187 (5.3) 148 (4.2) 187 (5.3)
Fan
Type Cross Flow Fan Cross Flow Fan
Motor Output W 18 18
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.18 0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.6 96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) in (mm) 10-3/4 × 30-7/8 × 7-11/16” (273× 784 × 195 mm) 10-3/4 × 30-7/8 × 7-11/16” (273 × 784 × 195 mm) Packaged Dimensions (H×W×D) in (mm) 10-3/16 × 32-13/16 × 12-13/16” (259 × 833× 325 mm) 10-3/16 × 32-13/16 × 12-13/16” (259 × 833 × 325 mm) Weight Lbs (kg) 16.6 lbs (7.5 kg) 16.6 lbs (7.5 kg) Gross Weight Lbs (kg) 25.0 lbs (11 kg) 25.0 lbs (11 kg) Operation Sound H / M / L dBA 38 / 32 / 25 38 / 33 / 28 40 / 33 / 26 39 / 34 / 29
Outdoor Units RX09FAVJU RX12FAVJU
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 1YC23NXD 1YC23NXD
Motor Output W 600 600
Refrigerant Oil
Type FVC50K FVC50K
Charge oz (kg) 12.6 oz (0.36 kg) 12.6 oz (0.36 kg)
Refrigerant
Type R-410A R-410A
Charge Lbs (kg) 1.76 Lbs (0.8 kg) 2.20 Lbs (1.0 kg)
Airflow Rate cfm (m³/min)
H 1,120 (31.7) 1,008 (28.5) 1,031 (29.2) 927 (26.3) L 816 (23.1) 813 (23.0) 737 (20.9) 737 (20.9)
Fan
Type Propeller Propeller
Motor Output W 31 31 Running Current (Rated) A 4.38 5.03 5.07 5.02 Power Consumption (Rated) W 810 1,080 1,310 1,060 Power Factor % 80.4 93.3 97.1 91.8 Dimensions (H×W×D) in (mm) 21-5/8 × 30-1/8 × 11-1/4” (549 × 765 × 286 mm) 21-5/8 × 30-1/8 × 11-1/4” (549 × 765 × 286 mm) Packaged Dimensions (H×W×D) in (mm) 25×34-5/8×14-3/16” (635×879.5×360.4 mm) 25×34-5/8×14-3/16” (635×879.5×360.4 mm) Weight Lbs (kg) 74.0 lbs (34 kg) 80.0 lbs (36 kg) Gross Weight Lbs (kg) 86.0 lbs (39 kg) 92.0 lbs (42 kg) Operation
Sound
H / L dBA 48 / — 49 / — 49 / — 51 / —
Drawing No. 3D062872A 3D062873A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25 ft (7.5 m)
SiUS04-904 Specifications
Specifications 9
60Hz 230V
Note: The data are based on the conditions shown in the table below.
Model
Indoor Units FTXS15HVJU FTXS18HVJU
Outdoor Units
RX15FVJU RX18FVJU
Cooling Heating Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 15,000 (6,800~15,000) 18,000 (6,800~21,200) 18,000 (6,800~18,000) 21,600 (6,800~24,000)
Moisture Removal Pt/h 3.4 4.3 — Running Current (Rated) A 6.01 7.58 7.67 9.58 Power Consumption Rated
(Min.~Max.)
