1.1About this document ...................................................................................................................................................... 4
2 General safety precautions5
2.1About the documentation .............................................................................................................................................. 5
2.1.1Meaning of warnings and symbols ................................................................................................................5
2.2For the installer............................................................................................................................................................... 6
2.2.2Installation site ............................................................................................................................................... 7
2.2.3Refrigerant — in case of R410A or R32..........................................................................................................7
3.1Instructions for equipment using R32 refrigerant ......................................................................................................... 14
3.1.1Installation space requirements..................................................................................................................... 15
5.2Information requirements for fan coil units................................................................................................................... 24
8.2.3Adjusting the airflow direction....................................................................................................................... 28
8.3To operate the system.................................................................................................................................................... 29
9 Energy saving and optimum operation30
10 Maintenance and service31
10.1 Precautions for maintenance and service ...................................................................................................................... 31
10.2 Cleaning the air filter, suction grille, air outlet and outside panels............................................................................... 32
10.2.1To clean the air filter ...................................................................................................................................... 32
10.2.2To clean the suction grille .............................................................................................................................. 33
10.2.3To clean the air outlet and outside panels .................................................................................................... 34
10.3 Maintenance before a long stop period......................................................................................................................... 35
10.4 Maintenance after a long stop period............................................................................................................................ 35
10.5 About the refrigerant...................................................................................................................................................... 35
10.5.1About the refrigerant leakage sensor ............................................................................................................ 36
11 Troubleshooting38
11.1 Symptoms that are NOT system malfunctions............................................................................................................... 39
11.1.1Symptom: The system does not operate....................................................................................................... 39
11.1.2Symptom: The fan speed does not correspond to the setting...................................................................... 39
11.1.3Symptom: The fan direction does not correspond to the setting................................................................. 39
11.1.4Symptom: White mist comes out of a unit (Indoor unit) .............................................................................. 40
11.1.5Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)........................................................ 40
11.1.6Symptom: The user interface reads "U4" or "U5" and stops, but then restarts after a few minutes.......... 40
11.1.7Symptom: Noise of air conditioners (Indoor unit)......................................................................................... 40
11.1.8Symptom: Noise of air conditioners (Indoor unit, outdoor unit) .................................................................. 40
11.1.9Symptom: Dust comes out of the unit........................................................................................................... 40
11.1.10 Symptom: The units can give off odours ....................................................................................................... 40
Installer and user reference guide
2
12 Relocation41
13 Disposal42
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Table of contents
For the installer43
14 About the box44
14.1 Overview: About the box ................................................................................................................................................ 44
14.2 Indoor unit ...................................................................................................................................................................... 44
14.2.1To unpack and handle the unit ...................................................................................................................... 44
14.2.2To remove the accessories from the indoor unit .......................................................................................... 45
15.1.1Identification label: Indoor unit ..................................................................................................................... 46
15.2 About the indoor unit ..................................................................................................................................................... 46
15.3 System layout .................................................................................................................................................................. 46
15.4 Combining units and options .......................................................................................................................................... 47
15.4.1Possible options for the indoor unit............................................................................................................... 47
16 Unit installation49
16.1 Preparing the installation site......................................................................................................................................... 49
16.1.1Installation site requirements of the indoor unit .......................................................................................... 49
16.2 Mounting the indoor unit ............................................................................................................................................... 51
16.2.1Guidelines when installing the indoor unit.................................................................................................... 51
16.2.2Guidelines when installing the drain piping................................................................................................... 54
17.2.5To flare the pipe end ...................................................................................................................................... 60
17.2.6To connect the refrigerant piping to the indoor unit .................................................................................... 61
18 Electrical installation62
18.1 About connecting the electrical wiring .......................................................................................................................... 62
18.1.1Precautions when connecting the electrical wiring....................................................................................... 62
18.1.2Guidelines when connecting the electrical wiring......................................................................................... 63
18.1.3Specifications of standard wiring components.............................................................................................. 64
18.2 To connect the electrical wiring to the indoor unit ....................................................................................................... 65
19.2 Precautions when commissioning .................................................................................................................................. 67
19.3 Checklist before commissioning ..................................................................................................................................... 68
19.4 To perform a test run...................................................................................................................................................... 68
20 Configuration69
20.1 Field setting ..................................................................................................................................................................... 69
21 Hand-over to the user72
22 Troubleshooting73
22.1 Solving problems based on error codes ......................................................................................................................... 73
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
3
1 | About the documentation
1 About the documentation
1.1 About this document
Target audience
Authorised installers + end users
Documentation set
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light
industry and on farms, or for commercial use by lay persons.
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow
the instructions from Daikin and, in addition, comply with applicable legislation and
are performed by qualified persons only. In Europe and areas where IEC standards
apply, EN/IEC 60335-2-40 is the applicable standard.
This document is part of a documentation set. The complete set consists of:
▪ General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the indoor unit)
▪ Indoor unit installation and operation manual:
- Installation and operation instructions
- Format: Paper (in the box of the indoor unit)
▪ Installer and user reference guide:
- Preparation of the installation, good practices, reference data,…
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your dealer.
The original documentation is written in English. All other languages are
translations.
Technical engineering data
Installer and user reference guide
4
▪ A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
▪ The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
2 General safety precautions
2.1 About the documentation
▪ The original documentation is written in English. All other languages are
translations.
▪ The precautions described in this document cover very important topics, follow
them carefully.
▪ The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised
installer.
2.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
2 | General safety precautions
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or
cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
Installer and user reference guide
5
2 | General safety precautions
Symbols used in the documentation:
SymbolExplanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
For more information, see the installer and user reference
guide.
The unit contains rotating parts. Be careful when servicing or
inspecting the unit.
SymbolExplanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
2.2 For the installer
2.2.1 General
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
▪ Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return
to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in
electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable
legislation (on top of the instructions described in the Daikin documentation).
Installer and user reference guide
6
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially
children, can play with them. Possible risk: suffocation.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
2 | General safety precautions
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
▪ Do NOT place any objects or equipment on top of the unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to
avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a
logbook with the product containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
2.2.2 Installation site
Also, at least, following information MUST be provided at an accessible place at the
product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
▪ Provide sufficient space around the unit for servicing and air circulation.
▪ Make sure the installation site withstands the weight and vibration of the unit.
▪ Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
▪ In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
2.2.3 Refrigerant — in case of R410A or R32
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
▪ In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
If applicable. See the installation manual or installer reference guide of your
application for more information.
Installer and user reference guide
7
2 | General safety precautions
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
▪ Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Selfcombustion and explosion of the compressor because of air going into the
operating compressor.
▪ Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen
to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
▪ When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
Installer and user reference guide
8
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after
performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of
oxygen going into the operating compressor.
▪ In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
2 | General safety precautions
▪ The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the
system.
▪ Charge the liquid refrigerant as follows:
IfThen
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid
filling siphon attached")
A siphon tube is NOT presentCharge with the cylinder upside down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
2.2.4 Electrical
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before
servicing. The voltage MUST be less than 50VDC before you can touch electrical
components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
categoryIII condition, MUST be installed in the fixed wiring.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
9
2 | General safety precautions
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable legislation.
▪ All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
▪ NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
▪ Make sure to install the required fuses or circuit breakers.
▪ Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
▪ When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
CAUTION
▪ When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
▪ When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
▪ The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened
before the earth wire is in case the power supply is pulled loose from the stress
relief.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness, do as shown in the figure
above.
▪ For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Installer and user reference guide
10
Install power cables at least 1 m away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 m may not be
sufficient.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
2 | General safety precautions
WARNING
▪ After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes on and off while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
11
3 | Specific installer safety instructions
3 Specific installer safety instructions
Always observe the following safety instructions and regulations.
General
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow
the instructions from Daikin and, in addition, comply with applicable legislation and
are performed by qualified persons only. In Europe and areas where IEC standards
apply, EN/IEC 60335-2-40 is the applicable standard.
Installation site (see
"16.1Preparing the installation site"[449]
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.
Refrigerant piping installation (see
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
"17Piping installation"[457]
)
)
Installer and user reference guide
12
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
3 | Specific installer safety instructions
Electrical installation (see
WARNING
▪ If the power supply has a missing or wrong N-phase, equipment might break
down.
▪ Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
▪ Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
▪ All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
"18Electrical installation"[462]
)
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact
point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
CAUTION
▪ Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See
technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
▪ The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
Commisioning (see
WARNING
If the panels on the indoor units are not installed yet, make sure to power OFF the
system after finishing the test run. To do so, turn OFF operation via the user
interface. Do NOT stop operation by turning OFF the circuit breakers.
"19Commissioning"[467]
)
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
13
3 | Specific installer safety instructions
3.1 Instructions for equipment using R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
▪ Do NOT pierce or burn.
▪ Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
▪ Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a wellventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater) and have a room
size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation (for example national gas regulation) and
are executed only by authorised persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
▪ there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the
minimum floor area A (m²).
