Daikin RBLQ05CAV3, RBLQ07CAV3, RDLQ05CAV3, RDLQ07CAV3 Installation manuals

Installation manual
ROTEX HPSU low temperature monobloc
RBLQ05CAV3 RBLQ07CAV3  RDLQ05CAV3 RDLQ07CAV3
Installation manual
ROTEX HPSU low temperature monobloc
English

Table of Contents

Table of Contents

1 About the documentation 3

1.1 About this document.................................................................. 3

2 About the box 3

2.1 Outdoor unit............................................................................... 3
2.1.1 To remove the accessories from the outdoor unit....... 3
3 Preparation 4
3.1 Preparing installation site .......................................................... 4
3.1.1 Installation site requirements of the outdoor unit ........ 4
3.2 Preparing water piping .............................................................. 4
3.2.1 To check the water volume and flow rate ................... 4
3.3 Preparing electrical wiring ......................................................... 5
3.3.1 Overview of electrical connections for external and
internal actuators ........................................................ 5
4 Installation 5
4.1 Opening the units ...................................................................... 5
4.1.1 To open the outdoor unit............................................. 5
4.1.2 To open the switch box cover of the outdoor unit ....... 5
4.2 Mounting the outdoor unit.......................................................... 5
4.2.1 To provide the installation structure............................ 5
4.2.2 To install the outdoor unit............................................ 6
4.2.3 To provide drainage.................................................... 7
4.2.4 To prevent the outdoor unit from falling over .............. 7
4.3 Connecting the water piping...................................................... 8
4.3.1 To connect the water piping........................................ 8
4.3.2 To protect the water circuit against freezing ............... 8
4.3.3 To fill the water circuit ................................................. 9
4.3.4 To insulate the water piping........................................ 9
4.4 Connecting the electrical wiring................................................. 9
4.4.1 To connect the electrical wiring on the outdoor unit.... 9
4.4.2 To connect the main power supply ............................. 10
4.4.3 To connect the user interface ..................................... 10
4.4.4 To connect the shut-off valve...................................... 11
4.4.5 To connect the domestic hot water pump................... 11
5 Configuration 11
5.1 Overview: Configuration ............................................................ 11
5.1.1 To access the most used commands ......................... 12
5.2 Basic configuration .................................................................... 12
5.2.1 Quick wizard: Language / time and date..................... 12
5.2.2 Quick wizard: Standard............................................... 13
5.2.3 Quick wizard: Options................................................. 13
5.2.4 Quick wizard: Capacities (energy metering) ............... 14
5.2.5 Space heating/cooling control..................................... 14
5.2.6 Domestic hot water control ......................................... 16
5.2.7 Contact/helpdesk number........................................... 16
5.3 Menu structure: Overview installer settings............................... 17
6 Commissioning 18
6.1 Checklist before commissioning................................................ 18
6.2 Checklist during commissioning ................................................ 18
6.2.1 To perform an air purge .............................................. 18
6.2.2 To perform a test run .................................................. 19
6.2.3 To perform an actuator test run .................................. 19
6.2.4 To perform an underfloor heating screed dryout......... 19
1 About the documentation

1.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the outdoor unit)
Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
Control box installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the control box)
Option box installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the option box)
Backup heater installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the backup heater)
Installer reference guide:
▪ Preparation of the installation, technical specifications, good
practices, reference data,…
▪ Format: Digital files on the ROTEX homepage
Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the outdoor unit) + Digital files on
the ROTEX homepage
Latest revisions of the supplied documentation may be available on the regional ROTEX website or via your dealer.
The original documentation is written in English. All other languages are translations.
2 About the box

2.1 Outdoor unit

2.1.1 To remove the accessories from the outdoor unit

1 Open the outdoor unit.
7 Hand-over to the user 20
7.1 About locking and unlocking...................................................... 20
To activate or deactivate a function lock ................................... 20
To activate or deactivate button lock......................................... 20
8 Technical data 21
8.1 Wiring diagram .......................................................................... 21
8.1.1 Wiring diagram: Outdoor unit...................................... 21
RBLQ+RDLQ05+07CAV3 ROTEX HPSU low temperature monobloc 4P417248-1 – 2015.08
Installation manual
3

3 Preparation

a b c d
fe g
≤1200
>250/400
>250/400
>250
>350
>350
(mm)(mm)
a
b
b
a
INFORMATION
If shut-off valves are installed on the unit, provide a minimum space of 400mm at the air inlet side. If shut‑off valves are NOT installed on the unit, provide a minimum space of 250mm.
If the system contains a domestic hot water tank, meet the following requirements:
2 Remove the accessories.
a General safety precautions b Addendum book for optional equipment c Outdoor unit installation manual d Operation manual e Sealing ring for shut-off valve
f Shut-off valve
g Unit mounting plate
3 Preparation

