Daikin FXVQ125MY1 user guide manual

MODELS
Floor standing duct type
FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY1 FXVQ500MY16
INSTALLATION MANUAL
SYSTEM Air Conditioners
FX VQ125MY1 FXVQ200MY1 F XVQ 250MY1 FX VQ4 00 MY1 FXVQ500MY1 FXVQ 50 0MY16
VRV System
air conditioner
Installation
manual

CONTENTS

1. SAFET Y PRECAUTIONS ................................................. 1
2. BEFORE INSTALLATION ................................................. 2
3. CARRY-IN METHOD ........................................................ 3
4. INSTALLATION SITE ....................................................... 3
5. CAUTION AT INSTALLATION .......................................... 4
6. REFRIGERANT PIPING ................................................... 4
7. DRAIN PIPING ................................................................. 6
8. ELECTRIC WIRING.......................................................... 6
9.
FIELD SETTING AND CONTROL WIRING ......................... 9
10.
TRIAL OPERATION .............................................................10

1. SAFETY PRECAUTIONS

Be sure to follow this “SAFETY PRECAUTIONS”. This product comes under the term “appliances not accessible to the general public”.
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
This manual classies the precautions into WARNINGS and
CAUTIONS. Be sure to follow all the precautions below: They are all important for ensuring safety.
WARNING ......... Indicates a potentially hazardous
situation which, if not avoided, could result in death or serious injury.
CAUTION .......... Indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
After the installation is completed, test the air conditioner and check if the air conditioner operates properly. Give the user adequate instructions concerning the use and cleaning of the indoor unit according to the Operation Manual. Ask the user to keep this manual and the Operation Manual together in a handy place for future reference.
WARNING
• Ask your local dealer or qualied personnel to carry out
installation work. Improper installation may result in water leakage, electric
shocks or a re.
Perform installation work in accordance with this installation
manual. Improper installation may result in water leakage, electric
shocks or a re.
Consult your local dealer regarding what to do in case of
refrigerant leakage. When the air conditioner is installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage. Otherwise, this may lead to an accident due to oxygen
deciency.
• Be sure to use only the specied parts and accessories for
installation work.
Failure to use the specied parts may result in the air
conditioner falling down, water leakage, electric shocks, a
re, etc.
Install the air conditioner on a foundation that can
withstand its mass. It may lead to vibration of indoor units and cause unpleasant chattering noise.
• Carry out the specied installation work in consideration of
strong winds, typhoons, or earthquakes. Improper installation may result in an accident such as air conditioner falling.
Make certain that all electrical work is carried out by qualied personnel according to the applicable legislation
(note 1) and this installation manual, using a separate circuit. In addition, even if the wiring is short, make sure to use
a wiring that has sufcient length and never connect additional wiring to make the length sufcient. Insufcient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a re.
(note 1) applicable legislation means “All international,
national and local directives, laws, regulations and/or codes which are relevant and applicable for a certain product or domain”.
Earth the air conditioner. Do not connect the earth wiring to gas or water piping, lightning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a re.
Be sure to install an earth leakage circuit breaker. Failure to do so may cause electric shocks and a re.
Disconnect the power supply before touching the electric
components. If you touch the live part, you may get an electric shocks.
• Make sure that all wiring is secure, using the specied
wiring and ensuring that external forces do not act on the terminal connections or wiring.
Incomplete connection or xing may cause an overheat or a re.
When wiring between the indoor and outdoor units, and
wiring the power supply, form the wiring orderly so that the control box lid can be securely fastened. If the control box lid is not in place, overheat of the
terminals, electric shocks or a re may be caused.
If refrigerant gas leaks during installation work, ventilate
the area immediately. Toxic gas may be produced if refrigerant gas comes into
contact with a re.
After completing the installation work, check to make sure
that there is no leakage of refrigerant gas. Toxic gas may be produced if refrigerant gas leaks into the
room and comes into contact with a source of a re, such
as a fan heater, stove or cooker.
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
CAUTION
Install drain piping according to this installation manual to ensure good drainage, and insulate the piping to prevent condensation. Improper drain piping may cause water leakage, make the furniture get wet.
1 English
Install the air conditioner, power supply wiring, remote controller wiring and transmission wiring at least 1 meter away from televisions or radios to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may
not be sufcient to eliminate the noise.)
Do not install the air conditioner in places such as the
following:
1. Where there is mist of oil, oil spray or vapour for
example a kitchen. Resin parts may deteriorate, and cause them to fall out or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is
produced. Corrosion of copper pipings or brazed parts may cause the refrigerant to leak.
3. Where there is machinery which emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
4. Where ammable gases may leak, where carbon bre
or ignitable dust is suspended in the air or where volatile
ammables, such as thinner or gasoline, are handled.
If the gas should leak and remained around the air conditioner, it may cause ignition.