▪ no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching device);
▪ only auxiliary devices approved by the manufacturer are used in the duct work;
▪ air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
NOTICE
▪ Precautions shall be taken to avoid excessive vibration or pulsation to
refrigeration piping.
▪ Protection devices, piping and fittings shall be protected as far as possible against
adverse environmental effects.
▪ Provision shall be made for expansion and contraction of long runs of piping.
▪ Piping in refrigerating systems shall be designed and installed such as to minimise
the likelihood of hydraulic shock damaging the system.
▪ The indoor equipment and pipes shall be securely mounted and guarded such
that accidental rupture of equipment or pipes cannot occur from events such as
moving furniture or reconstruction activities.
Installer and user reference guide
14
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant
leaks.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
NOTICE
▪ Do NOT re-use joints and copper gaskets which have been used already.
▪ Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
3.1.1 Installation space requirements
CAUTION
The total refrigerant charge in the system cannot exceed the requirements for
minimum floor area of the smallest room that is served. For minimum floor area
requirements for indoor units, see the installation and operation manual of the
outdoor unit.
WARNING
This appliance contains R32 refrigerant. For the minimum floor area of the room in
which the appliance is stored refer to installation and operation manual of the
outdoor unit.
NOTICE
▪ Pipework shall be protected from physical damage.
▪ Installation of pipework shall be kept to a minimum.
3 | Specific installer safety instructions
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
15
For the user
For the user
Installer and user reference guide
16
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
4 User safety instructions
Always observe the following safety instructions and regulations.
4.1 General
WARNING
If you are NOT sure how to operate the unit, contact your
installer.
WARNING
Children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of
experience and knowledge can only use this appliance if
they have been given supervision or instruction concerning
the use of the appliance by a person responsible for their
safety.
4 | User safety instructions
Children MUST NOT play with the appliance.
Cleaning and user maintenance MUST NOT be carried out
by children without supervision.
WARNING
To prevent electrical shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet hands.
▪ Do NOT place any objects containing water on the unit.
CAUTION
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
17
4 | User safety instructions
▪ Units are marked with the following symbol:
▪ Batteries are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with
unsorted household waste. Do NOT try to dismantle the system yourself: the
dismantling of the system, treatment of the refrigerant, of oil and of other parts
must be done by an authorized installer and must comply with applicable
legislation.
Units must be treated at a specialized treatment facility for reuse, recycling and
recovery. By ensuring this product is disposed of correctly, you will help to
prevent potential negative consequences for the environment and human
health. For more information, contact your installer or local authority.
This means that the batteries may NOT be mixed with unsorted household
waste. If a chemical symbol is printed beneath the symbol, this chemical symbol
means that the battery contains a heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility for reuse. By
ensuring waste batteries are disposed of correctly, you will help to prevent
potential negative consequences for the environment and human health.
4.2 Instructions for safe operation
WARNING
▪ Do NOT modify, disassemble, remove, reinstall or repair
the unit yourself as incorrect dismantling or installation
may cause an electric shock or fire. Contact your dealer.
▪ In case of accidental refrigerant leaks, make sure there
are no naked flames. The refrigerant itself is entirely
safe, non-toxic and mildly flammable, but it will
generate toxic gas when it accidentally leaks into a room
where combustible air from fan heaters, gas cookers,
etc. is present. Always have qualified service personnel
confirm that the point of leakage has been repaired or
corrected before resuming operation.
CAUTION
This unit is equipped with electrically powered safety
measures, such as a refrigerant leak detector. In order to
be effective, the unit must be electrically powered at all
times after installation, except for short service periods.
Installer and user reference guide
18
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
4 | User safety instructions
CAUTION
▪ NEVER touch the internal parts of the controller.
▪ Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may
happen. For checking and adjusting the internal parts,
contact your dealer.
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been
carried out correctly by an installer.
CAUTION
It is unhealthy to expose your body to the air flow for a
long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently
if equipment with burner is used together with the system.
CAUTION
Do NOT operate the system when using a room
fumigation-type insecticide. Chemicals could collect in the
unit, and endanger the health of people who are
hypersensitive to chemicals.
CAUTION
NEVER expose little children, plants or animals directly to
the airflow.
WARNING
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Do NOT place objects below the indoor and/or outdoor
unit that may get wet. Otherwise condensation on the unit
or refrigerant pipes, air filter dirt or drain blockage may
cause dripping, and objects under the unit may get dirty or
damaged.
Installer and user reference guide
19
4 | User safety instructions
WARNING
Do NOT place a flammable spray bottle near the air
conditioner and do NOT use sprays near the unit. Doing so
may result in a fire.
Maintenance and service (see
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any
maintenance task.
CAUTION
Do NOT insert fingers, rods or other objects into the air
inlet or outlet. When the fan is rotating at high speed, it
will cause injury.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere
ratings or other wires when a fuse blows out. Use of wire
or copper wire may cause the unit to break down or cause
a fire.
"10Maintenance and service"[431]
)
CAUTION
After a long use, check the unit stand and fitting for
damage. If damaged, the unit may fall and result in injury.
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop
operation and turn all power supplies off. Otherwise, an
electric shock and injury may result.
WARNING
Be careful with ladders when working in high places.
CAUTION
Turn off the unit before cleaning the air filter, suction
grille, air outlet and outside panels.
CAUTION
Installer and user reference guide
20
Before accessing terminal devices, make sure to interrupt
all power supply.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
4 | User safety instructions
WARNING
Do NOT let the indoor unit get wet. Possible consequence:
Electric shock or fire.
About the refrigerant (see
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but
normally does NOT leak. If the refrigerant leaks in the
room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.
"10.5About the refrigerant"[435]
)
Turn off any combustible heating devices, ventilate the
room, and contact the dealer where you purchased the
unit.
Do NOT use the unit until a service person confirms that
the part from which the refrigerant leaked has been
repaired.
WARNING
It is necessary to replace the sensor after every detection
or at the end of the lifetime. Authorized person only MUST
replace the sensor.
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
21
4 | User safety instructions
Troubleshooting (see
WARNING
Stop operation and shut off the power if anything
unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may
cause breakage, electric shock or fire. Contact your dealer.
"11Troubleshooting"[438]
)
Installer and user reference guide
22
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
5 About the system
a
b
d
e
h
f
g
c
WARNING
▪ Do NOT modify, disassemble, remove, reinstall or repair the unit yourself as
incorrect dismantling or installation may cause an electric shock or fire. Contact
your dealer.
▪ In case of accidental refrigerant leaks, make sure there are no naked flames. The
refrigerant itself is entirely safe, non-toxic and mildly flammable, but it will
generate toxic gas when it accidentally leaks into a room where combustible air
from fan heaters, gas cookers, etc. is present. Always have qualified service
personnel confirm that the point of leakage has been repaired or corrected
before resuming operation.
NOTICE
Do NOT use the system for other purposes. In order to avoid any quality
deterioration, do NOT use the unit for cooling precision instruments, food, plants,
animals, or works of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future system extensions) is available
in technical engineering data and should be consulted. Contact your installer to
receive more information and professional advice.
5 | About the system
5.1 System layout
CAUTION
This unit is equipped with electrically powered safety measures, such as a refrigerant
leak detector. In order to be effective, the unit must be electrically powered at all
times after installation, except for short service periods.
INFORMATION
The following illustration is an example and might NOT match your system layout.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
23
5 | About the system
5.2 Information requirements for fan coil units
a Indoor unit
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + transmission cable
g Drain pipe
h Suction grille and air filter
ItemSymbolValueUnit
Cooling capacity (sensible)P
Cooling capacity (latent)P
Heating capacityP
Total electric power inputP
Sound power level (per speed setting, if
L
WA
rated,c
rated,c
rated,h
elec
AkW
BkW
CkW
DkW
EdB
applicable)
Contact details:
DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o. U Nové Hospody 1/1155, 301 00 Plzeň
Skvrňany, Czech Republic
ABCDE
FXZA151.20.51.90.03649
FXZA201.50.72.50.03649
FXZA251.90.93.20.03650
FXZA322.51.140.03851
FXZA403.11.450.05354
FXZA503.81.86.30.08660
Installer and user reference guide
24
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
6 User interface
CAUTION
▪ NEVER touch the internal parts of the controller.
▪ Do NOT remove the front panel. Some parts inside are dangerous to touch and
NOTICE
Do NOT wipe the controller operation panel with benzine, thinner, chemical dust
cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily
dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the
panel clean. Wipe it with another dry cloth.
NOTICE
NEVER press the button of the user interface with a hard, pointed object. The user
interface may be damaged.
6 | User interface
appliance problems may happen. For checking and adjusting the internal parts,
contact your dealer.
NOTICE
NEVER pull or twist the electric wire of the user interface. It may cause the unit to
malfunction.
This operation manual offers a non-exhaustive overview of the main functions of
the system.
For more information about the user interface, see the operation manual of the
installed user interface.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
25
7 | Before operation
7 Before operation
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by
an installer.
