Anti-Corrosion Treatment of Outdoor
Heat Exchanger
Indoor Unit
5-Rooms Centralized Controller
(Option)
Remote Control Adaptor
(Normal Open-Pulse Contact) (Option)
Remote Control Adaptor
(Normal Open Contact) (Option)
Wireless
FTKS09/12JEVJU
RKS09/12JEVJU
FTXS09/12JEVJU
——
——
32.8ft32.8ft
——
——
——
RXS09/12JEVJU
Note: : Holding Functions
— : No Functions
4Room Air Conditioners J-Series
Page 6
EDUS041011Specifications
3.Specifications
3.1Cooling Only
Models
60Hz 208-230V
Capacity
Rated (Min.~Max.)
Running Current (Rated)A4.1-3.74.1-3.7
Power Consumption Rated
Power Factor%79.7-79.993.8-94.0
COP (Rated) (Min.~Max.)W/W3.66 (3.94~3.48)3.66 (3.94~2.98)
EER (Rated) (Min.~Max.)
Piping
Connections
Heat InsulationBoth Liquid and Gas PipesBoth Liquid and Gas Pipes
Max. Interunit Piping Lengthfeet49.249.2
Max. Interunit Height Differencefeet39.339.3
Chargelessfeet32.832.8
Amount of Additional Charge of
Refrigerant
Indoor UnitsFTKS09JEVJUFTKS12JEVJU
Front Panel ColorWhiteWhite
Airflow Ratem³/min (cfm)
Fan
Air Direction ControlRight, Left, Horizontal and DownwardRight, Left, Horizontal and Downward
Air FilterRemovable / Washable / Mildew ProofRemovable / Washable / Mildew Proof
Running Current (Rated)A0.20-0.180.20-0.18
Power Consumption (Rated)W4040
Power Factor%96.2-96.696.2-96.6
Temperature ControlMicrocomputer ControlMicrocomputer Control
Dimensions (H×W×D)inch11-9/64×30-5/16×7-51/6411-9/64×30-5/16×7-51/64
Packaged Dimensions (H×W×D)inch10-17/64×33-7/32×13-15/3210-17/64×33-7/32×13-15/32
WeightLbs1616
Gross WeightLbs2424
Operation SoundH/M/L/SLdBA40 / 33 / 26 / 2241 / 34 / 27 / 23
Sound PowerdBA5657
Outdoor UnitsRKS09JEVJURKS12JEVJU
Casing ColorIvory WhiteIvory White
Compressor
Refrigerant Oil
Refrigerant
Airflow Ratem³/min (cfm)H26.1 (921)26.1 (921)
Fan
Running Current (Rated)A3.90-3.523.90-3.52
Power Consumption (Rated)W640760
Power Factor%78.9-79.193.7-93.9
Starting CurrentA4.14.8
Dimensions (H×W×D)inch21-21/32×25-29/32×10-13/1621-21/32×25-29/32×10-13/16
Packaged Dimensions (H×W×D)inch23-5/16×30-23/64×13-45/6423-5/16×30-23/64×13-45/64
WeightLbs6666
Gross WeightLbs7575
Operation SounddBA4848
Sound PowerdBA6262
Drawing No.C: 3D066330BC: 3D066331B
TypeCross Flow FanCross Flow Fan
Motor OutputW1616
SpeedSteps5 Steps, Quiet and Auto5 Steps, Quiet and Auto
TypeHermetically Sealed Swing TypeHermetically Sealed Swing Type
Model1YC23AEXD1YC23AEXD
Motor OutputW750750
TypeFVC50KFVC50K
Chargeoz12.512.5
TypeR-410AR-410A
ChargeLbs2.202.20
TypePropellerPropeller
Motor OutputW3333
kW2.49 (1.30~2.78)2.93 (1.3~3.52)
Btu/h8,500 (4,400~9,500)10,000 (4,400~12,000)
kal/h2,140 (1,120~2,390)2,520 (1,120~3,030)
W680 (330~800)800 (330~1,180)
Btu/h·W
oz/ft0.220.22
H9.2 (325)9.3 (328)
M7.4 (261)7.7 (272)
L5.3 (187)5.6 (198)
SL4.0 (141)4.4 (155)
12.50 (13.33~11.90)12.50 (13.33~10.20)
Note:
The data are based on the conditions shown in the table below.
CoolingPiping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
25ft
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Room Air Conditioners J-Series5
Page 7
SpecificationsEDUS041011
3.2Heat Pump
Models
60Hz 208-230V
Capacity
Rated (Min.~Max.)
Running Current (Rated)A4.1-3.74.0-3.64.1-3.74.8-4.3
Power Consumption Rated
Power Factor%79.7-79.993.1-93.693.8-94.093.1-94.0
COP (Rated) (Min.~Max.)W/W3.66 (3.94~3.48)3.78 (4.19~4.05)3.66 (3.94~2.98)3.78 (4.19~3.20)
EER (Rated) (Min.~Max.)
Piping
Connections
Heat InsulationBoth Liquid and Gas PipesBoth Liquid and Gas Pipes
Max. Interunit Piping Lengthfeet49.249.2
Max. Interunit Height Differencefeet39.339.3
Chargelessfeet32.832.8
Amount of Additional Charge of
Refrigerant
Indoor UnitsFTXS09JEVJUFTXS12JEVJU
Front Panel ColorWhiteWhite
Airflow Ratem³/min (cfm)
Fan
Air Direction ControlRight, Left, Horizontal and DownwardRight, Left, Horizontal and Downward
Air FilterRemovable / Washable / Mildew ProofRemovable / Washable / Mildew Proof
Running Current (Rated)A0.20-0.180.20-0.18
Power Consumption (Rated)W4040
Power Factor%96.2-96.696.2-96.6
Temperature ControlMicrocomputer ControlMicrocomputer Control
Dimensions (H×W×D)inch11-9/64×30-5/16×7-51/6411-9/64×30-5/16×7-51/64
Packaged Dimensions (H×W×D)inch10-17/64×33-7/32×13-15/3210-17/64×33-7/32×13-15/32
WeightLbs1616
Gross WeightLbs2424
Operation SoundH/M/L/SLdBA40 / 33 / 26 / 2240 / 34 / 28 / 2541 / 34 / 27 / 2341 / 35 / 29 / 26
Sound PowerdBA5657
Outdoor UnitsRXS09JEVJURXS12JEVJU
Casing ColorIvory WhiteIvory White
Compressor
Refrigerant Oil
Refrigerant
Airflow Ratem³/min (cfm)H26.1 (921)26.1 (921)
Fan
Running Current (Rated)A3.90-3.523.80-3.423.90-3.524.60-4.12
Power Consumption (Rated)W640735760890
Power Factor%78.9-79.193.0-93.493.7-93.993.0-93.9
Starting CurrentA4.14.14.8
Dimensions (H×W×D)inch21-21/32×25-29/32
Packaged Dimensions (H×W×D)inch23-5/16×30-23/64×13-45/6423-5/16×30-23/64×13-45/64
WeightLbs6868
Gross WeightLbs7777
Operation SounddBA484849
Sound PowerdBA626263
Drawing No.C: 3D066292BC: 3D066329B
AFR: Airflow rate(m3/min.)1. Ratings shown are net capacities which include a deduction for indoor fan
BF: Bypass factor
EWB: Entering wet bulb temp.(°C) / (°F)
EDB: Entering dry bulb temp.(°C) / (°F)
TC: Total capacity(kW) / (kBtu/h)
SHC: Sensible heating capacity (kW) / (kBtu/h)
PI: Power input(kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in
the above tables. (Figures out of the tables should not be used for
calculation.)
4. About SHC which are not mentioned on the table, please calculate them
with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25ft
Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
AFR: Airflow rate(m3/min.)1. Ratings shown are net capacities which include a deduction for indoor fan
BF: Bypass factor
EWB: Entering wet bulb temp.(°C) / (°F)
EDB: Entering dry bulb temp.(°C) / (°F)
TC: Total capacity(kW) / (kBtu/h)
SHC: Sensible heating capacity (kW) / (kBtu/h)
PI: Power input(kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in
the above tables. (Figures out of the tables should not be used for
calculation.)
4. About SHC which are not mentioned on the table, please calculate them
with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25ft
Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
AFR: Airflow rate(m3/min.)1. Ratings shown are net capacities which include a deduction for indoor fan
BF: Bypass factor
EWB: Entering wet bulb temp.(°C) / (°F)
EDB: Entering dry bulb temp.(°C) / (°F)
TC: Total capacity(kW) / (kBtu/h)
SHC: Sensible heating capacity (kW) / (kBtu/h)
PI: Power input(kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in
the above tables. (Figures out of the tables should not be used for
calculation.)
4. About SHC which are not mentioned on the table, please calculate them
with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25ft
Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
AFR: Airflow rate(m3/min.)1. Ratings shown are net capacities which include a deduction for indoor fan
BF: Bypass factor
EWB: Entering wet bulb temp.(°C) / (°F)
EDB: Entering dry bulb temp.(°C) / (°F)
TC: Total capacity(kW) / (kBtu/h)
SHC: Sensible heating capacity (kW) / (kBtu/h)
PI: Power input(kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in
the above tables. (Figures out of the tables should not be used for
calculation.)
4. About SHC which are not mentioned on the table, please calculate them
with around values in direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25ft
Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066178
Room Air Conditioners J-Series17
Page 19
Capacity TablesEDUS041011
Capacity correction factor
1
16.432.849.2
0.9
0.8
R-410A (09/12 class)
Piping length (ft)
(R11493)
Range of the refrigerant
additional charge
7.3Capacity correction factor by the length of refrigerant piping (Reference)
The cooling and the heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance
between the indoor unit and the outdoor unit)
<— line : cooling capacity>
<--- line : heating capacity>
The graph shows the factor when additional refrigerant of the proper quantity is charged.
Note:
18Room Air Conditioners J-Series
Page 20
EDUS041011Operation Limit
122
114.8
104
86
68
Pull-down period
Continuous operation
Outdoor temp. (˚FDB)
50
32
866857.25073.4 82.4
Indoor temp. (˚FWB)
Notes:
The graphs are based
on the following conditions.
• Equivalent piping length25ft
• Level difference0ft
• Air flow rateHigh
4D066173
Heating
Cooling
68
122
114.8
59
104
50
86
41
32
68
Pull-down period
Outdoor temp. (˚FWB)
23
Continuous operation
Outdoor temp. (˚FDB)
50
Continuous operation
14
32
5
82.4688673.457.250
(5˚FDB)
Indoor temp. (˚FWB)
508668
Notes:
Indoor temp. (˚FDB)
The graphs are based
on the following conditions.
