Daikin FTKS12JEVJU, RXS09JEVJU, RKS12JEVJU, RXS12JEVJU, RKS09JEVJU User Manual

...
- Cooling Only / Heat Pump -
EDUS041011
SEER 18 Models
J-Series
EDUS041011
Room Air Conditioners
J-Series
The Single Split Duct-Free System
FTKS09JEVJU
RKS09JEVJU
Cooling Only
FTKS12JEVJU
FTXS09JEVJU
RKS12JEVJU
RXS09JEVJU
Heat Pump
FTXS12JEVJU
1. Power Supply ..........................................................................................3
2. Functions.................................................................................................4
3. Specifications ..........................................................................................5
3.1 Cooling Only.............................................................................................5
3.2 Heat Pump ...............................................................................................6
4. Dimensions .............................................................................................7
4.1 Indoor Units ..............................................................................................7
4.2 Outdoor Units ...........................................................................................8
5. Wiring Diagrams......................................................................................9
5.1 Indoor Units ..............................................................................................9
5.2 Outdoor Units ...........................................................................................9
6. Piping Diagrams....................................................................................10
6.1 Indoor Units ............................................................................................10
6.2 Outdoor Units .........................................................................................11
7. Capacity Tables ....................................................................................12
7.1 Cooling Only...........................................................................................12
7.2 Heat Pump .............................................................................................14
7.3 Capacity correction factor by the length of refrigerant piping ................ 18
8. Operation Limit......................................................................................19
9. Sound Level ..........................................................................................20
9.1 Measuring Location ................................................................................20
9.2 Octave Band Level .................................................................................21
10.Electric Characteristics..........................................................................23
11.Installation Manual ................................................................................24
11.1 Indoor Units ............................................................................................24
11.2 Outdoor Units .........................................................................................36
12. Safety Considerations ..........................................................................48
13.Optional Accessories ............................................................................75
13.1 Option List ..............................................................................................75
RXS12JEVJU
Room Air Conditioners J-Series 1
EDUS041011
13.2 <BRC944B2> Wired Remote Controller.................................................76
13.3 <KRP980B1> Interface Adaptor for Wired Remote Controller...............90
13.4 <KPW937A4> Air Direction Adjustment Grille........................................94
2 Room Air Conditioners J-Series
EDUS041011 Power Supply
1. Power Supply
Indoor Units Outdoor Units Power Supply
FTKS09JEVJU RKS09JEVJU
The Single Split
Duct-Free System
Power Supply Intake ; Outdoor Unit
FTKS12JEVJU RKS12JEVJU
FTXS09JEVJU RXS09JEVJU
FTXS12JEVJU RXS12JEVJU
, 208-230V, 60Hz
1
Note:
Room Air Conditioners J-Series 3
Functions EDUS041011
2. Functions
Category Functions
FTKS09/12JEVJU
RKS09/12JEVJU
Basic Function
Compressor Oval Scroll Compressor Air Filter (Prefilter) 
Comfortable Airflow
Comfort Control
Operation Automatic Operation DIII-NET Compatible (Adaptor) (Option)
Lifestyle Convenience
Inverter (with Inverter Power Control) Health &
50~
Operation Limit for Cooling (°FDB)
Operation Limit for Heating (°FWB) 5~68
PAM Control 
Swing Compressor  Wipe-clean Flat Panel 
Rotary Compressor Washable Grille
Reluctance DC Motor  Filter Cleaning Indicator
Power-Airflow Louver (Horizontal Blade)
Power-Airflow Dual Louvers Timer 24-Hour ON/OFF Timer 
Power-Airflow Diffuser NIGHT SET Mode 
Wide-Angle Fins (Vertical Blades) Worry Free
Vertical Auto-Swing (Up and Down)  Self-Diagnosis (Digital, LED) Display 
Horizontal Auto-Swing (Right and Left) Wiring Error Check
3-D Airflow
COMFORT AIRFLOW Operation 
Auto Fan Speed  Flexible Voltage Correspondence
Indoor Unit Quiet Operation  High Ceiling Application
NIGHT QUIET Mode (Automatic) Chargeless
Outdoor Unit Quiet Operation (Manual) Either Side Drain (Right or Left) 
INTELLIGENT EYE Operation Power Selection
Quick Warming Function
Hot-Start Function
Automatic Defrosting
Program Dry Function Remote
Fan Only  Wired 
New POWERFUL Operation (Non-Inverter)
Inverter POWERFUL Operation 
Priority-Room Setting
COOL / HEAT Mode Lock
HOME LEAVE Operation
ECONO Operation 
Indoor Unit ON/OFF Button 
Signal Receiving Sign 
Temperature Display
Another Room Operation
114.8
50~
114.8
 Good-Sleep Cooling Operation
——
Category Functions
FTXS09/12JEVJU
RXS09/12JEVJU
Clean
“Reliability & Durability”
Flexibility Multi-Split / Split Type Compatible
Remote Control
Controller
Air-Purifying Filter
Photocatalytic Deodorizing Filter
Air-Purifying Filter with Photocatalytic Deodorizing Function
Titanium Apatite Photocatalytic Air-Purifying Filter
Auto-Restart (after Power Failure) 
Anti-Corrosion Treatment of Outdoor Heat Exchanger
Indoor Unit
5-Rooms Centralized Controller (Option)
Remote Control Adaptor (Normal Open-Pulse Contact) (Option)
Remote Control Adaptor (Normal Open Contact) (Option)
Wireless 
FTKS09/12JEVJU
RKS09/12JEVJU
FTXS09/12JEVJU
——


——
32.8ft 32.8ft
——
——
——
RXS09/12JEVJU
Note:  : Holding Functions
— : No Functions
4 Room Air Conditioners J-Series
EDUS041011 Specifications
3. Specifications
3.1 Cooling Only
Models
60Hz 208-230V
Capacity Rated (Min.~Max.)
Running Current (Rated) A 4.1-3.7 4.1-3.7 Power Consumption Rated Power Factor % 79.7-79.9 93.8-94.0 COP (Rated) (Min.~Max.) W/W 3.66 (3.94~3.48) 3.66 (3.94~2.98) EER (Rated) (Min.~Max.)