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner
is used together with the system.
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide.
Chemicals could collect in the unit, and endanger the health of people who are
hypersensitive to chemicals.
NOTICE
Be sure to turn ON the power 6 hours before operation in order to have power
running to the crankcase heater and to protect the compressor.
This operation manual is for the following systems with standard control. Before
initiating operation, contact your dealer for the operation that corresponds to your
system type and mark. If your installation has a customised control system, ask
your dealer for the operation that corresponds to your system.
Installer and user reference guide
26
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
8 Operation
8.1 Operation range
INFORMATION
For the operation limits see the technical data of the connected outdoor unit.
8.2 About operation modes
INFORMATION
Depending on the installed system, some operation modes will not be available.
▪ The air flow rate may adjust itself depending on the room temperature or the fan
may stop immediately. This is not a malfunction.
8 | Operation
▪ If the main power supply is turned off during operation, operation will restart
automatically after the power turns back on again.
▪ Setpoint. Target temperature for the Cooling, Heating, and Auto operation
modes.
▪ Setback. A function that keeps the room temperature in a specific range when
the system is turned off (by the user, the schedule function, or the OFF timer).
8.2.1 Basic operation modes
The indoor unit can operate in various operation modes.
IconOperation mode
Cooling. In this mode, cooling will be activated as required by the
setpoint, or by Setback operation.
Heating. In this mode, heating will be activated as required by
the setpoint, or by Setback operation.
Fan only. In this mode, air circulates without heating or cooling.
Dry. In this mode, the air humidity will be lowered with a
minimal temperature decrease.
The temperature and fan speed are controlled automatically and
cannot be controlled by the controller.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Dry operation will not function if the room temperature is too
low.
Auto. In Auto mode, the indoor unit automatically switches
between heating and cooling mode, as required by the setpoint.
Installer and user reference guide
27
8 | Operation
8.2.2 Special heating operation modes
OperationDescription
DefrostTo prevent a loss of heating capacity
due to frost accumulation in the
outdoor unit, the system will
automatically switch to defrost
operation.
During defrost operation, the indoor
unit fan will stop operation, and the
following icon will appear on the home
screen:
The system will resume normal
operation after approximately 6 to 8
minutes.
Hot startDuring hot start, the indoor unit fan will
stop operation, and the following icon
will appear on the home screen:
8.2.3 Adjusting the airflow direction
The following airflow directions can be set:
Fixed position. The indoor unit blows
air in 1 of 4 fixed positions.
Swing. The indoor unit alternates
between the 4 positions.
Auto. The indoor unit adjusts its airflow
direction according to movement
sensed by a movement sensor.
INFORMATION
Depending on system layout and organisation, Auto airflow direction may not be
available.
DirectionScreen
Installer and user reference guide
28
INFORMATION
For setting procedure of the airflow direction, see the reference guide or the manual
of the used user interface.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
8 | Operation
Automatic airflow control
In the following operating conditions, the airflow direction of the indoor units is
controlled automatically:
▪ When the room temperature is higher than the controller's setpoint for heating
operation (including auto operation).
▪ When the indoor units run in heating operation mode, and the Defrost function
is active.
▪ When the indoor units run in Continuous operation, and the airflow direction is
Horizontal.
WARNING
Never touch the air outlet or the horizontal blades while the swing flap is in
operation. Fingers may become caught or the unit may break down.
NOTICE
Avoid operating in the horizontal direction. It may cause dew or dust to settle on the
ceiling or flap.
8.3 To operate the system
INFORMATION
For setting of the operation mode, airflow direction or other settings, see the
reference guide or operation manual of the user interface.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
29
9 | Energy saving and optimum operation
9 Energy saving and optimum operation
CAUTION
NEVER expose little children, plants or animals directly to the airflow.
WARNING
Do NOT place objects below the indoor and/or outdoor unit that may get wet.
Otherwise condensation on the unit or refrigerant pipes, air filter dirt or drain
blockage may cause dripping, and objects under the unit may get dirty or damaged.
WARNING
Do NOT place a flammable spray bottle near the air conditioner and do NOT use
sprays near the unit. Doing so may result in a fire.
Observe the following precautions to ensure the system operates properly.
▪ Prevent direct sunlight from entering a room during cooling operation by using
curtains or blinds.
▪ Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪ Ventilate often. Extended use requires special attention to ventilation.
▪ Keep doors and windows closed. If the doors and windows remain open, air will
flow out of your room causing a decrease in the cooling or heating effect.
▪ Be careful NOT to cool or heat too much. To save energy, keep the temperature
setting at a moderate level.
▪ NEVER place objects near the air inlet or the air outlet of the unit. Doing so may
cause a reduced heating/cooling effect or stop operation.
▪ When the display shows (time to clean the air filter), clean the filters (see
"10.2.1To clean the air filter"[432]).
▪ Condensation may form if the humidity is above 80% or if the drain outlet gets
blocked.
▪ Adjust the air outlet properly and avoid direct air flow to room inhabitants.
Installer and user reference guide
30
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
10 Maintenance and service
10.1 Precautions for maintenance and service
NOTICE
Maintenance MUST be done by an authorized installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any maintenance task.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. When the fan
is rotating at high speed, it will cause injury.
10 | Maintenance and service
NOTICE
NEVER inspect or service the unit by yourself. Ask a qualified service person to
perform this work. However, as end user, you may clean the air filter, suction grille,
air outlet and outside panels.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a
fuse blows out. Use of wire or copper wire may cause the unit to break down or
cause a fire.
CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit
may fall and result in injury.
NOTICE
Do NOT wipe the controller operation panel with benzine, thinner, chemical dust
cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily
dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the
panel clean. Wipe it with another dry cloth.
CAUTION
Before accessing terminal devices, make sure to interrupt all power supply.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop operation and turn all power
supplies off. Otherwise, an electric shock and injury may result.
WARNING
Be careful with ladders when working in high places.
Installer and user reference guide
31
10 | Maintenance and service
1
Following symbols may occur on the indoor unit:
SymbolExplanation
10.2 Cleaning the air filter, suction grille, air outlet and outside panels
10.2.1 To clean the air filter
When to clean the air filter:
▪ Rule of thumb: Clean every 6 months. If the air in the room is extremely
contaminated, increase the cleaning frequency.
Measure the voltage at the terminals of main circuit capacitors or
electrical components before servicing.
CAUTION
Turn off the unit before cleaning the air filter, suction grille, air outlet and outside
panels.
▪ Depending on the settings, the user interface can display the "Time to clean
filter" notification. Clean the air filter when the notification is displayed.
▪ If the dirt becomes impossible to clean, change the air filter (= optional
equipment).
How to clean the air filter:
NOTICE
Do NOT use water of 50°C or higher. Possible consequence: Discoloration and
deformation.
1Open the suction grille.
BYFQ60BBYFQ60C
2Remove the air filter.
Installer and user reference guide
32
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
10 | Maintenance and service
1
3
3
2
3
3
1
2
1
BYFQ60BBYFQ60C
3Clean the air filter. Use a vacuum cleaner or wash with water. If the air filter is
very dirty, use a soft brush and neutral detergent.
4Dry the air filter in the shadow.
5Reattach the air filter and close the suction grille.
6Turn ON the power.
7To remove warning screens, see the reference guide of the user interface.
10.2.2 To clean the suction grille
1Open the suction grille.
NOTICE
Do NOT use water of 50°C or higher. Possible consequence: Discoloration and
deformation.
BYFQ60BBYFQ60C
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
2Remove the suction grille.
Installer and user reference guide
33
10 | Maintenance and service
45°
1
90°
1
3
3
2
3
3
1
2
BYFQ60B
BYFQ60C
3Remove the air filter.
BYFQ60B
4Clean the suction grille. Wash with a soft bristle brush and water or neutral
detergent. If the suction grille is very dirty, use a typical kitchen cleaner, leave
it on for 10min, then wash it with water.
5Reattach the air filter (step 3 in reverse order).
6Reattach the suction grille and close it (step 2 and 1 in reverse order).
10.2.3 To clean the air outlet and outside panels
BYFQ60C
Installer and user reference guide
34
WARNING
Do NOT let the indoor unit get wet. Possible consequence: Electric shock or fire.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
NOTICE
▪ Do NOT use gasoline, benzene, thinner polishing powder or liquid insecticide.
Possible consequence: Discoloration and deformation.
▪ Do NOT use water or air of 50°C or higher. Possible consequence: Discoloration
and deformation.
▪ Do NOT scrub firmly when washing the blade with water. Possible consequence:
The surface sealing peels off.
Clean with a soft cloth. If it is difficult to remove stains, use water or neutral
detergent.
10.3 Maintenance before a long stop period
E.g., at the end of the season.
▪ Let the indoor units run in fan only operation for about half a day in order to dry
the interior of the units.