• Equivalent piping length25ft
• Level difference0ft
• Air flow rateHigh
3D066174
8.Operation Limit
RKS09/12JEVJU
RXS09/12JEVJU
Room Air Conditioners J-Series19
Page 21
Sound LevelEDUS041011
3.3ft
2.6ft
(R5162)
3.3ft
(R4796)
9.Sound Level
9.1Measuring Location
Indoor Unit
The Single Split Duct-Free System
Outdoor Unit
1. Operation sound is measured in an anechoic chamber.
2. The data are based on the conditions shown in the table below.
CoolingHeatingPiping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
Note:
25ft
20Room Air Conditioners J-Series
Page 22
EDUS041011Sound Level
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz60Hz
208/230V208/230V
(H)(L)
4026
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
4D066168
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz60Hz
208/230V208/230V
(H)(L)
4127
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
4D066169
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
10
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLINGHEATING
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz60Hz
208/230V208/230V
(H)(L)
4026
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
60Hz60Hz
208/230V208/230V
(H)(L)
4028
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
NC-50
NC-40
NC-30
NC-20
NC-10
Heating
3D066170
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
10
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
10
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLINGHEATING
NC-50
NC-40
NC-30
NC-20
NC-10
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz60Hz
208/230V208/230V
(H)(L)
4127
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
60Hz60Hz
208/230V208/230V
(H)(L)
4129
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Heating
3D066171
9.2Octave Band Level
9.2.1Indoor Units
FTKS09JEVJUFTKS12JEVJU
FTXS09JEVJU
FTXS12JEVJU
Room Air Conditioners J-Series21
Page 23
Sound LevelEDUS041011
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
4D066163
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
4D066164
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLINGHEATING
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
NC-60
NC-50
NC-40
NC-30
NC-20
208/230V 60Hz
60Hz 208/230V
Heating
60Hz
208/230V(H)
48
3D066166
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS
NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLINGHEATING
NC-60
NC-20
NC-40
NC-50
NC-30
48
208/230V(H)
60Hz
Cooling
208/230V 60Hz
60Hz 208/230V
49
208/230V(H)
60Hz
208/230V 60Hz
60Hz 208/230V
Heating
NC-50
NC-20
NC-30
NC-60
NC-40
3D066167
9.2.2Outdoor Units
RKS09JEVJURKS12JEVJU
RXS09JEVJU
RXS12JEVJU
22Room Air Conditioners J-Series
Page 24
EDUS041011Electric Characteristics
10.Electric Characteristics
Representative Unit CombinationPower SupplyCOMPOFMIFM
MCA: MIN. CIRCUIT AMPS (A)1. Maximum allowable voltage variation between phases is 2%.
MOP: MAX OVERCURRENT PROTECTION
RLA: RATED LOAD AMPS (A)
OFM: OUTDOOR FAN MOTOR
IFM: INDOOR FAN MOTOR
FLA: FULL LOAD AMPS (A)
W: FAN MOTOR RATED OUTPUT (W)
2. Select wire size based on the larger value of MCA.
3. Instead of fuse, use circuit breaker.
4. Be sure to install a ground leak detector. (One that can handle
higher harmonics.)
(This unit uses an inverter, which means that it must use a ground
leak detector capable handling high harmonics in order to prevent
malfunctioning of the ground leak detector itself.)
3.7
3.7
3.7
4.4
33
33
33
33
0.19
0.19
0.19
0.19
40
40
40
40
0.20
0.20
0.20
0.20
3D066179B
Room Air Conditioners J-Series23
Page 25
Installation ManualEDUS041011
1
Safety Precautions
• Read these Safety Precautions carefully to ensure correct installation.
• This manual classifies the precautions into DANGER, WARNING and CAUTION. Be sure to follow all the precautions
below: they are all important for ensuring safety.
DANGER..........Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
........Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTION .........Failure to follow any of CAUTION may in some cases result in grave consequences.
• The following safety symbols are used throughout this manual:
•
After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use
and cleaning of the unit according to the Operation Manual.
Be sure to observe this instruction.Be sure to establish a ground connection.Never attempt.
DANGER
• Refrigerant gas is heavier than air and replaces oxygen. A massive leak could lead to oxygen depletion, especially
in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• If the refrigerant gas leaks during installation, ventilate the area immediately.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas
could cause severe injury or death.
• After completing the installation work, check that the refrigerant gas does not leak.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas
could cause severe injury or death.
• Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could cause a
severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an
explosion which could lead to severe injury or death.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apar t and throw away plastic
packaging bags so that children will not play with them. Children playing with plastic bags face the danger of death by suffocation.
•
Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death.
•
Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in
severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
WARNING
• Installation should be left to the authorized dealer or another trained professional.
Improper installation may cause water leakage, electrical shock, fire, or equipment damage.
• Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire or equipment damage.
• Be sure to use the supplied or exact specified installation parts.
Use of other parts may cause the unit to come to fall, water leakage, electrical shock, fire or equipment damage.
• Install the air conditioner on a solid base that is level and can support the weight of the unit.
An inadequate base or incomplete installation may cause injury or equipment damage in the event the unit falls off the base or comes loose.
• Electrical work should be carried out in accordance with the installation manual and the national, state and local
electrical wiring codes.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire or equipment damage.
• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
Follow all appropriate electrical codes.
• For wiring, use a wire or cable long enough to cover the entire distance with no splices if possible. Do not use an
extension cord. Do not put other loads on the power supply. Use an only a separate dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock, fire or equipment damage.)
• Use the specified types of wires for electrical connections between the indoor and outdoor units. Follow all state
and local electrical codes.
Firmly clamp the inter-unit wiring so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal
overheating, fire or equipment damage.
• After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical
covers, panels or terminals.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock,fire or equipment damage.
• When installing or relocating the system, be sure to keep the refrigerant circuit free from all substances other than
the specified refrigerant (R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which may result in rupture, resulting in injury.)
11.Installation Manual
11.1Indoor Units
24Room Air Conditioners J-Series
Page 26
EDUS041011Installation Manual
2
Safety Precautions
Accessories
– ,
Choosing an Installation Site
• Before choosing the installation site, obtain user approval.
1.
Indoor unit
• The indoor unit should be sited in a place where:
1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air inlet and air outlet have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool (warm) air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the
remote controller range,
8)
the unit is at least 3.5 feet (1m) away from any television or radio set (unit may cause interference with the picture or sound).
2.
Wireless remote controller
1) Turn on all the fluorescent lamps in the room, if any, and find the site where remote control signals are properly received
by the indoor unit (within 23 feet (7m)).
WARNING
• During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed,
causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing
abnormally high pressure which could lead to equipment damage and personal injury.
• Be sure to install a ground fault circuit interrupter breaker.
Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.
CAUTION
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual.
Inadequate piping may cause water damage.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
Hook fingers on the tabs on the left and right of the main body, and open
until the panel stops. Slide the front panel sideways to disengage the
rotating shaft. Then pull the front panel toward you to remove it.
••Installation method
Align the tabs of the front panel with the grooves, and push all the way in.
Then close slowly. Push the center of the lower surface of the panel firmly
to engage the tabs.
2.
Removing and installing front grille
R
emoval method
1) Remove front panel to remove the air filter.
2) Remove 2 screws from the front grille.
3) In front of the
mark of the front grille, there are 3 upper hooks.
Lightly pull the front grille toward you with one hand, and push down on
the hooks with the fingers of your other hand.
When there is no work space because the unit is close to ceiling
CAUTION
• Be sure to wear protection gloves.
Place both hands under the center of the front grille, and while pushing up, pull it toward you.
• Installation method
1) Install the front grille and firmly engage the upper hooks (3 locations).
2) Install 2 screws of the front grille.
3) Install the air filter and then mount the front panel.
3.
How to set the different addresses
When two indoor units are installed in one room, the two wireless remote controllers
can be set for different addresses.
1) In the same way as when connecting to an HA system, remove the metal plate
electrical wiring cover.
2) Cut the address jumper (JA) on the printed circuit board.
3) Cut the address jumper (J4) in the remote controller.
Push the rotating
shaft of the front
panel into the groove.
mar
k area
(3 locations)
Upper hook
Lightly pull the front
grille toward you with
one hand, and push
down on the hooks with
the fingers of your other
hand. (3 locations)
Push
down.
Upper hook
1) Push up.
2) Pull toward you.
ADDRESS
EXIST
CUT12
JA
JA
ADDRESS
J4
EXIST
1
CUT2
J4
26Room Air Conditioners J-Series
Page 28
EDUS041011Installation Manual
4
Indoor Unit Installation Drawings
How to attach the indoor unit
Hook the claws of the bottom frame
Mounting plate
A
The mounting plate
should be installed on a
wall which can support the
Mounting plate fixing screw
B
3/16” × 1” (M4 × 25mm)
Front panel
1-15/16” (50mm)
or more from walls
(on both sides)
Air filters
Titanium apatite photocatalytic
C
air-purifying filter (2)
Air filter
weight of the indoor unit.
1-3/16” (30mm) or more
from ceiling
3/16” × 5/8”
(M4 × 16mm)
Opening service lid
Service lid is opening/closing type.
Opening method
to the mounting plate.
If the claws are difficult to hook,
remove the front grille.
How to remove the indoor unit
Push up the marked area (at the
lower part of the front grille) to
release the claws. If it is difficult to
release, remove the front grille.
Service lid
1) Remove the service lid screws.
2) Pull out the service lid diagonally
down in the direction of the arrow.
3) Pull down.
Caulk
pipe hole
gap
with putty.
Front grille
Mounting
A
plate
Bottom frame
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe’s cut line.
Wrap the insulation pipe with
the finishing tape from bottom
to top.
Mark (rear side)
Clip
Filter frame
Titanium apatite
photocatalytic
Ta b
Room Air Conditioners J-Series27
air-purifying filter
Fixing screw for remote
F
controller holder
1/8” × 13/16” (M3 × 20mm)
D
Wireless
remote
controller
Before screwing the remote
controller holder to the wall,
make sure that control
signals are properly
received by indoor unit.
E
Remote
controller holder
Page 29
Installation ManualEDUS041011
5
Indoor Unit Installation
1.
Installing the mounting plate
• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the boring
points on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
* The removed pipe port cover can be
kept in the mounting plate pocket.
Removed pipe
port cover
A
Mounting plate
Use tape measure as shown.
Position the end of a tape
measure at .
Liquid pipe end
Gas pipe end
Throughthe-wall hole
φ2-9/16 (φ65)
Recommended mounting plate
retention spots (5 spots in all)
Place a leveler
on raised tab.
9-33/64
(241.7)
1-5/8
(41.3)
13-1/64
(330.5)
13-1/32
(331)
6-19/64
(160)
2-1/8
(54)
30-5/16
(770)
9-33/64
(241.7)
1-5/8
(41.3)
2-9/64
(54.5)
6-19/64
(160)
1-31/32
(50)
4-31/32
(101)
4-47/64
(120.5)
7-63/64
(203)
9-23/32
(247)
Drain hose
position
unit: inch (mm)
(Bolt size: 3/8 (M10))(Bolt size: 3/8 (M10))
28Room Air Conditioners J-Series
Page 30
EDUS041011Installation Manual
6
Indoor Unit Installation
2.
