READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
The English text is the original instruction. Other languages are
translations of the original instructions.
Installation must be done by a licensed technician.
The choice of materials and installation must comply
with the applicable national and international
regulations.
BEFOREINSTALLATION
■Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.
■Refer to the installation manual of the outdoor unit for items not
described in this manual.
■Caution concerning refrigerant series R410A:
The connectable outdoor units must be designed exclusively for
R410A.
■Do not place objects in direct proximity of the outdoor unit and
do not let leaves and other debris accumulate around the unit.
Leaves are a hotbed for small animals which can enter the unit.
Once in the unit, such animals can cause malfunctions, smoke
or fire when making contact with electrical parts.
Precautions
■Do not install or operate the unit in rooms mentioned below.
- Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)
- Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)
- Where volatile flammable gas like thinner or gasoline is used.
- Where machines generating electromagnetic waves exist.
(Control system may malfunction.)
- Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories).
Also in vehicles or vessels.
■Do not install accessories on the casing directly. Drilling holes in
the casing may damage electrical wires and consequently cause
fire.
■This appliance is not intended for use by persons, including
children, with reduced physical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance
by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Accessories
Check if the following accessories are included with your unit.
12
Installation and operation manual
1
Metal clamp
1 piece
Large sealing pad
1 piece
Other: installation and operation manual
Drain hose
1 piece
Insulation for fitting
for gas pipe
1 piece
Washer for
hanging bracket
8 pieces
for liquid pipe
1 piece
Screws for fixing panels are attached to the air inlet panel.
VRV System air conditioners
Medium
sealing pad
2 pieces
Screws for duct
flanges
1 set
16 pieces
FXSQ20~140P7VEB
4PW56483-1
Optional accessories
■There are two types of remote controllers: wired and wireless.
Select a remote controller according to customer request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
■When installing bottom suction: air inlet panel and canvas
connection for the air inlet panel.
For the following items, take special care during
construction and check after installation is finished
Tick ✓
when
checked
Is the indoor unit fixed firmly?
■
■
■
■
■
■
■
■
■
■
■
■
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling or heating.
Is the unit fully insulated and checked for air leaks?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
Are wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
Are the air filters fixed properly (when installing with rear duct)?
Maintenance of the air filters can be impossible.
Is the external static pressure set?
It may result in insufficient cooling or heating.
SELECTINGINSTALLATIONSITE
(See figure 1 and figure 2)
1Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.
- Where optimum air distribution can be ensured.
- Where nothing blocks air passage.
- Where condensate water can be properly drained.
- Where the false ceiling is not noticeably on an incline.
- Where sufficient clearance for maintenance and service can
be ensured.
- Where there is no risk of flammable gas leaking.
- The equipment is not intended for use in a potentially
explosive atmosphere.
- Where piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manual of
the outdoor unit.)
-Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and noise in
those electrical appliances. (Noise may be generated
depending on the conditions under which the electric wave is
generated, even if 1 meter is kept.)
- When installing the wireless remote controller kit, the
distance between wireless remote controller and indoor unit
might be shorter if there are fluorescent lights who are
electrically started in the room. The indoor unit must be
installed as far as possible away from fluorescent lights.
- Do not place objects that are susceptible to moisture directly
beneath the indoor or outdoor units. Under certain
conditions, condensation on the main unit or refrigerant
pipes, air filter dirt or drain blockage may cause dripping,
resulting in fouling or failure of the object concerned.
2Ensure that a protective guard is installed on air suction and air
outlet side to prevent that the fan blades or heat exchanger be
touched.
The protection must comply with relevant European and national
regulations.
3Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.
Notes to the installer
■Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.
■Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.
IMPORTANTINFORMATIONREGARDINGTHE
REFRIGERANTUSED
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.
Refrigerant type:R410A
(1)
GWP
value:1975
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.
1Service space
2Drain pipe
3Power supply wiring port
4Tr ansmission wiring port
5Maintenance drain outlet
6Gas pipe
7Liquid pipe
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
Installation and operation manual
2
PREPARATIONSBEFOREINSTALLATION
1Relation of ceiling opening to unit and suspension bolt position.
Installation with rear duct and duct service opening (See
figure 6b)
Installation with rear duct, no duct service opening (See
figure 6c)
NOTE
Before installation of the unit (in case of installation
with duct, but no duct service opening): modify the
position of the air filters.
