Daikin FXZA15A2VEB, FXZA20A2VEB, FXZA25A2VEB, FXZA32A2VEB, FXZA40A2VEB Installer reference guide

...
Installer and user reference guide
VRV system air conditioner
FXZA15A2VEB FXZA20A2VEB FXZA25A2VEB FXZA32A2VEB FXZA40A2VEB FXZA50A2VEB

Table of contents

Table of contents
1 About the documentation 4
1.1 About this document ...................................................................................................................................................... 4
2 General safety precautions 5
2.1 About the documentation .............................................................................................................................................. 5
2.1.1 Meaning of warnings and symbols ................................................................................................................ 5
2.2 For the installer............................................................................................................................................................... 6
2.2.1 General ........................................................................................................................................................... 6
2.2.2 Installation site ............................................................................................................................................... 7
2.2.3 Refrigerant — in case of R410A or R32.......................................................................................................... 7
2.2.4 Electrical ......................................................................................................................................................... 9
3 Specific installer safety instructions 12
3.1 Instructions for equipment using R32 refrigerant ......................................................................................................... 14
3.1.1 Installation space requirements..................................................................................................................... 15
For the user 16
4 User safety instructions 17
4.1 General............................................................................................................................................................................ 17
4.2 Instructions for safe operation ....................................................................................................................................... 18
5 About the system 23
5.1 System layout.................................................................................................................................................................. 23
5.2 Information requirements for fan coil units................................................................................................................... 24
6 User interface 25
7 Before operation 26
8 Operation 27
8.1 Operation range.............................................................................................................................................................. 27
8.2 About operation modes.................................................................................................................................................. 27
8.2.1 Basic operation modes ................................................................................................................................... 27
8.2.2 Special heating operation modes................................................................................................................... 28
8.2.3 Adjusting the airflow direction....................................................................................................................... 28
8.3 To operate the system.................................................................................................................................................... 29
9 Energy saving and optimum operation 30
10 Maintenance and service 31
10.1 Precautions for maintenance and service ...................................................................................................................... 31
10.2 Cleaning the air filter, suction grille, air outlet and outside panels............................................................................... 32
10.2.1 To clean the air filter ...................................................................................................................................... 32
10.2.2 To clean the suction grille .............................................................................................................................. 33
10.2.3 To clean the air outlet and outside panels .................................................................................................... 34
10.3 Maintenance before a long stop period......................................................................................................................... 35
10.4 Maintenance after a long stop period............................................................................................................................ 35
10.5 About the refrigerant...................................................................................................................................................... 35
10.5.1 About the refrigerant leakage sensor ............................................................................................................ 36
11 Troubleshooting 38
11.1 Symptoms that are NOT system malfunctions............................................................................................................... 39
11.1.1 Symptom: The system does not operate....................................................................................................... 39
11.1.2 Symptom: The fan speed does not correspond to the setting...................................................................... 39
11.1.3 Symptom: The fan direction does not correspond to the setting................................................................. 39
11.1.4 Symptom: White mist comes out of a unit (Indoor unit) .............................................................................. 40
11.1.5 Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)........................................................ 40
11.1.6 Symptom: The user interface reads "U4" or "U5" and stops, but then restarts after a few minutes.......... 40
11.1.7 Symptom: Noise of air conditioners (Indoor unit)......................................................................................... 40
11.1.8 Symptom: Noise of air conditioners (Indoor unit, outdoor unit) .................................................................. 40
11.1.9 Symptom: Dust comes out of the unit........................................................................................................... 40
11.1.10 Symptom: The units can give off odours ....................................................................................................... 40
Installer and user reference guide
2
12 Relocation 41
13 Disposal 42
FXZA15~50A2VEB
VRV system air conditioner
Table of contents
For the installer 43
14 About the box 44
14.1 Overview: About the box ................................................................................................................................................ 44
14.2 Indoor unit ...................................................................................................................................................................... 44
14.2.1 To unpack and handle the unit ...................................................................................................................... 44
14.2.2 To remove the accessories from the indoor unit .......................................................................................... 45
15 About the units and options 46
15.1 Identification ................................................................................................................................................................... 46
15.1.1 Identification label: Indoor unit ..................................................................................................................... 46
15.2 About the indoor unit ..................................................................................................................................................... 46
15.3 System layout .................................................................................................................................................................. 46
15.4 Combining units and options .......................................................................................................................................... 47
15.4.1 Possible options for the indoor unit............................................................................................................... 47
16 Unit installation 49
16.1 Preparing the installation site......................................................................................................................................... 49
16.1.1 Installation site requirements of the indoor unit .......................................................................................... 49
16.2 Mounting the indoor unit ............................................................................................................................................... 51
16.2.1 Guidelines when installing the indoor unit.................................................................................................... 51
16.2.2 Guidelines when installing the drain piping................................................................................................... 54
17 Piping installation 57
17.1 Preparing refrigerant piping ........................................................................................................................................... 57
17.1.1 Refrigerant piping requirements.................................................................................................................... 57
17.1.2 Refrigerant piping insulation.......................................................................................................................... 58
17.2 Connecting the refrigerant piping .................................................................................................................................. 58
17.2.1 About connecting the refrigerant piping ....................................................................................................... 58
17.2.2 Precautions when connecting the refrigerant piping.................................................................................... 59
17.2.3 Guidelines when connecting the refrigerant piping...................................................................................... 59
17.2.4 Pipe bending guidelines ................................................................................................................................. 60
17.2.5 To flare the pipe end ...................................................................................................................................... 60
17.2.6 To connect the refrigerant piping to the indoor unit .................................................................................... 61
18 Electrical installation 62
18.1 About connecting the electrical wiring .......................................................................................................................... 62
18.1.1 Precautions when connecting the electrical wiring....................................................................................... 62
18.1.2 Guidelines when connecting the electrical wiring......................................................................................... 63
18.1.3 Specifications of standard wiring components.............................................................................................. 64
18.2 To connect the electrical wiring to the indoor unit ....................................................................................................... 65
19 Commissioning 67
19.1 Overview: Commissioning .............................................................................................................................................. 67
19.2 Precautions when commissioning .................................................................................................................................. 67
19.3 Checklist before commissioning ..................................................................................................................................... 68
19.4 To perform a test run...................................................................................................................................................... 68
20 Configuration 69
20.1 Field setting ..................................................................................................................................................................... 69
21 Hand-over to the user 72
22 Troubleshooting 73
22.1 Solving problems based on error codes ......................................................................................................................... 73
22.1.1 Error codes: Overview.................................................................................................................................... 73
23 Disposal 75
24 Technical data 76
24.1 Wiring diagram................................................................................................................................................................ 76
24.1.1 Unified wiring diagram legend....................................................................................................................... 76
25 Glossary 79
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
3
1 | About the documentation

1 About the documentation

1.1 About this document

Target audience
Authorised installers + end users
Documentation set
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
This document is part of a documentation set. The complete set consists of:
General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the indoor unit)
Indoor unit installation and operation manual:
- Installation and operation instructions
- Format: Paper (in the box of the indoor unit)
Installer and user reference guide:
- Preparation of the installation, good practices, reference data,…
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
Installer and user reference guide
4
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
FXZA15~50A2VEB
VRV system air conditioner

2 General safety precautions

2.1 About the documentation

The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised installer.

2.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
2 | General safety precautions
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
Installer and user reference guide
5
2 | General safety precautions
Symbols used in the documentation:
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".

2.2 For the installer

2.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Installer and user reference guide
6
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
FXZA15~50A2VEB
VRV system air conditioner
2 | General safety precautions
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…

2.2.2 Installation site

Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.

2.2.3 Refrigerant — in case of R410A or R32

FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
If applicable. See the installation manual or installer reference guide of your application for more information.
Installer and user reference guide
7
2 | General safety precautions
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self­combustion and explosion of the compressor because of air going into the operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
Installer and user reference guide
8
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
FXZA15~50A2VEB
VRV system air conditioner
2 | General safety precautions
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the system.
Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.