Piping Connections
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length feet 49.2 49.2 Max. Interunit Height Difference feet 39.3 39.3 Chargeless feet 32.8 32.8 Amount of Additional Charge of
Refrigerant
Indoor Units FTKS09JEVJU FTKS12JEVJU
Front Panel Color White White
Airflow Rate m³/min (cfm)
Fan
Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.20-0.18 0.20-0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.2-96.6 96.2-96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) inch 11-9/64×30-5/16×7-51/64 11-9/64×30-5/16×7-51/64 Packaged Dimensions (H×W×D) inch 10-17/64×33-7/32×13-15/32 10-17/64×33-7/32×13-15/32 Weight Lbs 16 16 Gross Weight Lbs 24 24 Operation Sound H/M/L/SL dBA 40 / 33 / 26 / 22 41 / 34 / 27 / 23 Sound Power dBA 56 57
Outdoor Units RKS09JEVJU RKS12JEVJU
Casing Color Ivory White Ivory White
Compressor
Refrigerant Oil
Refrigerant
Airflow Rate m³/min (cfm) H 26.1 (921) 26.1 (921)
Fan
Running Current (Rated) A 3.90-3.52 3.90-3.52 Power Consumption (Rated) W 640 760 Power Factor % 78.9-79.1 93.7-93.9 Starting Current A 4.1 4.8 Dimensions (H×W×D) inch 21-21/32×25-29/32×10-13/16 21-21/32×25-29/32×10-13/16 Packaged Dimensions (H×W×D) inch 23-5/16×30-23/64×13-45/64 23-5/16×30-23/64×13-45/64 Weight Lbs 66 66 Gross Weight Lbs 75 75 Operation Sound dBA 48 48 Sound Power dBA 62 62 Drawing No. C: 3D066330B C: 3D066331B
Indoor Units FTKS09JEVJU FTKS12JEVJU Outdoor Units RKS09JEVJU RKS12JEVJU
(Min.~Max.)
Liquid inch 1/4 1/4 Gas inch 3/8 3/8 Drain inch 5/8 5/8
Type Cross Flow Fan Cross Flow Fan Motor Output W 16 16 Speed Steps 5 Steps, Quiet and Auto 5 Steps, Quiet and Auto
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 750 750 Type FVC50K FVC50K Charge oz 12.5 12.5 Type R-410A R-410A Charge Lbs 2.20 2.20
Type Propeller Propeller Motor Output W 33 33
kW 2.49 (1.30~2.78) 2.93 (1.3~3.52)
Btu/h 8,500 (4,400~9,500) 10,000 (4,400~12,000)
kal/h 2,140 (1,120~2,390) 2,520 (1,120~3,030)
W 680 (330~800) 800 (330~1,180)
Btu/h·W
oz/ft 0.22 0.22
H 9.2 (325) 9.3 (328)
M 7.4 (261) 7.7 (272)
L 5.3 (187) 5.6 (198)
SL 4.0 (141) 4.4 (155)
12.50 (13.33~11.90) 12.50 (13.33~10.20)
Note:
The data are based on the conditions shown in the table below.
Cooling Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
25ft
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Room Air Conditioners J-Series 5
Specifications EDUS041011
3.2 Heat Pump
Models
60Hz 208-230V
Capacity Rated (Min.~Max.)
Running Current (Rated) A 4.1-3.7 4.0-3.6 4.1-3.7 4.8-4.3 Power Consumption Rated Power Factor % 79.7-79.9 93.1-93.6 93.8-94.0 93.1-94.0 COP (Rated) (Min.~Max.) W/W 3.66 (3.94~3.48) 3.78 (4.19~4.05) 3.66 (3.94~2.98) 3.78 (4.19~3.20) EER (Rated) (Min.~Max.)
Piping Connections
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length feet 49.2 49.2 Max. Interunit Height Difference feet 39.3 39.3 Chargeless feet 32.8 32.8 Amount of Additional Charge of
Refrigerant
Indoor Units FTXS09JEVJU FTXS12JEVJU
Front Panel Color White White
Airflow Rate m³/min (cfm)
Fan
Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.20-0.18 0.20-0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.2-96.6 96.2-96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) inch 11-9/64×30-5/16×7-51/64 11-9/64×30-5/16×7-51/64 Packaged Dimensions (H×W×D) inch 10-17/64×33-7/32×13-15/32 10-17/64×33-7/32×13-15/32 Weight Lbs 16 16 Gross Weight Lbs 24 24 Operation Sound H/M/L/SL dBA 40 / 33 / 26 / 22 40 / 34 / 28 / 25 41 / 34 / 27 / 23 41 / 35 / 29 / 26 Sound Power dBA 56 57
Outdoor Units RXS09JEVJU RXS12JEVJU
Casing Color Ivory White Ivory White
Compressor
Refrigerant Oil
Refrigerant
Airflow Rate m³/min (cfm) H 26.1 (921) 26.1 (921)
Fan
Running Current (Rated) A 3.90-3.52 3.80-3.42 3.90-3.52 4.60-4.12 Power Consumption (Rated) W 640 735 760 890 Power Factor % 78.9-79.1 93.0-93.4 93.7-93.9 93.0-93.9 Starting Current A 4.1 4.1 4.8 Dimensions (H×W×D) inch 21-21/32×25-29/32 Packaged Dimensions (H×W×D) inch 23-5/16×30-23/64×13-45/64 23-5/16×30-23/64×13-45/64 Weight Lbs 68 68 Gross Weight Lbs 77 77 Operation Sound dBA 48 48 49 Sound Power dBA 62 62 63 Drawing No. C: 3D066292B C: 3D066329B
Indoor Units FTXS09JEVJU FTXS12JEVJU
Outdoor Units
kW 2.49 (1.30~2.78) 2.93 (1.3~3.4) 2.93 (1.3~3.52) 3.52 (1.3~4.8)
Btu/h 8,500 (4,400~9,500) 10,000 (4,400~11,600) 10,000 (4,400~12,000) 12,000 (4,400~16,400)
kal/h 2,140 (1,120~2,390) 2,520 (1,120~2,920) 2,520 (1,120~3,030) 3,030 (1,120~4,130)
(Min.~Max.)