1Remove the air filter(s) at the
outside of the unit
2Remove the interchangeable
plate
3Install the air filter(s) from the
inside of the unit
4Reinstall the interchangeable
plate
3
2
4
Bottom suction (See figure 7c)
NOTE
NOTE
2The fan speed for this indoor unit is preset to provide standard
3Install the suspension bolts.
Installation example
(See figure 3)
1
The unit can be used with bottom suction by replacing
the interchangeable plate by the air filter holding plate.
1Air filter holding plate with air filter(s)
2Interchangeable plate
For other installation than standard installation, contact
your Daikin dealer for details.
external static pressure.
(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.
1Anchor
2Ceiling slab
3Long nut or turn-buckle
4Suspension bolt
5Indoor unit
NOTE
When installing an air inlet duct, select fixing screws
that shall stick out maximum 5 mm at the inside of the
flange to protect the air filter from damage during
maintenance of the filter.
1Air inlet duct
2Inside of the flange
3Fixing screw
Installation and operation manual
3
12
3
≤5 mm
NOTE
All the above parts are field supplied.
VRV System air conditioners
FXSQ20~140P7VEB
4PW56483-1
INDOORUNITINSTALLATION
C
356
6
C
356
6
When installing optional accessories (except for the air inlet panel),
read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed.
1Install the indoor unit temporarily.
- Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket. (See figure 4)
1Nut (field supply)
2Washer for hanger bracket (supplied with the unit)
3Tighten (double nut)
2Check if the unit is horizontally levelled.
- Do not install the unit tilted. The indoor unit is equipped with a
built-in drain pump and float switch. (If the unit is tilted
against condensate flow, the float switch may malfunction
and cause water to drip.)
- Check if the unit is levelled at all four corners with a water
level or a water-filled vinyl tube as shown in figure 9.
1Water level
2Vinyl tube
3Tighten the upper nut.
REFRIGERANTPIPINGWORK
■Refer to Ta b le 1 for the dimensions of flare nut spaces and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
Ta ble 1
■When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.
■If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a fire.
■Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.
■Finally, insulate as shown in the figures below.
Piping insulation procedure
Gas pipingLiquid piping
For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.
Before rigging tubes, check which type of refrigerant is used.
All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.
■Use a pipe cutter and flare suitable for the used refrigerant.
■To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.
■Use copper alloy seamless pipes (ISO 1337).
■The outdoor unit is charged with refrigerant.
■To prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C, use insulation which is sufficiently
heat resistant.
■Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.
1Torque wrench
2Spanner
3Piping union
4Flare nut
12
3
4
■Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.
■Use annealed material only for flare connections.
1Piping insulation material (field supply)
2Flare nut connection
3Insulation for fitting (delivered with the unit)
4Piping insulation material (main unit)
5Main unit
6Clamp (field supply)
7Medium 1 sealing pad for gas piping (delivered with the unit)
Medium 2 sealing pad for liquid piping (delivered with the unit)
ATurn seams up
BAttach to base
CTighten the part other than the piping insulation material
DWrap over from the base of the unit to the top of the flare nut
connection
For local insulation, be sure to insulate local piping all
the way into the pipe connections inside the unit.
Exposed piping may cause condensation or may
cause burns when touched.
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
Installation and operation manual
4
Cautions for brazing
A'
■Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.
■When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).
12345
6
1Refrigerant piping
2Part to be brazed
3Taping
4Hands valve
5Pressure-reducing valve
6Nitrogen
6
DRAINPIPINGWORK
Rig the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.
1-1.5 m
1Hanging bar
■Install the drain pipes.
-Keep piping as short as possible and slope it downwards at a
gradient of at least 1/100 so that air may not remain trapped
inside the pipe.
-Keep pipe size equal to or greater than that of the connecting
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter).
- Push the supplied drain hose as far as possible over the
drain socket.
- Tighten the metal clamp until the screw head is less than
4 mm from the metal clamp part as indicated in the
illustration.
1235
A
A
1
4
- Insulate the complete drain piping inside the building (field
supply).
- If the drain hose cannot be sufficiently set on a slope, fit the
hose with drain raising piping (field supply).
■How to perform drain piping (See figure 10)
1Ceiling slab
2Hanger bracket
3Adjustable range
4Drain raising pipe
5Drain hose (supplied with the unit)
6Clamp metal (supplied with the unit)
1Connect the drain hose to the drain raising pipes, and insulate
them.
2Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.