2. BEFORE I N STALLATI O N

Make sure to use the R410A refrigerant before the installation work. (Otherwise, the unit can not operate normally.)
For installation of outdoor unit, refer to the installation manual attached to the outdoor unit.
Do not throw away the accessories required for installation until the installation is nished.
2-1 PRECAUTION
Be sure to instruct the customer how to properly operate the system (particularly the cleaning of air lter, operation
method, temperature adjusting method) showing the attached operation manual to the person.
Do not install the unit where the atmosphere is salty such as near the seaside, where the voltage frequently
uctuates or in a vehicle or a boat.
2-2 ACCESSORIES
Check if the following accessories are included in the indoor unit.
Insulation
Name Connection pipings
1 pc.
Quantity
Shape
Location Partition plate
(125-250 type)
(Gas
piping)
For each 1 pc.
(400 · 500 type)
(Liquid piping)
(Gas
piping)
Drain
plug cap
for Drain
plug
1 pc. 1 pc. 3 pcs. 1 pc.
Clamp
Hanging
bolt for fan
motor
(only
50 0MY16)
Name Bolts (for anges)
Quantity
Shape
Location
Name Nuts (for anges)
Quantity
Shape
Location
14 pcs.
(125 · 200 type)
Partition plate (However, 2 bolts and 2 nuts are used for
ange temporary xing.)
14 pcs.
(125 · 200 type)
Partition plate (However, 2 bolts and 2 nuts
are used for ange temporary xing.)
30 pcs.
(250 type)
30 pcs.
(250 type)
18 pcs.
(40 0 type)
M8
18 pcs.
(40 0 type)
M8×20
(500 type)
36 pcs.
36 pcs.
(500 type)
[Others]
Operation manual Installation
manual
Stay for control panel
2-3 CARRY OUT THE WORK GIVING
CAUTION TO THE FOLLOWING ITEMS AND AFTER THE WORK IS COMPLETED CHECK THESE AGAIN.
1. Items to be checked after the installation work is completed
Items to be checked In case of defective
Are the air conditioner rigidly
xed?
Are the installation work of the
air conditioner complete?
Have you carried out a leakage test with the test
pressure specied in the
outdoor unit installation
manual?
Is the insulation of refrigerant piping and drain piping
completely carried out?
Does the drain ow out smoothly?
Is the power supply voltage identical to that stated in the manufacturer’s label on the air
conditioner?
Are you sure that there is no wrong wiring nor piping or no
loose wiring?
Is earthing completed? Danger in case of leakage
Are the sizes of electric wiring
according to the specication?
Is any of air outlets or inlets of the air conditioner blocked with
obstacles?
(It may lead to capacity drop due to fan speed drop or malfunction of equipment.)
Have you recorded the refrigerant piping length and
the refrigerant charge added?
Make sure to recheck the items of “SAFETY PRECAUTIONS”.
Drop · vibration · noise
Does not operate · burnout
Does not cool / Does not heat
Water leakage
Water leakage
Does not operate · burnout
Does not operate · burnout
Does not operate · burnout
Does not cool / Does not heat
Refrigerant charge amount is not clear
Check
column
2English
2. Items to be checked at delivery
Items to be checked
Have you carried out eld setting? (if necessary)
Are the control box lid, the air lter and the suction grille attached?
Does the cool air discharge during the cooling operation and the warm air discharge during heating
operation?
Have you explained how to operate the air conditioner
showing the operation manual to the customer?
Have you explained the description of cooling and
heating given in the operation manual to the customer?
Have you handed the operation manual and the
installation manual to the customer?
Check
column
Points of the operation explanation
In addition to the general usage, since the items in the operation manual with the
WARNING and CAUTION marks are likely to result in human bodily injuries and property damages, it is necessary not only to explain these items to the customer but also to have the customer read them. It is also necessary to explain the items of “NOT MALFUNCTION OF THE AIR CONDITIONER” to the customer and have the customer read them carefully.

3. CARRY-IN METHOD

Note
Do not throw away the accessories required for installation
until the installation is nished.
Choose the carry-in route of the indoor unit.
When lifting the unit with a crane, use belt sling and
perform lifting the unit as shown in the gure below.
Belt sling
Put a rag or a corrugated
fiberboard to prevent damage of
the suction grille and the control
panel part.