▪ Clean air filters and casings of indoor units (see "10.2.1 To clean the air
filter"[432] and "10.2.3To clean the air outlet and outside panels"[434]).
10 | Maintenance and service
▪ Remove the batteries from the user interface (if applicable).
10.4 Maintenance after a long stop period
E.g., at the beginning of the season.
▪ Check and remove everything that might be blocking inlet and outlet vents of
indoor units and outdoor units.
▪ Clean air filters and casings of indoor units (see "10.2.1 To clean the air
filter"[432] and "10.2.3To clean the air outlet and outside panels"[434]).
▪ Insert batteries in the user interface (if applicable).
10.5 About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent gases into the
atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent tonnes: GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Please contact your installer for more information.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Installer and user reference guide
35
10 | Maintenance and service
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
▪ Be aware that the refrigerant inside the system is odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the
refrigerant leaks in the room and comes in contact with fire from a burner, a heater,
or a cooker, this may result in fire, or the formation of a harmful gas.
Turn off any combustible heating devices, ventilate the room, and contact the dealer
where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.
10.5.1 About the refrigerant leakage sensor
WARNING
It is necessary to replace the sensor after every detection or at the end of the
lifetime. Authorized person only MUST replace the sensor.
NOTICE
Functionality of the safety measures are periodically automatically checked. In case
of malfunction, error code will display on the user interface.
NOTICE
The R32 refrigerant leakage sensor is a semiconductor detector which may
incorrectly detect substances other than R32 refrigerant. Avoid using chemical
substances (e.g. organic solvents, hair spray, paint) in high concentrations, in the
close proximity of the indoor unit because this may cause misdetection of the R32
refrigerant leakage sensor.
INFORMATION
Lifetime of the sensor is 10years. The user interface displays error "CH-05" 6months
before the end of the sensor lifetime and error "CH-02" after the end of the sensor
lifetime. For more information refer to the reference guide of the user interface and
contact you dealer.
Installer and user reference guide
36
In case of detection when the unit is standby
When the detection occurs when the unit is standby, "false detection check" will
occur.
False detection check
1Unit starts fan operation on the lowest setting.
2User interface displays error code "A0-13", emits alarm sound and status
indicator is blinking.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
10 | Maintenance and service
3Sensor checks if refrigerant leakage or misdetection occurred.
▪ If refrigerant leakage is NOT detected, Result: system returns to normal
operation after approximately 2 minutes.
▪ If refrigerant leakage is detected, Result:
1User interface displays error "A0-11", emits alarm sound and status indicator
is blinking.
2Contact your dealer immediately. For more information, see the installation
manual of the outdoor unit.
In case of detection when the unit is turned on
1User interface displays error "A0-11", emits alarm sound and status indicator
is blinking.
2Contact your dealer immediately. For more information, see the installation
manual of the outdoor unit.
INFORMATION
To stop alarm of the user interface see the reference guide of the user interface.
INFORMATION
The minimum airflow during normal operation or during the refrigerant leakage
detection is always >240m3/h.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
37
11 | Troubleshooting
11 Troubleshooting
If one of the following malfunctions occur, take the measures shown below and
contact your dealer.
WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells
etc.).
Leaving the unit running under such circumstances may cause breakage, electric
shock or fire. Contact your dealer.
The system MUST be repaired by a qualified service person.
MalfunctionMeasure
If a safety device such as a fuse, a circuit breaker
or a residual current device frequently actuates
Turn OFF all main power supply
switches to the unit.
or the ON/OFF switch does NOT function
properly.
If water leaks from the unit.Stop operation.
The operation switch does NOT function
Turn OFF the power supply.
properly.
If the user interface displays .Notify your installer and report
the error code. To display an
error code see the reference
guide of the user interface.
If the system does NOT operate properly except for the above mentioned cases
and none of the above mentioned malfunctions is evident, investigate the system
in accordance with the following procedures.
MalfunctionMeasure
If the system does not
operate at all.
▪ Check if there is no power failure. Wait until
power is restored. If power failure occurs during
operation, the system automatically restarts
immediately after power is restored.
▪ Check if no fuse has blown or breaker is activated.
Change the fuse or reset the breaker if necessary.
Installer and user reference guide
38
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
11 | Troubleshooting
MalfunctionMeasure
The system operates but
cooling or heating is
insufficient.
▪ Check if air inlet or outlet of outdoor or indoor
unit is not blocked by obstacles. Remove any
obstacles and make sure the air can flow freely.
▪ Check if the air filter is not clogged (see "10.2.1To
clean the air filter"[432]).
▪ Check the temperature setting.
▪ Check the fan speed setting on your user
interface.
▪ Check for open doors or windows. Close doors and
windows to prevent wind from coming in.
▪ Check if there are too many occupants in the room
during cooling operation. Check if the heat source
of the room is excessive.
▪ Check if direct sunlight enters the room. Use
curtains or blinds.
▪ Check if the air flow angle is proper.
If after checking all above items, it is impossible to fix the problem yourself, contact
your installer and state the symptoms, the complete model name of the unit (with
manufacturing number if possible) and the installation date (possibly listed on the
warranty card).
11.1 Symptoms that are NOT system malfunctions
The following symptoms are NOT system malfunctions:
11.1.1 Symptom: The system does not operate
▪ The air conditioner does not start immediately after the ON/OFF button on the
user interface is pressed. If the operation lamp lights, the system is in normal
condition. To prevent overloading of the compressor motor, the air conditioner
starts 5 minutes after it is turned ON again in case it was turned OFF just before.
The same starting delay occurs after the operation mode selector button was
used.
▪ The system does not start immediately after the power supply is turned on. Wait
one minute until the micro computer is prepared for operation.
11.1.2 Symptom: The fan speed does not correspond to the setting
The fan speed does not change even if the fan speed adjustment button in
pressed. During heating operation, when the room temperature reaches the set
temperature, the outdoor unit goes off and the indoor unit changes to whisper fan
speed. This is to prevent cold air blowing directly on occupants of the room. The
fan speed will not change if the button is pressed.
11.1.3 Symptom: The fan direction does not correspond to the setting
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
The fan direction does not correspond with the user interface display. The fan
direction does not swing. This is because the unit is being controlled by the micro
computer.
Installer and user reference guide
39
11 | Troubleshooting
11.1.4 Symptom: White mist comes out of a unit (Indoor unit)
11.1.5 Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)
11.1.6 Symptom: The user interface reads "U4" or "U5" and stops, but then restarts after a few
minutes
▪ When humidity is high during cooling operation. If the interior of an indoor unit is
extremely contaminated, the temperature distribution inside a room becomes
uneven. It is necessary to clean the interior of the indoor unit. Ask your dealer for
details on cleaning the unit. This operation requires a qualified service person.
▪ Immediately after the cooling operation stops and if the room temperature and
humidity are low. This is because warm refrigerant gas flows back into the indoor
unit and generates steam.
When the system is changed over to heating operation after defrost operation.
Moisture generated by defrost becomes steam and is exhausted.
This is because the user interface is intercepting noise from electric appliances
other than the air conditioner. The noise prevents communication between the
units, causing them to stop. Operation automatically restarts when the noise
ceases.
11.1.7 Symptom: Noise of air conditioners (Indoor unit)
▪ A "zeen" sound is heard immediately after the power supply is turned on. The
electronic expansion valve inside an indoor unit starts working and makes the
noise. Its volume will reduce in about one minute.
▪ A continuous low "shah" sound is heard when the system is in cooling operation
or at a stop. When the drain pump is in operation, this noise is heard.
▪ A "pishi-pishi" squeaking sound is heard when the system stops after heating
operation. Expansion and contraction of plastic parts caused by temperature
change make this noise.
11.1.8 Symptom: Noise of air conditioners (Indoor unit, outdoor unit)
▪ A continuous low hissing sound is heard when the system is in cooling or defrost
operation. This is the sound of refrigerant gas flowing through both indoor and
outdoor units.
▪ A hissing sound which is heard at the start or immediately after stopping
operation or defrost operation. This is the noise of refrigerant caused by flow
stop or flow change.
11.1.9 Symptom: Dust comes out of the unit
When the unit is used for the first time in a long time. This is because dust has
gotten into the unit.
11.1.10 Symptom: The units can give off odours
The unit can absorb the smell of rooms, furniture, cigarettes, etc., and then emit it
again.
Installer and user reference guide
40
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
12 Relocation
Contact your dealer for removing and reinstalling the total unit. Moving units
requires technical expertise.
12 | Relocation
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
41
13 | Disposal
13 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
Installer and user reference guide
42
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
For the installer
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
For the installer
Installer and user reference guide
43
14 | About the box
12
14 About the box
14.1 Overview: About the box
This chapter describes what you have to do after the box with the indoor unit is
delivered on-site.
It contains information about:
▪ Unpacking and handling the unit
▪ Removing the accessories from the unit
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
▪ Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
▪ Prepare the path along which you want to bring the unit inside in advance.