InstallationA (mm)
Rear suction installation231
When canvas duct is installed350-530
When air inlet panel is directly installed231
■Precautions
- Install the drain raising pipes at a height of less than 625 mm.
- Install the drain raising pipes at a right angle to the indoor
unit and no more than 300 mm from the unit.
-To prevent air bubbles, install the drain hose level or slightly
tilted up (≤75 mm).
NOTE
The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.
To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.
When unifying multiple drain pipes, install the
pipes as shown in figure 11. Select converging
drain pipes whose gauge is suitable for the
operating capacity of the unit.
1T-joint converging drain pipes
Testing of drain piping
After piping work is finished, check if drainage flows smoothly.
■Add approximately 1 l of water gradually through the air
discharge outlet. Check for water leaks.
Method of adding water. See figure 8.
1Water inlet
2Portable pump
3Water inlet cover
4Bucket (adding water through water inlet)
5Drain outlet for maintenance (with rubber drain plug)
6Refrigerant pipes
A'
A'
≤4 mm
A-A'
1Drain socket (attached to the unit)
2Drain hose (supplied with the unit)
3Metal clamp (supplied with the unit)
4Drain piping (field supply)
5Large sealing pad (supplied with the unit)
-Wrap the supplied large sealing pad over the metal clamp
and drain hose to insulate and fix it with clamps.
Installation and operation manual
5
5
3
1
2
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
Caution for drain socket
Do not remove the drain pipe plug. Water might leak out.
The drain outlet is only used to discharge water if the drain
pump is not used or before maintenance. Gently put in and
out the drain plug. Excessive force may deform the drain
socket of the drain pan.
■Pulling out the plug
1
1Drain plug
Do not wiggle the plug up and down
■Pushing in the plug
1
2
1Drain plug
2Crosshead screwdriver
Set the plug and push it by using a crosshead screwdriver
First perform electric wiring work as instructed in "Electric wiring
work" on page 6 and how to set the remote controller as explained in
"Wiring example and how to set the remote controller" on page 7.
When electric wiring work is finished
Check drainage flow during COOL running, explained in "Test operation"
on page 10.
When electric wiring work is not finished
Remove the switch box cover and connect the single-phase power
supply and the remote controller to the terminals. (Refer to "Electric
wiring work" on page 6 for switch box attachment/detachment.)
(Refer to figure 12 and figure 14)
1Switch box cover
2Tr ansmission wiring port
3Power supply wiring port
4Wiring diagram
5Switch box
6Plastic clamp
7Remote controller wiring
8Te r minal board for unit transmission wiring
9Power supply wiring
10Indoor PC board 1
11Power supply terminal board
12Tr ansmission wiring between units
13Indoor PC board 2
14Indoor PC board 3 (only for 63~140 units)
ELECTRICWIRINGWORK
General instructions
■All field supplied parts and materials and electric works must
conform to local codes.
■Use copper wire only.
■Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".
■All wiring must be performed by an authorized electrician.
■Attach the earth leakage circuit breaker and fuse to the power
supply line.
■A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
■This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.
■Be sure to ground the air conditioner.
■Do not connect the ground wire to:
- gas pipes: might cause explosions or fire if gas leaks.
- telephone ground wires or lightning rods: might cause
abnormally high electric potential in the ground during
lightning storms.
- plumbing pipes: no grounding effect if hard vinyl piping is
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
NOTE
For details, refer to "Electrical data" in the technical
data book.
MCAMFA
0.5
16 A
Next, press the inspection/test operation button on the remote
controller. The unit will engage the test operation mode. Press the
operation mode selector button until selecting fan operation
. Then, press the on/off button . The indoor unit fan and drain
pump will start up. Check that the water has drained from the unit.
Press to go back to the first mode.
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
Installation and operation manual
6
Specifications for field supplied fuses and wire
Power supply wiring
ModelField fusesWireSize
20~14016 AH05VV-U3GLocal codes
- When connecting wires of the same gauge, connect them
according to the figure.
ModelWireSize
20~140Sheathed wire (2)
NOTE
For details, refer to "Wiring example" on page 8.
0.75-1.25 mm
2
Allowable length of transmission wiring between indoor and outdoor
units, and between the indoor unit and the remote controller is as
follows:
1.Outdoor unit - indoor unit: max. 1000 m (total wiring length:
2000 m)
2.Indoor unit - remote controller: max 500 m
WIRINGEXAMPLEANDHOWTOSETTHE
REMOTECONTROLLER
How to connect wiring
Remove the switch box cover as shown in figure 12, and make the
connections.