Boring a wall hole and installing wall embedded pipe
• For walls containing metal frame or metal board, be sure to use a wall
embedded pipe and wall cover in the feed-through hole to prevent possible
heat, electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking material to prevent
water leakage.
1) Bore a feed-through hole of 2-9/16 inch (65mm) in the wall so it has a
down slope toward the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole
gap with putty.
3.
Installing indoor unit
• In the case of bending or curing refrigerant pipes, keep the following
precautions in mind.
Abnormal sound may be generated if improper work is conducted.
1) Do not strongly press the refrigerant pipes onto the bottom frame.
2) Do not strongly press the refrigerant pipes on the front grille, either.
3-1. Right-side, right-back, or right-bottom piping
1) Attach the drain hose to the underside of the refrigerant pipes with
an adhesive vinyl tape.
2) Wrap the refrigerant pipes and drain hose together with insulation
tape.
3) Pass the drain hose and refrigerant pipes through the wall hole, then
set the indoor unit on the mounting plate hooks by using the
markings at the top of the indoor unit as a guide.
4) Open the front panel, then open the service lid.
5) Pass the inter-unit wiring from the outdoor unit through the
feed-through wall hole and then through the back of the indoor
unit. Pull them through the front side. Bend the ends of tie
wires upward for easier work in advance. (If the inter-unit wiring
ends are to be stripped first, bundle wire ends with adhesive
tape.)
6) Press the bottom frame of the indoor unit with both hands to set
it on the mounting plate hooks. Make sure the wires do not
catch on the edge of the indoor unit.
InsideOutside
Caulking
Wall embedded pipe
(field supply)
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
φ2-9/16”
( 65mm)
1)
2)
Right-bottom
piping
Right-side piping
Right-back piping
Bind coolant pipe
and drain hose
together with
insulating tape.
Remove pipe port cover
here for right-side piping.
Remove pipe port cover
here for right-bottom piping.
Mounting plate
A
When stripping the
ends of inter-unit wiring in
advance, bind right ends
of wires with insulating tape.
Hang indoor unit’s hook here.
Inter-unit wiring
Mounting plate
A
Room Air Conditioners J-Series29
Page 31
Installation ManualEDUS041011
7
3-2. Left-side, left-back, or left-bottom piping
1) Attach the drain hose to the underside of the refrigerant pipes
with adhesive vinyl tape.
2) Be sure to connect the drain hose to the drain port in place of a
drain plug.
3) Shape the refrigerant pipes along the pipe
path marking on the mounting plate.
4) Pass drain hose and refrigerant pipes
through the wall hole, then set the indoor
unit on mounting plate hooks, using the
markings at the top of indoor unit as a
guide.
5) Pull in the inter-unit wiring.
6) Connect the inter-unit piping.
7) Wrap the refrigerant pipes and drain hose together with insulation tape as
right figure, in case of setting the drain hose through the back of the indoor
unit.
8) While exercising care so that the inter-unit wiring do not catch indoor unit,
press the bottom edge of indoor unit with both hands until it is firmly
caught by the mounting plate hooks. Secure indoor unit to the mounting
plate with indoor unit fixing screws 3/16 × 1/2 inch (M4 × 12mm).
3-3. Wall embedded piping
• Insert the drain hose to this depth so it won’t be pulled out of the drain pipe.
Remove pipe port cover here for left-bottom piping.
Remove pipe
port cover
here for leftside piping.
Left-bottom piping
Left-side
piping
Left-back
piping
How to set drain plug.
No gap.
Do not apply lubricating
oil (refrigeration oil)
when inserting.
Application of causes
deterioration and drain
leakage of the plug.
Insert a hexagonal wrench 3/16” (4mm).
Drain
hose
Caulk this hole
with putty or
caulking material.
Bind with vinyl
tape.
A
Mounting plate
Wrap insulating tape around the
bent portion of refrigerant pipes.
Overlap at least half the width of
the tape with each turn.
Refrigerant
pipes
Drain hose
Bottom frame
H Indoor unit fixing screw
3/16” × 1/2” (M4 × 12mm)
(2 point)
Mounting
plate
A
Inter-unit wiring
Inner wall
Vinyl chloride
drain pipe
(VP-30)
Drain hose1-15/16” (50mm)
or more
Insert the drain
hose to this depth
so it won’t be pulled
out of drain pipe.
Outer wall
How to replace the drain plug and drain hose
• Replacing onto the left side
1) Remove the insulation fixing screws on the right
to remove the drain hose.
2) Reattach the insulation fixing screw on the right
as it was.
* (Forgetting to attach this may cause water
leakages.)
3) Remove the drain plug on the left side and
attach it to the right side.
4) Insert the drain hose and tighten with included
insulation fixing screw.
Drain hose attachment position
* The drain hose is on the back of the unit.
Front side of unit
Attachment on the left side
Insulation
fixing screw
Drain hoseDrain hose
Attachment on the right side (factory default)
Right sideLeft side
Insulation
fixing screw
30Room Air Conditioners J-Series
Page 32
EDUS041011Installation Manual
8
Indoor Unit Installation
4.
Wiring
1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut onto
the conduit mounting plate.
2) Strip wire ends (9/16 inch (15mm)).
3) Match wire colors with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the
corresponding terminals.
4) Connect the ground wires to the corresponding terminals.
5) Pull wires to make sure that they are securely latched up.
6) In case of connecting to an adapter system. Run the remote control cable and attach the S21.
7) Shape the wires so that the service lid fits securely, then close service lid.
WARNING
• Do not use tapped wires, strand wires, extension cords, or starburst connections, as they may cause overheating, electrical
shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• When carrying out wiring connection, take care not to pull at the conduit.
5.
When connecting to a wired remote controller
* If work space is available on the right side of the indoor unit, the work
can be performed with the electrical component box attached. Omit the
steps involved with removing and installing the electrical component
box in order to perform the work more efficiently.
5-1. Remove the front grille (2 screws).
5-2. Remove the service lid (1 screw).
5-3. Remove the cover from the indoor unit electrical
component box [Figure 1].
*5-4.
Remove the indoor unit electrical component box.
1) Remove the louver.
2) Disconnect the communication wiring.
3) Disconnect the connector (S200).
4) Remove the thermistor from the heat exchanger.
5) Remove the electrical component box installation screw (1 screw).
123
Terminal block
Electrical component box
Use the specified wire type.
Shape wires so that the
service lid will fit securely.
1
2
3
123
L1L
2
When wire length exceeds
33ft (10m), use AWG14 wires.
Outdoor unit
Indoor
unit
Conduit
mounting
plate
Conduit
Lock nut
Back
Use AWG16 or AWG14 wire
for the inter-unit wiring.
Disengage the tab.
Figure 1: Removing the cover from
the indoor unit electrical
component box
Disengage the tab.
Cover of the indoor unit
electrical component box
Room Air Conditioners J-Series31
Page 33
Installation ManualEDUS041011
9
5-5. Prepare the accessory (separate product) [Figure 2].
1) Remove the cover from the accessory (separate product).
2) Insert the connection cord into connector “S21” (white) in the accessory (separate product).
3) Route each of the connection cords through the cut-outs in the accessor y, then reinstall the accessory cover in its
original position.
4) Insert the accessory (separate product) connector into connector “S403” in the indoor unit electrical component box.
Then route the connection cord through the cut-out in the indoor unit electrical component box.
5-6. Install the cover of the electrical component box in its original position [Figure 3].
5-7. Install the accessory (separate product) [Figure 3].
1) Install the accessory (separate product) into the indoor unit electrical component box.
2) Route the connection cord as shown in [Figure 3].
* 5-8. Install the indoor unit electrical component box in its original position.
1) Install the louver.
2) Install the electrical component box (1 screw).
3) Install the thermistor in its original position on the heat exchanger.
4) Install the connector (S200) in its original position.
5) Connect the communication wiring in its original position.
5-9. Install the front grille in its original position (2 screws).
5-10. Install the service lid (1 screw).
Figure 2: Preparing the accessory
Remove the accessory cover.
Accessory
Insert “S403”.
Disengage the tab.
Route each of the
“S21”
connection cords.
Figure 3: Installing the accessory
Install the accessory cover
in its original position.
Accessory
cover
Accessory
Accessory cover
Install the accessory.
Route the connection
cords through the cut-outs.
Cut-outs for the connection cords
Cut-out for the “S403”
connection
Cut-out for the
connection cord
32Room Air Conditioners J-Series
Page 34
EDUS041011Installation Manual
10
Indoor Unit Installation
6.
Drain piping
1) Connect the drain hose, as described right.
2) Remove the air filters and pour some water into the drain pan to check the water
flows smoothly.
3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.
[Figure of hose front end]
4) When extending the drain hose, use a commercially available
extension hose with an inner diameter of 5/8 inch (16mm).
Be sure to thermally insulate the indoor section of the extension
hose.
5) When connecting a rigid polyvinyl chloride pipe
(nominal diameter 1/2 inch (13mm)) directly to
the drain hose attached to the indoor unit as
with embedded piping work, use any
commercially available drain socket (nominal
diameter 1/2 inch (13mm)) as a joint.
Refrigerant Piping Work
1.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward
so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
The drain hose should
be inclined downward.
No trap is permitted.
Do not put the end
of the hose in water.
φ11/16” (φ18mm)φ5/8” (φ16mm)
φ5/8”
(φ16mm)
The drain hose provided
to indoor unit.
Indoor unit
drain hose
φ5/8”
(φ16mm)
Extension drain hose
Heat insulation tube
(field supply)
Commercially available drain socket
(nominal diameter 1/2 inch (13mm))
Commercially available rigid
polyvinyl chloride pipe
(nominal diameter 1/2 inch
(13mm))
The drain hose provided
to indoor unit.
φ18
Set exactly at the position shown below.
A
Flaring
Die
A
0-0.020 inch (0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch (1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch (1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
(Cut exactly at
right angles.) Remove burrs.
Check
Flare’s inner surface
must be flaw-free.
The pipe end must
be evenly flared in a
perfect circle.
Make sure that the
flare nut is fitted.
Room Air Conditioners J-Series33
Page 35
Installation ManualEDUS041011
11
2.
Refrigerant piping
CAUTION
• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
2-1. Caution on piping handling
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender
for bending.
2-2.
Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to
0.045kcal/mh°C))
2) Be sure to insulate both the gas and liquid piping and to provide insulation
dimensions as below.