4. INSTALLATION SITE

Note
Do not apply force on the resin parts in case of carrying the indoor unit when and after unpacking.
(1) Select an installation site where the following conditions
are satised and obtain the customer’s approval before
installation.
The foundation is strong enough to support the weight of the unit and the oor is at to prevent vibration and
noise generation.
The place where the cold (warm) air is spread all over the room. (In case of free blow by the plenum chamber)
The place where the condensate can be properly drained.
• The place where there is no possibility of ammable
gas leak.
The place where is not heat affected by other heating equipment.
The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available.
The place where the piping length between indoor unit and outdoor unit is within the allowable limit. (Refer to the installation manual attached to the outdoor unit.)
(2) After installation, remove the shipping brackets attached
to the bottom frame.
(3) Secure the unit to its base using foundation bolts.
4-1 EXAMPLE OF REQUIRED SPACE
• Select a suitable pattern from the gure below according
to local space in view of walkway and ventilation when installing.
(If the given eld space fails to meet the conditions of work in this gure, contact the dealer.)
Piping connection A B
Left side 500 mm 100 mm
Right side 100 m m 500 mm
Make sure to sling over the hanger.
φ15 hole (125 φ17 hole (400 · 500 type
or more
A
900 mm or more
Foundation bolts fixing plate
Indoor unit
<
Front
side
(
4 Portions
>
)
-
250 type
B
) )
100 mm
or more
or more
3 English

5. CAUTION AT INSTALL AT I ON

5-1 HOW TO REPLACE PULLEY
<125-250 type>
(1) Remove the suction grille. (2) Remove the protection net. Then remove the cushioning
material on the protection net. (3) Remove the front panel (upper). (4) Remove the front panel (lower). (5) Put the iron plate, which must be wider than the fan
motor, under the fan motor, and on the heat exchanger
for protection for its n. (Iron plate must be supplied in the
eld.)
(6) Remove the terminal for the fan motor lead wire from the
magnet switch. (7) Pull out the fan motor lead wire to the fan housing parts,
and let it out of the unit from the opening part on the front
plate (upper). (8) Remove the nuts of the motor base. (9) Remove the belt. Hold the fan motor base rmly when
working so that it may not move suddenly. (10) Slide the fan housing assembly on the iron plate on which
the fan motor is put (the above procedure (5)) frontward
slowly. Work must be conducted by more than 3 persons.
One of them must hold the motor base, and two or more
of them must hold the fan housing. (11) Move the fan housing assembly to the location where can
be worked and replace the pulley. (12) After replacing, follow the above procedure in the reverse
order.
<400 · 500 type>
Follow the above procedure (1)-(4), (6), (7), (10), (11), (12) in th e order.
(2)
(3)
Front panel (
)
upper
(1)
Suction grille
(4) Front panel
(
)
lower
Fan motor lead wire
5-2 PARALLELISM OF PULLEY
Adjust the parallelism of the pulley between the fan and
the motor so as to meet the standard as below.
Fan pulley
Parallelism Less than 10
Protection net
(5)
Iron plate (
Field supply
(10)
(7)
(6)
K
K
K
K
K
K (arc-m inute) Note
)
Motor pulley
Equivalent to 3 mm displacement per 1 m
(8)
(9)
Fan motor
Heat exchanger
5-3 TENSION OF V BELT
• Tension of a V belt must meet the deection load (W) as
shown.
Calculate the required deection length (L) by the equation
(1), its tolerance must be within the range as below.
W
C
L
L= 0.016 × C (mm) C : Distance between the shafts of the pulley (mm
Types of V belt Deection load W (N)
A type 13.7-20.6
B type 22.6-34.3
Deflection load
(1)
)
Note
It is recommended to check the tension as above after 24­28 hours of the operation. When the new belts are used, it is preferable to adjust to
about 1.3 times the maximum value of Deection load (W).