1Switch box cover
2Tr ansmission wiring port
3Power supply wiring port
4Wiring diagram
5Switch box
PRECAUTIONS
1Observe the notes mentioned below when wiring to the power
supply terminal board.
- Use a round crimp-style terminal for insulation sleeve for
connection to the terminal block for wiring the units. When
none are available, follow the instructions below.
- Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
3Wiring
Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. Use torques according to the table below.
Tightening torque (N•m)
Te r minal block for unit transmission and
remote controller
Te r minal block for power supply1.2
0.9
- When attaching the control box lid, make sure not to pinch
any wires.
- After all wiring connections are done, fill in any gaps in the
casing wiring holes with putty or insulation material (field
supply) thus to prevent small animals or dirt from entering the
unit from outside and causing short circuits in the control box.
2Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm
2
(Ø1.6).
The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.
3Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.
4Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.
5For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.
6Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.
7Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the switch box
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire.
Installation and operation manual
7
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
WIRINGEXAMPLE
FIELDSETTING
Fit the power supply wiring of each unit with a switch and fuse as
shown in figure 16.
1Power supply
2Main switch
3Power supply wiring
4Tr ansmission wiring
5Switch
6Fuse
7BS unit REYQ only
8Indoor unit
9Remote controller
Complete system example (3 systems)
When using 1 remote controller for 1 indoor unit (Normal operation)
(See figure 15)
For group control or use with 2 remote controllers (See figure 17)
When including BS unit (See figure 13)
1Outdoor unit
2Indoor unit
3Remote controller (optional accessories)
4Most downstream indoor unit
5For use with 2 remote controllers
6BS unit
NOTE
PRECAUTIONS
■A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
■For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.
■Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.
It is not necessary to designate an indoor unit address
when using group control. The address is
automatically set when the power is activated.
Field setting must be made on the remote controller in function of the
installation condition.
■Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".
■For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.
Summary of field settings
Mode
First
No.
code
(Note 1)
No.
Description of setting
Filter contamination
- Heavy/Light
= Setting to define
time between 2 filter
cleaning display
indications. (When
0
contamination is
high, setting can be
changed to half the
time inbetween 2
filter cleaning
display indications.)
10
(20)
12
(22)
15
(25)
Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,
Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remote control sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,
Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group
Note 7 : More settings for Differential automatic change over temperatures are:
Thermostat sensor selection
2
Setting for display of time
between 2 filter cleaning display
3
indications
Thermostat sensor in group
6
control
Output signal X1-X2 of the
0
optional KRP1B PCB kit
ON/OFF input from outside
(T1/T2 input) = Setting when
1
forced ON/OFF is to be
operated from outside.
Fan setting during thermostat
3
OFF at heating operation
Differential automatic
4
changeover
Auto-restart after power failure DisabledEnabled——
5
Fixed cool/heat masterDisabledEnabled——
9
Drain pump operation +
3
humidifier interlock
indoor units can also be set individually.
10-2-02 or 10-2-03 have priority.
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have
priority.
Second code No.054°C
Ultra-longlife filter
Long-life
filter
Standard
filter
065°C
076°C
087°C
Second code No. (Note 2)
01020304
±10,000 hrs.
±2,500 hrs.±1,250 hrs.
Light
±200 hrs.±100 hrs.
Use both the
unit sensor (or
remote sensor if
installed) AND
the remote
controller
sensor.
(See note 5+6)
DisplayDo not display ——
Use unit sensor
only (or remote
sensor if
installed).
(See note 6)
Thermostat-on +
compressor run
Forced OFF
LLSet speed
0°C1°C2°C
EquippedNot equipped——
±5,000 hrs.
Heavy
Use unit sensor
only (or remote
sensor if
installed).
(See note 5+6)
Use both the
unit senor (or
remote sensor if
installed) AND
the remote
controller
sensor. (See
note 4+5+6)
—Operation
ON/OFF
operation
——
Use remote
controller
sensor only.
(See note 5+6)
——
——
OFF
(See note 3)
—
Malfunction
—
3°C
(See
note 7)
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
Installation and operation manual
8
External static pressure settings
Settings for external static pressure can be achieved in 2 ways:
Using the airflow automatic adjustment function
Airflow automatic adjustment is the volume of blow-off air that
has been automatically adjusted to the rated quantity.