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Gas sideLiquid side
Gas pipe thermal
insulation
Liquid pipe thermal
insulation
O.D. 3/8 inch (9.5mm) O.D. 1/4 inch (6.4mm)
I.D. 0.427-0.590 inch
(12-15mm)
I.D. 0.315-0.393 inch
(8-10mm)
Minimum bend radiusThickness 0.393 inch (10mm) Min.
1-3/16 inch (30mm) or more
Thickness 0.031 inch (0.8mm) (C1220T-O)
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration oil to
the inner surface of the
flare.
Do not apply refrigeration
oil to the flare nut avoid
tightening with over torque.
[Apply oil]
Tor que wrench
Piping union
Flare nut
Spanner
[Tighten]
Flare nut tightening torque
Gas sideLiquid side
3/8 inch (9.5mm)1/4 inch (6.4mm)
24.1-29.4ft • lbf
(32.7-39.9N • m)
10.4-12.7ft • lbf
(14.2-17.2N • m)
Wall
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Be sure to
place a cap.
Rain
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Inter-unit wiring
Be sure to use insulation that is designed for use with HVAC Systems.
34Room Air Conditioners J-Series
Page 36
EDUS041011Installation Manual
12
Trial Operation and Testing
1.
Trial operation and testing
1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.
For Heat pump
•
In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable
temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
Use the remote controller for trial operation as described below.
2) After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to 28°C) in cooling mode,
68°F to 75°F (20°C to 24°C) in heating mode).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
For Cooling only
• Select the lowest programmable temperature.
1) Trial operation in cooling mode may be disabled depending on the room temperature.
Use the remote controller for trial operation as described below.
2) After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to 28°C)).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts,
such as fin movement, are working properly.
• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some
time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation
mode when the circuit breaker is opened again.
2.
Test items
Test items
Symptom
(diagnostic display on RC)
Check
Indoor and outdoor units are installed properly on solid bases.Fall, vibration, noise
No refrigerant gas leaks.
Incomplete cooling/heating
function
Refrigerant gas and liquid pipes and indoor drain hose extension are
thermally insulated.
Water leakage
Draining line is properly installed.Water leakage
System is properly grounded.Electrical leakage
The specified wires are used for inter-unit wiring connections.Inoperative or burn damage
Indoor or outdoor unit’s air inlet or air outlet has clear path of air.
Stop valves are opened.
Incomplete cooling/heating
function
Indoor unit properly receives remote control commands.Inoperative
1) Press “ON/OFF” button to turn on the system.
2) Press “TEMP” button (2 locations) and “MODE” button at the same time.
3) Press “MODE” button twice.
(“ ” will appear on the display to indicate that trial operation mode is selected.)
4) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press
“ON/OFF” button.
Trial operation from remote controller
3P253189-1
Room Air Conditioners J-Series35
Page 37
Installation ManualEDUS041011
1
Safety Precautions
• Read these Safety Precautions carefully to ensure correct installation.
• This manual classifies the precautions into DANGER, WARNING and CAUTION.
Be sure to follow all the precautions below: they are all important for ensuring safety.
DANGER............... Indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING ............. Failure to follow any of WARNING is likely to result in such grave consequences as death or serious
injury.
CAUTION .............. Failure to follow any of CAUTION may in some cases result in grave consequences.
• The following safety symbols are used throughout this manual:
• After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use
and cleaning of the unit according to the Operation Manual.
Be sure to observe this instruction.Be sure to establish a ground connection.Never attempt.
DANGER
• Refrigerant gas is heavier than air and replaces oxygen. A massive leak could lead to oxygen depletion, especially
in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• If the refrigerant gas leaks during installation, ventilate the area immediately.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device.
Exposure to this gas could cause severe injury or death.
• After completing the installation work, check that the refrigerant gas does not leak.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device.
Exposure to this gas could cause severe injury or death.
• Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could cause a
severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an
explosion which could lead to severe injury or death.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that children will not play with them.
Children playing with plastic bags face the danger of death by suffocation.
• Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious
injury or death.
• Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock
hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which
could lead to severe injury or death.
WARNING
• Installation should be left to the authorized dealer or another trained professional.
Improper installation may cause water leakage, electrical shock, fire, or equipment damage.
• Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire or equipment damage.
• Be sure to use the supplied or exact specified installation parts.
Use of other parts may cause the unit to come to fall, water leakage, electrical shock, fire or equipment damage.
• Install the air conditioner on a solid base that is level and can support the weight of the unit.
An inadequate base or incomplete installation may cause injury or equipment damage in the event the unit falls off the base or comes loose.
• Electrical work should be carried out in accordance with the installation manual and the national, state and local
electrical wiring codes.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire or equipment damage.
• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
Follow all appropriate electrical codes.
• For wiring, use a wire or cable long enough to cover the entire distance with no splices if possible.
Do not use an extension cord. Do not put other loads on the power supply.
Use an only a separate dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock, fire or equipment damage.)
• Use the specified types of wires for electrical connections between the indoor and outdoor units.
Follow all state and local electrical codes.
Firmly clamp the inter-unit wiring so their terminals receive no external stresses.
Incomplete connections or clamping may cause terminal overheating, fire or equipment damage.
11.2Outdoor Units
36Room Air Conditioners J-Series
Page 38
EDUS041011Installation Manual
2
Safety Precautions
WARNING
• After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical
covers, panels or terminals.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, fire or equipment damage.
• When installing or relocating the system, be sure to keep the refrigerant circuit free from all substances other than
the specified refrigerant (R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which may result in rupture, resulting
in injury.)
• During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed,
causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing
abnormally high pressure which could lead to equipment damage and personal injur y.
• Be sure to install a ground fault circuit interrupter breaker.
Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.
CAUTION
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual.
Inadequate piping may cause water damage.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small
animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around
the unit clean.
Room Air Conditioners J-Series37
Page 39
Installation ManualEDUS041011
3
Accessories
Accessories supplied with the outdoor unit:
Precautions for Selecting the Location
1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of
the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit wiring at least 10 feet (3m) away from television and radio sets. This is to prevent
interference to images and sounds. (Noises may be heard even if they are more than 10 feet (3m) away depending on radio wave
conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.
NOTE
Cannot be installed hanging from ceiling or stacked.
CAUTION
When operating the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described below.
• To prevent exposure to wind, install the outdoor unit with its suction
side facing the wall.
• Never install the outdoor unit at a site where the suction side may
be exposed directly to wind.
• To prevent exposure to wind, it is recommended to install a baffle
plate on the air discharge side of the outdoor unit.
• In heavy snowfall areas, select an installation site where the snow will not affect the unit.
(A) Installation manual1
(B) Drain plug (Heat pump models)
There is on the bottom packing case.
1
Construct a large canopy.
Construct a pedestal.
Install the unit high enough off the
ground to prevent burying in snow.
38Room Air Conditioners J-Series
Page 40
EDUS041011Installation Manual
4
Outdoor Unit
Installation Drawings
CAUTION
Set the piping length from
4.92ft (1.5m) to 49.2ft (15m).
Wrap the insulation pipe with
the finishing tape from bottom
to top.
In sites with poor drainage, use
block bases for outdoor unit.
Adjust foot height until the unit
is leveled. Otherwise, water
leakage or pooling of water may
occur.
Where there is a danger of the unit
falling, use foot bolts, or wires.
Allow space for piping
and electrical servicing.
9-27/32 (250) from wall
unit: inch (mm)
O.D. 3/8 inch (9.5mm)
Gas pipe
Liquid pipe
O.D. 1/4 inch (6.4mm)
0.22oz/ft
Max. allowable length
39.3ft (12m)
49.2ft (15m)
Max. allowable height
Additional refrigerant
required for refrigerant
pipe exceeding
33ft (10m) in length.
*
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced perfomance.
*
The suggested shortest pipe length is 4.92ft (1.5m), in order to
avoid noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
4.92ft (1.5m)
Min. allowable length
18-1/2 (470)
(Foot bolt-hole centers)
(From unit’s side)
3-25/32 (96)
(Foot bolt-hole
centers)
11-13/16 (300)
How to remove the stop
valve cover
Remove the screw on the
stop valve cover.
Slide the lid downward
to remove it.
How to attach the stop
valve cover
Insert the upper part of
the stop valve cover into the
outdoor unit to install.
Tighten the screws.
Stop valve cover
*
Room Air Conditioners J-Series39
Page 41
Installation ManualEDUS041011
5
Installation Guidelines
• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4 inch (1200mm) or less.
Precautions on Installation
• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10
foundation bolts, nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their length are 3/4 inch (20mm) from the foundation surface.
Outdoor Unit Installation
1.
Installing outdoor unit
1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation
Drawings”.
2) If drain work is necessary, follow the procedures below.
2.
Drain work (Heat pump models)
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place
additional foot bases of at least 1-1/4 inch (30mm) in height under the outdoor
unit’s feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
More than 1-15/16 (50)More than 1-15/16 (50)
More than 5-7/8 (150)
More than
3-15/16 (100)
More than 1-15/16 (50)More than 3-15/16 (100)
Side view
47-1/4
(1200)
or less
Wall facing one sideWalls facing two sides
Top view
Top view
unit: inch (mm)
More than 5-7/8 (150)
More than 11-13/16 (300)
More than 1-15/16 (50)
Walls facing three sides
3/4”
(20mm)
Drain port
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 5/8 inch (16mm))
40Room Air Conditioners J-Series
Page 42
EDUS041011Installation Manual
6
Outdoor Unit Installation
3.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
4.
Refrigerant piping
CAUTION
• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
A
Check
Flare’s inner
surface must
be flaw-free.
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
(Cut exactly at
right angles.) Remove burrs.
Flaring
Set exactly at the position shown below.
A
0-0.020 inch
(0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch
(1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch
(1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
Die
Flare nut tightening torque
Gas sideLiquid side
3/8 inch (9.5mm)1/4 inch (6.4mm)
24.1-29.4ft lbf 10.4-12.7ft lbf
(32.7-39.9N m) (14.2-17.2N m)
Valve cap tightening torque
Gas sideLiquid side
3/8 inch (9.5mm)1/4 inch (6.4mm)
15.9-20.2ft lbf 15.9-20.2ft lbf
(21.6-27.4N m) (21.6-27.4N m)
Service port cap 7.9-10.8ft lbf
tightening torque
(10.8-14.7N m)
Torque wrench
Piping union
Flare nut
Spanner
[Tighten]
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration oil to
the inner surface of the
flare.
Do not apply refrigeration
oil to the flare nut avoid
tightening with over torque.
[Apply oil]
•
••
••
••
•
•
•
Room Air Conditioners J-Series41
Page 43
Installation ManualEDUS041011
7
5.
Purging air and checking gas leakage
• When piping work is completed, it is necessary to purge the air and check for gas leakage.
WARNING
• Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum
pump or the unit.
• If using additional refrigerant, perform air purging from the refrigerant pipes and
indoor unit using a vacuum pump, then charge additional refrigerant.
• Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified
tightening torque.
*1. Pipe length vs. vacuum pump run time.
*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. Check
all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).
1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.
2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)
3) Do vacuum pumping and make sure that the compound pressure gauge reads –29.9inHg (–0.1MPa).*1.
4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.
(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.
5) Remove caps from liquid stop valve and gas stop valve.
6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.
After the check is complete, wipe all soapy water off.
7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.
(Do not attempt to turn valve rod beyond its stop.)
8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.
Pipe lengthUp to 49.2ft (15m)
Run timeNot less than 10 min.
Compound
pressure gauge
Pressure
meter
Highpressure
valve
Low-pressure
valve
Vacuum pump
Service port
Liquid
stop
valve
Valve caps
Gas stop valve
Charging
hoses
Gauge
manifold
42Room Air Conditioners J-Series
Page 44
EDUS041011Installation Manual
8
Outdoor Unit Installation
6.
Refilling the refrigerant
Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cau se the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon
attached” displayed on it.)
•Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
7.
Refrigerant piping work
7-1 Cautions on pipe handling
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender
for bending.
7-2 Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C))
2) Be sure to insulate both the gas and liquid piping and to provide insulation
dimensions as below.
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Gas sideLiquid side
Gas pipe
thermal insulation
Liquid pipe
thermal insulation
O.D. 3/8 inch
(9.5mm)
O.D. 1/4 inch
(6.4mm)
I.D. 0.472-0.591 inch
(12-15mm)
I.D. 0.315-0.393 inch
(8-10mm)
Minimum bend radiusThickness 0.393 inch (10mm) Min.
1-3/16 inch (30mm) or more
Thickness 0.031 inch (0.8mm) (C1220T-O)
Filling a cylinder with an attached siphon
Stand the cylinder upright when
filling.
There is a siphon pipe inside, so the
cylinder need not be upside-down to
fill with liquid.
Filling other cylinders
Turn the cylinder upside-down
when filling.
Wall
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Be sure to
place a cap.
Rain
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Inter-unit wiring
Be sure to use insulation that is designed for use with HVAC Systems.
Room Air Conditioners J-Series43
Page 45
Installation ManualEDUS041011
9
Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
How to forced cooling operation mode
Using the indoor unit ON/OFF button
Press the indoor unit ON/OFF button for at least 5 seconds. (Operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes.
To force a trial operation to stop, press the indoor unit ON/OFF button.
Using the main unit’s remote controller
1) Press the “ON/OFF” button. (Operation will start.)
2) Press the “TEMP” button and the “MODE” button at the same time.
3) Press the “MODE” button twice.
(
“”
will be displayed and the unit will enter trial operation.)
4) Press the “MODE” button to return the operation mode to cooling.
• Trial operation will stop automatically after around 30 minutes. To force a trial operation to stop, press the “ON/OFF”
button.
CAUTION
• When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
• After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced operation.
Gas
stop valve
Valve cap
Hexagonal
wrench
Close
Liquid
stop valve
44Room Air Conditioners J-Series
Page 46
EDUS041011Installation Manual
10
Wiring
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical
shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Be sure to install a ground fault circuit interrupter breaker. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used a ground fault circuit interrupter breaker capable handling
harmonics in order to prevent malfunctioning of the ground fault circuit interrupter breaker itself.)
• Use an all-pole disconnection type breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring connection, take care not to pull at the conduit.
• Do not turn on the safety breaker until all work is completed.
1) Strip the insulation from the wire (3/4 inch
(20mm)).
2) Connect the connection wires between the
indoor and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a flathead
screwdriver be used to tighten the screws.
The screws are packed with the terminal
board.
<Work before wiring>
A protection plate is fixed for protection from the high-voltage section.
Before staring wiring work, dismount the protection plate by removing the 2 screws and dismount the conduit mounting plate cover
by removing the 1 screw.
<Method of mounting conduit>
1) Pass wires through the conduit and secure them with a lock nut.
2) After completing the work, reattach the conduit mounting plate cover and the protection plate to its original position.
Observe the notes mentioned following when wiring to the power supply
terminal board.
Precautions to be taken for power supply wiring.
Use a round crimp-style terminal for connection to the power supply
terminal board. In case it cannot be used due to unavoidable reasons, be
sure to observe the following instruction.
Place the round crimp-style terminals on the wires up to the covered part
and secure in place.
1
2
3
123
Safety
breaker
15A
Ground fault
circuit interrupter
breaker
Ground
If the length of a connection wire is
33ft (10m) or more, use AWG14 wire.
Firmly fix the wires with
the terminal screws.
Outdoor unit
Indoor
unit
Power supply
60Hz 208-230V
Use AWG 14 wires.
L1L
2
1 2 3
123
Power supply
terminal block
Use the
specified wire
type and
connect it
securely.
Shape wires so
that the service
lid and stop
valve cover fit
securely.
Conduit
mounting
plate
Conduit
Lock nut
Conduit
mounting
plate cover
Protection
plate
Screw
Screws
Stranded wire
Round crimp-style
terminal
Room Air Conditioners J-Series45
Page 47
Installation ManualEDUS041011
11
CAUTION
• When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling.
Problems with the work may cause heat and fires.
3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
Strip wire end
to this point.
Excessive strip length
may cause electrical
shock or leakage.
GoodWrong
Stripping wire at terminal block
46Room Air Conditioners J-Series
Page 48
EDUS041011Installation Manual
12
Trial Operation and Testing
1.
Trial operation and testing
1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.
For heat pump
• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable
temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (78˚F to 82˚F (26˚C to 28˚C) in coo ling mode,
68˚F to 75˚F (2 0˚C to 24˚C) in heating mode).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
For cooling only
• Select the lowest programmable temperature.
1) Trial operation in cooling mode may be disabled depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (78˚F to 82˚F (26˚C to 28˚C)).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts,
such as fin movement, are working properly.
• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some
time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation
mode when the circuit breaker is opened again.
2.
Test items
Test items
Symptom
(diagnostic display on RC)
Check
Indoor and outdoor units are installed properly on solid bases.Fall, vibration, noise
No refrigerant gas leaks.
Incomplete cooling/heating
function
Refrigerant gas and liquid pipes and indoor drain hose extension are
thermally insulated.
Water leakage
Draining line is properly installed.Water leakage
System is properly grounded.Electrical leakage
The specified wires are used for inter-unit wiring connections.Inoperative or burn damage
Indoor or outdoor unit’s air inlet or air outlet has clear path of air.
Stop valves are opened.
Incomplete cooling/heating
function
Indoor unit properly receives remote control commands.Inoperative
Room Air Conditioners J-Series47
3P253189-4
Page 49
Safety ConsiderationsEDUS041011
12. Safety Considerations
Read these SAFETY CONSIDERATIONS for Operations carefully before operating air conditioning equipment. Make sure that
the unit operates properly during the startup operation. Instruct the customer on how to operate and maintain the unit.
Inform customers that they should store this Operation Manual with the Installation Manual for future reference.
Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols:
DANGER .............. Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING ............ Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION ............. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.
NOTE ................... Indicates situations that may result in equipment or property-damage accidents only.
• Do not install the unit in an area where flammable materials are present due to risk of explosion resulting in serious
injury or death.
• Any abnormalities in the operation of the air conditioner such as smoke or fire could result in severe injury or death.
Turn off the power and contact your dealer immediately.
• Refrigerant gas may produce toxic gas if it comes into contact with fire, such as from a fan, heater, stove, or cooking
device. Exposure to this gas could cause severe injury or death.
• For refrigerant leakage, consult your dealer. Refrigerant gas is heavier than air and replaces oxygen. A massive leak
could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious
injury or death.
• If equipment utilizing a burner is used in the same room as the air conditioner, there is the danger of oxygen
deficiency which could lead to an asphyxiation hazard resulting in serious injury or death. Be sure to ventilate the
room sufficiently to avoid this hazard.
• Safely dispose of the packing materials. Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
• Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with
plastic bags face the danger of death by suffocation.
• Contact your dealer for repair and maintenance. Improper repair and maintenance may result in water leakage,
electric shock, and fire. Only use accessories made by Daikin that are specifically designed for use with the
equipment and have them installed by a professional.
• Contact your dealer to move and reinstall the air conditioner. Incomplete installation may result in water leakage,
electric shock, and fire.
• Never let the indoor unit or the remote controller get wet. Water can cause an electric shock or a fire.
• Never use flammable spray such as hair spray, lacquer, or paint near the unit. Flammable spray may cause a fire.
• When a fuse blows out, never replace it with one of incorrect ampere ratings or different wires. Always replace any
blown fuse with a fuse of the same specification.
• Never remove the fan guard of the unit. A fan rotating at high speed without the fan guard is very dangerous.
• Never inspect or service the unit by yourself. Contact a qualified service person to perform this work.
• Turn off all electrical power before doing any maintenance to avoid the risk of serious electric shock; never sprinkle
or spill water or liquids on the unit.
• Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock.
• Do not allow children to play on or around the unit to prevent injury.
48Room Air Conditioners J-Series
Page 50
EDUS041011Safety Considerations
• The heat exchanger fins are sharp enough to cut. To avoid injury wear gloves or cover the fins while working around
them.
• Do not put a finger or other objects into the air inlet or air outlet. The fan is rotating at high speed and will cause injury.
• Check the unit foundation for damage on a continuous basis, especially if it has been in use for a long time. If left in
a damaged condition the unit may fall and cause injury.
• Placing a flower vase or other containers with water or other liquids on the unit could cause a shock or fire if a spill
occurs.
• Do not touch the air outlet or horizontal blades while the swing flap is in operation because fingers could get caught
and injured.
• Never touch the internal parts of the controller. Do not remove the front panel because some parts inside are
dangerous to touch. To check and adjust internal parts, contact your dealer.
• Do not use the air conditioner for any other purposes other than comfort cooling or heating. Do not use the unit for
cooling precision instruments, food, plants, animals or works of art.
• Do not place items under the indoor unit as they may be damaged by condensates that may form if the humidity is
above 80% or if the drain outlet gets blocked.
• Before cleaning, stop the operation of the unit by turning the power off or by pulling the supply cord out from its
receptacle. Otherwise, an electric shock and injury may result.
• Do not wash the air conditioner with excessive water. An electric shock or fire may result.
• Avoid placing the controller in a spot splashed with water. Water entering the controller may cause an electric shock
or damage the internal electronic parts.
• Do not operate the air conditioner when using a room-fumigation type of insecticide. Failure to observe this could
cause the chemicals to be deposited in the unit and can endanger the health of those who are hypersensitive to
chemicals.
• Do not turn off the power immediately after stopping operation. Always wait for at least five minutes before turning
off the power. Otherwise, water leakage may occur.
• The appliance is not intended for use by young children or infirm persons without supervision.