W 1,360 (450~1,360) 1,730 (450~2,540) 1,750 (450~1,750) 2,200 (450~2,620) Power Factor % 98.4 99.2 99.2 99.8 EER (Rated)
Btu/h·W
11.0 10.3 — COP (Rated) W/W 3.05 2.88 Energy
Efficiency
SEER/HSPF 13.0 7.7 13.0 7.7
Piping Connections
Liquid in (mm) 1/4” (6.4 mm) 1/4” (6.4 mm) Gas in (mm) 1/2” (12.7 mm) 1/2” (12.7 mm)
Drain in (mm) 11/16” (17.5 mm) 11/16” (17.5 mm) Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length ft (m) 98.4’ (30 m) 98.4’ (30 m) Max. Interunit Height Difference ft (m) 65.6’ (20 m) 65.6’ (20 m) Chargeless ft (m) 33’ (10 m) 33’ (10 m) Amount of Additional Charge of
Refrigerant
oz/ft
(kg/ft)
0.22 oz (0.006 kg) 0.22 oz (0.006 kg)
Indoor Unit FTXS15HVJU FTXS18HVJU
Front Panel Color White White
Airflow Rate cfm (m³/min)
H 519 (14.7) 515 (14.6) 549 (15.5) 609 (17.2)
M 436 (12.3) 459 (13.0) 476 (13.5) 529 (15.0)
L 353 (10.0) 402 (11.4) 402 (11.4) 448 (12.7)
Fan
Type Cross Flow Fan Cross Flow Fan
Motor Output W 43 43
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.18 0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.6 96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) in (mm) 11-7/16 × 41-5/16 × 9-3/8” (291 × 1049 × 238 mm) 11-7/16 × 41-5/16 × 9-3/8” (291 × 1049 × 238 mm) Packaged Dimensions (H×W×D) in (mm) 13-1/4 × 45-3/16 × 14-7/16” (337 × 1148 × 367 mm) 13-1/4 × 45-3/16 × 14-7/16” (337 × 1148 × 367 mm) Weight Lbs (kg) 26.5 lbs (12 kg) 26.5 lbs (12 kg) Gross Weight Lbs (kg) 38.0 lbs (17 kg) 38.0 lbs (17 kg) Operation
Sound
H / M / L dBA 45 / 41 / 36 44 / 40 / 35 45 / 41 / 36 44 / 40 / 35
Outdoor Unit RX15FVJU RX18FVJU
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2YC32JXD 2YC32JXD
Motor Output W 1,500 1,500
Refrigerant Oil
Model FVC50K FVC50K
Charge oz (kg) 21.8 oz (0.61 kg) 21.8 oz (0.61 kg)
Refrigerant
Model R-410A R-410A
Charge Lbs(kg) 3.75 Lbs (1.7 kg) 3.75 Lbs (1.7 kg)
Airflow Rate cfm (m³/min)
H 1,603 (45.4) 1,367 (38.7) 1,603 (45.4) 1,367 (38.7) L 1,451 (41.1) 1,367 (38.7) 1,451 (41.1) 1,367 (38.7)
Fan
Type Propeller Propeller
Motor Output W 53 53 Running Current (Rated) A 5.83 7.4 7.49 9.40 Power Consumption (Rated) W 1,320 1,690 1,710 2,160 Power Factor % 98.4 99.3 99.3 99.9 Dimensions (H×W×D) in (mm) 28-15/16 × 32-1/2× 11-13/16” (735 × 826× 300 mm) 28-15/16 × 32-1/2 × 11-13/16” (735 × 826 × 300 mm) Packaged Dimensions (H×W×D) in (mm) 31-7/16 × 37-15/16 × 15-3/8” (799 × 948×391 mm) 31-7/16 × 37-15/16 × 15-3/8” (799 × 948 × 391 mm) Weight Lbs (kg) 117.0 lbs (53 kg) 117.0 lbs (53 kg) Gross Weight Lbs (kg) 133.0 lbs (60.3 kg) 133.0 lbs (60.3 kg) Operation
Sound
H / L dBA 51 / — 51 / — 51 / — 51 / —
Drawing No. 3D062874A 3D062875A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25 ft (7.5 m)
Specifications SiUS04-904
10 Specifications
60Hz 230V
Note: The data are based on the conditions shown in the table below.
Model
Indoor Units FTXS24HVJU
Outdoor Units
RX24FVJU
Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 22,000 (7,500~22,000) 24,000 (7,500~25,400)
Moisture Removal Pt/h 6.3 — Running Current (Rated) A 11.35 12.43 Power Consumption Rated
(Min.~Max.)