1Make sure the test run is done with a dry coil.
If the coil is not dry, run the unit for 2 hours with fan only to dry
the coil.
2Check if the power supply wiring to the air conditioning unit is
completed along with the duct installation.
If a closing damper is installed in the air conditioning unit, make
sure that it is open.
Also check if the air filter is properly attached into the air
passage on the air suction side of the air conditioning unit.
3If there is more than one air inlet and outlet, adjust the dampers
so that the airflow rate of each air inlet and outlet is conform with
the designed airflow rate.
Make sure the air conditioning unit is in fan operation mode.
Press and set the airflow adjustment button on the remote
controller to change the airflow rate to H or L.
4Setting the airflow automatic adjustment settings.
When the air conditioning unit is running in fan operation mode
perform the next steps:
- stop the air conditioning unit,
- go to field setting mode,
- select mode No. 21 (or 11 in case of group setting),
- set the first code No. to "7",
- set the second code No. to "03".
Return to normal operating mode after setting these settings
and press the ON/OFF operation button. The operation lamp will
light up and the air conditioning unit will start the fan operation
for airflow automatic adjustment.
Do not adjust the dampers during fan operation for
airflow automatic adjustment.
After 1 to 8 minutes, the air conditioning unit stops operating
automatically when the fan operation for airflow automatic
adjustment has been carried out, the operation lamp will be off.
Mode
No.
11 (21)7
5When the air conditioning unit has stopped, check on an indoor
unit if the second code No. of mode No. 21 is set to "02".
If the air conditioning unit does not stop operating or the second
code No. is not "02", repeat step 4.
If the outdoor unit is not turned on, the display on the remote
controller will show "U4" or "UH" (refer to "Test operation" on
page 10). However, you can continue setting this function
because these messages are only applicable to outdoor units.
After setting this function, be sure to turn on the outdoor unit
before performing the test operation on the outdoor unit.
If any other error display occurs on the display of the remote
controller, refer to "Test operation" on page 10 and the operation
manual of the outdoor unit. Check the defective point.
First
code No.
Second
code No.
Setting content
01Airflow adjustment is OFF
02Completion of airflow adjustment
03Start of airflow adjustment
■If the external static pressure of the FXSQ140P7VEB
is higher than 100 Pa, do not use airflow automatic
adjustment function.
■If there is no change after airflow adjustment in the
ventilation paths, be sure to perform setting the airflow
automatic adjustment again.
■Contact your dealer if there is no change after
performing airflow adjustment in the ventilation paths,
after performing the test operation of the outdoor unit
or when the air conditioning unit is moved to another
location.
■If booster fans, an outdoor air processing unit or HRV
via duct are used, do not use airflow automatic
adjustment control with a remote controller.
■If the ventilation paths have been changed, perform
the setting of the airflow automatic adjustment again
as described above from step 3 onwards.
Using the remote controller
Check on an indoor unit if the second code of mode No. 21 is set to
"01" (= factory setting). Change the second code according to the
external static pressure of the duct to be connected as shown in
table 2.
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".
MAIN/SUB CHANGEOVER
■Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. (See figure 18)
(The remote controller PC board is attached to the upper part of
the remote controller.)
■Tu rn the main/sub changeover switch on one of the two remote
controller PC boards to "S". (See figure 19)
(Leave the switch of the other remote controller set to "M".)
1Remote controller PC board
2Factory setting
3Only one remote controller needs to be changed
Installation and operation manual
9
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
Computerised control (forced off and on/off operation)
1Wire specifications and how to perform wiring
- Connect input from outside to terminals T1 and T2 of the
terminal board (remote controller to transmission wiring).
Wire specificationSheathed vinyl cord or cable (2 wire)
Gauge
LengthMax. 100 m
External terminalContact that can ensure the minimum
F2 T1T2
FORCED
OFF
Input A
0.75-1.25 mm
applicable load of 15 V DC, 10 mA
2
2Actuation
- The following table explains "forced off" and "on/off
operations" in response to input A.
Forced offon/off operation
Input "on" stops operation input off ➜ on: turns on the unit
Input "off" enables control input on ➜ off: turns off the unit by
(impossible by remote controllers)
remote controller
3How to select forced off and on/off operation
-Turn the power on and then use the remote controller to
select operation.
- Set the remote controller to the field set mode. For details,
refer to the chapter "How to set in the field", in the remote
controller manual.