6. REFRIGERANT PIPING

For the refrigerant piping of the outdoor unit, refer to the installation manual attached to the outdoor unit.
Make sure to use R410A as refrigerant before the installation work. (Otherwise, the unit can not operate normally)
Make sure to insulate the piping on both the liquid side and the gas side. Otherwise, water leakage may be caused.
Use a heat insulating material sufciently resistant to
120 °C. Reinforce the refrigerant piping according to the installation environment. Otherwise, condensation may form on the surface of the insulation.
CAUTION
This unit is for using R410A only. Make sure to follow the items as shown in below when working.
• Use the pipe cutter and the aring tool that are
exclusively used for R410A.
• At are connection, apply ETHER oil or ESTER oil to the are section.
Protect the piping by a pinch or taping to prevent invasion of contamination, moisture and dusts into the piping.
6-1 MATERIAL OF PIPING
Use the copper tube according to the following table.
Indoor unit
capacity
125 t yp e
200 type
250 type
400 type
500 type
Piping on gas side Piping on liquid side
φ15.9 × t1.0 mm φ9.5 × t0.8 mm
φ19.1 × t1.0 mm φ9.5 × t0.8 mm
φ22.2 × t1.0 mm φ9.5 × t0.8 mm
φ28.6 × t1.0 mm φ12.7 × t0.8 mm
φ28.6 × t1.0 mm φ15.9 × t1.0 mm
Piping size
4English
6-2 HOW TO WORK THE REFRIGERANT
PIPING
Remove the pinched pipings brazed to the end of the internal piping. Braze and connect the standard accessory piping.
Do not directly
flame the pipe fixing plate.
Do not directly
flame the solenoid valve and motor operated valve.
Do not directly flame the drain pan and thermistor.
Air filter must be removed.
Connection pipings
Remove the pinched pipings.
6-3 PIPING CONNECTION
CAUTION
Do not use anti-oxidants when brazing the piping joints. Residue can clog pipings and break equipment.
Be sure to perform a nitrogen blow when brazing Brazing without performing nitrogen replacement or releasing nitrogen into the piping will create large
quantities of oxidized lm on the inside of the pipings,
( )
adversely affecting valves and compressors in the refrigerating system and preventing normal operation.
Note
For nitrogen replacement, refer to the installation work
manual. (Contact the dealer.)
• When brazing pipes while owing nitrogen, set the nitrogen
pressure to 0.02 MPa or less using a pressure reducing valve (to the extent that your cheeks feel breeze).
• Do not use a ux when brazing the refrigerant system. Use
phosphor copper brazing ( /795: ISO 3677
) which does not require ux. Using a chorine ux may cause the pipes to corrode, and if it contains uoride, it may cause the refrigerant
lubricant to deteriorate, adversely affecting the
( )
refrigerant piping system.
Refrigerant piping
CAUTION
Do not let any refrigerant other than R410A enter the refrigerant system. Ventilate if the refrigerant gas leaks during work.
BCup-2: JIS Z 3264/B-Cu93P-710
Pressure reducing valve
Location to be brazed
Nitrogen
Taping
Manual valve
Nitrogen
6-4 PROCESSING METHOD OF CONNECTION
PIPING
See the following table for the Processing connection piping.
• For right side piping, replace the partition bush xed on the right side panel with the bush for hole xed on the left side
panel.
Piping on liquid side (125-250 type)
Piping on liquid side (400 · 500 type)
Piping on gas side (125 -5 00 type)
Left side piping connection
Pass the piping from the hole on the left side into the unit, conduct
sleeve are process
and brazed connection.
Note
Inside dia. of Flare (
See the table for
flare part dimensions
Connect the accessory pipes and bring them outside of the unit.
Right side piping connection
Pass the piping from the hole on the right side into the unit,
conduct sleeve are
process and brazed connection.
)
Inside dia. of Flare (
See the table for flare
)
part dimensions
Modify the accessory left side piping and use it for the right side.
For left side
Cut the piping
Connection side
( )
inside the unit
Flare the pipe end or
use the fitting and connect
the piping by brazing.
)
Note
)
For right side
6-5 THE TABLE FOR FLARE PART
DIMENSIONS
Refer to the below table for are part dimensions
(Unit: mm)
Piping
Indoor
unit
capacity
125 t yp e
200 type
250 type
size
d0 d1
φ9.5
×t0.8 or
more
Inside dia. of
are
Tolerance
+0.1
9.64
Note
Braze by socket if sleeve are process cannot be conducted.
CAUTION
Thermal insulation of the eld piping must be carried out
including the piping connection parts. Otherwise, it may cause heat injury by condensation or connecting to the exposed piping.
0
Allowance of inserting part
L
Tolerance
+1. 5
7
0
Bend
radius
R18
Flare shape
C1220T
φd1
φd0
L
Secure the piping so that it does not touch the wiring.
Insulation of pipes must be perfectly carried out without
leaving any clearance to avoid condensation.
When connecting liquid and gas connection pipings, insulate all the internal pipings with eld supplied insulation
material for refrigerant pipings. (See following sketch.)
5 English
<125-250 type>
More than 40 mm
Downward inclination 1/100 or more
Unit bottom line
Indoor unit
Gas piping
Liquid piping
Connection piping (Accessory)
More than 40 mm
Refrigerant piping (Field supply)
Refrigerant piping insulation (Field supply)
<400 · 500 type>
More than 40 mm
Gas piping
Connection piping (Accessory)
Liquid piping
More than 40 mm
Refrigerant piping insulation (Field supply)