14.2 Indoor unit
14.2.1 To unpack and handle the unit
Use a sling of soft material or protective plates together with a rope when lifting
the unit. This to avoid damage or scratches to the unit.
1Lift the unit by holding on to the hanger brackets without exerting any
pressure on other parts, especially on refrigerant piping, drain piping and
other resin parts.
Installer and user reference guide
44
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
14.2.2 To remove the accessories from the indoor unit
7×
1×1×
4×
1×
1×
1×
1×
dcb
f
e
g
jk
a
4×8×
ih
B
A
B
B
B
A
A
a Paper pattern for installation (upper part of packing)
b General safety precautions
c Indoor unit installation and operation manual
d Tie wraps
e Sealing pads: Large (drain pipe), medium 1 (gas pipe), medium 2 (liquid pipe), small (electrical wiring)
f Metal clamp
g Drain hose
h Washers for hanger bracket
i Screws
j Insulation piece: Small (liquid pipe)
k Insulation piece: Large (gas pipe)
14 | About the box
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
15.1.1Identification label: Indoor unit ............................................................................................................................. 46
15.2 About the indoor unit ............................................................................................................................................................. 46
15.3 System layout.......................................................................................................................................................................... 46
15.4 Combining units and options.................................................................................................................................................. 47
15.4.1Possible options for the indoor unit ...................................................................................................................... 47
15.1 Identification
15.1.1 Identification label: Indoor unit
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch
the service panels between different models.
Location
15.2 About the indoor unit
INFORMATION
For the operation limits see the technical data of the connected outdoor unit.
15.3 System layout
Installer and user reference guide
46
INFORMATION
The following illustration is an example and might NOT match your system layout.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
a
b
d
e
h
f
g
c
a Indoor unit
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + transmission cable
g Drain pipe
h Suction grille and air filter
15 | About the units and options
15.4 Combining units and options
INFORMATION
Certain options might not be available in your country.
15.4.1 Possible options for the indoor unit
Make sure you have the following mandatory options:
▪ User interface: Only a safety system compatible remote controller can be used.
See technical data sheet for remote controller compatibility (e.g. BRC1H52/82*)
Note: The user interface will generate a visible and audible warning sign in case of
refrigerant leakage detection. E.g. the BRC1H52* remote controllers can generate
an alarm of 65dB (sound pressure, measured at 1m distance of the alarm). Sound
data is available in the technical data sheet of the remote controller. The alarm
should always be 15dB louder than the background noise of the room. In case of
higher background noise we recommend to use an external alarm (field supply) to
connect to the optional output PCB of the indoor unit. This field supply alarm has
to be mounted in every room where an indoor unit is installed.
CAUTION
▪ Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See
technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
▪ The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
47
15 | About the units and options
▪ Optional output PCB (to provide output for external device): The PCB will trigger
in case of leak detection, sensor fails or when sensor is disconnected. For exact
model name see option list of the indoor unit. For more information about this
option, refer to the installation manual of the optional output PCB.
▪ Decoration panel: Standard
INFORMATION
All possible options are mentioned in the option list of the indoor unit. For more
information about an option, refer to the installation and operation manual of the
option.
Installer and user reference guide
48
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
16 Unit installation
In this chapter
16.1 Preparing the installation site ................................................................................................................................................ 49
16.1.1Installation site requirements of the indoor unit.................................................................................................. 49
16.2 Mounting the indoor unit ....................................................................................................................................................... 51
16.2.1Guidelines when installing the indoor unit............................................................................................................ 51
16.2.2Guidelines when installing the drain piping .......................................................................................................... 54
16.1 Preparing the installation site
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
Choose an installation location with sufficient space for carrying the unit in and out
of the site.
Avoid installation in an environment with a lot of organic solvents such as ink and
siloxane.
16 | Unit installation
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
16.1.1 Installation site requirements of the indoor unit
INFORMATION
Also read the general installation site requirements. See the ""2 General safety
precautions"[45]" chapter.
INFORMATION
The sound pressure level is less than 70dBA.
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Do NOT install the unit in the following places:
▪ In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present
Installer and user reference guide
49
16 | Unit installation
abc
(mm)
≥1500
≥
2000
≥
4000
≥1500
A
B
C
badac
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for power
and transmission lines.
▪ Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
▪ Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
▪ Air flow. Make sure nothing blocks the air flow.
▪ Drainage. Make sure condensation water can be evacuated properly.
▪ Paper pattern for installation (upper part of packing) (accessory). When
selecting the installation location, use the paper pattern. It contains the
dimensions of the unit and the required ceiling opening.
▪ Air flow directions. You can select different air flow directions. Choose the one
best suited for the room. For more information, see the installation manual of
the optional blocking pad kit.
Example:
a 4-way air flow (all air outlets open)
b 3-way air flow (1 air outlet closed) (optional blocking pad kit required)
c 2-way air flow (2 air outlets closed) (optional blocking pad kit required)
▪ Ceiling insulation. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional
insulation is required (minimum 10mm thickness, polyethylene foam).
▪ Spacing. Mind the following requirements:
Installer and user reference guide
50
A Minimum distance to the wall
≥1500mm: Air outlet open
≥200mm: Air outlet closed
B Minimum and maximum distance to the floor (see below)
C ≥295mm: In case of installation with BYFQ60B
≥308mm: In case of installation with BYFQ60C
a Indoor unit
b Lighting (the figure shows ceiling-mounted lighting, but recessed lighting is also allowed)
c Air fan
d Static volume (example: table)
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
16 | Unit installation
450
450
a
(mm)
(300)
▪ B: Minimum and maximum distance to the floor:
- Minimum: 2.7m to avoid accidental touching.
- Maximum: Depends on the air flow directions and the capacity class. Also make
sure the "Ceiling height" field setting corresponds with the actual situation. See
"20.1Field setting"[469].
▪ Install inspection opening on the control box side to make maintenance easier.
a Inspection opening
INFORMATION
Some options may require additional service space. Refer to the installation manual
of the used option before installation.
Minimum floor area requirements
CAUTION
The total refrigerant charge in the system cannot exceed the requirements for
minimum floor area of the smallest room that is served. For minimum floor area
requirements for indoor units, see the installation and operation manual of the
outdoor unit.
16.2 Mounting the indoor unit
16.2.1 Guidelines when installing the indoor unit
INFORMATION
Optional equipment. When installing optional equipment, also read the installation
manual of the optional equipment. Depending on the field conditions, it might be
easier to install the optional equipment first.
▪ Decoration panel. Install the decoration panel always after installing the unit.
NOTICE
After installing the decoration panel:
▪ Make sure there is no gap between the unit body and the decoration panel.
Possible consequence: Air might leak and cause dew drop.
▪ Make sure no oil remains on the plastic parts of the decoration panel. Possible
consequence: Degradation and damage of plastic parts.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
▪ Ceiling strength. Check whether the ceiling is strong enough to support the
weight of the unit. If there is a risk, reinforce the ceiling before installing the unit.
- For existing ceilings, use anchors.
- For new ceilings, use sunken inserts, sunken anchors or other field supplied
parts.
Installer and user reference guide
51
16 | Unit installation
A
c
b
d
e
a
(mm)
a1
b
b
a2
c
4×
533
533
acbd
A 50~100 mm
a Ceiling slab
b Anchor
c Long nut or turnbuckle
d Suspension bolt
e Suspended ceiling
▪ Suspension bolts. Use M8~M10 suspension bolts for installation. Attach the
hanger bracket to the suspension bolt. Fix it securely using a nut and washer
from the upper and lower sides of the hanger bracket.
▪ Paper pattern for installation (upper part of the packing). Use the paper pattern
to determine the correct horizontal positioning. It contains the necessary
dimensions and centers. You can attach the paper pattern to the unit.
a Centre of the unit
b Centre of the ceiling opening
c Paper pattern for installation (upper part of the packing)
d Screws (accessories)
▪ Ceiling opening and unit:
- Make sure the ceiling opening is within the following limits:
Minimum: 585mm to be able to fit the unit.
Maximum: 660mm in case of installation with BYFQ60B and 595mm in case of
installation with BYFQ60C ensure enough overlapping between the decoration
panel and the suspended ceiling. If the ceiling opening is larger, add extra
ceiling material.
Installer and user reference guide
52
- Make sure the unit and its hanger brackets (suspension) are centered within
the ceiling opening.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
(mm)
c
d
A
B
A
B
533
350
575
c
d
533
575
b
a
A 585~660mm: In case of installation with BYFQ60B
A
C
B
c
bba
585~595 mm: In case of installation with BYFQ60C
B 700mm: In case of installation with BYFQ60B
620 mm: In case of installation with BYFQ60C
a Drain piping
b Refrigerant piping
c Hanger bracket pitch (suspension)
d Unit
ExampleIf A
16 | Unit installation
(a)
BYFQ60B
Then
(a)
B
(a)
C
585mm5mm57.5mm
660mm42.5mm20mm
BYFQ60C
585mm5mm17.5mm
595mm10mm12.5mm
(a)
A: Ceiling opening
B: Distance between the unit and the ceiling opening
C: Overlap between the decoration panel and the suspended ceiling
▪ Level. Make sure the unit is level at all 4 corners using a level or a water-filled
vinyl tube.
a Level
b Vinyl tube
c Water level
NOTICE
Do NOT install the unit tilted. Possible consequence: If the unit is tilted against the
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
direction of the condensate flow (the drain piping side is raised), the float switch
might malfunction and cause water to drip.