• The remote controller should be kept away from children so they cannot play with it.
• Consult with the installation contractor for cleaning.
• Incorrect cleaning of the inside of the air conditioner could make the plastics parts break and cause water leakage or
electric shock.
• Do not touch the air inlet or aluminum fin of the air conditioner as they can cut and cause injury.
• Do not place objects in direct proximity of the outside unit. Do not let leaves and other debris accumulate around the
unit. Leaves are a hotbed for small animals which can enter the unit. Once inside the unit, animals can cause the unit
to malfunction, and cause smoke or fire when they make contact with electrical parts.
• Never press the button of the remote controller with a hard, pointed object. The remote controller may be damaged.
• Never pull or twist the electric wire of the remote controller. It may cause the unit to malfunction.
• Do not place appliances that produce open flames in places that are exposed to the air flow of the unit or under the
indoor unit. It may cause incomplete combustion or deformation of the unit due to the heat.
• Do not expose the controller to direct sunlight. The LCD display can become discolored and may fail to display the
data.
Room Air Conditioners J-Series49
Page 51
Safety ConsiderationsEDUS041011
• Do not wipe the controller operation panel with benzene, thinner, chemical dust cloth, etc. The panel may get
discolored or the coating can peel off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it
well and wipe the panel clean. Then wipe it with another dry cloth.
• Dismantling of the unit, disposal of the refrigerant, oil, and additional parts, should be done in accordance with the
relevant local, state, and national regulations.
• Operate the air conditioner in a sufficiently ventilated area and not surrounded by obstacles. Do not use the air
conditioner in the following places.
a. Places with a mist of mineral oil, such as cutting oil.
b. Locations such as coastal areas where there is a lot of salt in the air.
c. Locations such as hot springs where there is a lot of sulfur in the air.
d. Locations such as factories where the power voltage varies a lot.
e. In cars, boats, and other vehicles.
f. Locations such as kitchens where oil may splatter or where there is steam in the air.
g. Locations where equipment produces electromagnetic waves.
h. Places with an acid or alkaline mist.
i. Places where fallen leaves can accumulate or where weeds can grow.
• Take snow protection measures. Contact your dealer for the details of snow protection measures, such as the use of
a snow protection hood.
• Do not attempt to do electrical work or grounding work unless you are licensed to do so. Consult with your dealer for
electrical work and grounding work.
• Pay Attention to Operating Sound. Be sure to use the following places:
a. Places that can sufficiently withstand the weight of the air conditioner yet can suppress the operating sound and
vibration of the air conditioner.
b. Places where warm air from the air outlet of the outside unit or the operating sound of the outside unit does not
annoy neighbors.
• Make sure that there are no obstacles close to the outside unit. Obstacles close to the outside unit may drop the
performance of the outside unit or increase the operating sound of the outside unit.
• Consult your dealer if the air conditioner in operation generates unusual noise.
• Make sure that the drainpipe is installed properly to drain water. If no water is discharged from the drainpipe while the
air conditioner is in the cooling mode, the drainpipe may be clogged with dust or dirt and water leakage from the
indoor unit may occur. Stop operating the air conditioner and contact your dealer.
50Room Air Conditioners J-Series
Page 52
EDUS041011Safety Considerations
Room Air Conditioners J-Series51
Page 53
Safety ConsiderationsEDUS041011
52Room Air Conditioners J-Series
Page 54
EDUS041011Safety Considerations
Room Air Conditioners J-Series53
Page 55
Safety ConsiderationsEDUS041011
54Room Air Conditioners J-Series
Page 56
EDUS041011Safety Considerations
Room Air Conditioners J-Series55
Page 57
Safety ConsiderationsEDUS041011
56Room Air Conditioners J-Series
Page 58
EDUS041011Safety Considerations
Room Air Conditioners J-Series57
Page 59
Safety ConsiderationsEDUS041011
58Room Air Conditioners J-Series
Page 60
EDUS041011Safety Considerations
Room Air Conditioners J-Series59
Page 61
Safety ConsiderationsEDUS041011
60Room Air Conditioners J-Series
Page 62
EDUS041011Safety Considerations
Room Air Conditioners J-Series61
Page 63
Safety ConsiderationsEDUS041011
62Room Air Conditioners J-Series
Page 64
EDUS041011Safety Considerations
Room Air Conditioners J-Series63
Page 65
Safety ConsiderationsEDUS041011
64Room Air Conditioners J-Series
Page 66
EDUS041011Safety Considerations
Room Air Conditioners J-Series65
Page 67
Safety ConsiderationsEDUS041011
66Room Air Conditioners J-Series
Page 68
EDUS041011Safety Considerations
Room Air Conditioners J-Series67
Page 69
Safety ConsiderationsEDUS041011
68Room Air Conditioners J-Series
Page 70
EDUS041011Safety Considerations
Room Air Conditioners J-Series69
Page 71
Safety ConsiderationsEDUS041011
70Room Air Conditioners J-Series
Page 72
EDUS041011Safety Considerations
Room Air Conditioners J-Series71
Page 73
Safety ConsiderationsEDUS041011
72Room Air Conditioners J-Series
Page 74
EDUS041011Safety Considerations
Room Air Conditioners J-Series73
Page 75
Safety ConsiderationsEDUS041011
3P253185-1
74Room Air Conditioners J-Series
Page 76
EDUS041011Optional Accessories
13.Optional Accessories
13.1Option List
13.1.1 Indoor Units
Option NameFTK(X)S09/12JEVJU
1Wired Remote Controller
2Interface Adaptor for Wired Remote ControllerKRP980B1
5Remote Controller Loss Prevention with ChainKKF910A4
1 An interface adaptor (KRP980B1) and a cord (BRCW901A03 or BRCW901A08) are necessary.
2 Standard accessory
13.1.2 Outdoor Units
1BRC944B2
Length 3 m (Shielded Wire)BRCW901A03
Length 8 m (Shielded Wire)BRCW901A08
KAF970A46
Option NameRKS09/12JEVJURXS09/12JEVJU
1Drain Plug—KKP937A4
2Air Direction Adjustment GrilleKPW937A4
Room Air Conditioners J-Series75
Page 77
Optional AccessoriesEDUS041011
Switch box
(Field supplied parts)
Machine screws (M4 x 16)
For the field supplied switch box,
use optional accessories
KJB1111A or KJB2121A.
KJB2121A
CAUTION
1. No switch box or staple is supplied. Prepare them locally.
2. No remote controller cord is supplied. Prepare the optional remote controller cord 4 wire.
3. Be sure to turn off the power to any apparatus connected prior to mounting.
4. Prior to mounting equipment, touch something metallic such as a doorknob to remove static
electricity from your body. Never touch the remote controller board or the adapter board.
5. Keep the wiring away from any other power source lines to avoid electric noise (external noise).
6. Select a flat surface, wherever possible, to mount the remote controller. To prevent deformation
of the cases, do not overtighten the mounting screws.
Insert a bladed screwdriver into the concave ( ) in the remote controller lower case to remove the
upper case assembly (two locations).
(1) Exposed mounting
Secure the remote controller lower case with the
two supplied wood screws.
(2) Embedded mounting
Secure the remote controller lower case with the
two supplied machine screws.
The remote controller board is located on the
upper case. Take care not to scratch the
board with the screwdriver.
1. Securing the remote controller lower case
Upper case
Lower case
Screwdriver
To remove, insert and twist
the screwdriver slightly.
Wood screws (φ3.5mm x 16mm)
KJB1111A
13.2<BRC944B2> Wired Remote Controller
13.2.1 Installation Manual
76Room Air Conditioners J-Series
Page 78
EDUS041011Optional Accessories
Remove the upper case of the remote control adapter
and secure the lower case assembly.
During mounting of the remote
controller cord, be careful not to pinch
or otherwise damage the wires.
(Remote controller cord 4 wire)
2. Securing the remote control adapter
3. Wiring
4.
Placing the upper case assembly of the remote controller and the upper case of the remote controller adapter back into their original positions
5. Temperature indication change
Wood screws (φ3.5mm x 16mm)
(Mounting with supplied wood screws)
Remote control adapter (attached)
(Mounting with supplied double-face adhesive tape)
Double-face
adhesive tape
Attached
five-wire cord
Remote controller cord
(Note 1)
Connector
Connector
Connector
Tie-band
(to secure the cord)
Tie-band
(to secure the cord)
Tie-band
(to secure the cord)
Upper case
assembly
Lower case
(Cord drawn out on the back)
Catch the lower hook first.
(Cord drawn out on the top)
To remote control adapter
Remote controller
board
Remote controller
board
Note 1) Ground the both ends of the shielded wire.
Using wire cutters, make
a notch for wiring and
then seal the notch to
ensure it is waterproof.
To indoor unit S21-HA connector
Remote controller cord 4 wire
Item No.
BRCW901A03
BRCW901A08
Length
Approx. 3m (10ft)
Approx. 8m (26ft)
To change from Celsius temperature indication to Fahrenheit one
Press and hold down at the
same time for 5 seconds while the
Celsius temperature is indicated.
← See Operation Manual
3P202923-2B
Room Air Conditioners J-Series77
Page 79
Optional AccessoriesEDUS041011
4
Controller Commands and their Corresponding Functions
Run indicator lamp (green)
ON/OFF button
Press to start the system.
Press again to stop the system.
Mode select button
Swing button
Timer setting button
Sets the current time and timer.
Temperature adjustment
button
Adjusts the temperature setting.
Airflow rate button
Adjusts the airflow rate.
Time setting button
for the timer
Display
Timer select button
Displays the operating
conditions.
Clock setting button
( page 9)
( page 7)
( page 5)
Selects an operation mode.
Displays the operating
conditions.
Selects one of the following:
ONE TIME timer ON
DAILY timer ON
TIMER OFF
CAUTION
•This remote controller cannot be used together with a standard wireless remote controller.
Otherwise, what appears on this remote controller's display may fail to correspond to actual
operating conditions.
13.2.2 Operation Manual
78Room Air Conditioners J-Series
Page 80
EDUS041011Optional Accessories
5
Preparation before Operation
Checking the power
If nothing appears on the remote controller's
display, turn on the circuit breaker.
Setting the current time
1
Press
.
The current time starts blinking.
lights up.
2
Press and set the current time.
Hold the button down to rapidly advance the time.
3
Press
.
(This completes the current time setting)
The clock's accuracy is ±30 seconds per month.
blinks.
2
1
·
3
Avoid overcooling or overheating.
Moderate room temperature setting
contributes to power saving.
Hang a blind or a curtain on the window.
This will enhance the cooling/heating effect
by intercepting direct sunlight and drafts.
A clogged air filter reduces
the cooling/heating effect and wastes
energy. Clean the air filter monthly (every
two weeks as required) or so.