7. DRAIN PIPING

7-1 INSTALL DRAIN PIPING
Install drain piping is order to ensure proper drainage and insulate piping in order to prevent condensation.
Keep the piping length as short as possible and slope the pipe with a gradient of 1/100 or more. Do not create any air accumulated pocket in the piping.
Use the pipe size equivalent or larger to the pipe connection size of the unit.
The drain connection is available from both (left and right) sides.
For the right side connection, change the drain plug from right to left.
For piping goes through the indoor, make sure to insulate the indoor drain socket to the end of socket.
When connecting the drain piping, insulate the drain plug on the opposite side of drain piping connection completely with the attached insulation.
Always make a drain trap at the drain outlet.
Check
• After completion of drain piping, let water ow into the
drain pan and check for drain and water leakage from the piping connection area.
Drain plug cap (accessories)
Insulation for drain plug (accessories)
The end of the drain port must be always kept in the
water to prevent backflow of
odor from the sewage.
Remove the released paper, and make sure to label on the unit.
Drain plug
50 mm
or more
100 mm
or more
Drain trap
(for Left side connection)
Drain trap
make a drain trap
Drain piping
CAUTION
The connection of the drain piping Do not directly connect the drain piping to sewerage, which odor may smell like ammonia. Sewerage may contain it, which may pass through the drain piping, and result in corrosion of the indoor unit heat exchanger.