Liquid inch 1/4 1/4 Gas inch 3/8 3/8 Drain inch 5/8 5/8
Type Cross Flow Fan Cross Flow Fan Motor Output W 16 16 Speed Steps 5 Steps, Quiet and Auto 5 Steps, Quiet and Auto
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 750 750 Type FVC50K FVC50K Charge oz 12.5 12.5 Type R-410A R-410A Charge Lbs 2.20 2.20
Type Propeller Propeller Motor Output W 33 33
W 680 (330~800) 775 (310~840) 800 (330~1,180) 930 (310~1,500)
Btu/h·W
oz/ft 0.22 0.22
H 9.2 (325) 9.7 (342) 9.3 (328) 10.1 (357)
M 7.4 (261) 8.1 (286) 7.7 (272) 8.4 (297)
L 5.3 (187) 6.4 (226) 5.6 (198) 6.7 (237)
SL 4.0 (141) 5.6 (198) 4.4 (155) 5.9 (208)
Cooling Heating Cooling Heating
12.50 (13.33~11.90) 12.90 (14.19~13.81) 12.50 (13.33~11.90) 12.90 (14.19~10.90)
RXS09JEVJU RXS12JEVJU
×10-13/16 21-21/32×25-29/32×10-13/16
Note:
The data are based on the conditions shown in the table below.
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25ft
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
6 Room Air Conditioners J-Series
EDUS041011 Dimensions
AIRFLOW (INDOOR)
THE MARK () SHOWS PIPING DIRECTION
REAR
30-5/16(770mm)
RIGHTLEFT
1-3/16(30mm)MIN.
INCLUDING MOUNTING PLATE
(SPACE FOR
PERFORMANCE)
7-7/8(200mm)
1-15/16(50mm)MIN.
1-15/16(50mm)MIN.
7-51/64(198mm)
(SPACE FOR
(SPACE FOR
FRONT PANEL FIXING SCREWS
REQUIRED SPACE
MAINTENANCE)
MAINTENANCE)
(INSIDE)
GENERAL RATING NAME PLATE
SIGNAL RECEIVER
TERMINAL BLOCK
OPERATION LAMP
WITH EARTH
TIMER LAMP
TERMINAL
F
F
O
O N
INDOOR UNIT ON/OFF SWITCH
(INSIDE)
11-9/64(283mm)
BOTTOM
ROOM TEMP. THERMISTOR
FLAPS
GAS PIPE φ3/8(φ9.5mm) CuT
(INSIDE)
DRAIN HOSE
(THE LENGTH OF PIPE OUTSIDE
(CONNECTING PART
THE UNIT : ABOUT 15-23/64(390mm))
I.D.
F
F
O
O N
LIQUID PIPE φ1/4(φ6.4mm) CuT
O.D.
φ
9/16(φ14mm)
φ
5/8(φ16mm)
(THE LENGTH OF PIPE OUTSIDE
THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 17-21/64(440mm))
THE UNIT IS ABOUT 17-23/32(450mm))
30-5/16(770mm)
MODEL NAME
SIGNAL TRANSMITTER
15/64(6mm)
21-39/64(549mm)
5/8(16mm)
PLATE
3-31/32(101mm)
11/16(18mm)2-5/16(58mm)
BLADE ANGLE
6-49/64(172mm)
UP/DOWN (AUTOMATIC)
11-9/64(283mm)
1-5/8(41.3mm)
COOLING DRY FAN
45˚ 45˚45˚
2-9/64(54.5mm) 2-1/8(54mm)
1-5/8(41.3mm)
7-3/8(187mm)
WALL HOLE FOR EMBEDDED PIPING
RIGHT/LEFT (MANUAL)
φ
2-9/16(φ65mm) HOLE
WALL HOLE
φ
2-9/16(φ65mm) HOLE
STANDARD LOCATIONS OF WALL HOLES
WIRELESS REMOTE CONTROLLER
45˚
45˚
(ARC452A14)
3D065952B
AIRFLOW (INDOOR)
THE MARK () SHOWS PIPING DIRECTION
REAR
30-5/16(770mm)
RIGHT
LEFT
1-3/16(30mm)MIN.
INCLUDING MOUNTING PLATE
(SPACE FOR
PERFORMANCE)
7-7/8(200mm)
1-15/16(50mm)MIN.
1-15/16(50mm)MIN.
7-51/64(198mm)
(SPACE FOR
(SPACE FOR
FRONT PANEL FIXING SCREWS
REQUIRED SPACE
MAINTENANCE)
MAINTENANCE)
(INSIDE)
GENERAL RATING NAME PLATE
SIGNAL RECEIVER
TERMINAL BLOCK
OPERATION LAMP
WITH EARTH
TIMER LAMP
TERMINAL
F
F
O
O N
INDOOR UNIT ON/OFF SWITCH
(INSIDE)
11-9/64(283mm)
BOTTOM
ROOM TEMP. THERMISTOR
FLAPS
GAS PIPE φ3/8(φ9.5mm) CuT
(INSIDE)
DRAIN HOSE
(THE LENGTH OF PIPE OUTSIDE
(CONNECTING PART
THE UNIT : ABOUT 15-23/64(390mm))
I.D.
F
F
O
O N
LIQUID PIPE φ1/4(φ6.4mm) CuT
O.D.