2.2.4 Electrical

DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50VDC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
9
2 | General safety precautions
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
Installer and user reference guide
10
Install power cables at least 1 m away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 m may not be sufficient.
FXZA15~50A2VEB
VRV system air conditioner
2 | General safety precautions
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
11
3 | Specific installer safety instructions

3 Specific installer safety instructions

Always observe the following safety instructions and regulations.
General
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin and, in addition, comply with applicable legislation and are performed by qualified persons only. In Europe and areas where IEC standards apply, EN/IEC 60335-2-40 is the applicable standard.
Installation site (see
"16.1Preparing the installation site"[449]
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
Refrigerant piping installation (see
CAUTION
Do NOT use mineral oil on flared part.Do NOT reuse piping from previous installations.NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
"17Piping installation"[457]
)
)
Installer and user reference guide
12
CAUTION
Incomplete flaring may cause refrigerant gas leakage.Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrigerant, unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion.
FXZA15~50A2VEB
VRV system air conditioner
3 | Specific installer safety instructions
Electrical installation (see
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
"18Electrical installation"[462]
)
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
CAUTION
Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
Commisioning (see
WARNING
If the panels on the indoor units are not installed yet, make sure to power OFF the system after finishing the test run. To do so, turn OFF operation via the user interface. Do NOT stop operation by turning OFF the circuit breakers.
"19Commissioning"[467]
)
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
13
3 | Specific installer safety instructions

3.1 Instructions for equipment using R32 refrigerant

WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
Do NOT pierce or burn.Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well­ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater) and have a room size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
NOTICE
Precautions shall be taken to avoid excessive vibration or pulsation to
refrigeration piping.
Protection devices, piping and fittings shall be protected as far as possible against
adverse environmental effects.
Provision shall be made for expansion and contraction of long runs of piping.Piping in refrigerating systems shall be designed and installed such as to minimise
the likelihood of hydraulic shock damaging the system.
The indoor equipment and pipes shall be securely mounted and guarded such
that accidental rupture of equipment or pipes cannot occur from events such as moving furniture or reconstruction activities.
Installer and user reference guide
14
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant leaks.
FXZA15~50A2VEB
VRV system air conditioner
NOTICE
Do NOT re-use joints and copper gaskets which have been used already.Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.

3.1.1 Installation space requirements

CAUTION
The total refrigerant charge in the system cannot exceed the requirements for minimum floor area of the smallest room that is served. For minimum floor area requirements for indoor units, see the installation and operation manual of the outdoor unit.
WARNING
This appliance contains R32 refrigerant. For the minimum floor area of the room in which the appliance is stored refer to installation and operation manual of the outdoor unit.
NOTICE
Pipework shall be protected from physical damage.Installation of pipework shall be kept to a minimum.
3 | Specific installer safety instructions
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
15

For the user

For the user
Installer and user reference guide
16
FXZA15~50A2VEB
VRV system air conditioner

4 User safety instructions

Always observe the following safety instructions and regulations.

4.1 General

WARNING
If you are NOT sure how to operate the unit, contact your installer.
WARNING
Children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge can only use this appliance if they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
4 | User safety instructions
Children MUST NOT play with the appliance. Cleaning and user maintenance MUST NOT be carried out
by children without supervision.
WARNING
To prevent electrical shocks or fire:
Do NOT rinse the unit.Do NOT operate the unit with wet hands.Do NOT place any objects containing water on the unit.
CAUTION
Do NOT place any objects or equipment on top of the
unit.
Do NOT sit, climb or stand on the unit.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
17
4 | User safety instructions
Units are marked with the following symbol:
Batteries are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
This means that the batteries may NOT be mixed with unsorted household waste. If a chemical symbol is printed beneath the symbol, this chemical symbol means that the battery contains a heavy metal above a certain concentration. Possible chemical symbols are: Pb: lead (>0.004%). Waste batteries must be treated at a specialized treatment facility for reuse. By ensuring waste batteries are disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.

4.2 Instructions for safe operation

WARNING
Do NOT modify, disassemble, remove, reinstall or repair
the unit yourself as incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
In case of accidental refrigerant leaks, make sure there
are no naked flames. The refrigerant itself is entirely safe, non-toxic and mildly flammable, but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters, gas cookers, etc. is present. Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation.
CAUTION
This unit is equipped with electrically powered safety measures, such as a refrigerant leak detector. In order to be effective, the unit must be electrically powered at all times after installation, except for short service periods.
Installer and user reference guide
18
FXZA15~50A2VEB
VRV system air conditioner
4 | User safety instructions
CAUTION
NEVER touch the internal parts of the controller.Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide. Chemicals could collect in the unit, and endanger the health of people who are hypersensitive to chemicals.
CAUTION
NEVER expose little children, plants or animals directly to the airflow.
WARNING
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
Installer and user reference guide
19
4 | User safety instructions
WARNING
Do NOT place a flammable spray bottle near the air conditioner and do NOT use sprays near the unit. Doing so may result in a fire.
Maintenance and service (see
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running. Be sure to turn off the main switch before executing any
maintenance task.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. When the fan is rotating at high speed, it will cause injury.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.
"10Maintenance and service"[431]
)
CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop operation and turn all power supplies off. Otherwise, an electric shock and injury may result.
WARNING
Be careful with ladders when working in high places.
CAUTION
Turn off the unit before cleaning the air filter, suction grille, air outlet and outside panels.
CAUTION
Installer and user reference guide
20
Before accessing terminal devices, make sure to interrupt all power supply.
FXZA15~50A2VEB
VRV system air conditioner
4 | User safety instructions
WARNING
Do NOT let the indoor unit get wet. Possible consequence: Electric shock or fire.
About the refrigerant (see
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
Do NOT pierce or burn refrigerant cycle parts.Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended by the manufacturer.
Be aware that the refrigerant inside the system is
odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the refrigerant leaks in the room and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful gas.
"10.5About the refrigerant"[435]
)
Turn off any combustible heating devices, ventilate the room, and contact the dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.
WARNING
It is necessary to replace the sensor after every detection or at the end of the lifetime. Authorized person only MUST replace the sensor.
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
21
4 | User safety instructions
Troubleshooting (see
WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may cause breakage, electric shock or fire. Contact your dealer.
"11Troubleshooting"[438]
)
Installer and user reference guide
22
FXZA15~50A2VEB
VRV system air conditioner

5 About the system

a
b
d
e
h
f
g
c
WARNING
Do NOT modify, disassemble, remove, reinstall or repair the unit yourself as
incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
In case of accidental refrigerant leaks, make sure there are no naked flames. The
refrigerant itself is entirely safe, non-toxic and mildly flammable, but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters, gas cookers, etc. is present. Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation.
NOTICE
Do NOT use the system for other purposes. In order to avoid any quality deterioration, do NOT use the unit for cooling precision instruments, food, plants, animals, or works of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future system extensions) is available in technical engineering data and should be consulted. Contact your installer to receive more information and professional advice.
5 | About the system

5.1 System layout

CAUTION
This unit is equipped with electrically powered safety measures, such as a refrigerant leak detector. In order to be effective, the unit must be electrically powered at all times after installation, except for short service periods.
INFORMATION
The following illustration is an example and might NOT match your system layout.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
23
5 | About the system

5.2 Information requirements for fan coil units

a Indoor unit
b Outdoor unit
c User interface d Suction air e Discharge air
f Refrigerant piping + transmission cable g Drain pipe h Suction grille and air filter
Item Symbol Value Unit
Cooling capacity (sensible) P Cooling capacity (latent) P Heating capacity P Total electric power input P Sound power level (per speed setting, if
L
WA
rated,c
rated,c
rated,h
elec
A kW B kW C kW D kW E dB
applicable) Contact details:
DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o. U Nové Hospody 1/1155, 301 00 Plzeň Skvrňany, Czech Republic
A B C D E
FXZA15 1.2 0.5 1.9 0.036 49
FXZA20 1.5 0.7 2.5 0.036 49
FXZA25 1.9 0.9 3.2 0.036 50
FXZA32 2.5 1.1 4 0.038 51
FXZA40 3.1 1.4 5 0.053 54
FXZA50 3.8 1.8 6.3 0.086 60
Installer and user reference guide
24
FXZA15~50A2VEB
VRV system air conditioner

6 User interface

CAUTION
NEVER touch the internal parts of the controller.Do NOT remove the front panel. Some parts inside are dangerous to touch and
NOTICE
Do NOT wipe the controller operation panel with benzine, thinner, chemical dust cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. Wipe it with another dry cloth.
NOTICE
NEVER press the button of the user interface with a hard, pointed object. The user interface may be damaged.
6 | User interface
appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
NOTICE
NEVER pull or twist the electric wire of the user interface. It may cause the unit to malfunction.
This operation manual offers a non-exhaustive overview of the main functions of the system.
For more information about the user interface, see the operation manual of the installed user interface.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
25
7 | Before operation

7 Before operation

WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide. Chemicals could collect in the unit, and endanger the health of people who are hypersensitive to chemicals.
NOTICE
Be sure to turn ON the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor.
This operation manual is for the following systems with standard control. Before initiating operation, contact your dealer for the operation that corresponds to your system type and mark. If your installation has a customised control system, ask your dealer for the operation that corresponds to your system.
Installer and user reference guide
26
FXZA15~50A2VEB
VRV system air conditioner

8 Operation

8.1 Operation range

INFORMATION
For the operation limits see the technical data of the connected outdoor unit.

8.2 About operation modes

INFORMATION
Depending on the installed system, some operation modes will not be available.
The air flow rate may adjust itself depending on the room temperature or the fan
may stop immediately. This is not a malfunction.
8 | Operation
If the main power supply is turned off during operation, operation will restart
automatically after the power turns back on again.
Setpoint. Target temperature for the Cooling, Heating, and Auto operation
modes.
Setback. A function that keeps the room temperature in a specific range when
the system is turned off (by the user, the schedule function, or the OFF timer).