8. ELECTRIC WIRING

CAUTION
Install earth leakage circuit breaker. It is our obligation to mount earth leakage circuit breaker in order to prevent accidents such as electric
shocks and/or re.
• All eld wiring and components must be installed by a
licensed electrician and must comply with relevant local and national regulations.
Use copper conductors only.
Be sure to install an earth leakage breaker.
(Failure to install an earth leakage breaker may result in
electric shocks, or re.)
Always ground wires. (In accordance with national
regulations of the pertinent country.)
Do not connect the ground wire to gas pipe, sewage pipe, lightning rods, or telephone ground wires.
• Gas pipe: can explode or catch re if there is a gas
leak.
Sewage pipes: no grounding effect is possible if hard plastic piping is used.
Telephone ground wires and lighting rods: dangerous when struck by lighting due to abnormal rise in electrical potential in the grounding.
• The eld wiring must be carried out in accordance with the
wiring diagrams and the instructions given below.
If the fan rotates reversely, change the connection of two power supply wires out of three.
For connection to the terminal block, use ring type crimp style terminal suitable for the wire size.
Do not close the branch switch and overcurrent circuit breaker until all the works are completed.
6English
<Method of wiring for the wiring between indoor unit and outdoor unit, the earth wiring and the power supply wiring>
(1) Remove the front panel (lower). (2) Fix the each wire on the control box with the attached
clamp.
(3) For wiring specications, refer to the [DETAILS OF
STANDARD DEVICES].
CAUTION
Apply putty or insulation material (Field supply) without any clearance on the wiring intake section to prevent small animals from entering the unit. (If small animals such as insects enter the inside of the unit, it may cause short circuit in the control box.)
Connect the wire securely using designated wire and x it
with attached clamp without applying external pressure on the terminal parts. Make sure the wiring and the control box lid do not stick up
above the structure, and close the control box lid rmly.
8-1 REMOVE THE FRONT PANEL (LOWER)
When removing the front panel (lower), there is the control box.
<400 · 500 type>
Wiring from right side
Earth terminal for
Terminal block for the wiring between indoor unit and outdoor unit
Control box
Earth terminal
shield wire
Terminal block for power supply wiring
Pass the attached clamp through the resin clamp, and bundle each
wiring in one and fix them.
Wiring from left side
Terminal block for the wiring between indoor unit and outdoor unit
Pass the attached clamp through the resin clamp, and bundle each
wiring in one and fix them.
Earth terminal for shield wire
Earth terminal
Terminal block for power supply wiring
8-3 EXAMPLE OF WIRING
The control panel is the standard built-in.
Ex1. When using in pairs
Power supply
Outdoor unit
Control box
OUT-OUT
IN-OUT
F1 F2 F1 F2
Control box
Front panel (lower
)
Screw
Front panel (
)
lower
Remove the screw attached front panel (lower).
8-2 EXTERNAL WIRING METHOD
<125-250 type>
Wiring from right side
Terminal block for power supply wiring
Control box
Earth terminal
Wiring from left side
Pass the attached clamp through the resin clamp, and bundle each
wiring in one and fix them.
Terminal block for the wiring between indoor unit and outdoor unit
Pass the attached clamp through the resin clamp, and bundle each
wiring in one and fix them.
Earth terminal for shield wire
Terminal block for power supply wiring
Terminal block for the wiring between indoor unit and outdoor unit
Earth terminal
Control box
Earth terminal for shield wire
Branch switch Overcurrent circuit breaker
The wiring between indoor unit and outdoor unit
Never to connect high-voltage electricity such as power supply cables.
Prohibited
Control panel
P1
P2
or
or
L1
L2 L3
F1F2 T1 T2
N
P
N
Indoor unit A
Earth
Ex2. For multiple indoor units
Power supply
Branch switch Overcurrent circuit breaker
Earth
Outdoor unit
Control box
IN-OUT
OUT-OUT
F1 F2 F1 F2
The wiring between indoor unit and outdoor unit
Never to connect high-voltage electricity such as
Prohibited
power supply cables.
The wiring between indoor
F1F2T1T
unit and indoor unit
2
Earth Earth
Control panel
P1
P2
or
or
L2L3 NL1 L2L3 NL1 L2L3 NL1
P
N
Indoor unit A
Control panel
P1
P2
F1F2T1T
or
or
P
N
Indoor unit B
2
Control panel
P1
P2
F1F2T1T
or
or
P
N
Final indoor unit
2
CAUTION
Do not have low-voltage wires (wiring between units) and other high-voltage run through the same locations, and there must be min. 50 mm distance between wires outside of the unit. Or it may cause a malfunction or a breakdown of the unit by receiving electrical noise (external noise).