φ
9/16(φ14mm)
φ
5/8(φ16mm)
(THE LENGTH OF PIPE OUTSIDE
THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 17-21/64(440mm))
THE UNIT IS ABOUT 17-23/32(450mm))
30-5/16(770mm)
MODEL NAME
SIGNAL TRANSMITTER
15/64(6mm)
21-39/64(549mm)
5/8(16mm)
PLATE
3-31/32(101mm)
11/16(18mm)2-5/16(58mm)
BLADE ANGLE
6-49/64(172mm)
UP/DOWN (AUTOMATIC)
11-9/64(283mm)
1-5/8(41.3mm)
COOLING HEATING DRY
15˚
45˚
45˚
2-9/64(54.5mm) 2-1/8(54mm)
45˚
1-5/8(41.3mm)
7-3/8(187mm)
FAN
WALL HOLE FOR EMBEDDED PIPING
RIGHT/LEFT (MANUAL)
φ
2-9/16(φ65mm) HOLE
WALL HOLE
φ
2-9/16(φ65mm) HOLE
STANDARD LOCATIONS OF WALL HOLES
WIRELESS REMOTE CONTROLLER
45˚
45˚
45˚
(ARC452A12)
3D065951B
4. Dimensions
4.1 Indoor Units
FTKS09/12JEVJU
FTXS09/12JEVJU
Room Air Conditioners J-Series 7
Dimensions EDUS041011
DRAIN OUTLET
4-HOLES FOR ANCHOR BOLTS
(I.D5/8 [φ15.9] HOSE FOR CONNECTION
(M8 OR M10)
WITH DRAIN JOINT [ OPTION ] )
18-1/2(470) 3-25/32(96)
1-9/16(40)
7/16(11)
14-29/32(379)
11-11/16(297)
OUTDOOR AIR THERMISTOR
BRAND NAME LABEL
MANUFACTURE'S LABEL
HANDLE
5/16(8)
5/16(8) 1-31/32(50)
10-13/16(275)
15/32(12) 25-29/32(658)
LIQUID STOP VALVE 1/4(φ6.4)CuT
SERVICE PORT
21-21/32(550)
6-5/8(168)
6-3/32(155)
WALL HEIGHT ON AIR OUTLET SIDE
MINIMUM SPACE FOR AIR PASSAGE
4-1/4(108)
=LESS THAN 47-3/16(1200)
IN CASE OF REMOVING
GAS STOP
VALVE
STOP VALVE
3/8(φ9.5)CuT
5-7/8(150)
5-7/8(150)
1-15/16(50)1-15/16(50)1-15/16(50)
3-15/16(100)
1-15/16(50)
UNIT = INCH(mm)
3-15/16(100)
11-13/16(300)
3D065923A
4.2 Outdoor Units
RKS09/12JEVJU, RXS09/12JEVJU
8 Room Air Conditioners J-Series
EDUS041011 Wiring Diagrams
PCB 2
PCB 1
S26S27
FIELD WIRING.
BLK
19
BLK
TRANSMISSION
BLK
GRN/YLW
LED1 H1P
CIRCUIT
BLK
BLK
3
FG
LED2 H2P
BLK
GRN
BLK
2
RECTIFIER
H3
BLK
+
RED
3
1
BLK
OUTDOOR
9
MR10
1
V1
H2
WHT
2
H1
CAUTION
BLK
S1W
1
NOTE THAT OPERATION WILL
F1U
RESTART AUTOMATICALLY IF
X1M
3.15A
THE MAIN POWER SUPPLY IS
+
R1T
TURNED OFF AND THEN BACK
IPM200
SIGNAL
ON AGAIN.
RECEIVER
11125 10S40312916
S32
S200
S6
INDOOR
BLK BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLKBLK
YLW
BLKBLKBLK
WIRELESS
BLU
BLK
RED
WHT
ORG
FG
REMOTE
F1U
1416
S601S602
CONTROLLER
H1~H3
MM
H1P~H2P
M1S
M1F
M1F
R2T
M1S PCB1~PCB3 R1T, R2T
NOTE)
S6~S602
S21
S1W
1.PCB3 SHOWS THE CASE OF X1M
OPTION CONNECTION.
PCB 3
OPTION
: FRAME GROUND : FUSE : HARNESS : PILOT LAMP : FAN MOTOR : SWING MOTOR : PRINTED CIRCUIT BOARD : THERMISTOR : CONNECTOR : OPERATION SWITCH : TERMINAL STRIP : PROTECTIVE EARTH
3D065939A
5. Wiring Diagrams
5.1 Indoor Units
FTKS09/12JEVJU, FTXS09/12JEVJU
5.2 Outdoor Units
RKS09/12JEVJU, RXS09/12JEVJU
Room Air Conditioners J-Series 9
Piping Diagrams EDUS041011
INDOOR UNIT
HEAT EXCHANGER
9/32CuT
3/16CuT
9/32CuT
THERMISTOR ON HEAT EXCH.
9/32CuT
9/32CuT
CROSS FLOW FAN
FIELD PIPING (1/4CuT)
M
FAN MOTOR
3/8CuT
FIELD PIPING (3/8CuT)
REFRIGERANT FLOW
COOLING
4D066315
INDOOR UNIT
HEAT EXCHANGER
9/32CuT
3/16CuT
9/32CuT
THERMISTOR ON HEAT EXCH.