8.2.1 Basic operation modes

The indoor unit can operate in various operation modes.
Icon Operation mode
Cooling. In this mode, cooling will be activated as required by the
setpoint, or by Setback operation.
Heating. In this mode, heating will be activated as required by the setpoint, or by Setback operation.
Fan only. In this mode, air circulates without heating or cooling.
Dry. In this mode, the air humidity will be lowered with a
minimal temperature decrease.
The temperature and fan speed are controlled automatically and cannot be controlled by the controller.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Dry operation will not function if the room temperature is too low.
Auto. In Auto mode, the indoor unit automatically switches between heating and cooling mode, as required by the setpoint.
Installer and user reference guide
27
8 | Operation

8.2.2 Special heating operation modes

Operation Description
Defrost To prevent a loss of heating capacity
due to frost accumulation in the outdoor unit, the system will automatically switch to defrost operation.
During defrost operation, the indoor unit fan will stop operation, and the following icon will appear on the home screen:
The system will resume normal operation after approximately 6 to 8 minutes.
Hot start During hot start, the indoor unit fan will
stop operation, and the following icon will appear on the home screen:

8.2.3 Adjusting the airflow direction

The following airflow directions can be set:
Fixed position. The indoor unit blows air in 1 of 4 fixed positions.
Swing. The indoor unit alternates between the 4 positions.
Auto. The indoor unit adjusts its airflow direction according to movement sensed by a movement sensor.
INFORMATION
Depending on system layout and organisation, Auto airflow direction may not be available.
Direction Screen
Installer and user reference guide
28
INFORMATION
For setting procedure of the airflow direction, see the reference guide or the manual of the used user interface.
FXZA15~50A2VEB
VRV system air conditioner
8 | Operation
Automatic airflow control
In the following operating conditions, the airflow direction of the indoor units is controlled automatically:
When the room temperature is higher than the controller's setpoint for heating
operation (including auto operation).
When the indoor units run in heating operation mode, and the Defrost function
is active.
When the indoor units run in Continuous operation, and the airflow direction is
Horizontal.
WARNING
Never touch the air outlet or the horizontal blades while the swing flap is in operation. Fingers may become caught or the unit may break down.
NOTICE
Avoid operating in the horizontal direction. It may cause dew or dust to settle on the ceiling or flap.

8.3 To operate the system

INFORMATION
For setting of the operation mode, airflow direction or other settings, see the reference guide or operation manual of the user interface.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
29
9 | Energy saving and optimum operation

9 Energy saving and optimum operation

CAUTION
NEVER expose little children, plants or animals directly to the airflow.
WARNING
Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
WARNING
Do NOT place a flammable spray bottle near the air conditioner and do NOT use sprays near the unit. Doing so may result in a fire.
Observe the following precautions to ensure the system operates properly.
Prevent direct sunlight from entering a room during cooling operation by using
curtains or blinds.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Ventilate often. Extended use requires special attention to ventilation.
Keep doors and windows closed. If the doors and windows remain open, air will
flow out of your room causing a decrease in the cooling or heating effect.
Be careful NOT to cool or heat too much. To save energy, keep the temperature
setting at a moderate level.
NEVER place objects near the air inlet or the air outlet of the unit. Doing so may
cause a reduced heating/cooling effect or stop operation.
When the display shows (time to clean the air filter), clean the filters (see
"10.2.1To clean the air filter"[432]).
Condensation may form if the humidity is above 80% or if the drain outlet gets
blocked.
Adjust the air outlet properly and avoid direct air flow to room inhabitants.
Installer and user reference guide
30
FXZA15~50A2VEB
VRV system air conditioner

10 Maintenance and service

10.1 Precautions for maintenance and service

NOTICE
Maintenance MUST be done by an authorized installer or service agent.
We recommend performing maintenance at least once a year. However, applicable legislation might require shorter maintenance intervals.
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any maintenance task.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. When the fan is rotating at high speed, it will cause injury.
10 | Maintenance and service
NOTICE
NEVER inspect or service the unit by yourself. Ask a qualified service person to perform this work. However, as end user, you may clean the air filter, suction grille, air outlet and outside panels.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.
CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.
NOTICE
Do NOT wipe the controller operation panel with benzine, thinner, chemical dust cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. Wipe it with another dry cloth.
CAUTION
Before accessing terminal devices, make sure to interrupt all power supply.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop operation and turn all power supplies off. Otherwise, an electric shock and injury may result.
WARNING
Be careful with ladders when working in high places.
Installer and user reference guide
31
10 | Maintenance and service
1
Following symbols may occur on the indoor unit:
Symbol Explanation

10.2 Cleaning the air filter, suction grille, air outlet and outside panels

10.2.1 To clean the air filter

When to clean the air filter:
Rule of thumb: Clean every 6 months. If the air in the room is extremely
contaminated, increase the cleaning frequency.
Measure the voltage at the terminals of main circuit capacitors or electrical components before servicing.
CAUTION
Turn off the unit before cleaning the air filter, suction grille, air outlet and outside panels.
Depending on the settings, the user interface can display the "Time to clean
filter" notification. Clean the air filter when the notification is displayed.
If the dirt becomes impossible to clean, change the air filter (= optional
equipment).
How to clean the air filter:
NOTICE
Do NOT use water of 50°C or higher. Possible consequence: Discoloration and deformation.
1 Open the suction grille.
BYFQ60B BYFQ60C
2 Remove the air filter.
Installer and user reference guide
32
FXZA15~50A2VEB
VRV system air conditioner
10 | Maintenance and service
1
3
3
2
3
3
1
2
1
BYFQ60B BYFQ60C
3 Clean the air filter. Use a vacuum cleaner or wash with water. If the air filter is
very dirty, use a soft brush and neutral detergent.
4 Dry the air filter in the shadow.
5 Reattach the air filter and close the suction grille.
6 Turn ON the power.
7 To remove warning screens, see the reference guide of the user interface.

10.2.2 To clean the suction grille

1 Open the suction grille.
NOTICE
Do NOT use water of 50°C or higher. Possible consequence: Discoloration and deformation.
BYFQ60B BYFQ60C
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
2 Remove the suction grille.
Installer and user reference guide
33
10 | Maintenance and service
45°
1
90°
1
3
3
2
3
3
1
2
BYFQ60B
BYFQ60C
3 Remove the air filter.
BYFQ60B
4 Clean the suction grille. Wash with a soft bristle brush and water or neutral
detergent. If the suction grille is very dirty, use a typical kitchen cleaner, leave it on for 10min, then wash it with water.
5 Reattach the air filter (step 3 in reverse order).
6 Reattach the suction grille and close it (step 2 and 1 in reverse order).

10.2.3 To clean the air outlet and outside panels

BYFQ60C
Installer and user reference guide
34
WARNING
Do NOT let the indoor unit get wet. Possible consequence: Electric shock or fire.
FXZA15~50A2VEB
VRV system air conditioner
NOTICE
Do NOT use gasoline, benzene, thinner polishing powder or liquid insecticide.
Possible consequence: Discoloration and deformation.
Do NOT use water or air of 50°C or higher. Possible consequence: Discoloration
and deformation.
Do NOT scrub firmly when washing the blade with water. Possible consequence:
The surface sealing peels off.
Clean with a soft cloth. If it is difficult to remove stains, use water or neutral detergent.

10.3 Maintenance before a long stop period

E.g., at the end of the season.
Let the indoor units run in fan only operation for about half a day in order to dry
the interior of the units.
Clean air filters and casings of indoor units (see "10.2.1 To clean the air
filter"[432] and "10.2.3To clean the air outlet and outside panels"[434]).
10 | Maintenance and service
Remove the batteries from the user interface (if applicable).

10.4 Maintenance after a long stop period

E.g., at the beginning of the season.
Check and remove everything that might be blocking inlet and outlet vents of
indoor units and outdoor units.
Clean air filters and casings of indoor units (see "10.2.1 To clean the air
filter"[432] and "10.2.3To clean the air outlet and outside panels"[434]).
Insert batteries in the user interface (if applicable).

10.5 About the refrigerant

This product contains fluorinated greenhouse gases. Do NOT vent gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent tonnes: GWP value of the refrigerant × total refrigerant charge [in kg] / 1000
Please contact your installer for more information.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Installer and user reference guide
35
10 | Maintenance and service
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
WARNING
Do NOT pierce or burn refrigerant cycle parts.Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
Be aware that the refrigerant inside the system is odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the refrigerant leaks in the room and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful gas.
Turn off any combustible heating devices, ventilate the room, and contact the dealer where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.