Please take note of the following points
Electric power is consumed even when the air
conditioner is not in operation.
When the unit is not used for a long period of
time such as during off-season, turn off the
breaker.
Operating conditions
If the operation is continued under any
conditions other than the following, the safety
device may work to stop the operation.
Also, dew may form on the indoor unit and drip
from it. (Cooling/DRY)
Operation limit differ according to the model.
Notes
To use the unit efficiently
Recommended
temperature setting
For cooling ·············· 26~28˚C (79˚F~82˚F)
For heating ············· 20~22˚C (68˚F~72˚F)
Cooling
DRY
Heating
Outdoor temp.
Room temp.
Indoor humidity
Outdoor temp.
Room temp.
Indoor humidity
Outdoor temp.
Room temp.
-10 to 46
˚C (14˚F to 115˚F)
18 to 32
˚C (64˚F to 90˚F)
Less than 80%
-10 to 46
˚C (14˚F to 115˚F)
18 to 32
˚C (64˚F to 90˚F)
Less than 80%
-15 to 20
˚C (5˚F to 68˚F)
Less than 27
˚C
Room Air Conditioners J-Series79
Page 81
Optional AccessoriesEDUS041011
6
1 Press and hold down at the
same time for 5 seconds while the
Celsius temperature is indicated.
Preparation before Operation
2 Press and hold down at the
same time for 5 seconds while
the Fahrenheit temperature is
indicated.
Setting Temperature Indication change
Temperature indication can be changed between Celsius and Fahrenheit before use.
1·2
Notes
Temperature indication change between Celsius and Fahrenheit on the remote controller
Change the temperature indication in the modes other than the DRY mode.
In the DRY mode, temperature indication setting cannot be changed because the temperature is not indicated.
When the Fahrenheit temperature indication is changed to Celsius one, the temperature value
(0.5˚C) will be rounded up. Thus, the preset temperature may be changed.
Example:
A preset temperature of 65˚F (equivalent to 18.5˚C) will be changed to 19˚C (66˚F) b y changing the temperature indication.
In this case, if you change the Celsius temperature indication again to the Fahrenheit one, the preset temperature is shown not as 65˚F but
as 66˚F (equivalent to 19˚C). If the preset temperature is 66˚F (equivalent to 19˚C) and is changed to the Celsius temperature indication,
the indication becomes 19˚C (66˚F). In this case, no change by the temperature indication change is observed.
When the temperature indication change is set, the preset temperature is transmitted to the
indoor unit so that the reception sound will be heard from the indoor unit.
To change from Celsius temperature
indication to Fahrenheit one
To change from Fahrenheit
temperature indication to Celsius one
80Room Air Conditioners J-Series
Page 82
EDUS041011Optional Accessories
7
1
Press
to select your desired
operation mode.
Each time the button is pressed, the mode
changes as follows.
The system does not have the FAN mode.
Automatic · DRY · Cooling · Heating Operation
2
Press .
The run indicator lamp lights up.
Select your desired operation mode.
Once preset, the system can get restarted in the same operation mode.
1
2
Run indicator lamp (green)
(Automatic)
(DRY)
(Heating)
(Cooling)
(DRY)(Cooling)
Cooling only
model
Heat pump
model
To stop the operation:
Press again.
The run indicator lamp goes out.
In Automatic, the temperature setting and
operation mode (DRY, Cooling or Heating) are
automatically selected according to the room
temperature and outdoor temperature at the
time of starting operation.
DRY operation
In this mode, humidity is removed from the air.
Note
While running in the DRY mode, you may
feel cool or warm air from the air outlet. In
this case, readjust the airflow direction with
the vertical airflow direction louvers. (except
Duct Connected type)
Automatic operation
Room Air Conditioners J-Series81
Page 83
Optional AccessoriesEDUS041011
8
Heating operation
Since the heating operation is performed by
taking the heat from outdoor into the room,
the heating capacity decreases as the outdoor
temperature lowers. If the room is not heated
sufficiently, it is recommended to use other
heating appliance at the same time.
Since the air conditioner heats the whole room
by circulating hot air, it takes some time to
heat the entire room completely.
If the outdoor unit gets frosted during heating
operation, the heating capacity is decreased.
In this case, the unit starts defrosting
operation.
No hot air comes out of the indoor unit during
defrosting operation.
To adjust the temperature and airflow rate:
To adjust the airflow direction:
( page 9)
Operation
mode
Setting
to be adjusted
AutomaticDRYCoolingHeating
(Temperature)
(Airflow rate)
Temperature
cannot be
adjusted.
Airflow rate
cannot be
adjusted.
Temperature is adjustable.
Recommended temperature
Cooling : 26˚C-28˚C (79˚F~82˚F)
Five levels of airflow rate setting
from " " to " " plus " " are available.
Heating : 20˚C-22˚C (68˚F~72˚F)
When the unit runs in the cooling or heating mode at a low airflow rate, the cooling or heating effect
may be insufficient.
82Room Air Conditioners J-Series
Page 84
EDUS041011Optional Accessories
9
Notes
In fixing the horizontal airflow direction, keep the horizontal airflow direction louvers tilted
downward in the heating mode, and keep them nearly horizontal level in the cooling or DRY mode.
This will enhance the cooling and heating effect.
On the air conditioners with vertical and horizontal swing function, be sure to adjust the airflow
directions using the remote controller. Do not forcibly adjust louvers by hand or a malfunction may
occur.
The horizontal airflow direction louvers
move up and down.
The louvers stop just when the
button is pressed.
Swing
Airflow direction
louvers stop
Adjustment of horizontal airflow direction
The automatic moving range of the horizontal airflow direction louvers varies depending on the
operation mode.
Room Air Conditioners J-Series83
Page 85
Optional AccessoriesEDUS041011
10
Wall Mounted Type (with horizontal swing function)
The horizontal airflow direction louvers
move up and down.
The horizontal airflow direction louvers
stop just when the button is pressed.
Then the vertical ones start moving
right and left.
The vertical airflow direction louvers
stop just when the button is pressed.
Swing horizontally
Swing vertically
Airflow direction
louvers stop
The vertical and horizontal louvers cannot move at the same time.
Note
The operating procedure and remote controller display are different depending on the
indoor unit being connected.
Read How to Adjust the Airflow Direction in the air conditioner’s Operation Manual.
Duct Connected Type (without swing function)
This function cannot be used.
84Room Air Conditioners J-Series
Page 86
EDUS041011Optional Accessories
11
Timer Operation
To select the ONE TIME timer
mode:
1
Press
to select the ONE TIME
timer mode.
Each time the button is pressed,
the modes change as follows.
The Timer Operation feature automatically turns off operation when you go to sleep and turns it back
on when you wake up.
Use the DAILY Timer mode on weekdays, and the ONE TIME timer mode on weekends.
To cancel the timer settings:
1 Press to clear the timer settings.
Precautions in setting the timer
Before starting the timer operation, make sure
the current time is correct. If not, set the clock
correctly. (
page 5)
In making time settings,
is displayed to
make it easy to disable the timer too.
If one minute has passed before making any
timer setting, the previous timer settings are
reintroduced and the timer is on standby.
In this case, use the
(time setting) button
and make your desired timer settings.
ONE TIME timer
DAILY timer
TIMER OFF
ON time
OFF time
(Timer settings displayed)
1
2·4·6
3·5
The timer lamp lights up.
The ONE TIME or
DAILY TIMER disappears
from the display, and the
timer lamp goes out too.
Notes
Even when the timer has been off, its
programmed settings are still in memory.
If the system has the timer control ON but
you start and stop it manually using the
ON/OFF button before the designated ON
time, the system will restart again at the
programmed ON time.
Timer operation
When the ON timer is programmed, the
system starts one hour (maximum) earlier
so that the temperature set by the remote
controller is reached just in time.
When the ONE TIME timer is programmed,
the current time is no longer displayed.
Room Air Conditioners J-Series85
Page 87
Optional AccessoriesEDUS041011
12
1
Press
to select the ONE TIME timer.
2 Press .
3 Press to make the ON timer setting.
Example of display with the ONE TIME timer programmed
ONE TIME timer
Once the timer has been activated and then deactivated, it is in the OFF mode.
The ON or OFF timers can be programmed.
light up.
ONE TIME
blinks.
Each time the button is pressed,
the setting changes in a 10minute increment or decrement.
Hold the button down to advance
quickly.
When the ON timer is not used,
save the setting as
4 Press .
5
Press
to make the OFF timer setting.
6 Press .
(The ONE TIME timer is now programmed.)
Both of the ON and OFF time
cannot be set as
blinks.
When the OFF timer is not used,
save the setting as .
ONE TIME timer
programmed.
The set time is
displayed.
ON timer activated
and system starts.
The ON timer setting
no longer displays.
OFF timer activated,
and system stops.
The timer setting no
longer displays.
Notes
In the following cases, reset the
clock (the time setting is kept in the
memory).
The circuit breaker has been
activated.
The power fails.
86Room Air Conditioners J-Series
Page 88
EDUS041011Optional Accessories
13
Timer Operation
To select the DAILY timer mode:
1
Press
to select the DAILY timer mode.
Each time the button is pressed, the modes
change as follows.
To cancel the timer settings:
1 Press to clear the timer settings.
Example of display with DAILY timer programmed
ONE TIME timer
DAILY timer
TIMER OFF
The timer lamp lights up.
1 2
12
ON time
24-hour timer display
OFF time
Timers
The settings of timers
and can be seen
at a glance.
Two pairs of ON and OFF time
settings can be programmed.
(Timer settings displayed)
1
2·3
2
The ONE TIME or
DAILY TIMER , and the
timer lamp are no longer
displayed.
Timers and
programmed.
Timer alone
programmed.
11
2
Note
The system starts and stops
repeatedly until the DAILY timer is
set off. Before you leave home for a
long time, set the DAILY timer off.
Room Air Conditioners J-Series87
Page 89
Optional AccessoriesEDUS041011
14
1
Press
to select the DAILY timer.
2
Make the ON and OFF time settings.
Take the steps from to .
Program example: 8:00
~ 10:00, and 18:00 ~ 23:00
DAILY timer
After programming, the system starts and stops each day at the preset times. Two pairs of time settings
can be programmed.
(Example: 8:00
~10:00, and 18:00 ~ 23:00)
DAILY timer indication appears.
lights up.
3
Press
.
The DAILY timer is now programmed.
Note
If the following appears on the display, the timer must be reprogrammed.
The 24-hour timer display
is blinking.
The 24-hour timer display
is blinking.
This means that Timers and are
programmed for the same time settings.
New time settings must be made.
This means that the timer has not been
programmed yet.
When the timer is not
used, save the setting
as
PressPress
to make the
timer setting.