9/32CuT
9/32CuT
CROSS FLOW FAN
FIELD PIPING (1/4CuT)
M
FAN MOTOR
3/8CuT
FIELD PIPING (3/8CuT)
REFRIGERANT FLOW
COOLING HEATING
4D066211
6. Piping Diagrams
6.1 Indoor Units
FTKS09/12JEVJU FTXS09/12JEVJU
10 Room Air Conditioners J-Series
EDUS041011 Piping Diagrams
OUTDOOR UNIT
HEAT EXCHANGER
9/32CuT
9/32CuT
3/8CuT
MOTOR OPERATED VALV E
3/16CuT
1/4CuT
1/4CuT
3/16CuT
THERMSTOR
MUFFLER
HEAT EXCHANGER
WITH
FILTER
FAN
MOTOR
M
PROPELLER FAN
1/4CuT
3/8CuT
STRAINER
FIELD PIPING
3/16CuT
(1/4CuT)
LIQUID STOP
3/8CuT
VALV E
1/4CuT
REFRIGERANT FLOW
MUFFLER MUFFLER
FIELD PIPING
3/8CuT
DISCHARGE PIPE
COOLING
COMPRESSOR
THERMISTOR
(3/8CuT)
GAS STOP VALV EACCUMULATOR
3D065937
OUTDOOR UNIT
OUTDOOR TEMPERATURE
HEAT EXCHANGER
9/32CuT
THERMISTOR
9/32CuT
3/8CuT
MOTOR OPERATED VALV E
3/16CuT
1/4CuT 1/4CuT
3/16CuT
MUFFLER
THERMISTOR
WITH
HEAT EXCHANGER
FILTER
FAN
MOTOR
M
PROPELLER FAN
1/4CuT
3/8CuT
3/8CuT
STRAINER
FOUR WAY VALV E ON : HEATING
FIELD PIPING
3/16CuT
(1/4CuT)
LIQUID STOP
3/8CuT
VALV E
1/4CuT
REFRIGERANT FLOW
MUFFLER MUFFLER
FIELD PIPING
3/8CuT
DISCHARGE PIPE
COOLING
COMPRESSOR
THERMISTOR
(3/8CuT)
GAS STOP
HEATING
VALV E
ACCUMULATOR
3D065936
6.2 Outdoor Units
RKS09/12JEVJU
RXS09/12JEVJU
Room Air Conditioners J-Series 11
Capacity Tables EDUS041011
7. Capacity Tables
7.1 Cooling Only
FTKS09JEVJU + RKS09JEVJU (60Hz 208/230V)
AFR 9.2
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.211.770.492.211.770.552.211.770.612.211.770.642.201.760.672.091.710.72
16.022.02.671.900.522.551.850.572.431.790.632.391.770.652.321.740.682.201.690.73
18.025.02.781.990.532.661.940.582.551.900.632.501.880.652.431.850.682.321.800.73
19.426.72.842.110.532.722.060.582.612.010.632.561.990.65
22.030.03.012.040.532.891.990.582.781.950.632.731.940.652.661.910.682.551.870.73
24.032.03.121.980.543.011.950.592.891.910.642.851.890.662.781.870.692.661.830.74
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.545.170.467.545.170.537.545.170.607.545.170.637.525.150.677.134.830.68
60.871.69.106.140.528.705.790.578.315.460.638.155.330.657.915.140.687.524.830.68
64.477.09.496.180.539.105.850.588.705.530.638.545.400.658.305.220.687.914.920.69
67.080.09.696.260.539.295.930.588.905.620.638.745.500.65
71.6 86.0 10.27 6.02 0.53 9.88 5.71 0.58 9.48 5.42 0.63 9.32 5.31 0.65 9.09 5.15 0.68 8.69 4.88 0.69
75.289.610.675.810.5410.275.520.599.875.250.649.725.150.669.484.990.699.084.740.69
2.49 1.97 0.68 2.37 1.92 0.73
8.50 5.32 0.68 8.10 5.03 0.69
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066175
12 Room Air Conditioners J-Series
EDUS041011 Capacity Tables
FTKS12JEVJU + RKS12JEVJU (60Hz 208/230V)
AFR 9.3
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.221.770.542.221.770.612.221.770.692.221.770.722.221.770.762.221.770.84
16.022.02.972.050.602.972.050.672.861.990.742.811.970.762.731.930.792.591.870.85
18.025.03.272.220.623.142.150.683.002.090.742.942.070.762.862.030.802.731.980.86
19.426.73.342.330.623.202.270.683.072.210.743.012.190.76
22.030.03.542.240.633.412.190.693.272.140.753.212.120.773.132.090.813.002.040.86
24.032.03.682.180.633.542.130.693.402.080.753.352.070.773.272.040.813.131.990.87
2.93 2.15 0.80 2.79 2.10 0.86
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.585.200.487.585.200.557.585.200.627.585.200.657.585.200.707.585.200.74
60.871.610.147.100.5910.147.100.679.776.750.749.596.580.769.316.320.798.845.900.80
64.4 77.0 11.17 7.73 0.62 10.70 7.27 0.68 10.24 6.83 0.74 10.05 6.66 0.76 9.77 6.42 0.80 9.30 6.02 0.81
67.0 80.0 11.40 7.81 0.62 10.93 7.36 0.68 10.47 6.93 0.74 10.28 6.76 0.76
71.6 86.0 12.09 7.54 0.63 11.62 7.12 0.69 11.16 6.72 0.75 10.97 6.56 0.77 10.69 6.33 0.81 10.23 5.97 0.81
75.2 89.6 12.55 7.30 0.63 12.08 6.90 0.69 11.62 6.52 0.75 11.43 6.37 0.77 11.15 6.16 0.81 10.69 5.81 0.82
10.00 6.52 0.80 9.53 6.12 0.81
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066176
Room Air Conditioners J-Series 13
Capacity Tables EDUS041011
7.2 Heat Pump
FTXS09JEVJU + RXS09JEVJU (60Hz 208/230V)
Cooling
AFR 9.2
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.211.770.492.211.770.552.211.770.612.211.770.642.201.760.672.091.710.72
16.022.02.671.900.522.551.850.572.431.790.632.391.770.652.321.740.682.201.690.73
18.025.02.781.990.532.661.940.582.551.900.632.501.880.652.431.850.682.321.800.73
19.426.72.842.110.532.722.060.582.612.010.632.561.990.65
22.030.03.012.040.532.891.990.582.781.950.632.731.940.652.661.910.682.551.870.73
24.032.03.121.980.543.011.950.592.891.910.642.851.890.662.781.870.692.661.830.74
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.545.170.467.545.170.537.545.170.607.545.170.637.525.150.677.134.830.68
60.871.69.106.140.528.705.790.578.315.460.638.155.330.657.915.140.687.524.830.68
64.477.09.496.180.539.105.850.588.705.530.638.545.400.658.305.220.687.914.920.69