10.5.1 About the refrigerant leakage sensor

WARNING
It is necessary to replace the sensor after every detection or at the end of the lifetime. Authorized person only MUST replace the sensor.
NOTICE
Functionality of the safety measures are periodically automatically checked. In case of malfunction, error code will display on the user interface.
NOTICE
The R32 refrigerant leakage sensor is a semiconductor detector which may incorrectly detect substances other than R32 refrigerant. Avoid using chemical substances (e.g. organic solvents, hair spray, paint) in high concentrations, in the close proximity of the indoor unit because this may cause misdetection of the R32 refrigerant leakage sensor.
INFORMATION
Lifetime of the sensor is 10years. The user interface displays error "CH-05" 6months before the end of the sensor lifetime and error "CH-02" after the end of the sensor lifetime. For more information refer to the reference guide of the user interface and contact you dealer.
Installer and user reference guide
36
In case of detection when the unit is standby
When the detection occurs when the unit is standby, "false detection check" will occur.
False detection check
1 Unit starts fan operation on the lowest setting.
2 User interface displays error code "A0-13", emits alarm sound and status
indicator is blinking.
FXZA15~50A2VEB
VRV system air conditioner
10 | Maintenance and service
3 Sensor checks if refrigerant leakage or misdetection occurred.
If refrigerant leakage is NOT detected, Result: system returns to normal
operation after approximately 2 minutes.
If refrigerant leakage is detected, Result:
1 User interface displays error "A0-11", emits alarm sound and status indicator
is blinking.
2 Contact your dealer immediately. For more information, see the installation
manual of the outdoor unit.
In case of detection when the unit is turned on
1 User interface displays error "A0-11", emits alarm sound and status indicator
is blinking.
2 Contact your dealer immediately. For more information, see the installation
manual of the outdoor unit.
INFORMATION
To stop alarm of the user interface see the reference guide of the user interface.
INFORMATION
The minimum airflow during normal operation or during the refrigerant leakage detection is always >240m3/h.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
37
11 | Troubleshooting

11 Troubleshooting

If one of the following malfunctions occur, take the measures shown below and contact your dealer.
WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may cause breakage, electric shock or fire. Contact your dealer.
The system MUST be repaired by a qualified service person.
Malfunction Measure
If a safety device such as a fuse, a circuit breaker or a residual current device frequently actuates
Turn OFF all main power supply
switches to the unit. or the ON/OFF switch does NOT function properly.
If water leaks from the unit. Stop operation.
The operation switch does NOT function
Turn OFF the power supply. properly.
If the user interface displays . Notify your installer and report
the error code. To display an
error code see the reference
guide of the user interface.
If the system does NOT operate properly except for the above mentioned cases and none of the above mentioned malfunctions is evident, investigate the system in accordance with the following procedures.
Malfunction Measure
If the system does not operate at all.
Check if there is no power failure. Wait until
power is restored. If power failure occurs during operation, the system automatically restarts immediately after power is restored.
Check if no fuse has blown or breaker is activated.
Change the fuse or reset the breaker if necessary.
Installer and user reference guide
38
FXZA15~50A2VEB
VRV system air conditioner
11 | Troubleshooting
Malfunction Measure
The system operates but cooling or heating is insufficient.
Check if air inlet or outlet of outdoor or indoor
unit is not blocked by obstacles. Remove any obstacles and make sure the air can flow freely.
Check if the air filter is not clogged (see "10.2.1To
clean the air filter"[432]).
Check the temperature setting.
Check the fan speed setting on your user
interface.
Check for open doors or windows. Close doors and
windows to prevent wind from coming in.
Check if there are too many occupants in the room
during cooling operation. Check if the heat source of the room is excessive.
Check if direct sunlight enters the room. Use
curtains or blinds.
Check if the air flow angle is proper.
If after checking all above items, it is impossible to fix the problem yourself, contact your installer and state the symptoms, the complete model name of the unit (with manufacturing number if possible) and the installation date (possibly listed on the warranty card).

11.1 Symptoms that are NOT system malfunctions

The following symptoms are NOT system malfunctions:

11.1.1 Symptom: The system does not operate

The air conditioner does not start immediately after the ON/OFF button on the
user interface is pressed. If the operation lamp lights, the system is in normal condition. To prevent overloading of the compressor motor, the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before. The same starting delay occurs after the operation mode selector button was used.
The system does not start immediately after the power supply is turned on. Wait
one minute until the micro computer is prepared for operation.

11.1.2 Symptom: The fan speed does not correspond to the setting

The fan speed does not change even if the fan speed adjustment button in pressed. During heating operation, when the room temperature reaches the set temperature, the outdoor unit goes off and the indoor unit changes to whisper fan speed. This is to prevent cold air blowing directly on occupants of the room. The fan speed will not change if the button is pressed.

11.1.3 Symptom: The fan direction does not correspond to the setting

FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
The fan direction does not correspond with the user interface display. The fan direction does not swing. This is because the unit is being controlled by the micro computer.
Installer and user reference guide
39
11 | Troubleshooting

11.1.4 Symptom: White mist comes out of a unit (Indoor unit)

11.1.5 Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)

11.1.6 Symptom: The user interface reads "U4" or "U5" and stops, but then restarts after a few minutes

When humidity is high during cooling operation. If the interior of an indoor unit is
extremely contaminated, the temperature distribution inside a room becomes uneven. It is necessary to clean the interior of the indoor unit. Ask your dealer for details on cleaning the unit. This operation requires a qualified service person.
Immediately after the cooling operation stops and if the room temperature and
humidity are low. This is because warm refrigerant gas flows back into the indoor unit and generates steam.
When the system is changed over to heating operation after defrost operation. Moisture generated by defrost becomes steam and is exhausted.
This is because the user interface is intercepting noise from electric appliances other than the air conditioner. The noise prevents communication between the units, causing them to stop. Operation automatically restarts when the noise ceases.

11.1.7 Symptom: Noise of air conditioners (Indoor unit)

A "zeen" sound is heard immediately after the power supply is turned on. The
electronic expansion valve inside an indoor unit starts working and makes the noise. Its volume will reduce in about one minute.
A continuous low "shah" sound is heard when the system is in cooling operation
or at a stop. When the drain pump is in operation, this noise is heard.
A "pishi-pishi" squeaking sound is heard when the system stops after heating
operation. Expansion and contraction of plastic parts caused by temperature change make this noise.

11.1.8 Symptom: Noise of air conditioners (Indoor unit, outdoor unit)

A continuous low hissing sound is heard when the system is in cooling or defrost
operation. This is the sound of refrigerant gas flowing through both indoor and outdoor units.
A hissing sound which is heard at the start or immediately after stopping
operation or defrost operation. This is the noise of refrigerant caused by flow stop or flow change.

11.1.9 Symptom: Dust comes out of the unit

When the unit is used for the first time in a long time. This is because dust has gotten into the unit.

11.1.10 Symptom: The units can give off odours

The unit can absorb the smell of rooms, furniture, cigarettes, etc., and then emit it again.
Installer and user reference guide
40
FXZA15~50A2VEB
VRV system air conditioner

12 Relocation

Contact your dealer for removing and reinstalling the total unit. Moving units requires technical expertise.
12 | Relocation
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
41
13 | Disposal

13 Disposal

NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
Installer and user reference guide
42
FXZA15~50A2VEB
VRV system air conditioner

For the installer

FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
For the installer
Installer and user reference guide
43
14 | About the box
1 2

14 About the box

14.1 Overview: About the box

This chapter describes what you have to do after the box with the indoor unit is delivered on-site.
It contains information about:
Unpacking and handling the unit
Removing the accessories from the unit
Keep the following in mind:
At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
Prepare the path along which you want to bring the unit inside in advance.

14.2 Indoor unit

14.2.1 To unpack and handle the unit

Use a sling of soft material or protective plates together with a rope when lifting the unit. This to avoid damage or scratches to the unit.
1 Lift the unit by holding on to the hanger brackets without exerting any
pressure on other parts, especially on refrigerant piping, drain piping and other resin parts.
Installer and user reference guide
44
FXZA15~50A2VEB
VRV system air conditioner

14.2.2 To remove the accessories from the indoor unit

dcb
f
e
g
j k
a
ih
B
A
B
B
B
A
A
a Paper pattern for installation (upper part of packing) b General safety precautions c Indoor unit installation and operation manual d Tie wraps e Sealing pads: Large (drain pipe), medium 1 (gas pipe), medium 2 (liquid pipe), small (electrical wiring)
f Metal clamp g Drain hose h Washers for hanger bracket
i Screws
j Insulation piece: Small (liquid pipe) k Insulation piece: Large (gas pipe)
14 | About the box
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
45
15 | About the units and options

15 About the units and options

In this chapter

15.1 Identification........................................................................................................................................................................... 46
15.1.1 Identification label: Indoor unit ............................................................................................................................. 46
15.2 About the indoor unit ............................................................................................................................................................. 46
15.3 System layout.......................................................................................................................................................................... 46
15.4 Combining units and options.................................................................................................................................................. 47
15.4.1 Possible options for the indoor unit ...................................................................................................................... 47

15.1 Identification

15.1.1 Identification label: Indoor unit

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.
Location

15.2 About the indoor unit

INFORMATION
For the operation limits see the technical data of the connected outdoor unit.