Installer and user reference guide
53
16 | Unit installation
1~1.5 m
a
≤675
≤300
0~75
1000~1500
(mm)
ba
bc
a
dd
≥100
≤675
(mm)
a
16.2.2 Guidelines when installing the drain piping
General guidelines
Make sure condensation water can be evacuated properly. This involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
▪ Pipe length. Keep drain piping as short as possible.
▪ Pipe size. Keep the pipe size equal to or greater than that of the connecting pipe
(vinyl pipe of 25mm nominal diameter and 32mm outer diameter).
▪ Slope. Make sure the drain piping slopes down (at least 1/100) to prevent air
from being trapped in the piping. Use hanging bars as shown.
a Hanging bar
O Allowed
X Not allowed
▪ Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
▪ Rising piping. If necessary to make the slope possible, you can install rising
piping.
- Drain hose inclination: 0~75mm to avoid stress on the piping and to avoid air
bubbles.
a Metal clamp (accessory)
b Drain hose (accessory)
c Rising drain piping (vinyl pipe of 25mm nominal diameter and 32mm outer diameter) (field supply)
d Hanging bars (field supply)
▪ Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with a correct gauge for the operating capacity of the units.
Installer and user reference guide
54
a T-joint
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
To connect the drain piping to the indoor unit
≤4 mm
A
A'
A-A'
A
A'
e
542
c
b
d
b
a
d
c
a
3
1
2~51
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
1Push the drain hose as far as possible over the drain pipe connection.
2Tighten the metal clamp until the screw head is less than 4 mm from the
metal clamp part.
3Check for water leaks (see "To check for water leaks"[455]).
4Wind the large sealing pad (= insulation) around the metal clamp and drain
hose, and fix it with tie wraps.
5Connect the drain piping to the drain hose.
16 | Unit installation
a Drain pipe connection (attached to the unit)
b Drain hose (accessory)
c Metal clamp (accessory)
d Large sealing pad (accessory)
e Drain piping (field supply)
To check for water leaks
The procedure differs depending on whether installation of the system is already
completed. When installation of the system is not yet completed, temporarily
connect the user interface and power supply to the unit.
When installation of the system is not yet completed
1Temporarily connect electrical wiring.
▪ Remove the service cover (a).
▪ Connect the power supply (d).
▪ Connect the user interface (f).
▪ Reattach the service cover (a).
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
55
16 | Unit installation
L
N
1×
b
cd
a
b
1×
P1P2 F1F2 T1T2
e
d
c
≥100 mm
a
b
a Service cover with wiring diagram
b Opening for cables
c User interface terminal block
d Power supply terminal block
2Turn ON the power.
3Start fan only operation (see the reference guide or the service manual of the
user interface).
4Gradually pour approximately 1 l of water through the air discharge outlet,
and check for leaks.
a Plastic watering can
b Service drain outlet (with rubber plug). Use this outlet to drain water from the drain pan.
c Drain pump location
d Drain pipe connection
e Drain pipe
5Turn OFF the power.
6Disconnect the electrical wiring.
▪ Remove the service cover.
▪ Disconnect the power supply.
▪ Disconnect the user interface.
▪ Reattach the service cover.
When installation of the system is already completed
1Start cooling operation (see the reference guide or the service manual of the
user interface).
2Gradually pour approximately 1l of water through the water inlet, and check
for leaks (see "When installation of the system is not yet completed"[455]).
17.2 Connecting the refrigerant piping .......................................................................................................................................... 58
17.2.1About connecting the refrigerant piping............................................................................................................... 58
17.2.2Precautions when connecting the refrigerant piping............................................................................................ 59
17.2.3Guidelines when connecting the refrigerant piping.............................................................................................. 59
17.2.5To flare the pipe end.............................................................................................................................................. 60
17.2.6To connect the refrigerant piping to the indoor unit............................................................................................ 61
17.1 Preparing refrigerant piping
17.1.1 Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[45].
17 | Piping installation
▪ Foreign materials inside pipes (including oils for fabrication) must be
≤30mg/10m.
Refrigerant piping diameter
For piping connections of the indoor unit use the following piping diameters:
15~32Ø6.4Ø9.5
40+50Ø6.4Ø12.7
Refrigerant piping material
CAUTION
Piping MUST be installed according to instructions given in "17 Piping
installation" [4 57]. Only mechanical joints (e.g. braze+flare connections) that are
compliant with the latest version of ISO14903 can be used.
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.
ClassPipe outer diameter (mm)
Liquid pipeGas pipe
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Depending on the applicable legislation and the maximum working pressure of the unit
(see "PS High" on the unit name plate), larger piping thickness might be required.
17.1.2 Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
If the temperature is higher than 30°C and the humidity is higher than RH80%, the
thickness of the insulation materials should be at least 20 mm to prevent
condensation on the surface of the insulation.
17.2 Connecting the refrigerant piping
17.2.1 About connecting the refrigerant piping
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the indoor unit
▪ Connecting the refrigerant piping to the outdoor unit
▪ Insulating the refrigerant piping
▪ Keeping in mind the guidelines for:
- Pipe bending
- Flaring pipe ends
- Using the stop valves
Installer and user reference guide
58
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
17.2.2 Precautions when connecting the refrigerant piping
INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF BURNING/SCALDING
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
NOTICE
Take the following precautions on refrigerant piping into account:
▪ Avoid anything but the designated refrigerant to get mixed into the refrigerant
cycle (e.g. air).
▪ Only use R32 when adding refrigerant.
▪ Only use installation tools (e.g. manifold gauge set) that are exclusively used for
R32 installations to withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
▪ Install the piping so that the flare is NOT subjected to mechanical stress.
▪ Protect the piping as described in the following table to prevent dirt, liquid or
dust from entering the piping.
▪ Use caution when passing copper tubes through walls (see figure below).
17 | Piping installation
17.2.3 Guidelines when connecting the refrigerant piping
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
UnitInstallation periodProtection method
Outdoor unit>1monthPinch the pipe
<1monthPinch or tape the pipe
Indoor unitRegardless of the period
INFORMATION
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When
you need to charge additional refrigerant it is recommended to open the refrigerant
stop valve after charging.
Take the following guidelines into account when connecting pipes:
Installer and user reference guide
59
17 | Piping installation
a
b
c
d
R=
0.4~0.8
±2
45°
90°
±2
ØA
ab
A
▪ Coat the flare inner surface with ether oil or ester oil when connecting a flare
nut. Tighten 3 or 4 turns by hand, before tightening firmly.
▪ ALWAYS use 2 wrenches together when loosening a flare nut.
▪ ALWAYS use a spanner and torque wrench together to tighten the flare nut when
connecting the piping. This to prevent nut cracking and leaks.
a Torque wrench
b Spanner
c Piping union
d Flare nut
Piping size (mm)Tightening torque
(N•m)
Flare dimensions
(A) (mm)
Flare shape (mm)
Ø6.415~178.7~9.1
Ø9.533~3912.8~13.2
Ø12.750~6016.2~16.6
17.2.4 Pipe bending guidelines
Use a pipe bender for bending. All pipe bends should be as gentle as possible
(bending radius should be 30~40 mm or larger).
17.2.5 To flare the pipe end
1Cut the pipe end with a pipe cutter.
2Remove burrs with the cut surface facing down so that the chips do NOT enter
the pipe.
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
Installer and user reference guide
60
a Cut exactly at right angles.
b Remove burrs.
3Remove the flare nut from the stop valve and put the flare nut on the pipe.
4Flare the pipe. Set exactly at the position as shown in the following figure.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
17 | Piping installation
ab
c
BA
adcefbb
adcefbb
2
4
3
g
1
23
4
g
1
AB
Flare tool for R32
(clutch type)
A0~0.5mm1.0~1.5mm1.5~2.0mm
5Check that the flaring is properly made.
a Flare’s inner surface MUST be flawless.
b The pipe end MUST be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
17.2.6 To connect the refrigerant piping to the indoor unit
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
▪ Pipe length. Keep refrigerant piping as short as possible.
▪ Flare connections. Connect refrigerant piping to the unit using flare connections.
▪ Insulation. Insulate the refrigerant piping on the indoor unit as follows:
A Gas piping
B Liquid piping
a Insulation material (field supply)
b Tie wrap (accessory)
c Insulation pieces: Large (gas pipe), small (liquid pipe) (accessories)
d Flare nut (attached to the unit)
e Refrigerant pipe connection (attached to the unit)
f Unit
g Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe) (accessories)
1 Turn up the seams of the insulation pieces.
2 Attach to the base of the unit.
3 Tighten the tie wrap on the insulation pieces.
4 Wrap the sealing pad from the base of the unit to the top of the flare nut.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause
condensation.