- When in the field set mode, select mode No. 12, then set the
first code No. to "1". Then set second code (position) No. to
"01" for forced off and to "02" for on/off operation. (forced off
at factory set.) (See figure 20)
For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.
TESTOPERATION
Refer to the installation manual of the outdoor unit.
The operation lamp of the remote controller will flash when an error
occurs. Check the error code on the liquid crystal display to identify
the trouble.
Error codeMeaning
A8Error in power supply to indoor unit
C1
C6
U3Test operation of the indoor unit has not been finished
Tr ansmission error between fan driver PCB and controller
PCB of the indoor unit
Improper combination of fan driver PCB of the indoor unit or
setting failure in control PCB type
If any of the items in following table are displayed on the remote
controller, there may be a problem with the wiring or power, so check
the wiring again.
Error codeMeaning
There is a short circuit at the forced off terminals (T1, T2)
U4 or UH
no display
- The power on the outdoor unit is off
- The outdoor unit has not been wired for power supply
- Incorrect transmission of forced off wiring
- The power on the indoor unit is off
- The indoor unit has not been wired for power supply
- Incorrect transmission wiring, forced off wiring or remote
controller wiring
MAINTENANCE
Caution
■Only a qualified service person is allowed to perform
maintenance.
■Before obtaining access to terminal devices, all power
supply circuits must be interrupted.
■Do not use water or air of 50°C or higher for cleaning
air filters and outside panels.
■When cleaning the heat exchanger, be sure to remove
the switchbox, fan motor, auxiliary electric heater and
drain pump. Water or detergent may deteriorate the
insulation of electronic components and result in
burn-out of these components.
■If the main power supply is turned off during
operation, operation will restart automatically after the
power turns back on again.
INSTALLATIONOFTHEDECORATIONPANEL
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel.
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
How to clean the air filter
Clean the air filter when the display shows "" (TIME TO CLEAN
AIR FILTER).
Increase the frequency of cleaning if the unit is installed in a room
where the air is extremely contaminated.
If the dirt becomes impossible to clean, change the air filter. (Air filter
for exchange is optional.)
1Open the suction grille. (Only for bottom suction.)
Slide both knobs simultaneously as shown and then pull them
downward.
Installation and operation manual
10
If chains are present, unhook the chains.
5Shut the air inlet grille. (Only for bottom suction.)
Refer to item no. 1.
6After turning on the power, press FILTER SIGN RESET button.
The "TIME TO CLEAN AIR FILTER" display is turned off.
How to clean air outlet and outside panels
2Remove the air filters.
Remove the air filters by pulling their cloth upward (rear suction)
or backward (bottom suction).
rear suction
bottom suction
3Clean the air filter.
Use vacuum cleaner (A) or wash the air filter with water (B).
(A) Using a vacuum cleaner
(B) Washing with water
■Clean with soft cloth.
■When it is difficult to remove stains, use water of neutral
detergent.
■Clean the air inlet grille when it is shut.
NOTE
Do not use gasoline, benzene, thinner, polishing
powder, liquid insecticide. It may cause discolouring or
warping.
Do not let the indoor unit get wet. It may cause an
electric shock or a fire.
Start up after a long stop
Confirm the following:
■Check that the air inlet and outlet are not blocked. Remove any
obstacle.
■Check if the earth is connected.
Clean the air filter and outside panels.
■After cleaning the air filter, make sure to attach it.
Tu rn on the main power supply switch.
■The control panel display lights when the power is turned on.
■To protect the unit, turn on the main power switch at least
6 hours before operation.
What to do when stopping the system for a long period
When the air filter is very dirty, use soft brush and neutral
detergent.
Remove water and dry in the shade.
4Fix the air filter.
rear suction
bottom suction
Tu rn on FAN OPERATION for half a day and dry the unit.
■Refer to the operation manual of the outdoor unit.
Cut off the power supply.
■When the main power switch is turned on, some wattage is
being consumed even if the system is not operating.
■The remote controller display is turned off when the main power
switch is turned off.
DISPOSALREQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
Align the two hanger brackets and push the two clips in their
place (pull the cloth if necessary).
Confirm that four hangers are fixed.
Installation and operation manual
11
FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1
WIRINGDIAGRAM
: FIELD WIRINGBLK : BLACKORG : ORANGE
: CONNECTORBLU : BLUEPNK : PINK
: WIRE CLAMPBRN : BROWNRED : RED