15.3 System layout

Installer and user reference guide
46
INFORMATION
The following illustration is an example and might NOT match your system layout.
FXZA15~50A2VEB
VRV system air conditioner
a
b
d
e
h
f
g
c
a Indoor unit b Outdoor unit c User interface d Suction air e Discharge air
f Refrigerant piping + transmission cable g Drain pipe h Suction grille and air filter
15 | About the units and options

15.4 Combining units and options

INFORMATION
Certain options might not be available in your country.

15.4.1 Possible options for the indoor unit

Make sure you have the following mandatory options:
User interface: Only a safety system compatible remote controller can be used.
See technical data sheet for remote controller compatibility (e.g. BRC1H52/82*)
Note: The user interface will generate a visible and audible warning sign in case of refrigerant leakage detection. E.g. the BRC1H52* remote controllers can generate an alarm of 65dB (sound pressure, measured at 1m distance of the alarm). Sound data is available in the technical data sheet of the remote controller. The alarm should always be 15dB louder than the background noise of the room. In case of higher background noise we recommend to use an external alarm (field supply) to connect to the optional output PCB of the indoor unit. This field supply alarm has to be mounted in every room where an indoor unit is installed.
CAUTION
Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
47
15 | About the units and options
Optional output PCB (to provide output for external device): The PCB will trigger
in case of leak detection, sensor fails or when sensor is disconnected. For exact model name see option list of the indoor unit. For more information about this option, refer to the installation manual of the optional output PCB.
Decoration panel: Standard
INFORMATION
All possible options are mentioned in the option list of the indoor unit. For more information about an option, refer to the installation and operation manual of the option.
Installer and user reference guide
48
FXZA15~50A2VEB
VRV system air conditioner

16 Unit installation

In this chapter

16.1 Preparing the installation site ................................................................................................................................................ 49
16.1.1 Installation site requirements of the indoor unit.................................................................................................. 49
16.2 Mounting the indoor unit ....................................................................................................................................................... 51
16.2.1 Guidelines when installing the indoor unit............................................................................................................ 51
16.2.2 Guidelines when installing the drain piping .......................................................................................................... 54

16.1 Preparing the installation site

Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit MUST be covered.
Choose an installation location with sufficient space for carrying the unit in and out of the site.
Avoid installation in an environment with a lot of organic solvents such as ink and siloxane.
16 | Unit installation
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).

16.1.1 Installation site requirements of the indoor unit

INFORMATION
Also read the general installation site requirements. See the ""2 General safety
precautions"[45]" chapter.
INFORMATION
The sound pressure level is less than 70dBA.
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Do NOT install the unit in the following places:
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
Installer and user reference guide
49
16 | Unit installation
a b c
(mm)
≥1500
2000
4000
≥1500
A
B
C
ba dac
NOTICE
The equipment described in this manual may cause electronic noise generated from radio-frequency energy. The equipment complies to specifications that are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a way that they keep a proper distance from stereo equipment, personal computers, etc.
In places with weak reception, keep distances of 3 m or more to avoid electromagnetic disturbance of other equipment and use conduit tubes for power and transmission lines.
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
Air flow. Make sure nothing blocks the air flow.
Drainage. Make sure condensation water can be evacuated properly.
Paper pattern for installation (upper part of packing) (accessory). When
selecting the installation location, use the paper pattern. It contains the dimensions of the unit and the required ceiling opening.
Air flow directions. You can select different air flow directions. Choose the one
best suited for the room. For more information, see the installation manual of the optional blocking pad kit.
Example:
a 4-way air flow (all air outlets open) b 3-way air flow (1 air outlet closed) (optional blocking pad kit required)
c 2-way air flow (2 air outlets closed) (optional blocking pad kit required)
Ceiling insulation. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional insulation is required (minimum 10mm thickness, polyethylene foam).
Spacing. Mind the following requirements:
Installer and user reference guide
50
A Minimum distance to the wall
≥1500mm: Air outlet open
≥200mm: Air outlet closed B Minimum and maximum distance to the floor (see below) C ≥295mm: In case of installation with BYFQ60B
≥308mm: In case of installation with BYFQ60C a Indoor unit b Lighting (the figure shows ceiling-mounted lighting, but recessed lighting is also allowed)
c Air fan
d Static volume (example: table)
FXZA15~50A2VEB
VRV system air conditioner
16 | Unit installation
450
450
a
(mm)
(300)
B: Minimum and maximum distance to the floor:
- Minimum: 2.7m to avoid accidental touching.
- Maximum: Depends on the air flow directions and the capacity class. Also make
sure the "Ceiling height" field setting corresponds with the actual situation. See
"20.1Field setting"[469].
Install inspection opening on the control box side to make maintenance easier.
a Inspection opening
INFORMATION
Some options may require additional service space. Refer to the installation manual of the used option before installation.
Minimum floor area requirements
CAUTION
The total refrigerant charge in the system cannot exceed the requirements for minimum floor area of the smallest room that is served. For minimum floor area requirements for indoor units, see the installation and operation manual of the outdoor unit.

16.2 Mounting the indoor unit

16.2.1 Guidelines when installing the indoor unit

INFORMATION
Optional equipment. When installing optional equipment, also read the installation
manual of the optional equipment. Depending on the field conditions, it might be easier to install the optional equipment first.
Decoration panel. Install the decoration panel always after installing the unit.
NOTICE
After installing the decoration panel:
Make sure there is no gap between the unit body and the decoration panel.
Possible consequence: Air might leak and cause dew drop.
Make sure no oil remains on the plastic parts of the decoration panel. Possible
consequence: Degradation and damage of plastic parts.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Ceiling strength. Check whether the ceiling is strong enough to support the
weight of the unit. If there is a risk, reinforce the ceiling before installing the unit.
- For existing ceilings, use anchors.
- For new ceilings, use sunken inserts, sunken anchors or other field supplied
parts.
Installer and user reference guide
51
16 | Unit installation
A
c
b
d
e
a
(mm)
a1 b
b a2
c
533
533
a cb d
A 50~100 mm a Ceiling slab b Anchor
c Long nut or turnbuckle d Suspension bolt e Suspended ceiling
Suspension bolts. Use M8~M10 suspension bolts for installation. Attach the
hanger bracket to the suspension bolt. Fix it securely using a nut and washer from the upper and lower sides of the hanger bracket.
a1 Nut (field supply) a2 Double nut (field supply)
b Washer (accessories)
c Hanger bracket (attached to the unit)
Paper pattern for installation (upper part of the packing). Use the paper pattern
to determine the correct horizontal positioning. It contains the necessary dimensions and centers. You can attach the paper pattern to the unit.
a Centre of the unit b Centre of the ceiling opening
c Paper pattern for installation (upper part of the packing) d Screws (accessories)
Ceiling opening and unit:
- Make sure the ceiling opening is within the following limits:
Minimum: 585mm to be able to fit the unit.
Maximum: 660mm in case of installation with BYFQ60B and 595mm in case of
installation with BYFQ60C ensure enough overlapping between the decoration panel and the suspended ceiling. If the ceiling opening is larger, add extra ceiling material.
Installer and user reference guide
52
- Make sure the unit and its hanger brackets (suspension) are centered within
the ceiling opening.
FXZA15~50A2VEB
VRV system air conditioner
(mm)
c d
A B
A
B
533
350
575
c
d
533
575
b
a
A 585~660mm: In case of installation with BYFQ60B
A
C
B
c
bba
585~595 mm: In case of installation with BYFQ60C
B 700mm: In case of installation with BYFQ60B
620 mm: In case of installation with BYFQ60C
a Drain piping
b Refrigerant piping
c Hanger bracket pitch (suspension)
d Unit
Example If A
16 | Unit installation
(a)
BYFQ60B
Then
(a)
B
(a)
C
585mm 5mm 57.5mm
660mm 42.5mm 20mm
BYFQ60C
585mm 5mm 17.5mm
595mm 10mm 12.5mm
(a)
A: Ceiling opening
B: Distance between the unit and the ceiling opening
C: Overlap between the decoration panel and the suspended ceiling
Level. Make sure the unit is level at all 4 corners using a level or a water-filled
vinyl tube.
a Level
b Vinyl tube
c Water level
NOTICE
Do NOT install the unit tilted. Possible consequence: If the unit is tilted against the
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
direction of the condensate flow (the drain piping side is raised), the float switch might malfunction and cause water to drip.
Installer and user reference guide
53
16 | Unit installation
1~1.5 m
a
≤675
≤300
0~75
1000~1500
(mm)
ba
b c
a
dd
≥100
≤675
(mm)
a