Installer and user reference guide
61
18 | Electrical installation
18 Electrical installation
In this chapter
18.1 About connecting the electrical wiring
18.1 About connecting the electrical wiring .................................................................................................................................. 62
18.1.1Precautions when connecting the electrical wiring .............................................................................................. 62
18.1.2Guidelines when connecting the electrical wiring ................................................................................................ 63
18.1.3Specifications of standard wiring components ..................................................................................................... 64
18.2 To connect the electrical wiring to the indoor unit ............................................................................................................... 65
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1Making sure the power supply system complies with the electrical
specifications of the units.
2Connecting the electrical wiring to the outdoor unit.
3Connecting the electrical wiring to the indoor unit.
4Connecting the main power supply.
18.1.1 Precautions when connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[45].
INFORMATION
Also read "18.1.3Specifications of standard wiring components"[464].
WARNING
▪ All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
Installer and user reference guide
62
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
18 | Electrical installation
ba
c b
c
aa
A
AA´
A´
WARNING
▪ If the power supply has a missing or wrong N-phase, equipment might break
down.
▪ Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
▪ Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact
point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
18.1.2 Guidelines when connecting the electrical wiring
Keep the following in mind:
▪ If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the
covered part and fasten the terminal with the appropriate tool.
a Stranded conductor wire
b Round crimp-style terminal
▪ Use the following methods for installing wires:
Wire typeInstallation method
Single-core wire
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
a Curled single-core wire
b Screw
c Flat washer
Installer and user reference guide
63
18 | Electrical installation
c bbac
a
B
B
Wire typeInstallation method
Stranded conductor wire
with round crimp-style
terminal
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
WiringScrew sizeTightening torque
(N•m)
Power supply cableM41.08~1.32
Transmission cable
(indoor↔outdoor)
User interface cable
▪ The earth wire between the wire retainer and the terminal must be longer than
the other wires.
18.1.3 Specifications of standard wiring components
ComponentClass
Power supply
cable
(a)
MCA
Voltage220~240V
Phase1~
Frequency50/60Hz
Wire sizes1.5mm2 (3‑core wire)
M3.50.79~0.97
15~2532~4050
0.3A0.4A0.6A
H07RN-F (60245 IEC 66)
Installer and user reference guide
64
Transmission wiring0.75 to 1.25mm2 (2‑core wire)
User interface cable
H05RN-F (60245 IEC 57)
User interface - maximum 500m
Recommended field fuse6A
Residual current deviceMust comply with applicable legislation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of
indoor unit for exact values).
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
18 | Electrical installation
a
b
18.2 To connect the electrical wiring to the indoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
▪ For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
▪ Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
It is important to keep the power supply and the transmission wiring separated
from each other. In order to avoid any electrical interference the distance between
both wirings should ALWAYS be at least 50mm.
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run parallel.
1Remove the service cover.
2User interface cable: Route the cable through the frame, connect the cable to
the terminal block (symbols P1, P2) and fix the cable with a tie wrap.
3Transmission cable: Route the cable through the frame, connect the cable to
the terminal block (make sure the symbols F1, F2 match with the symbols on
the outdoor unit), and fix the cable with a tie wrap.
4Power supply cable: Route the cable through the frame and connect the
cable to the terminal block (L, N, earth).
a Circuit breaker
b Residual current device
5Divide the small sealing (accessory) and wrap it around the cables to prevent
water from entering the unit.
6Seal all gaps with a sealing material (field supply) to prevent small animals
from entering the system.
7Reattach the service cover.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
65
18 | Electrical installation
1×
L
N
1×
a
b
b
10~15
70~90
10~20
10~15
70~90
7
d
d
e
c
P1P2 F1 F2
LNLNLN
IN/D OUT/D
F
1 F2 F1 F2
Control box
P1P
2
P1P
2
P1P
2
P1P
2
P1P
2
F1F2T1T
2
P1P2F1F2T1T
2
P1P2F1F2T1T
2
P1P2F1F2T1T
2
N L
a
d
c
b
LN
N LN LN L
a Service cover (with wiring diagram)
b Opening for cables
c Connection of power supply
d Tie wrap
e Connection of user interface and transmission cable
Complete system example
1 user interface controls 1 indoor unit.
a Outdoor unit
b Indoor unit
c User interface
d Most downstream indoor unit
NOTICE
Group control connection is NOT allowed.
CAUTION
▪ Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See
technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
▪ The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
19.2 Precautions when commissioning.......................................................................................................................................... 67
19.3 Checklist before commissioning............................................................................................................................................. 68
19.4 To perform a test run ............................................................................................................................................................. 68
19.1 Overview: Commissioning
This chapter describes what you have to do and know to commission the system
after it is installed.
Typical workflow
Commissioning typically consists of the following stages:
1Checking the "Checklist before commissioning".
2Performing a test run for the system.
19 | Commissioning
19.2 Precautions when commissioning
INFORMATION
During the first running period of the unit, the required power may be higher than
stated on the nameplate of the unit. This phenomenon is caused by the compressor,
that needs a continuous run time of 50hours before reaching smooth operation and
stable power consumption.
NOTICE
Before starting up the system, the unit MUST be energised for at least 6hours to
avoid compressor breakdown during startup.
NOTICE
ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT,
burning of the compressor might be the result.
NOTICE
ALWAYS complete the refrigerant piping of the unit before operating. If NOT, the
compressor will break.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
NOTICE
Cooling operation mode. Perform the test run in cooling operation mode so that
stop valves failing to open can be detected. Even if the user interface was set to
heating operation mode, the unit will run in cooling operation mode during 2‑3
minutes (although the user interface will display the heating icon), and then
automatically switch to heating operation mode.
Installer and user reference guide
67
19 | Commissioning
19.3 Checklist before commissioning
WARNING
If the panels on the indoor units are not installed yet, make sure to power OFF the
system after finishing the test run. To do so, turn OFF operation via the user
interface. Do NOT stop operation by turning OFF the circuit breakers.
After the installation of the unit, first check the items listed below. Once all checks
are fulfilled, the unit must be closed. Power-up the unit after it is closed.
You read the complete installation and operation instructions, as described in the installerand user reference guide.
The indoor unit is properly mounted.
The outdoor unit is properly mounted.
Make sure drain piping is properly installed, insulated and drainage flows smoothly. Check
for water leaks.
Possible consequence: Condensate water might drip.
The refrigerant pipes (gas and liquid) are installed correctly and thermally insulated.
There are NO refrigerant leaks.
There are NO missing phases or reversed phases.
The system is properly earthed and the earth terminals are tightened.
The fuses or locally installed protection devices are installed according to this document,
and have NOT been bypassed.
The power supply voltage matches the voltage on the identification label of the unit.
There are NO loose connections or damaged electrical components in the switchbox.
There are NO damaged components or squeezed pipes on the inside of the indoor and
outdoor units.
The stop valves (gas and liquid) on the outdoor unit are fully open.
19.4 To perform a test run
INFORMATION
▪ Perform the test run according to the instructions in the outdoor unit manual.
▪ The test run is only completed if there is no malfunction code displayed on the
▪ See the service manual for the complete list of error codes and a detailed
user interface or the outdoor unit 7‑segment display.
troubleshooting guideline for each error.
Installer and user reference guide
68
NOTICE
Do NOT interrupt the test run.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
20 Configuration
20.1 Field setting
Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
▪ Ceiling height
▪ Airflow direction range
▪ Air volume when thermostat control is OFF
▪ Time to clean air filter
▪ Thermostat sensor selection
▪ Thermostat differential changeover (if remote sensor is used)
▪ Differential automatic changeover
▪ Auto-restart after power failure
20 | Configuration
INFORMATION
▪ The connection of optional accessories to the indoor unit might cause changes to
some field settings. For more information, see the installation manual of the
optional accessory.
▪ Following setting are only applicable when using the BRC1H52* user interface.
When using any other user interface, see the installation manual or service
manual of the user interface.
Setting: Ceiling height
This setting must correspond with the actual distance to the floor, capacity class
and air flow directions.
▪ For 3-way and 2-way airflows (which require an optional blocking pad kit), see
the installation manual of the optional blocking pad kit.
▪ For 4-way airflow, use the table below.
If the distance to the floor is (m)Then
(1)
MSW—
≤2.713 (23)001
2.7<x≤3.002
3.0<x≤3.503
Setting: Airflow direction range
This setting must correspond with the needs of the user.
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
•: Default
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
69
20 | Configuration
If you want set the airflow direction range to…Then
(1)
MSW—
Upper13 (23)401
Medium02
Lower03
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It determines the fan
speed of the indoor unit during thermostat OFF condition.