67.080.09.696.260.539.295.930.588.905.620.638.745.500.65
71.6 86.0 10.27 6.02 0.53 9.88 5.71 0.58 9.48 5.42 0.63 9.32 5.31 0.65 9.09 5.15 0.68 8.69 4.88 0.69
75.289.610.675.810.5410.275.520.599.875.250.649.725.150.669.484.990.699.084.740.69
2.49 1.97 0.68 2.37 1.92 0.73
8.50 5.32 0.68 8.10 5.03 0.69
Heating
AFR 9.7
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15.0 –10.0 –5.0 0 6.0 10.0
°C TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.40 0.50 1.68 0.52 1.96 0.55 2.63 0.72 3.03 0.76 3.30 0.78
21.1 1.31 0.51 1.59 0.54 1.87 0.56 2.53 0.74
22.0 1.27 0.52 1.56 0.54 1.84 0.57 2.49 0.74 2.89 0.78 3.15 0.81
24.0 1.24 0.52 1.52 0.55 1.80 0.58 2.45 0.75 2.85 0.79 3.11 0.81
25.0 1.22 0.53 1.50 0.55 1.79 0.58 2.43 0.75 2.83 0.79 3.09 0.82
27.0 1.19 0.53 1.47 0.56 1.75 0.58 2.39 0.76 2.79 0.80 3.05 0.82
2.93 0.78 3.19 0.80
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5.0 14.0 23.0 32.0 43.0 50.0
°F TC PI TC PI TC PI TC PI TC PI TC PI
59.0 4.76 0.50 5.72 0.52 6.68 0.55 8.99 0.72 10.35 0.76 11.25 0.78
70.0 4.47 0.51 5.43 0.54 6.39 0.56 8.64 0.74
71.6 4.35 0.52 5.31 0.54 6.27 0.57 8.51 0.74 9.86 0.78 10.77 0.81
75.2 4.23 0.52 5.19 0.55 6.15 0.58 8.37 0.75 9.72 0.79 10.63 0.81
77.0 4.18 0.53 5.14 0.55 6.10 0.58 8.30 0.75 9.65 0.79 10.56 0.82
80.6 4.06 0.53 5.02 0.56 5.98 0.58 8.16 0.76 9.52 0.80 10.42 0.82
10.00 0.78 10.90 0.80
14 Room Air Conditioners J-Series
EDUS041011 Capacity Tables
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066177
Room Air Conditioners J-Series 15
Capacity Tables EDUS041011
FTXS12JEVJU + RXS12JEVJU (60Hz 208/230V)
Cooling
AFR 9.3
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.221.770.542.221.770.612.221.770.692.221.770.722.221.770.762.221.770.84
16.022.02.972.050.602.972.050.672.861.990.742.811.970.762.731.930.792.591.870.85
18.025.03.272.220.623.142.150.683.002.090.742.942.070.762.862.030.802.731.980.86
19.426.73.342.330.623.202.270.683.072.210.743.012.190.76
22.030.03.542.240.633.412.190.693.272.140.753.212.120.773.132.090.813.002.040.86
24.032.03.682.180.633.542.130.693.402.080.753.352.070.773.272.040.813.131.990.87
2.93 2.15 0.80 2.79 2.10 0.86
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.585.200.487.585.200.557.585.200.627.585.200.657.585.200.707.585.200.74
60.871.610.147.100.5910.147.100.679.776.750.749.596.580.769.316.320.798.845.900.80
64.4 77.0 11.17 7.73 0.62 10.70 7.27 0.68 10.24 6.83 0.74 10.05 6.66 0.76 9.77 6.42 0.80 9.30 6.02 0.81
67.0 80.0 11.40 7.81 0.62 10.93 7.36 0.68 10.47 6.93 0.74 10.28 6.76 0.76
71.6 86.0 12.09 7.54 0.63 11.62 7.12 0.69 11.16 6.72 0.75 10.97 6.56 0.77 10.69 6.33 0.81 10.23 5.97 0.81
75.2 89.6 12.55 7.30 0.63 12.08 6.90 0.69 11.62 6.52 0.75 11.43 6.37 0.77 11.15 6.16 0.81 10.69 5.81 0.82
10.00 6.52 0.80 9.53 6.12 0.81
Heating
AFR 10.1
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15.0 –10.0 –5.0 0 6.0 10.0
°C TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.68 0.60 2.01 0.63 2.35 0.66 3.16 0.86 3.64 0.91 3.96 0.94
21.1 1.57 0.62 1.91 0.65 2.25 0.68 3.04 0.88
22.0 1.53 0.62 1.87 0.65 2.21 0.68 2.99 0.89 3.47 0.94 3.79 0.97
24.0 1.49 0.63 1.83 0.66 2.17 0.69 2.95 0.90 3.42 0.95 3.74 0.98
25.0 1.47 0.63 1.81 0.66 2.15 0.69 2.92 0.90 3.40 0.95 3.72 0.98
27.0 1.43 0.64 1.77 0.67 2.10 0.70 2.87 0.91 3.35 0.96 3.67 0.99
3.52 0.93 3.84 0.96
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5.0 14.0 23.0 32.0 43.0 50.0
°F TC PI TC PI TC PI TC PI TC PI TC PI
59.0 5.71 0.60 6.87 0.63 8.02 0.66 10.79 0.86 12.41 0.91 13.50 0.94
70.0 5.36 0.62 6.51 0.65 7.67 0.68 10.37 0.88
71.6 5.22 0.62 6.37 0.65 7.53 0.68 10.21 0.89 11.83 0.94 12.92 0.97
75.2 5.08 0.63 6.23 0.66 7.38 0.69 10.04 0.90 11.67 0.95 12.75 0.98
77.0 5.01 0.63 6.16 0.66 7.31 0.69 9.96 0.90 11.59 0.95 12.67 0.98
80.6 4.87 0.64 6.02 0.67 7.17 0.70 9.79 0.91 11.42 0.96 12.50 0.99
12.00 0.93 13.08 0.96
16 Room Air Conditioners J-Series
EDUS041011 Capacity Tables
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066178
Room Air Conditioners J-Series 17
Capacity Tables EDUS041011
Capacity correction factor
1
16.4 32.8 49.2
0.9
0.8
R-410A (09/12 class)
Piping length (ft)
(R11493)
Range of the refrigerant additional charge
7.3 Capacity correction factor by the length of refrigerant piping (Reference)
The cooling and the heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit)
<— line : cooling capacity> <--- line : heating capacity>
The graph shows the factor when additional refrigerant of the proper quantity is charged.
Note:
18 Room Air Conditioners J-Series
EDUS041011 Operation Limit
122
114.8
104
86
68
Pull-down period
Continuous operation
Outdoor temp. (˚FDB)
50
32
866857.250 73.4 82.4
Indoor temp. (˚FWB)
Notes:
The graphs are based on the following conditions.