16.2.2 Guidelines when installing the drain piping

General guidelines
Make sure condensation water can be evacuated properly. This involves:
General guidelines
Connecting the drain piping to the indoor unit
Checking for water leaks
Pipe length. Keep drain piping as short as possible.
Pipe size. Keep the pipe size equal to or greater than that of the connecting pipe
(vinyl pipe of 25mm nominal diameter and 32mm outer diameter).
Slope. Make sure the drain piping slopes down (at least 1/100) to prevent air
from being trapped in the piping. Use hanging bars as shown.
a Hanging bar
O Allowed
X Not allowed
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
Rising piping. If necessary to make the slope possible, you can install rising
piping.
- Drain hose inclination: 0~75mm to avoid stress on the piping and to avoid air
bubbles.
a Metal clamp (accessory) b Drain hose (accessory)
c Rising drain piping (vinyl pipe of 25mm nominal diameter and 32mm outer diameter) (field supply) d Hanging bars (field supply)
Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with a correct gauge for the operating capacity of the units.
Installer and user reference guide
54
a T-joint
FXZA15~50A2VEB
VRV system air conditioner
To connect the drain piping to the indoor unit
≤4 mm
A
A'
A-A'
A
A'
e
542
c
b
d
b a
d c
a
3
1
2~51
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the installation space and surroundings.
1 Push the drain hose as far as possible over the drain pipe connection.
2 Tighten the metal clamp until the screw head is less than 4 mm from the
metal clamp part.
3 Check for water leaks (see "To check for water leaks"[455]).
4 Wind the large sealing pad (= insulation) around the metal clamp and drain
hose, and fix it with tie wraps.
5 Connect the drain piping to the drain hose.
16 | Unit installation
a Drain pipe connection (attached to the unit)
b Drain hose (accessory)
c Metal clamp (accessory)
d Large sealing pad (accessory)
e Drain piping (field supply)
To check for water leaks
The procedure differs depending on whether installation of the system is already completed. When installation of the system is not yet completed, temporarily connect the user interface and power supply to the unit.
When installation of the system is not yet completed
1 Temporarily connect electrical wiring.
Remove the service cover (a).Connect the power supply (d).Connect the user interface (f).Reattach the service cover (a).
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
55
16 | Unit installation
L
N
b
c d
a
b
P1P2 F1F2 T1T2
e
d
c
≥100 mm
a
b
a Service cover with wiring diagram b Opening for cables
c User interface terminal block d Power supply terminal block
2 Turn ON the power.
3 Start fan only operation (see the reference guide or the service manual of the
user interface).
4 Gradually pour approximately 1 l of water through the air discharge outlet,
and check for leaks.
a Plastic watering can b Service drain outlet (with rubber plug). Use this outlet to drain water from the drain pan.
c Drain pump location d Drain pipe connection e Drain pipe
5 Turn OFF the power.
6 Disconnect the electrical wiring.
Remove the service cover.Disconnect the power supply.Disconnect the user interface.Reattach the service cover.
When installation of the system is already completed
1 Start cooling operation (see the reference guide or the service manual of the
user interface).
2 Gradually pour approximately 1l of water through the water inlet, and check
for leaks (see "When installation of the system is not yet completed"[455]).
Installer and user reference guide
56
FXZA15~50A2VEB
VRV system air conditioner

17 Piping installation

In this chapter

17.1 Preparing refrigerant piping ................................................................................................................................................... 57
17.1.1 Refrigerant piping requirements ........................................................................................................................... 57
17.1.2 Refrigerant piping insulation.................................................................................................................................. 58
17.2 Connecting the refrigerant piping .......................................................................................................................................... 58
17.2.1 About connecting the refrigerant piping............................................................................................................... 58
17.2.2 Precautions when connecting the refrigerant piping............................................................................................ 59
17.2.3 Guidelines when connecting the refrigerant piping.............................................................................................. 59
17.2.4 Pipe bending guidelines ......................................................................................................................................... 60
17.2.5 To flare the pipe end.............................................................................................................................................. 60
17.2.6 To connect the refrigerant piping to the indoor unit............................................................................................ 61

17.1 Preparing refrigerant piping

17.1.1 Refrigerant piping requirements

INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[45].
17 | Piping installation
Foreign materials inside pipes (including oils for fabrication) must be
≤30mg/10m.
Refrigerant piping diameter
For piping connections of the indoor unit use the following piping diameters:
15~32 Ø6.4 Ø9.5
40+50 Ø6.4 Ø12.7
Refrigerant piping material
CAUTION
Piping MUST be installed according to instructions given in "17 Piping
installation" [4 57]. Only mechanical joints (e.g. braze+flare connections) that are
compliant with the latest version of ISO14903 can be used.
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.
Class Pipe outer diameter (mm)
Liquid pipe Gas pipe
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Piping material: Phosphoric acid deoxidised seamless copper.
Flare connections: Only use annealed material.
Piping temper grade and thickness:
Installer and user reference guide
57
17 | Piping installation
t
Ø
ØiØ
i
t
ØpØ
p
Outer diameter (Ø) Temper grade Thickness (t)
6.4mm (1/4") Annealed (O) ≥0.8mm
9.5mm (3/8")
12.7mm (1/2")
(a)
Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High" on the unit name plate), larger piping thickness might be required.

17.1.2 Refrigerant piping insulation

Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness
Pipe outer diameter (Øp) Insulation inner diameter
6.4mm (1/4") 8~10mm ≥10mm
9.5mm (3/8") 12~15mm ≥13mm
(a)
Insulation thickness (t)
(Øi)
12.7mm (1/2") 14~16mm ≥13mm
If the temperature is higher than 30°C and the humidity is higher than RH80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.

17.2 Connecting the refrigerant piping

17.2.1 About connecting the refrigerant piping

Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
Connecting the refrigerant piping to the indoor unit
Connecting the refrigerant piping to the outdoor unit
Insulating the refrigerant piping
Keeping in mind the guidelines for:
- Pipe bending
- Flaring pipe ends
- Using the stop valves
Installer and user reference guide
58
FXZA15~50A2VEB
VRV system air conditioner

17.2.2 Precautions when connecting the refrigerant piping

INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautionsPreparation
DANGER: RISK OF BURNING/SCALDING
CAUTION
Do NOT use mineral oil on flared part.Do NOT reuse piping from previous installations.NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
NOTICE
Take the following precautions on refrigerant piping into account:
Avoid anything but the designated refrigerant to get mixed into the refrigerant
cycle (e.g. air).
Only use R32 when adding refrigerant.Only use installation tools (e.g. manifold gauge set) that are exclusively used for
R32 installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils and moisture) from mixing into the system.
Install the piping so that the flare is NOT subjected to mechanical stress.Protect the piping as described in the following table to prevent dirt, liquid or
dust from entering the piping.
Use caution when passing copper tubes through walls (see figure below).
17 | Piping installation

17.2.3 Guidelines when connecting the refrigerant piping

FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Unit Installation period Protection method
Outdoor unit >1month Pinch the pipe
<1month Pinch or tape the pipe
Indoor unit Regardless of the period
INFORMATION
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging.
Take the following guidelines into account when connecting pipes:
Installer and user reference guide
59
17 | Piping installation
a
b
c
d
R=
0.4~0.8
±2
45°
90°
±2
ØA
a b
A
Coat the flare inner surface with ether oil or ester oil when connecting a flare
nut. Tighten 3 or 4 turns by hand, before tightening firmly.
ALWAYS use 2 wrenches together when loosening a flare nut.
ALWAYS use a spanner and torque wrench together to tighten the flare nut when
connecting the piping. This to prevent nut cracking and leaks.
a Torque wrench b Spanner
c Piping union d Flare nut
Piping size (mm) Tightening torque
(N•m)
Flare dimensions
(A) (mm)
Flare shape (mm)
Ø6.4 15~17 8.7~9.1
Ø9.5 33~39 12.8~13.2
Ø12.7 50~60 16.2~16.6

17.2.4 Pipe bending guidelines

Use a pipe bender for bending. All pipe bends should be as gentle as possible (bending radius should be 30~40 mm or larger).

17.2.5 To flare the pipe end

1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing down so that the chips do NOT enter
the pipe.
CAUTION
Incomplete flaring may cause refrigerant gas leakage.Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
Installer and user reference guide
60
a Cut exactly at right angles. b Remove burrs.
3 Remove the flare nut from the stop valve and put the flare nut on the pipe.
4 Flare the pipe. Set exactly at the position as shown in the following figure.
FXZA15~50A2VEB
VRV system air conditioner
17 | Piping installation
a b
c
BA
a dc e fb b
a dc e fb b
2
4
3
g
1
23
4
g
1
A B
Flare tool for R32
(clutch type)
A 0~0.5mm 1.0~1.5mm 1.5~2.0mm
5 Check that the flaring is properly made.
a Flare’s inner surface MUST be flawless.
b The pipe end MUST be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.