W 2,600 (450~2,600) 2,850 (450~3,320) Power Factor % 99.6 99.7 EER (Rated)
Btu/h·W
8.5 — COP (Rated) W/W 2.47 Energy
Efficiency
SEER/HSPF 13.0 7.7
Piping Connections
Liquid in (mm) 1/4” (6.4 mm) Gas in (mm) 5/8” (15.8 mm)
Drain in (mm) 11/16” (17.5 mm) Heat Insulation Both Liquid and Gas Pipes Max. Interunit Piping Length ft (m) 98.4’ (30 m) Max. Interunit Height Difference ft (m) 65.6’ (20 m) Chargeless ft (m) 33’ 10 m) Amount of Additional Charge of
Refrigerant
oz/ft
(kg/ft)
0.22 oz (0.006 kg)
Indoor Unit FTXS24HVJU
Front Panel Color White
Airflow Rate cfm (m³/min)
H 536 (15.2) 586 (16.6)
M 473 (13.4) 532 (15.1)
L 409 (11.6) 477 (13.5)
Fan
Type Cross Flow Fan
Motor Output W 43
Speed Steps 5 Steps, Quiet, Auto Air Direction Control Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Running Current (Rated) A 0.20 Power Consumption (Rated) W 45 Power Factor % 97.8 Temperature Control Microcomputer Control Dimensions (H×W×D) in (mm) 11-7/16 × 41-5/16× 9-3/8” (291× 1049 × 238 mm) Packaged Dimensions (H×W×D) in (mm) 13-1/4 × 45-3/16 × 14-7/16” (337 × 1148 × 367 mm) Weight Lbs (kg) 26.5 lbs (12 kg) Gross Weight Lbs (kg) 38.0 lbs (17 kg) Operation
Sound
H / M / L dBA 46 / 42 / 37 46 / 42 / 37
Outdoor Unit RX24FVJU
Casing Color Ivory White
Compressor
Type Hermetically Sealed Swing Type
Model 2YC45EXD
Motor Output W 1,900
Refrigerant Oil
Model FVC50K
Charge oz 25.2 oz (0.71 kg)
Refrigerant
Model R-410A
Charge Lbs (kg) 3.75 Lbs (1.7 kg)
Airflow Rate cfm (m³/min)
H 1,752 (49.6) 1,465 (41.5) L 1,529 (43.3) 1,398 (39.6)
Fan
Type Propeller
Motor Output W 53 Running Current (Rated) A 11.15 12.23 Power Consumption (Rated) W 2,555 2,805 Power Factor % 99.7 99.7 Dimensions (H×W×D) in (mm) 28-15/16 × 32-1/2 × 11-13/16” (735 × 826 × 300 mm) Packaged Dimensions (H×W×D) in (mm) 31-7/16 × 37-15/16 × 15-3/8” (799 × 948 × 391 mm) Weight Lbs (kg) 121.0 lbs (55 kg) Gross Weight Lbs (kg) 137.0 lbs (62 kg) Operation
Sound
H / L dBA 54 / — 54 / —
Drawing No. 3D063001A
Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25 ft (7.5 m)
SiUS04-904
Printed Circuit Board Connector Wiring Diagram 11
Part 3
Printed Circuit Board
Connector Wiring Diagram
1. Printed Circuit Board Connector Wiring Diagram..................................... 12
1.1 FTXS09/12HVJU....................................................................................... 12
1.2 FTXS15/18/24HVJU.................................................................................. 14
1.3 RXS09/12DAVJU, RX09/12FAVJU........................................................... 16
1.4 RXS15/18/24DVJU, RX15/18/24FVJU...................................................... 18
SiUS04-904 Printed Circuit Board Connector Wiring Diagram
12 Printed Circuit Board Connector Wiring Diagram
1. Printed Circuit Board Connector Wiring Diagram
1.1 FTXS09/12HVJU
Connectors PCB(1) (Control PCB) (indoor unit)
PCB(2) (Signal Receiver PCB)
PCB(3) (INTELLIGENT EYE sensor PCB)
Note: Other designations
PCB(1) (Control PCB) (indoor unit) PCB(2) (Signal Receiver PCB)
1) S1 Connector for fan motor
2) S6 Connector for swing motor (horizontal blades)
3) S7 Connector for fan motor (Hall IC)
4) S21 Connector for centralized control (HA)
5) S26 Connector for signal receiver PCB
6) S27 Connector for control PCB
7) S32 Connector for heat exchanger thermistor
8) S35 Connector for INTELLIGENT EYE sensor PCB
1) S36 Connector for control PCB
1) V1 Varistor
2) JA Address setting jumper
JB Fan speed setting when compressor is OFF on thermostat
JC Power failure recovery function (auto-restart)
Refer to page 255 for detail.