• Equivalent piping length 25ft
• Level difference 0ft
• Air flow rate High
4D066173
Heating
Cooling
68
122
114.8 59
104
50
86
41
32
68
Pull-down period
Outdoor temp. (˚FWB)
23
Continuous operation
Outdoor temp. (˚FDB)
50
Continuous operation
14
32
5
82.468 8673.457.250 (5˚FDB)
Indoor temp. (˚FWB)
50 8668
Notes:
Indoor temp. (˚FDB)
The graphs are based on the following conditions.
• Equivalent piping length 25ft
• Level difference 0ft
• Air flow rate High
3D066174
8. Operation Limit
RKS09/12JEVJU
RXS09/12JEVJU
Room Air Conditioners J-Series 19
Sound Level EDUS041011
3.3ft
2.6ft
(R5162)
3.3ft
(R4796)
9. Sound Level
9.1 Measuring Location
Indoor Unit
The Single Split Duct-Free System
Outdoor Unit
1. Operation sound is measured in an anechoic chamber.
2. The data are based on the conditions shown in the table below.
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
Note:
25ft
20 Room Air Conditioners J-Series
EDUS041011 Sound Level
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
40 26
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
4D066168
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
41 27
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
4D066169
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
10
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
40 26
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
60Hz 60Hz
208/230V 208/230V
(H) (L)
40 28
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
NC-50
NC-40
NC-30
NC-20
NC-10
Heating
3D066170
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
10
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
10
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-50
NC-40
NC-30
NC-20
NC-10
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
41 27
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
60Hz 60Hz
208/230V 208/230V
(H) (L)
41 29
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Heating
3D066171
9.2 Octave Band Level
9.2.1 Indoor Units
FTKS09JEVJU FTKS12JEVJU
FTXS09JEVJU
FTXS12JEVJU
Room Air Conditioners J-Series 21
Sound Level EDUS041011
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
4D066163
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
4D066164
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
NC-60
NC-50
NC-40
NC-30
NC-20
208/230V 60Hz
60Hz 208/230V
Heating
60Hz
208/230V(H)
48
3D066166
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-60
NC-20
NC-40
NC-50
NC-30
48
208/230V(H)
60Hz
Cooling
208/230V 60Hz
60Hz 208/230V
49
208/230V(H)
60Hz
208/230V 60Hz
60Hz 208/230V
Heating
NC-50
NC-20
NC-30
NC-60
NC-40
3D066167
9.2.2 Outdoor Units
RKS09JEVJU RKS12JEVJU
RXS09JEVJU
RXS12JEVJU
22 Room Air Conditioners J-Series
EDUS041011 Electric Characteristics
10.Electric Characteristics
Representative Unit Combination Power Supply COMP OFM IFM
Indoor Unit Outdoor Unit Hz-Volts Voltage Range MCA MOP RLA W FLA W FLA
FTKS09JEVJU RKS09JEVJU
FTKS12JEVJU RKS12JEVJU
FTXS09JEVJU RXS09JEVJU
FTXS12JEVJU RXS12JEVJU
60-208
60-230 3.4 0.17 0.18
60-208
60-230 3.4 0.17 0.18
60-208
60-230 3.3 0.17 0.18
60-208
60-230 4.0 0.17 0.18
MAX. 60Hz 253V
MIN. 60Hz 187V
MAX. 60Hz 253V
MIN. 60Hz 187V
MAX. 60Hz 253V
MIN. 60Hz 187V
MAX. 60Hz 253V
MIN. 60Hz 187V
4.4 15
4.4 15
4.3 15
5.2 15
Symbols: Note:
MCA : MIN. CIRCUIT AMPS (A) 1. Maximum allowable voltage variation between phases is 2%.
MOP : MAX OVERCURRENT PROTECTION
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
2. Select wire size based on the larger value of MCA.
3. Instead of fuse, use circuit breaker.
4. Be sure to install a ground leak detector. (One that can handle higher harmonics.) (This unit uses an inverter, which means that it must use a ground leak detector capable handling high harmonics in order to prevent malfunctioning of the ground leak detector itself.)
3.7
3.7
3.7
4.4
33
33
33
33
0.19
0.19
0.19
0.19
40
40
40
40
0.20
0.20
0.20
0.20
3D066179B
Room Air Conditioners J-Series 23
Installation Manual EDUS041011
1
Safety Precautions
• Read these Safety Precautions carefully to ensure correct installation.
• This manual classifies the precautions into DANGER, WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety.
DANGER..........Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
........Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTION .........Failure to follow any of CAUTION may in some cases result in grave consequences.
• The following safety symbols are used throughout this manual:
After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual.
Be sure to observe this instruction. Be sure to establish a ground connection. Never attempt.
DANGER
• Refrigerant gas is heavier than air and replaces oxygen. A massive leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• If the refrigerant gas leaks during installation, ventilate the area immediately.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• After completing the installation work, check that the refrigerant gas does not leak.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apar t and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face the danger of death by suffocation.
Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death.
Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
WARNING
• Installation should be left to the authorized dealer or another trained professional.
Improper installation may cause water leakage, electrical shock, fire, or equipment damage.
• Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire or equipment damage.
• Be sure to use the supplied or exact specified installation parts.
Use of other parts may cause the unit to come to fall, water leakage, electrical shock, fire or equipment damage.
• Install the air conditioner on a solid base that is level and can support the weight of the unit.
An inadequate base or incomplete installation may cause injury or equipment damage in the event the unit falls off the base or comes loose.
• Electrical work should be carried out in accordance with the installation manual and the national, state and local electrical wiring codes.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire or equipment damage.
• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. Follow all appropriate electrical codes.
• For wiring, use a wire or cable long enough to cover the entire distance with no splices if possible. Do not use an extension cord. Do not put other loads on the power supply. Use an only a separate dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock, fire or equipment damage.)
• Use the specified types of wires for electrical connections between the indoor and outdoor units. Follow all state and local electrical codes.