1If you have set the fan to operate, set the air volume speed:
If you want…Then
(1)
MSW—
During thermostat
OFF at cooling
operation
During thermostat
OFF at heating
operation
(a)
Only use in combination with optional remote sensor or when setting M 10 (20), SW 2, —
3 is used.
(2)
LL
Setup volume
(a)
OFF
Monitoring 1
Monitoring 2
(2)
LL
Setup volume
(a)
OFF
Monitoring 1
Monitoring 2
12 (22)601
(2)
02
03
(2)
(2)
04
05
12 (22)301
(2)
02
03
(2)
(2)
04
05
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room. It determines
the interval at which "Time to clean filter" notification is displayed on the user
interface.
If you want an interval of…
(air contamination)
MSW—
Then
(1)
±2500h (light)10 (20)001
±1250h (heavy)02
Notification ON301
Notification OFF02
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
•: Default
(2)
Fan speed:
• LL: Low fan speed (set during thermostat OFF)
• L: Low fan speed (set by the user interface)
• Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
• Monitoring 1, 2: The fan is OFF, but runs for a short time every 6minutes to detect the room temperature by LL (Monitoring 1) or by L
(Monitoring 2).
Installer and user reference guide
70
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
20 | Configuration
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller thermostat sensor
is used.
When the remote controller thermostat sensor
is…
MSW—
Used in combination with indoor unit thermistor10 (20)201
Not used (indoor unit thermistor only)02
Used exclusively03
Setting: Thermostat differential changeover (if remote sensor is used)
If the system contains a remote sensor, set the increase/decrease increments.
If you want to change increments to…Then
MSW—
1°C12 (22)201
0.5°C02
Setting: Differential for automatic changeover
Then
(1)
(1)
Set temperature difference between cooling setpoint and heating setpoint in
automatic mode (availability depends on the system type). Differential is cooling
setpoint minus heating setpoint.
If you want to set…Then
(1)
Example
MSW—
0°C12 (22)401cooling 24°C/heating 24°C
1°C02cooling 24°C/heating 23°C
2°C03cooling 24°C/heating 22°C
3°C04cooling 24°C/heating 21°C
4°C05cooling 24°C/heating 20°C
5°C06cooling 24°C/heating 19°C
6°C07cooling 24°C/heating 18°C
7°C08cooling 24°C/heating 17°C
Setting: Auto-restart after power failure
Depending on the needs of the user, you may disable/enable the automatic restart
after a power failure.
If you want auto-restart after power failure…Then
(1)
MSW—
(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
•: Default
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Disabled12 (22)501
Enabled02
Installer and user reference guide
71
21 | Hand-over to the user
21 Hand-over to the user
Once the test run is finished and the unit operates properly, please make sure the
following is clear for the user:
▪ Make sure that the user has the printed documentation and ask him/her to keep
▪ Explain the user how to properly operate the system and what to do in case of
▪ Show the user what to do for the maintenance of the unit.
it for future reference. Inform the user that he can find the complete
documentation at the URL mentioned earlier in this manual.
problems.
Installer and user reference guide
72
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
22 Troubleshooting
22.1 Solving problems based on error codes
If the unit runs into a problem, the user interface displays an error code. It is
important to understand the problem and to take measures before resetting an
error code. This should be done by a licensed installer or by your local dealer.
This chapter gives you an overview of most possible error codes and their
descriptions as they appear on the user interface.
INFORMATION
See the service manual for:
▪ The complete list of error codes
▪ A more detailed troubleshooting guideline for each error
22.1.1 Error codes: Overview
22 | Troubleshooting
In case other error codes appear, contact your dealer.
CodeDescription
The R32 sensor has detected a refrigerant leak
/Safety system error (leak detection)
R32 sensor malfunction
R32 sensor end of lifetime
6 months before the R32 sensor end of lifetime
Malfunction of indoor unit PCB
Drain level control system abnormality
Malfunction of freezing protection
High pressure control in heating, freeze-up protection control in cooling
Malfunction of fan motor
Malfunction of swing flap motor
Malfunction of power supply or AC input overcurrent
Malfunction of electronic expansion valve
Malfunction of a humidifier system
Malfunction of dust collector of air cleaner
Malfunction of capacity setting (Indoor unit PCB)
Failure of transmission (between indoor unit PCB and sub PCB)
Malfunction of liquid pipe thermistor for heat exchanger
Malfunction of gas pipe thermistor for heat exchanger
Malfunction of gas pipe thermistor for heat exchanger
Malfunction of suction air thermistor
Malfunction of discharge air thermistor
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
73
22 | Troubleshooting
CodeDescription
Room temperature thermistor in remote controller abnormality
Installer and user reference guide
74
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
23 Disposal
23 | Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
75
24 | Technical data
,
A
INDOOR
OUTDOOR
24 Technical data
24.1 Wiring diagram
24.1.1 Unified wiring diagram legend
▪ A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
▪ The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
For applied parts and numbering, refer to the wiring diagram on the unit. Part
numbering is by Arabic numbers in ascending order for each part and is
represented in the overview below by "*" in the part code.
SymbolMeaningSymbolMeaning
Circuit breakerProtective earth
ConnectionProtective earth (screw)
Connector
Rectifier
EarthRelay connector
Field wiringShort-circuit connector
FuseTerminal
Indoor unitTerminal strip
Outdoor unitWire clamp
Residual current
device
SymbolColourSymbolColour
BLKBlackORGOrange
BLUBluePNKPink
BRNBrownPRP, PPLPurple
GRNGreenREDRed
GRYGreyWHTWhite
Installer and user reference guide
76
YLWYellow
SymbolMeaning
A*PPrinted circuit board
BS*Pushbutton ON/OFF, operation switch
BZ, H*OBuzzer
C*Capacitor
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
SymbolMeaning
24 | Technical data
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*,
Connection, connector
MR*_A, MR*_B, S*, U, V, W, X*A,
K*R_*, NE
D*, V*DDiode
DB*Diode bridge
DS*DIP switch
E*HHeater
FU*, F*U, (for characteristics, refer to
Fuse
PCB inside your unit)
FG*Connector (frame ground)
H*Harness
H*P, LED*, V*LPilot lamp, light emitting diode
HAPLight emitting diode (service monitor
green)
HIGH VOLTAGEHigh voltage
IESIntelligent eye sensor
IPM*Intelligent power module
K*R, KCR, KFR, KHuR, K*MMagnetic relay
LLive
L*Coil
L*RReactor
M*Stepper motor
M*CCompressor motor
M*FFan motor
M*PDrain pump motor
M*SSwing motor
MR*, MRCW*, MRM*, MRN*Magnetic relay
NNeutral
n=*, N=*Number of passes through ferrite core
PAMPulse-amplitude modulation
PCB*Printed circuit board
PM*Power module
PSSwitching power supply
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
PTC*PTC thermistor
Q*Insulated gate bipolar transistor (IGBT )
Q*CCircuit breaker
Q*DI, KLMEarth leak circuit breaker
Q*LOverload protector
Installer and user reference guide
77
24 | Technical data
SymbolMeaning
Q*MThermo switch
Q*RResidual current device
R*Resistor
R*TThermistor
RCReceiver
S*CLimit switch
S*LFloat switch
S*NGRefrigerant leak detector
S*NPHPressure sensor (high)
S*NPLPressure sensor (low)
S*PH, HPS*Pressure switch (high)
S*PLPressure switch (low)
S*TThermostat
S*RHHumidity sensor
S*W, SW*Operation switch
SA*, F1SSurge arrester
SR*, WLUSignal receiver
SS*Selector switch
SHEET METALTerminal strip fixed plate
T*RTransformer
TC, TRCTransmitter
V*, R*VVaristor
V*RDiode bridge, Insulated-gate bipolar
transistor (IGBT) power module
WRCWireless remote controller
X*Terminal
X*MTerminal strip (block)
Y*EElectronic expansion valve coil
Y*R, Y*SReversing solenoid valve coil
Z*CFerrite core
Installer and user reference guide
78
ZF, Z*FNoise filter
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
25 Glossary
Dealer
Authorised installer
User
Applicable legislation
Service company
Installation manual
25 | Glossary
Sales distributor for the product.
Technical skilled person who is qualified to install the product.
Person who is owner of the product and/or operates the product.
All international, European, national and local directives, laws, regulations
and/or codes that are relevant and applicable for a certain product or
domain.
Qualified company which can perform or coordinate the required service to
the product.
Instruction manual specified for a certain product or application, explaining
how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining
how to operate it.
Accessories
Labels, manuals, information sheets and equipment that are delivered with
the product and that need to be installed according to the instructions in
the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the
product according to the instructions in the accompanying documentation.
Field supply
Equipment NOT made by Daikin that can be combined with the product
according to the instructions in the accompanying documentation.
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1B – 2020.10
Installer and user reference guide
79
Verantwortung für Energie und Umwelt
Copyright 2020 Daikin
4P599623-1B 2020.10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.