17.2.6 To connect the refrigerant piping to the indoor unit

CAUTION
Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrigerant, unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion.
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Pipe length. Keep refrigerant piping as short as possible.
Flare connections. Connect refrigerant piping to the unit using flare connections.
Insulation. Insulate the refrigerant piping on the indoor unit as follows:
A Gas piping B Liquid piping
a Insulation material (field supply)
b Tie wrap (accessory)
c Insulation pieces: Large (gas pipe), small (liquid pipe) (accessories)
d Flare nut (attached to the unit)
e Refrigerant pipe connection (attached to the unit)
f Unit
g Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe) (accessories)
1 Turn up the seams of the insulation pieces. 2 Attach to the base of the unit. 3 Tighten the tie wrap on the insulation pieces. 4 Wrap the sealing pad from the base of the unit to the top of the flare nut.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause condensation.
Installer and user reference guide
61
18 | Electrical installation

18 Electrical installation

In this chapter

18.1 About connecting the electrical wiring

18.1 About connecting the electrical wiring .................................................................................................................................. 62
18.1.1 Precautions when connecting the electrical wiring .............................................................................................. 62
18.1.2 Guidelines when connecting the electrical wiring ................................................................................................ 63
18.1.3 Specifications of standard wiring components ..................................................................................................... 64
18.2 To connect the electrical wiring to the indoor unit ............................................................................................................... 65
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1 Making sure the power supply system complies with the electrical
specifications of the units.
2 Connecting the electrical wiring to the outdoor unit. 3 Connecting the electrical wiring to the indoor unit. 4 Connecting the main power supply.

18.1.1 Precautions when connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[45].
INFORMATION
Also read "18.1.3Specifications of standard wiring components"[464].
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
Installer and user reference guide
62
FXZA15~50A2VEB
VRV system air conditioner
18 | Electrical installation
b a
c b
c
aa
A
AA´
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.

18.1.2 Guidelines when connecting the electrical wiring

Keep the following in mind:
If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool.
a Stranded conductor wire
b Round crimp-style terminal
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
a Curled single-core wire
b Screw
c Flat washer
Installer and user reference guide
63
18 | Electrical installation
c b ba c
a
B
B
Wire type Installation method
Stranded conductor wire with round crimp-style terminal
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
Wiring Screw size Tightening torque
(N•m)
Power supply cable M4 1.08~1.32
Transmission cable (indoor↔outdoor)
User interface cable
The earth wire between the wire retainer and the terminal must be longer than
the other wires.

18.1.3 Specifications of standard wiring components

Component Class
Power supply cable
(a)
MCA
Voltage 220~240V
Phase 1~
Frequency 50/60Hz
Wire sizes 1.5mm2 (3‑core wire)
M3.5 0.79~0.97
15~25 32~40 50
0.3A 0.4A 0.6A
H07RN-F (60245 IEC 66)
Installer and user reference guide
64
Transmission wiring 0.75 to 1.25mm2 (2‑core wire)
User interface cable
H05RN-F (60245 IEC 57)
User interface - maximum 500m
Recommended field fuse 6A
Residual current device Must comply with applicable legislation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of indoor unit for exact values).
FXZA15~50A2VEB
VRV system air conditioner
18 | Electrical installation
a
b

18.2 To connect the electrical wiring to the indoor unit

NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
It is important to keep the power supply and the transmission wiring separated
from each other. In order to avoid any electrical interference the distance between
both wirings should ALWAYS be at least 50mm.
NOTICE
Be sure to keep the power line and transmission line apart from each other. Transmission wiring and power supply wiring may cross, but may NOT run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame, connect the cable to
the terminal block (symbols P1, P2) and fix the cable with a tie wrap.
3 Transmission cable: Route the cable through the frame, connect the cable to
the terminal block (make sure the symbols F1, F2 match with the symbols on the outdoor unit), and fix the cable with a tie wrap.
4 Power supply cable: Route the cable through the frame and connect the
cable to the terminal block (L, N, earth).
a Circuit breaker
b Residual current device
5 Divide the small sealing (accessory) and wrap it around the cables to prevent
water from entering the unit.
6 Seal all gaps with a sealing material (field supply) to prevent small animals
from entering the system.
7 Reattach the service cover.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
65
18 | Electrical installation
L
N
a
b
b
10~15
70~90
10~20
10~15
70~90
7
d
d
e
c
P1P2 F1 F2
LN LN LN
IN/D OUT/D
F
1 F2 F1 F2
Control box
P1P
2
P1P
2
P1P
2
P1P
2
P1P
2
F1F2T1T
2
P1P2F1F2T1T
2
P1P2F1F2T1T
2
P1P2F1F2T1T
2
N L
a
d
c
b
LN
N L N L N L
a Service cover (with wiring diagram) b Opening for cables
c Connection of power supply d Tie wrap e Connection of user interface and transmission cable
Complete system example
1 user interface controls 1 indoor unit.
a Outdoor unit b Indoor unit
c User interface d Most downstream indoor unit
NOTICE
Group control connection is NOT allowed.
CAUTION
Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
Installer and user reference guide
66
FXZA15~50A2VEB
VRV system air conditioner

19 Commissioning

In this chapter

19.1 Overview: Commissioning ...................................................................................................................................................... 67
19.2 Precautions when commissioning.......................................................................................................................................... 67
19.3 Checklist before commissioning............................................................................................................................................. 68
19.4 To perform a test run ............................................................................................................................................................. 68

19.1 Overview: Commissioning

This chapter describes what you have to do and know to commission the system after it is installed.
Typical workflow
Commissioning typically consists of the following stages:
1 Checking the "Checklist before commissioning". 2 Performing a test run for the system.
19 | Commissioning

19.2 Precautions when commissioning

INFORMATION
During the first running period of the unit, the required power may be higher than stated on the nameplate of the unit. This phenomenon is caused by the compressor, that needs a continuous run time of 50hours before reaching smooth operation and stable power consumption.
NOTICE
Before starting up the system, the unit MUST be energised for at least 6hours to avoid compressor breakdown during startup.
NOTICE
ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT, burning of the compressor might be the result.
NOTICE
ALWAYS complete the refrigerant piping of the unit before operating. If NOT, the compressor will break.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
NOTICE
Cooling operation mode. Perform the test run in cooling operation mode so that
stop valves failing to open can be detected. Even if the user interface was set to heating operation mode, the unit will run in cooling operation mode during 2‑3 minutes (although the user interface will display the heating icon), and then automatically switch to heating operation mode.
Installer and user reference guide
67
19 | Commissioning

19.3 Checklist before commissioning

WARNING
If the panels on the indoor units are not installed yet, make sure to power OFF the system after finishing the test run. To do so, turn OFF operation via the user interface. Do NOT stop operation by turning OFF the circuit breakers.
After the installation of the unit, first check the items listed below. Once all checks are fulfilled, the unit must be closed. Power-up the unit after it is closed.
You read the complete installation and operation instructions, as described in the installer and user reference guide.
The indoor unit is properly mounted.
The outdoor unit is properly mounted.
Make sure drain piping is properly installed, insulated and drainage flows smoothly. Check for water leaks.
Possible consequence: Condensate water might drip.
The refrigerant pipes (gas and liquid) are installed correctly and thermally insulated.
There are NO refrigerant leaks.
There are NO missing phases or reversed phases.
The system is properly earthed and the earth terminals are tightened.
The fuses or locally installed protection devices are installed according to this document, and have NOT been bypassed.
The power supply voltage matches the voltage on the identification label of the unit.
There are NO loose connections or damaged electrical components in the switchbox.
There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units.
The stop valves (gas and liquid) on the outdoor unit are fully open.

19.4 To perform a test run

INFORMATION
Perform the test run according to the instructions in the outdoor unit manual.The test run is only completed if there is no malfunction code displayed on the
See the service manual for the complete list of error codes and a detailed
user interface or the outdoor unit 7‑segment display.
troubleshooting guideline for each error.
Installer and user reference guide
68
NOTICE
Do NOT interrupt the test run.
FXZA15~50A2VEB
VRV system air conditioner