3.1 Preparing installation site

Maximum allowable distance
between outdoor unit and …
domestic hot water tank 10m 3‑way valve 10m
The outdoor unit is designed for outdoor installation only, and for ambient temperatures ranging 10~43°C in cooling mode, –25~25°C in space heating mode, and –25~35°C in domestic hot water operation mode.
Distance

3.2 Preparing water piping

3.2.1 To check the water volume and flow rate

Minimum water volume
If Then
The system contains a backup heater
The system does NOT contain a backup heater
(a) The internal water volume of the outdoor unit NOT
included.
NOTICE
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup heater operation) in the installation is guaranteed in all conditions.
NOTICE
If glycol was added to the water circuit, and the temperature of the water circuit is low, the flow rate will NOT be displayed on the user interface. In this case, the minimum flow rate can be checked by way of the pump test (check that the user interface does NOT display error 7H).
The minimum water volume is
(a)
10l The minimum water volume is
(a)
20l

3.1.1 Installation site requirements of the outdoor unit

Mind the following spacing guidelines:
a Air outlet b Air inlet
Installation manual
4
NOTICE
When circulation in each or certain space heating loops is controlled by remotely controlled valves, it is important that the minimum flow rate is guaranteed, even if all valves are closed. In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating/operation).
See the installer reference guide for more information.
Minimum required flow rate
05+07 models 12l/min
See the recommended procedure as described in "6.2 Checklist
during commissioning"on page18.
RBLQ+RDLQ05+07CAV3
ROTEX HPSU low temperature monobloc
4P417248-1 – 2015.08

3.3 Preparing electrical wiring

1
2
a

3.3.1 Overview of electrical connections for external and internal actuators

4 Installation

Item Description Wires Maximum
Outdoor unit power supply
1 Power supply for
outdoor unit
2 Normal kWh rate power
supply
User interface
3 User interface 2
Optional equipment
4 Remote outdoor sensor 2
Field-supplied components
5 Domestic hot water
pump
6 Space heating/cooling
operation control (or shut‑off valve)
Interconnection cable
7 Interconnection cable
between outdoor unit and control box
(a) Refer to name plate on outdoor unit. (b) Cable section 0.75mm² till 1.25mm²; maximum length:
500m. Applicable for both single user interface and dual
user interface connection. (c) Minimum cable section 0.75mm². (d) Cable section 0.75mm² till 1.25mm²; maximum length:
20m. (e) If valve kit EKMBHBP1 is part of the system, then the
required cable section is 0.75mm². If valve kit EKMBHBP1
is NOT part of the system, then the minimum required
cable section is 0.75mm².
NOTICE
More technical specifications of the different connections are indicated on the inside of the outdoor unit.
2+GND
2 6.3A
2
2
2
running
current
(a)
(b)
(c)
(c)
(e)
(d)
4 Installation

4.1 Opening the units

4.1.1 To open the outdoor unit

4.1.2 To open the switch box cover of the outdoor unit

4.2 Mounting the outdoor unit

4.2.1 To provide the installation structure

INFORMATION
For information on the available options, contact your dealer.
If the unit is installed directly on the floor, prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply) as follows:
INFORMATION
The maximum height of the upper protruding part of the bolts is 15mm.
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with resin washers (a). If the coating on the fastening area is stripped off, the nuts rust easily.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
RBLQ+RDLQ05+07CAV3 ROTEX HPSU low temperature monobloc 4P417248-1 – 2015.08
Installation manual
5
4 Installation
283
740
<100
(mm)
<100
>300
283
740
<150
<150
(mm)
>300
100
a
>250/400
>300
>250/400
(mm)
a
In any case, provide at least 300mm of free space below the unit. Additionally, make sure the unit is positioned at least 100mm above the maximum expected level of snow.
a Maximum snowfall height
It is possible to install the unit on brackets to the wall:
a Maximum snowfall height
Installation manual
6

4.2.2 To install the outdoor unit

CAUTION
Do NOT remove the protective cardboard before the unit is installed properly.
RBLQ+RDLQ05+07CAV3
ROTEX HPSU low temperature monobloc
4P417248-1 – 2015.08
4 Installation
2
a a
1
b
a
1 Lift the outdoor unit.
2 Install the outdoor unit as follows:
NOTICE
To prevent damage to the supporting feet, do NOT tilt the unit sideways in any way:

4.2.3 To provide drainage

Make sure that condensate can be evacuated properly. When the unit is in cooling mode, condensate may also form in the hydro part. When providing drainage, therefore make sure to cover the entire unit.
NOTICE
If the unit is installed in a cold climate, take adequate measures so that the evacuated condensate cannot freeze.
INFORMATION
For information on the available options, contact your dealer.
a Air outlet
NOTICE
Properly align the unit. Make sure the backside of the unit does NOT protrude.
3 Remove the protective cardboard and instruction sheet.
a Protective cardboard b Instruction sheet
NOTICE
Provide at least 300 mm of free space below the unit. Additionally, make sure the unit is positioned at least 100mm above the expected level of snow.

4.2.4 To prevent the outdoor unit from falling over

1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit. 3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4 Attach the cable’s ends. Tighten those ends.
RBLQ+RDLQ05+07CAV3 ROTEX HPSU low temperature monobloc 4P417248-1 – 2015.08
Installation manual
7
4 Installation
a b

4.3 Connecting the water piping

4.3.1 To connect the water piping

NOTICE
Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit. Make sure that the tightening torque does NOT exceed 30N•m.
To facilitate service and maintenance, 2 shut-off valves are provided. Mount the valves on the water inlet and on the water outlet. Mind their position: the integrated drain valves will only drain the side of the circuit on which they are located. To be able to only drain the unit, make sure the drain valves are positioned between the shut‑off valves and the unit.
Lowest expected outdoor temperature
–5°C 10% 15% –10°C 15% 25% –15°C 20% 35% –20°C 25% — –25°C 30%
NOTICE
▪ The required concentration might differ depending on
the type of glycol. ALWAYS compare the requirements from the table above with the specifications provided by the glycol manufacturer. If necessary, meet the requirements set by the glycol manufacturer.
▪ The added concentration of glycol should NEVER
exceed 35%.
▪ If the liquid in the system is frozen, the pump will NOT
be able to start. Mind that if you only prevent the system from bursting, the liquid inside might still freeze.
▪ In case of a power supply failure or pump failure, and
NO glycol was added to the system, drain the system.
▪ When water is at standstill inside the system, the
system is very likely to freeze and get damaged.
The types of glycol that can be used depend on whether the system contains a domestic hot water tank:
Prevent from bursting
Prevent from freezing
a Water inlet b Water outlet
1 Screw the outdoor unit nuts on the shut-off valves. 2 Connect the field piping on the shut-off valves. 3 In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.
NOTICE
▪ Install a manometer in the system.
▪ Install air purge valves at all local high points.

4.3.2 To protect the water circuit against freezing

Frost can damage the system. To prevent the hydraulic components from freezing, the software is equipped with special frost protection functions, that include the activation of pump, internal heaters, and/ or backup heater operation in case of low temperatures.
However, in case of a power failure, these functions cannot guarantee protection. It is therefore recommended to add glycol to the water circuit. The required concentration depends on the lowest expected outdoor temperature, and on whether you want to protect the system from bursting or from freezing. To prevent the system from freezing, more glycol is required. Add glycol according to the table below.
INFORMATION
▪ Protection against bursting: the glycol will prevent the
piping from bursting, but NOT the liquid inside the piping from freezing.
▪ Protection against freezing: the glycol will prevent the
liquid inside the piping from freezing.
If… Then…
The system contains a domestic hot water tank
The system does NOT contain a domestic hot water tank
(a) Propylene glycol, including the necessary inhibitors,
classified as CategoryIII according to EN1717.
WARNING
Ethylene glycol is toxic.
NOTICE
Glycol absorbs water from its environment. Therefore do NOT add glycol that has been exposed to air. Leaving the cap off the glycol container causes the concentration of water to increase. The glycol concentration is then lower than assumed. As a result, the hydraulic components might freeze up after all. Take preventive actions to ensure a minimal exposure of the glycol to air.
NOTICE
▪ If overpressure occurs, the system will release some of
the liquid through the pressure relief valve. If glycol was added to the system, take adequate measures so as to safely recover it.
▪ In any case, make sure that the flexible hose of the
pressure relief valve is ALWAYS free to release pressure. Prevent water from staying and/or freezing up inside the hose.
Only use propylene glycol
You can use either propylene
(a)
glycol
or ethylene glycol
(a)
Installation manual
8
ROTEX HPSU low temperature monobloc
RBLQ+RDLQ05+07CAV3
4P417248-1 – 2015.08
4 Installation
a
b c
≥25 mm
WARNING
Due to presence of glycol, corrosion of the system is possible. Uninhibited glycol will turn acidic under the influence of oxygen. This process is accelerated by the presence of copper and high temperatures. The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system. Therefore it is important that:
▪ the water treatment is correctly executed by a qualified
water specialist,
▪ a glycol with corrosion inhibitors is selected to
counteract acids formed by the oxidation of glycols,
▪ no automotive glycol is used because their corrosion
inhibitors have a limited lifetime and contain silicates which can foul or plug the system,
▪ galvanized pipes are NOT used in glycol systems since
the presence may lead to the precipitation of certain components in the glycol's corrosion inhibitor.
Adding glycol to the water circuit reduces the maximum allowed water volume of the system. For more information, refer to the chapter "To check the water volume and flow rate" in the installer reference guide.