3) SW7 (S1W) Forced operation ON / OFF switch
4) LED1 LED for operation (green)
5) LED2 LED for timer (yellow)
6) LED3 LED for HOME LEAVE operation (red)
7) FU1 Fuse (3.15A)
8) RTH1 (R1T) Room temperature thermistor
9) LED A LED for service monitor (green)
Printed Circuit Board Connector Wiring Diagram SiUS04-904
Printed Circuit Board Connector Wiring Diagram 13
PCB Detail PCB(1): Control PCB (indoor unit)
PCB(2): Signal Receiver PCB
PCB(3): INTELLIGENT EYE sensor PCB
Control PCB
V1 FU1 S1
SW7
LED1
LED2
LED3
RTH1
S27
S7
S6
S26
S32JCJBJALED A
S35
S21
Signal Receiver PCB
(R4011)
S36
(R3321)
SiUS04-904 Printed Circuit Board Connector Wiring Diagram
14 Printed Circuit Board Connector Wiring Diagram
1.2 FTXS15/18/24HVJU
Connectors PCB(1) (Control PCB) (indoor unit)
PCB(2) (Signal Receiver PCB)
PCB(3) (Buzzer PCB)
PCB(4) (Display PCB)
PCB(5) (INTELLIGENT EYE sensor PCB)
Note: Other designations
PCB(1) (Control PCB) (indoor unit)
PCB(2) (Signal Receiver PCB)
PCB(3) (Buzzer PCB)
PCB(4) (Display PCB)
1) S1 Connector for fan motor
2) S6 Connector for swing motor (horizontal louvers)
3) S8 Connector for swing motor (vertical fins)
4) S21 Connector for centralized control (HA)
5) S26 Connector for buzzer PCB
6) S28 Connector for signal receiver PCB
7) S32 Connector for heat exchanger thermistor
8) S35 Connector for INTELLIGENT EYE sensor PCB
1) S29 Connector for control PCB
1) S27 Connector for control PCB
2) S38 Connector for display PCB
1) S37 Connector for buzzer PCB
1) S36 Connector for control PCB
1) V1 Varistor
2) JA Address setting jumper
JB Fan speed setting when compressor is OFF on thermostat
JC Power failure recovery function
Refer to page 255 for detail.