7 English
Ex3. For group control
Power supply
Outdoor unit
Control box
OUT-OUTIN-OUT
F1 F2 F1 F2
Branch switch Overcurrent circuit breaker
L2L3 NL1 L2L3 NL1 L2L3 NL1
Indoor unit A
Earth
The wiring between indoor unit and outdoor unit
Never to connect high-voltage electricity
Prohibited
such as power supply cables.
Control panel
P2
P1
F1F2T1T
or
or
N
P
2
The wiring between indoor unit and indoor unit
Earth
Indoor unit B
P2
P2
P1
F1F2T1T
or
or
2
N
P
Earth
P1
F1F2T1T
or
or
2
N
P
Final indoor unit
Note
1. It is not necessary to set the indoor unit address for group control. (The setting is made automatically when the power supply is turned on.)
2. Make sure to disconnect the control panel wiring of the units over the second one.
3. In this case, all indoor units within the group are controlled by the control panel for the group control.
Ex4. When including BS unit
Prohibited
Power supply
Branch switch Overcurrent circuit breaker
L2L3 NL1
Earth
Outdoor unit
Control box
F1 F2 F1 F2
*Control panel
P2
P1
or
or
N
P
Indoor unit A
OUT-OUTIN-OUT
The wiring between outdoor unit and BS unit
F1F2T1T
2
Never to connect high-voltage electricity such as power supply cables.
BS unit
Control box
IndoorOutdoor
F1 F2 F1 F2
The wiring between indoor unit and BS unit
Never to connect high-voltage electricity
Prohibited
such as power supply cables.
8-4 PRECAUTIONS WHEN LAYING POWER
WIRING
CAUTION FOR WIRING
For connection to the terminal block, use ring type crimp style terminals with insulation sleeve or insulate the wirings properly.
Insulation sleeve
Ring type crimp style terminal
Fig. 1
Connect the terminal as shown in Fig. 2.
• Do not carry out soldering nish when stranded wires are
used. (Otherwise, the loosening of wires may result in abnormal heat radiation.)
Wiring
Use wires the same in size (if the air conditioner is in simultaneous multi operation)
Fig. 2
(Abnormal heating may occur if the wirings are not tightened securely.)
• Use the required wirings, connect them securely and x
these wirings securely so that external force may not apply to the terminals.
Use a proper screw driver for tightening the terminal screws. If an improper screw driver is used, it may damage the screw head and a proper tightening cannot be carried out.
If a terminal is over tightened, it may be damaged. Refer to the table shown below for tightening torque of terminals.
Table 1
Tightening torque (N·m)
Terminal block for remote controller and transmission wirings
0.88 ± 0.08
Terminal for power supply 1.47 ± 0.14
Earth terminal 3.55 ± 0.53
• Do not carry out soldering nish when stranded wirings are
used.
WARNING
When wiring, form the wirings orderly so that the control box lid can be securely fastened. If the control box lid is not in place, the wirings may come out or be sandwiched
by the box and the lid and cause electric shocks or a re.
8-5 DETAILS OF STANDARD DEVICES
Refer to the installation manual attached to the outdoor unit for the details of the wire gauge of the power supply to the outdoor unit, the earth leakage breaker, the circuit breaker capacity and wiring.
• Use only the wiring devices specied in the following table
for the wiring between indoor unit and outdoor unit.
Branch off the exclusive lines for power supply to the indoor unit according to the following specication.
1. Electrical characteristics
Indoor units Power supply Fan motor
380­415V
Voltage
range
Max. 456V
Min. 342V
MCA
TOCA
MFA kW FLA
2.4 2.0 16 0.75 1. 9
Model Hz Volts
FX VQ125MY1
FX VQ2 00 MY1 4.5 3.6 16 1.5 3.6
FX VQ2 50MY1 4.5 3.6 16 1.5 3.6
FX VQ4 00 MY1 9.5 8.0 25 3.7 7. 6
50 Hz
FX VQ5 00 MY1 9.5 8.0 25 3.7 7. 6
FX VQ5 00 MY16 14.5 12.0 40 5.5 11.6
MCA: Min. Circuit Amps (A) MFA: Max. Fuse Amps (A) TOCA: Total Over Current Amp (A) kW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A)
8English
2. Specication for eld supplied fuses and wiring
Power supply wiring Transmission wiring
Model
FXVQ125MY1
FXVQ200MY1
FXVQ250MY1
FXVQ400MY1
FXVQ500MY1
FXVQ500MY16
Field fuses
16A
Wiring Size Wiring Size
H05VV
(Note 1)
Wiring size and length
must comply
with local
codes.
Balanced
type shield
wire
(Note 2)
0.75 − 1.25
mm
2
The lengths of remote controller wiring and transmission wiring are as follows:
Transmission wiring ...................... Total wiring length 2000 m
Outdoor unit - Indoor unit .... Max. 1000 m
Outdoor unit - BS unit .......... Max. 1000 m
BS unit - Indoor unit ............. Max. 1000 m
Indoor unit - Indoor unit ....... Max. 1000 m
Note
1. Shows only in case of protected piping. Use H07RN-F in case of no protection.
2. Use the shield wire. Or it may cause a malfunction or breakdown of the unit by receiving electrical noise (external noise)
9.