4.3.3 To fill the water circuit

1 Connect the water supply hose to the drain and fill valve.
9 Disconnect the water supply hose from the drain and fill valve.

4.3.4 To insulate the water piping

The piping in the complete water circuit MUST be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity.
To prevent the freezing of the outdoor water piping during winter time, the thickness of the sealing material MUST be at least 13mm (with λ=0.039W/mK).
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.
During winter, protect the water piping and shut‑off valves against freezing by adding heat tape (field supply). If the outdoor temperature can drop below –20°C and no heat tape is used, it is recommended to install the shut‑off valves indoors.

4.4 Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.

4.4.1 To connect the electrical wiring on the outdoor unit

1 Remove the switch box cover. See "4.1.1To open the outdoor
unit"on page5.
2 Insert the wiring from the back of the unit:
2 Open the drain and fill valve. 3 If an automatic air purge valve was installed, make sure it is
open.
4 Fill the circuit with water until the manometer (field supply)
indicates a pressure of ±2.0bar.
5 Purge as much air as possible from the water circuit. For
instructions, see "6Commissioning"on page18.
6 Refill the circuit until the pressure is ±2.0bar. 7 Repeat steps 5 and 6 until no more air is purged and there are
no more pressure drops.
8 Close the drain and fill valve.
Routing Possible cables (depends on the installed options)
a
Low voltage
RBLQ+RDLQ05+07CAV3 ROTEX HPSU low temperature monobloc 4P417248-1 – 2015.08
▪ User interface
▪ Interconnection cable to control box RKCB07CAV3
▪ Remote outdoor sensor (option)
a Low voltage b High voltage c Main power supply
NOTICE
The distance between the high voltage and low voltage cables should be at least 25mm.
Installation manual
9
4 Installation
a b
1 2 3
X4M
2 31
X5M
A5P A5P
1 2
a b
Routing Possible cables (depends on the installed options)
b
High voltage
c
Main power supply
▪ Normal kWh rate power supply
▪ Preferential kWh rate power supply
▪ Heat pump convector (option)
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Space heat/cool operation control ▪ Main power supply
3 Inside the unit, route the wiring as follows:
a Low voltage wiring b High voltage wiring + main power supply
4 Make sure that the cable does NOT come in contact with sharp
edges.
5 Install the switch box cover.
INFORMATION
When installing field supply or option cables, foresee sufficient cable length. This will make it possible to remove/ reposition the switch box and gain acces to other components during service.

4.4.3 To connect the user interface

INFORMATION
▪ If control box RKCB07CAV3 is NOT part of the system,
connect the user interface directly to the outdoor unit.
▪ If control box RKCB07CAV3 is part of the system, you
can also connect the user interface to the control box. To do this, connect the user interface to control box terminals X2M/20+21, and then connect the control box to the outdoor unit by connecting X2M/20+21 to outdoor unit terminals X5M/1+2.
INFORMATION
For details on how to connect the user interface to the control box, refer to the installer reference guide or the installation manual of the control box.
# Action
1 Connect the user interface cable to the outdoor unit.
CAUTION
Do NOT push or place redundant cable length in the unit.

4.4.2 To connect the main power supply

1 Connect the main power supply.
1 GND 2 L 3 N
a Main user interface
(a)
b Optional user interface
2 Insert a screwdriver into the slots underneath the user
interface and carefully separate the faceplate from the wallplate.
The PCB is mounted in the faceplate of the user interface. Be careful NOT to damage it.
3 Fix the wallplate of the user interface to the wall. 4 Connect as shown in 4A, 4B, 4C or 4D.
Installation manual
10
ROTEX HPSU low temperature monobloc
RBLQ+RDLQ05+07CAV3
4P417248-1 – 2015.08
Loading...
+ 22 hidden pages