1
Procedure
Settings
ON time setting
OFF time setting
OFF time setting
2
ON time setting
2
1
TimerTimer
When the timer is not
used, save the setting
as
88Room Air Conditioners J-Series
Page 90
EDUS041011Optional Accessories
15
Cleaning
Cleaning the remote controller
Wipe it clean with soft, dry cloth.
Do not use any water hotter than 40˚C (104˚F), or volatile liquids such as benzine, gasoline and
thinner, polishing powder, or anything hard such as a scrub brush.
When the unit is not used for a long time
On a sunny day, keep the system running for
half a day in the FAN mode to dry it up inside.
3
12
FAN mode
1
Press
to select the cooling
mode.
2
Press
to adjust the set
temperature to 32˚C (90˚F).
3
Press .
The airflow rate remains the same, and is not
adjustable.
Run the system when the room temperature
is below 28˚C (82˚F).
Finally turn off the circuit breaker dedicated for
the room air conditioner.
Clean the air filter and place it back into
position.
3P202922-2B
Room Air Conditioners J-Series89
Page 91
Optional AccessoriesEDUS041011
Inside indoor unit
This set
S602S601
S403
S21
Option
BRC944A2B
PCB of indoor unit
Note:
Wires indicated by
thick lines are
not provided to the set.
Flap
(in control of wind
directions upward
and downward)
Mounting position of the set
Electrical
component box
Safety Precautions
•
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies precautions into WARNING and CAUTION.
This set is an interface that connects a wired remote controller to a
room air conditioner.
Be sure to follow all the precautions below ; they are all important for
ensuring safety.
WARNING :
Failure to follow WARNING is very likely to result in
such grave consequences as death or serious injury.
CAUTION : Failure to follow CAUTION may result in serious
injury or property damage, and in certain
circumstances, may result in a grave consequence.
WARNING
CAUTION
•
After installation is complete, test the operation of the PCB set to
check for problems, and explain how to use the set to the end-user.
•
Starting and stopping the air conditioner and making mode and temperature
settings in the air conditioner through the wired remote controller (within a
range of 18˚C to 32˚C while in cooling mode, 14˚C to 30˚C while in heating
mode, but no temperature settings while in ventilation mode).
•
Monitoring the operating conditions, occurrence of errors, and contents of
errors of the air conditioner through the wired remote controller.
•
Restoring the operating condition of the air conditioner to the previous
condition at the time of power recovery in case of power failure.
•
Group control (i.e., the control a number of indoor units through a single
remote controller)
•
Monitoring of the following items:
Indoor temperature and operating conditions of thermo, compressor, indoor
fan, electric heater, and humidifier
•
Control of the following items:
Forced thermo OFF, filter sign display and reset, and air-conditioner charge
management
•
Energy-saving reference, low-noise reference, and demand reference
The set does not support the following functions.
Check that the set is provided with the following components.
ComponentComponent
Installation Manual
11
QuantityQuantity
Main component
Mounting PositionWiring
Components
Outline/Features
• Installation should be left to the dealer or another qualified
professional.
Improper installation by yourself may cause malfunction, electrical shock, or fire.
•
Install the set according to the instructions given in this manual.
Incomplete or improper installation may cause malfunction, electrical
shock, or fire.
•
Be sure to use the standard attachments or the genuine parts.
Use of other parts may cause malfunction, electrical shock, or fire.
• Disconnect power to the connected equipment before
starting installation.
Failure to do so may cause malfunction, electrical shock, or fire.
• An earth leakage circuit breaker should be installed.
If the breaker is not installed, electrical shock may occur.
•
Do not install the set in a location where there is danger of
exposure to inflammable gas.
Gas accumulated around the unit at the worst may cause fire.
• To prevent damage due to electrostatic discharge, touch
your hand to a nearby metal object (doorknob, aluminum
sash, etc.) to discharge static electricity from your body
before touching this kit.
Static electricity can damage this kit.
• Lay this cable separately from other power cables to avoid
external electrical noises.
Mounting Procedure
Mounting position
of the set
Electrical
component box
13.3<KRP980B1> Interface Adaptor for Wired Remote Controller
90Room Air Conditioners J-Series
Page 92
EDUS041011Optional Accessories
Rotating shaft
Service lid
Screw
Push
down.
Upper hook
Upper hook
2) Pull toward you.
1) Push up.
Removing and installing front panel
Removing and installing front grille
Opening service lid of indoor unit
• Removal method
1)Place your fingers in the indentations on the main unit
(one each on the left and right sides), and open the panel
until it stops.
2)Continue to open the front panel further while sliding the
panel to the right and pulling it toward you in order to
disengage the rotating shaft on the left side. To
disengage the rotating shaft on the right side, slide the
panel to the left while pulling it toward you.
• Installation method
Align the tabs of the front panel with the grooves, and push
all the way in. Then close slowly. Push the center of the
lower surface of the panel firmly to engage the tabs.
Place both hands under the center
of the front grille, and while
pushing up, pull it toward you.
Lightly pull the front
grille toward you with
one hand, and push
down on the hooks
with the fingers of your
other hand.
(3 locations)
<
When there is no work space because
the unit is close to ceiling
>
• Removal method
1)Remove front panel to remove the air filter.
2)Remove the screws (2) from the front grille.
3)In front of the mark of the front
grille, there are 3 upper hooks. Lightly
pull the front grille toward you with one
hand, and push down on the hooks
with the fingers of your other hand.
The service lid is of removable type.
• Opening method
1)Remove the single screw of the service lid.
2)Pull out the service lid frontward.
• Installation method
1)Install the front grille and firmly engage the upper
hooks (3 locations).
2)Install 2screws of the front grille.
3)Install the air filter and then mount the front panel.
Be sure to wear protection gloves.
CAUTION
Indentations on
the main unit
Push the rotating
shaft of the front
panel into the
groove.
mark area
(3 locations)
Upper hook
Room Air Conditioners J-Series91
Page 93
Optional AccessoriesEDUS041011
Positions of communication wiring and mounting
screw of electrical component box
Fig. 1
Position of thermistor
Fig. 3
Position of each
connector
Fig. 2
Electrical component box
Removing electrical component cover
Removing electrical component box
On completion of the connection of the
electrical component (this set), mount the
removed parts to the original positions.
If there is a workspace on the right-hand side of
the indoor unit, the installation work can be
conducted without removing the electrical
component box.
On completion of the connection of the
electrical component (this set), mount the
removed parts to the original positions.
* Refer to the surface page for the removal of each part in detail.
*1 Remove the front panel.
*2 Remove the front grille.
*3 Remove the service lid of the indoor unit.
4 Remove the cover of the electrical component cover.
1. Remove the flap (in control of wind directions upward and downward).
2. Disconnect the communication wiring (see Fig. 1).
3. Disconnect the S200 connector (see Fig. 2).
4. Disconnect the heat changer from the thermistor (see Fig. 3).
5. Remove the mounting screw of the electrical component box, and remove the electrical component box (see Fig. 1).
If there is a workspace on the right-hand side of the indoor unit, the installation work can be conducted without removing
the electrical component box.
WARNING
• Be sure to turn OFF the power at the time of
installation work.
Do not touch any electric parts with the power
turned ON. Otherwise, an electric shock may be
received.front panel.
Mounting screw of electrical
component box.
Remove the tabs.
Electric component
cover
Tab
Mounting screw of electrical
component box
Flap
Communication
wiring
Thermistor
Make sure that the mounting bracket
of the thermistor will not fall off.
S200
92Room Air Conditioners J-Series
Page 94
EDUS041011Optional Accessories
Preparing the electrical component (this set).
Installing electrical component
Remove the electrical
component cover.
Disengage
the tab.
S21
Route each connection
cord through the cut-out.
Electrical component
Cut-outs
Electric component cover
Cut-out A
S403 connection cut-out
Cut-out B
S403 connection cut-out
Cut-out C
Connection cord cut-out
*1 Connection cord cut-out
Routing connection cord
S403 connection cord
Connection cord
Fig. 1
Fig. 2
Connecting electrical component (this set)
1.
Prepare the electrical component (this set).
(See Fig. 1)
1) Remove the electrical component cover
of the set.
2) Insert the connection cord into the S21
connector (white) of the set.
3) Route each connection cord through the
cut-out of the set and mount the electrical
component cover to the original position.
4) Insert the connector of the set into the
S403 in the indoor unit electrical
component connector. Then route the
connection cord to the cut-out (cut-out A)
in the indoor unit electrical component.
2.
Mount the electrical component cover to
the original position. (See Fig. 2)
3.
Mount the set. (See Fig. 2)
1) Mount the set to the electrical component
box of the indoor unit.
2) Route the connection cord as shown in
Fig. 2 (Routing connection cord).
*1
Route the connection
cord through the cut-out
(cut-out A).
Insert the cord
into the S403.
Fit in.
Place the connection cord to come
in contact with the protruding part.
Connection cord
Protruding part
Install the electrical component cover
in its original position.
Install the electrical component.
Push the electrical component until it
snaps into engagement with the tab.
Electrical component
Electric component cover
Tab
3P214218-1
Room Air Conditioners J-Series93
Page 95
Optional AccessoriesEDUS041011
b)
Checking the parts
Installation of Louver
CAUTION
Louver
1piece1piece
Shape
Quantity
Selection of Installation Location
Check the following parts
a)
Before Installation
Installation Procedure
Use when installing in a location that meets the following conditions.
When installing near the border to a neighbor's house
If exhaust blows directly on passers-by because outdoor unit is installed facing a road.
Changing the fan direction of the outdoor unit to prevent it blowing directly on shrubbery, etc.
Installation is possible in the four directions:
upward, downward, rightward, and leftward.
The installation screws are attached to the louver.
First temporarily attach the louver with 4 screws,
then check that the angle is correct, and finally
tighten the screws fully.
1.Install so that a short circuit is prevented.
2.For the use in snowy regions, avoid installation
with the air outlet facing upward. Install so that
the air outlet faces leftward, rightward, or downward.
Snow accumulates in the air outlet of the outdoor
unit, causing malfunction of the main body of the
outdoor unit.
3.Be advised that if the fan direction is up,
dead leaves and other foreign matter
easily accumulates in the exhaust vent.
Name
With 4 screws
Installation manual
Prepared hole
pitch 435mm
Fan partition
Prepared hole
pitch 435mm
Fan partition
Part A
(see figure below)
The prepared hole is in between the grating
of the grille. Part A (prepared hole) cross
section (the shape of either a or b)
Grille grating
Prepared holePrepared hole
Grille grating
4P104499-1A
13.4<KPW937A4> Air Direction Adjustment Grille
94Room Air Conditioners J-Series
Page 96
Specifications, designs and other content appearing in this brochure are current as of April 2010 but subject to change without notice.
AMERICAS
1645 Wallace Drive, Suite 110
Carrollton, TX75006
info@daikinac.com
www.daikinac.com
EDUS041011
Printed in U.S.A. 04/2010 B AK
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.