3) FU1 Fuse (3.15A)
4) LED A LED for service monitor (green)
1) SW1 (S1W) Forced operation ON/OFF switch
1) RTH1 (R1T) Room temperature thermistor
1) LED1 LED for operation (green)
2) LED2 LED for timer (yellow)
3) LED3 LED for HOME LEAVE operation (red)
Printed Circuit Board Connector Wiring Diagram SiUS04-904
Printed Circuit Board Connector Wiring Diagram 15
PCB Detail PCB(1): Control PCB (indoor unit)
PCB(2): Signal Receiver PCB PCB(3): Buzzer PCB
PCB(4): Display PCB PCB(5): INTELLIGENT EYE sensor PCB
S1
V1
FU1
S6
S8
S26
(R2860)
S28S32JCJBJALED A
S21
S35
SW1
S29
(R2861)
(R2862)
RTH1
S38
S27
LED1 LED2 LED3 S37
(R2863)
S36
(R2864)
SiUS04-904 Printed Circuit Board Connector Wiring Diagram
16 Printed Circuit Board Connector Wiring Diagram
1.3 RXS09/12DAVJU, RX09/12FAVJU
Connectors PCB(1)(Filter PCB)
PCB(2)(Control PCB) (outdoor unit)
Note: Other designations
PCB(1)(Filter PCB)
PCB(2)(Control PCB) (outdoor unit)
1) S11 Connector for control PCB
1) S10 Connector for filter PCB
2) S20 Connector for electronic expansion valve coil
3) S30 Connector for compressor motor
4) S40 Connector for overload protector
5) S70 Connector for fan motor
6) S80 Connector for four-way valve coil
7) S90 Connector for thermistors (outdoor air, heat exchanger, discharge pipe)
8) HC3, HC4, HL3, HN3 Connector for filter PCB
1) FU3 Fuse (20A)
2) V2, V3 Varistor
1) FU1, FU2 Fuse (3.15A)
2) LED A Service monitor LED
3) V1 Varistor
Printed Circuit Board Connector Wiring Diagram SiUS04-904
Printed Circuit Board Connector Wiring Diagram 17
PCB Detail PCB(1): Filter PCB
PCB(2): Control PCB (outdoor unit)
FU3(20A)
S11
(R6969)
V3 V2
FU2(3.15A)
S30
HN3
HC3
S70
HC4
(R6970)
S40 LED A S90
HL3FU1(3.15A)V1S80S20
S10
SiUS04-904 Printed Circuit Board Connector Wiring Diagram
18 Printed Circuit Board Connector Wiring Diagram
1.4 RXS15/18/24DVJU, RX15/18/24FVJU
Connectors PCB(1)(Control PCB) (outdoor unit)
PCB(2)(Power Supply PCB)
PCB(3)(Service Monitor PCB)
MID
SPM
Note: Other Designations
PCB(1)(Control PCB) (outdoor unit)
PCB(2)(Power Supply PCB)
PCB(3)(Service Monitor PCB)
MID
1) S10, AC2 Connector for terminal strip
2) S20 Connector for electronic expansion valve coil
3) S31, S32 Connector for SPM
4) S33, S71 Connector for MID
5) S40 Connector for overload protector
6) S51, S101 Connector for service monitor PCB
7) S80 Connector for four-way valve coil
8) S90 Connector for thermistors (outdoor air, heat exchanger, and discharge pipe)
9) S91 Connector for fin thermistor
10) AC1, E Connector for power supply PCB
11) H1, H2 Connector for diode bridge
1) HL Connector for terminal strip
2) HAC1, HE1 Connector for control PCB
3) HE2 Connector for ground
1) S52, S102 Connector for control PCB
1) S34, S72 Connector for control PCB
2) S70 Connector for fan motor
1) CN11, CN14 Connector for control PCB
2) L1, L2 Connector for reactor
1) FU2 Fuse (3.15A)
1) FU1 Fuse (30A)
2) V3 Varistor
1) LED A Service monitor LED
2) SW1 (S1W) Forced operation ON/OFF switch
3) SW4 (S4W) Local setting switch
1) FU201 Fuse (3.15A)
Printed Circuit Board Connector Wiring Diagram SiUS04-904
Printed Circuit Board Connector Wiring Diagram 19
PCB Detail PCB(1): Control PCB (outdoor unit)
PCB(2): Power Supply PCB Service Monitor PCB
E AC1 FU2(3.15A)
H1
H2
S32
S33
S71
S31
S91
S40S20S90S101S51
S80
S10
AC2
HAC1
V3
HE1
HE2
(R2866)
HL
FU1(30A)
S52
S102 SW4
(R5140)
SW1
LED A
SiUS04-904 Printed Circuit Board Connector Wiring Diagram
20 Printed Circuit Board Connector Wiring Diagram
MID
SPM
S34
S72
(R2868)
S70FU201 (3.15A)
(R2869)
CN14
CN11
L1
L2
Printed Circuit Board Connector Wiring Diagram SiUS04-904
Printed Circuit Board Connector Wiring Diagram 21