20 Configuration

20.1 Field setting

Make the following field settings so that they correspond with the actual installation setup and with the needs of the user:
Ceiling height
Airflow direction range
Air volume when thermostat control is OFF
Time to clean air filter
Thermostat sensor selection
Thermostat differential changeover (if remote sensor is used)
Differential automatic changeover
Auto-restart after power failure
20 | Configuration
INFORMATION
The connection of optional accessories to the indoor unit might cause changes to
some field settings. For more information, see the installation manual of the optional accessory.
Following setting are only applicable when using the BRC1H52* user interface.
When using any other user interface, see the installation manual or service manual of the user interface.
Setting: Ceiling height
This setting must correspond with the actual distance to the floor, capacity class and air flow directions.
For 3-way and 2-way airflows (which require an optional blocking pad kit), see
the installation manual of the optional blocking pad kit.
For 4-way airflow, use the table below.
If the distance to the floor is (m) Then
(1)
M SW
≤2.7 13 (23) 0 01
2.7<x≤3.0 02
3.0<x≤3.5 03
Setting: Airflow direction range
This setting must correspond with the needs of the user.
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
SW: Setting number
—: Value number
: Default
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
69
20 | Configuration
If you want set the airflow direction range to… Then
(1)
M SW
Upper 13 (23) 4 01
Medium 02
Lower 03
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It determines the fan speed of the indoor unit during thermostat OFF condition.
1 If you have set the fan to operate, set the air volume speed:
If you want… Then
(1)
M SW
During thermostat OFF at cooling operation
During thermostat OFF at heating operation
(a)
Only use in combination with optional remote sensor or when setting M 10 (20), SW 2, — 3 is used.
(2)
LL
Setup volume
(a)
OFF
Monitoring 1
Monitoring 2
(2)
LL
Setup volume
(a)
OFF
Monitoring 1
Monitoring 2
12 (22) 6 01
(2)
02
03
(2)
(2)
04
05
12 (22) 3 01
(2)
02
03
(2)
(2)
04
05
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room. It determines the interval at which "Time to clean filter" notification is displayed on the user interface.
If you want an interval of…
(air contamination)
M SW
Then
(1)
±2500h (light) 10 (20) 0 01
±1250h (heavy) 02
Notification ON 3 01
Notification OFF 02
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
SW: Setting number
—: Value number
: Default
(2)
Fan speed:
LL: Low fan speed (set during thermostat OFF)
L: Low fan speed (set by the user interface)
Setup volume: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
Monitoring 1, 2: The fan is OFF, but runs for a short time every 6minutes to detect the room temperature by LL (Monitoring 1) or by L (Monitoring 2).
Installer and user reference guide
70
FXZA15~50A2VEB
VRV system air conditioner
20 | Configuration
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller thermostat sensor is used.
When the remote controller thermostat sensor
is…
M SW
Used in combination with indoor unit thermistor 10 (20) 2 01
Not used (indoor unit thermistor only) 02
Used exclusively 03
Setting: Thermostat differential changeover (if remote sensor is used)
If the system contains a remote sensor, set the increase/decrease increments.
If you want to change increments to… Then
M SW
1°C 12 (22) 2 01
0.5°C 02
Setting: Differential for automatic changeover
Then
(1)
(1)
Set temperature difference between cooling setpoint and heating setpoint in automatic mode (availability depends on the system type). Differential is cooling setpoint minus heating setpoint.
If you want to set… Then
(1)
Example
M SW
0°C 12 (22) 4 01 cooling 24°C/heating 24°C
1°C 02 cooling 24°C/heating 23°C
2°C 03 cooling 24°C/heating 22°C
3°C 04 cooling 24°C/heating 21°C
4°C 05 cooling 24°C/heating 20°C
5°C 06 cooling 24°C/heating 19°C
6°C 07 cooling 24°C/heating 18°C
7°C 08 cooling 24°C/heating 17°C
Setting: Auto-restart after power failure
Depending on the needs of the user, you may disable/enable the automatic restart after a power failure.
If you want auto-restart after power failure… Then
(1)
M SW
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
SW: Setting number
—: Value number
: Default
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Disabled 12 (22) 5 01
Enabled 02
Installer and user reference guide
71
21 | Hand-over to the user

21 Hand-over to the user

Once the test run is finished and the unit operates properly, please make sure the following is clear for the user:
Make sure that the user has the printed documentation and ask him/her to keep
Explain the user how to properly operate the system and what to do in case of
Show the user what to do for the maintenance of the unit.
it for future reference. Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual.
problems.
Installer and user reference guide
72
FXZA15~50A2VEB
VRV system air conditioner

22 Troubleshooting

22.1 Solving problems based on error codes

If the unit runs into a problem, the user interface displays an error code. It is important to understand the problem and to take measures before resetting an error code. This should be done by a licensed installer or by your local dealer.
This chapter gives you an overview of most possible error codes and their descriptions as they appear on the user interface.
INFORMATION
See the service manual for:
The complete list of error codesA more detailed troubleshooting guideline for each error

22.1.1 Error codes: Overview

22 | Troubleshooting
In case other error codes appear, contact your dealer.
Code Description
The R32 sensor has detected a refrigerant leak
/ Safety system error (leak detection)
R32 sensor malfunction
R32 sensor end of lifetime
6 months before the R32 sensor end of lifetime
Malfunction of indoor unit PCB
Drain level control system abnormality
Malfunction of freezing protection
High pressure control in heating, freeze-up protection control in cooling
Malfunction of fan motor
Malfunction of swing flap motor
Malfunction of power supply or AC input overcurrent
Malfunction of electronic expansion valve
Malfunction of a humidifier system
Malfunction of dust collector of air cleaner
Malfunction of capacity setting (Indoor unit PCB)
Failure of transmission (between indoor unit PCB and sub PCB)
Malfunction of liquid pipe thermistor for heat exchanger
Malfunction of gas pipe thermistor for heat exchanger
Malfunction of gas pipe thermistor for heat exchanger
Malfunction of suction air thermistor
Malfunction of discharge air thermistor
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
73
22 | Troubleshooting
Code Description
Room temperature thermistor in remote controller abnormality
Installer and user reference guide
74
FXZA15~50A2VEB
VRV system air conditioner

23 Disposal

23 | Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
75
24 | Technical data
,
A
INDOOR
OUTDOOR

24 Technical data

24.1 Wiring diagram

24.1.1 Unified wiring diagram legend

A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by "*" in the part code.
Symbol Meaning Symbol Meaning
Circuit breaker Protective earth
Connection Protective earth (screw)
Connector
Rectifier
Earth Relay connector
Field wiring Short-circuit connector
Fuse Terminal
Indoor unit Terminal strip
Outdoor unit Wire clamp
Residual current device
Symbol Colour Symbol Colour
BLK Black ORG Orange
BLU Blue PNK Pink
BRN Brown PRP, PPL Purple
GRN Green RED Red
GRY Grey WHT White
Installer and user reference guide
76
YLW Yellow
Symbol Meaning
A*P Printed circuit board
BS* Pushbutton ON/OFF, operation switch
BZ, H*O Buzzer
C* Capacitor
FXZA15~50A2VEB
VRV system air conditioner
Symbol Meaning
24 | Technical data
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*,
Connection, connector MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NE
D*, V*D Diode
DB* Diode bridge
DS* DIP switch
E*H Heater
FU*, F*U, (for characteristics, refer to
Fuse PCB inside your unit)
FG* Connector (frame ground)
H* Harness
H*P, LED*, V*L Pilot lamp, light emitting diode
HAP Light emitting diode (service monitor
green)
HIGH VOLTAGE High voltage
IES Intelligent eye sensor
IPM* Intelligent power module
K*R, KCR, KFR, KHuR, K*M Magnetic relay
L Live
L* Coil
L*R Reactor
M* Stepper motor
M*C Compressor motor
M*F Fan motor
M*P Drain pump motor
M*S Swing motor
MR*, MRCW*, MRM*, MRN* Magnetic relay
N Neutral
n=*, N=* Number of passes through ferrite core
PAM Pulse-amplitude modulation
PCB* Printed circuit board
PM* Power module
PS Switching power supply
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
PTC* PTC thermistor
Q* Insulated gate bipolar transistor (IGBT )
Q*C Circuit breaker
Q*DI, KLM Earth leak circuit breaker
Q*L Overload protector
Installer and user reference guide
77
24 | Technical data
Symbol Meaning
Q*M Thermo switch
Q*R Residual current device
R* Resistor
R*T Thermistor
RC Receiver
S*C Limit switch
S*L Float switch
S*NG Refrigerant leak detector
S*NPH Pressure sensor (high)
S*NPL Pressure sensor (low)
S*PH, HPS* Pressure switch (high)
S*PL Pressure switch (low)
S*T Thermostat
S*RH Humidity sensor
S*W, SW* Operation switch
SA*, F1S Surge arrester
SR*, WLU Signal receiver
SS* Selector switch
SHEET METAL Terminal strip fixed plate
T*R Transformer
TC, TRC Transmitter
V*, R*V Varistor
V*R Diode bridge, Insulated-gate bipolar
transistor (IGBT) power module
WRC Wireless remote controller
X* Terminal
X*M Terminal strip (block)
Y*E Electronic expansion valve coil
Y*R, Y*S Reversing solenoid valve coil
Z*C Ferrite core
Installer and user reference guide
78
ZF, Z*F Noise filter
FXZA15~50A2VEB
VRV system air conditioner

25 Glossary

Dealer
Authorised installer
User
Applicable legislation
Service company
Installation manual
25 | Glossary
Sales distributor for the product.
Technical skilled person who is qualified to install the product.
Person who is owner of the product and/or operates the product.
All international, European, national and local directives, laws, regulations and/or codes that are relevant and applicable for a certain product or domain.
Qualified company which can perform or coordinate the required service to the product.
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining how to operate it.
Accessories
Labels, manuals, information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Field supply
Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
FXZA15~50A2VEB VRV system air conditioner 4P599623-1B – 2020.10
Installer and user reference guide
79
Verantwortung für Energie und Umwelt
Copyright 2020 Daikin
4P599623-1B 2020.10
Loading...