Firmly clamp the inter-unit wiring so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating, fire or equipment damage.
• After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical covers, panels or terminals.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock,fire or equipment damage.
• When installing or relocating the system, be sure to keep the refrigerant circuit free from all substances other than the specified refrigerant (R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which may result in rupture, resulting in injury.)
11.Installation Manual
11.1 Indoor Units
24 Room Air Conditioners J-Series
EDUS041011 Installation Manual
2
Safety Precautions
Accessories
,
Choosing an Installation Site
• Before choosing the installation site, obtain user approval.
1.
Indoor unit
• The indoor unit should be sited in a place where:
1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air inlet and air outlet have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool (warm) air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the remote controller range,
8)
the unit is at least 3.5 feet (1m) away from any television or radio set (unit may cause interference with the picture or sound).
2.
Wireless remote controller
1) Turn on all the fluorescent lamps in the room, if any, and find the site where remote control signals are properly received by the indoor unit (within 23 feet (7m)).
WARNING
• During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing abnormally high pressure which could lead to equipment damage and personal injury.
• Be sure to install a ground fault circuit interrupter breaker.
Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.
CAUTION
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual.
Inadequate piping may cause water damage.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
Mounting plate
1
Remote controller holder
1
Operation manual
1
Mounting plate fixing screw 3/16” × 1” (M4 × 25mm)
6
Fixing screw for remote controller
holder 1/8” × 13/16” (M3 × 20mm)
2
Installation manual
1
Titanium apatite photocatalytic air-purifying filter
2
Dry battery AAA. LR03
(alkaline)
2
Wireless remote controller
1
Indoor unit fixing screw
3/16” × 1/2” (M4 × 12mm)
2
Indoor unit
A
K
A
E
J
B
F
K
C
G
D
H
Room Air Conditioners J-Series 25
Installation Manual EDUS041011
3
Preparation before Installation
1.
Removing and installing front panel
•Removal method
Hook fingers on the tabs on the left and right of the main body, and open until the panel stops. Slide the front panel sideways to disengage the rotating shaft. Then pull the front panel toward you to remove it.
••Installation method
Align the tabs of the front panel with the grooves, and push all the way in. Then close slowly. Push the center of the lower surface of the panel firmly to engage the tabs.
2.
Removing and installing front grille
R
emoval method
1) Remove front panel to remove the air filter.
2) Remove 2 screws from the front grille.
3) In front of the

mark of the front grille, there are 3 upper hooks. Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand.
When there is no work space because the unit is close to ceiling
CAUTION
• Be sure to wear protection gloves.
Place both hands under the center of the front grille, and while pushing up, pull it toward you.
• Installation method
1) Install the front grille and firmly engage the upper hooks (3 locations).
2) Install 2 screws of the front grille.
3) Install the air filter and then mount the front panel.
3.
How to set the different addresses
When two indoor units are installed in one room, the two wireless remote controllers can be set for different addresses.
1) In the same way as when connecting to an HA system, remove the metal plate electrical wiring cover.
2) Cut the address jumper (JA) on the printed circuit board.
3) Cut the address jumper (J4) in the remote controller.
Push the rotating shaft of the front panel into the groove.
mar

k area
(3 locations)
Upper hook
Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand. (3 locations)
Push down.
Upper hook
1) Push up.
2) Pull toward you.
ADDRESS
EXIST
CUT12
JA
JA
ADDRESS
J4
EXIST
1
CUT 2
J4
26 Room Air Conditioners J-Series
EDUS041011 Installation Manual
4
Indoor Unit Installation Drawings
How to attach the indoor unit
Hook the claws of the bottom frame
Mounting plate
A
The mounting plate should be installed on a wall which can support the
Mounting plate fixing screw
B
3/16” × 1” (M4 × 25mm)
Front panel
1-15/16” (50mm) or more from walls (on both sides)
Air filters
Titanium apatite photocatalytic
C
air-purifying filter (2)
Air filter
weight of the indoor unit.
1-3/16” (30mm) or more from ceiling
3/16” × 5/8” (M4 × 16mm)
Opening service lid
Service lid is opening/closing type.
Opening method
to the mounting plate. If the claws are difficult to hook, remove the front grille.
How to remove the indoor unit
Push up the marked area (at the lower part of the front grille) to release the claws. If it is difficult to release, remove the front grille.
Service lid
1) Remove the service lid screws.
2) Pull out the service lid diagonally down in the direction of the arrow.
3) Pull down.
Caulk pipe hole gap with putty.
Front grille
Mounting
A
plate
Bottom frame
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe’s cut line.
Wrap the insulation pipe with the finishing tape from bottom to top.
Mark (rear side)
Clip
Filter frame
Titanium apatite photocatalytic
Ta b
Room Air Conditioners J-Series 27
air-purifying filter
Fixing screw for remote
F
controller holder 1/8” × 13/16” (M3 × 20mm)
D Wireless remote controller
Before screwing the remote controller holder to the wall, make sure that control signals are properly received by indoor unit.
E Remote controller holder
Installation Manual EDUS041011
5
Indoor Unit Installation
1.
Installing the mounting plate
• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the boring points on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
* The removed pipe port cover can be kept in the mounting plate pocket.
Removed pipe port cover
A
Mounting plate
Use tape measure as shown.
Position the end of a tape measure at .
Liquid pipe end
Gas pipe end
Through­the-wall hole φ2-9/16 (φ65)
Recommended mounting plate retention spots (5 spots in all)
Place a leveler on raised tab.
9-33/64
(241.7)
1-5/8
(41.3)
13-1/64 (330.5)
13-1/32
(331)
6-19/64
(160)
2-1/8
(54)
30-5/16
(770)
9-33/64
(241.7)
1-5/8
(41.3)
2-9/64
(54.5)
6-19/64
(160)
1-31/32
(50)
4-31/32
(101)
4-47/64
(120.5)
7-63/64
(203)
9-23/32
(247)
Drain hose position
unit: inch (mm)
(Bolt size: 3/8 (M10)) (Bolt size: 3/8 (M10))
28 Room Air Conditioners J-Series
Loading...
+ 67 hidden pages