FIELD SETTING AND CONTROL WIRING

9-1 FIELD SETTING
Field setting of the following items is required depending
on the installation conditions.
If optional accessories are mounted on the indoor unit, the
indoor unit setting may have to be changed. Refer to the installation manual for each optional accessory.
<Procedure of eld setting>
(1) When in the normal mode, press the “
4 seconds or more, and the FIELD SETTING MODE is
entered. (2) Select the desired MODE NO. with the “ (3) During group control, when setting by each indoor unit
(mode No. 20, 22 and 23 have been selected), press the
” button () and select the INDOOR UNIT NO to be set. (This operation is unnecessary when setting by group.)
(4) Press the “
” upper button () and select FIRST
CODE NO.
(5) Press the “
” lower button () and select the
SECOND CODE NO.
(6) Press the “ ” button () once and the present
settings are SET.
TEST
(7) Press the “
” button () to return to the NORMAL
MODE.
TEST
” button () for
” button ().
UNIT NO.
SECOND CODE NO.
FIRST CODE NO.
UNIT NO.
SETTING
3
4
TEST
1
7
6
5
2
MODE NO.
FIELD SET MODE
Note
1. Setting is carried out in the group mode, however, set the mode number inside the ( ) for individual setting of the
each indoor unit or conrmation after setting.
2. The SECOND CODE NO. is set to in
number when
shipped from the factory.
3. Do not make any settings not given in the table on the below.
4. Not displayed if the indoor unit is not equipped with that function.
5. When returning to the normal mode, “88” may be displayed in the LCD in order for the remote.
<Filter sign setting>
Settings must be made when changing display interval of lter sign according to environment and lter type.
Mode
NO.
(N ote .1)
10
(20)
FIRST CODE
NO.
0
2
3
Description of setting
Filter Contamination-Heavy/ Light (Setting for spacing time of
display time to clean air lter) (Setting for when lter
contamination is heavy, and spacing time of display time to
clean air lter is to be halved)
Remote thermo-controller (Setup is made when using a remote thermo-controller.)
Spacing time of display time to
clean air lter count (Setting for when the lter sign
is not to be used)
SECOND CODE NO.
(Note.2)
01 02
Long life type
Approx. 2500
Light
Hrs.
Use Nonuse
Display
Approx. 1250
Heavy
Hrs.
Do not display
<Automatic reset of power failure>
For automatic reset of power fault, settings must be made as shown.
Mode NO.
12(22) 5 None Provided
FIRST CODE
NO.
SECOND CODE NO.
01 02
9 English
9-2 REMOTE CONTROLLER AND
CENTRALIZED CONTROL
<When operating forced OFF or ON/OFF control from the terminal block (X3M)>
1. Method of wiring and specications
Remote control can be carried out by connecting input
from outside to terminals T1 and T2 of the terminal block.
Class of wire Vinyl cord with sheath or 2-wire cable
Wire gauge 0.75-1.25 mm
Wire length MAX 100 m
Outside contact
specications
Contact that guarantees minimum applicable load DC15V · 1 mA
F2 T1 T2
2. Operation procedures
Operation is as given in the table below for input A of forced OFF, and ON/OFF control.
For forced OFF For ON/OFF control
Forced OFF (control panel rejection) by input A “ON”
Control panel acceptance by input A “OFF”
3. For selecting Forced OFF and ON/OFF control
Select input by control panel after turning on the power supp ly.
• Set to the eld set mode by control panel. (For eld setting, refer to the procedure shown on
previous page.)
• After entering the eld set mode, select mode No.12, set the rst code No.1, and set the second code No. to “01”
for forced OFF, or to “02” for ON/OFF control. (Factory setting is set to forced OFF)
<When operating forced OFF, ON/OFF control, operation display, and malfunction display from the wiring adaptor for electrical appendices (A2P).>
Refer to “For remote control” in the “VRV Engineering Data”.
<Operation by centralized control>
When using with the centralized control, remove the jumper of the group remote control printed circuit board mounted in the control box.
If controlled by the centralized control equipment (the central control panel (optional accessory)), the group NO. must be set by the control panel. For details, refer to the instruction of each centralized control equipment.
2
FORCED
OFF
Input A
Operate by switching input A from “OFF” to “ON”
Stop by switching input A from “ON” to “OFF”
10.

TRIAL OPERATION

(1) Conrm that the control box lid of the indoor units and the
outdoor unit are closed.
(2) Perform the test run according to the installation manual
attached to the outdoor unit.
• If the operation lamp on the control panel is ashing, it
indicates malfunction. Check the error code of the liquid crystal display and the malfunction source. For the error code and the details, refer to the operation manual attached to the indoor unit. In particular, if an error in the table 1 is displayed, it may be the error of wiring work or the power supply may not be turned ON.
(3) Carry out test run according to installation manual
attached to the outdoor unit.
Table 2
Control panel
(remote
controller)
display
“Under centralized control”
ashing
“U4”
ashing
“UH”
ashing
NOT display
E4
Terminal for forced OFF (T1·T2) may be short circuiting.
The power supply of the outdoor unit may not turned ON.
The power supply of the outdoor unit may not be installed yet.
Misconnection between the transmission wiring, and the control panel wiring or the forced OFF wiring.
Disconnection of the transmission wiring.
The power supply of the indoor unit is not turned ON.
The power supply of the indoor unit may not be installed yet.
Misconnection between the transmission wiring, and the control panel wiring or the forced OFF wiring.
Disconnection of the control panel wiring.
A test run is carried out from outdoor unit in a wrong mode (other than “standard” mode).
Content Solution
Fix not to short circuit.
Turn on the power of outdoor unit.
Proceed installation work for power supply.
Fix the wiring.
Turn on the power
of indoor unit.
Proceed installation work for power supply.
Fix the wiring.
Select the
“standard” mode, then test run again from outdoor unit.
WARNING
Even though the test run is nished, if the interior nish work
is not completed, instruct the user not to operate until the work is completed for protecting the indoor unit.
Paint or adhesive used for interior nish work may stain the
indoor unit, which may result in water splash or leak.
10English
3P345056-4F
EM13A0 04B
[15 11]
HT
Loading...