Daikin FTKS12JEVJU, RXS09JEVJU, RKS12JEVJU, RXS12JEVJU, RKS09JEVJU User Manual

...
Page 1
- Cooling Only / Heat Pump -
EDUS041011
SEER 18 Models
J-Series
Page 2
EDUS041011
Room Air Conditioners
J-Series
The Single Split Duct-Free System
FTKS09JEVJU
RKS09JEVJU
Cooling Only
FTKS12JEVJU
FTXS09JEVJU
RKS12JEVJU
RXS09JEVJU
Heat Pump
FTXS12JEVJU
1. Power Supply ..........................................................................................3
2. Functions.................................................................................................4
3. Specifications ..........................................................................................5
3.1 Cooling Only.............................................................................................5
3.2 Heat Pump ...............................................................................................6
4. Dimensions .............................................................................................7
4.1 Indoor Units ..............................................................................................7
4.2 Outdoor Units ...........................................................................................8
5. Wiring Diagrams......................................................................................9
5.1 Indoor Units ..............................................................................................9
5.2 Outdoor Units ...........................................................................................9
6. Piping Diagrams....................................................................................10
6.1 Indoor Units ............................................................................................10
6.2 Outdoor Units .........................................................................................11
7. Capacity Tables ....................................................................................12
7.1 Cooling Only...........................................................................................12
7.2 Heat Pump .............................................................................................14
7.3 Capacity correction factor by the length of refrigerant piping ................ 18
8. Operation Limit......................................................................................19
9. Sound Level ..........................................................................................20
9.1 Measuring Location ................................................................................20
9.2 Octave Band Level .................................................................................21
10.Electric Characteristics..........................................................................23
11.Installation Manual ................................................................................24
11.1 Indoor Units ............................................................................................24
11.2 Outdoor Units .........................................................................................36
12. Safety Considerations ..........................................................................48
13.Optional Accessories ............................................................................75
13.1 Option List ..............................................................................................75
RXS12JEVJU
Room Air Conditioners J-Series 1
Page 3
EDUS041011
13.2 <BRC944B2> Wired Remote Controller.................................................76
13.3 <KRP980B1> Interface Adaptor for Wired Remote Controller...............90
13.4 <KPW937A4> Air Direction Adjustment Grille........................................94
2 Room Air Conditioners J-Series
Page 4
EDUS041011 Power Supply
1. Power Supply
Indoor Units Outdoor Units Power Supply
FTKS09JEVJU RKS09JEVJU
The Single Split
Duct-Free System
Power Supply Intake ; Outdoor Unit
FTKS12JEVJU RKS12JEVJU
FTXS09JEVJU RXS09JEVJU
FTXS12JEVJU RXS12JEVJU
, 208-230V, 60Hz
1
Note:
Room Air Conditioners J-Series 3
Page 5
Functions EDUS041011
2. Functions
Category Functions
FTKS09/12JEVJU
RKS09/12JEVJU
Basic Function
Compressor Oval Scroll Compressor Air Filter (Prefilter) 
Comfortable Airflow
Comfort Control
Operation Automatic Operation DIII-NET Compatible (Adaptor) (Option)
Lifestyle Convenience
Inverter (with Inverter Power Control) Health &
50~
Operation Limit for Cooling (°FDB)
Operation Limit for Heating (°FWB) 5~68
PAM Control 
Swing Compressor  Wipe-clean Flat Panel 
Rotary Compressor Washable Grille
Reluctance DC Motor  Filter Cleaning Indicator
Power-Airflow Louver (Horizontal Blade)
Power-Airflow Dual Louvers Timer 24-Hour ON/OFF Timer 
Power-Airflow Diffuser NIGHT SET Mode 
Wide-Angle Fins (Vertical Blades) Worry Free
Vertical Auto-Swing (Up and Down)  Self-Diagnosis (Digital, LED) Display 
Horizontal Auto-Swing (Right and Left) Wiring Error Check
3-D Airflow
COMFORT AIRFLOW Operation 
Auto Fan Speed  Flexible Voltage Correspondence
Indoor Unit Quiet Operation  High Ceiling Application
NIGHT QUIET Mode (Automatic) Chargeless
Outdoor Unit Quiet Operation (Manual) Either Side Drain (Right or Left) 
INTELLIGENT EYE Operation Power Selection
Quick Warming Function
Hot-Start Function
Automatic Defrosting
Program Dry Function Remote
Fan Only  Wired 
New POWERFUL Operation (Non-Inverter)
Inverter POWERFUL Operation 
Priority-Room Setting
COOL / HEAT Mode Lock
HOME LEAVE Operation
ECONO Operation 
Indoor Unit ON/OFF Button 
Signal Receiving Sign 
Temperature Display
Another Room Operation
114.8
50~
114.8
 Good-Sleep Cooling Operation
——
Category Functions
FTXS09/12JEVJU
RXS09/12JEVJU
Clean
“Reliability & Durability”
Flexibility Multi-Split / Split Type Compatible
Remote Control
Controller
Air-Purifying Filter
Photocatalytic Deodorizing Filter
Air-Purifying Filter with Photocatalytic Deodorizing Function
Titanium Apatite Photocatalytic Air-Purifying Filter
Auto-Restart (after Power Failure) 
Anti-Corrosion Treatment of Outdoor Heat Exchanger
Indoor Unit
5-Rooms Centralized Controller (Option)
Remote Control Adaptor (Normal Open-Pulse Contact) (Option)
Remote Control Adaptor (Normal Open Contact) (Option)
Wireless 
FTKS09/12JEVJU
RKS09/12JEVJU
FTXS09/12JEVJU
——


——
32.8ft 32.8ft
——
——
——
RXS09/12JEVJU
Note:  : Holding Functions
— : No Functions
4 Room Air Conditioners J-Series
Page 6
EDUS041011 Specifications
3. Specifications
3.1 Cooling Only
Models
60Hz 208-230V
Capacity Rated (Min.~Max.)
Running Current (Rated) A 4.1-3.7 4.1-3.7 Power Consumption Rated Power Factor % 79.7-79.9 93.8-94.0 COP (Rated) (Min.~Max.) W/W 3.66 (3.94~3.48) 3.66 (3.94~2.98) EER (Rated) (Min.~Max.)
Piping Connections
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length feet 49.2 49.2 Max. Interunit Height Difference feet 39.3 39.3 Chargeless feet 32.8 32.8 Amount of Additional Charge of
Refrigerant
Indoor Units FTKS09JEVJU FTKS12JEVJU
Front Panel Color White White
Airflow Rate m³/min (cfm)
Fan
Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.20-0.18 0.20-0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.2-96.6 96.2-96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) inch 11-9/64×30-5/16×7-51/64 11-9/64×30-5/16×7-51/64 Packaged Dimensions (H×W×D) inch 10-17/64×33-7/32×13-15/32 10-17/64×33-7/32×13-15/32 Weight Lbs 16 16 Gross Weight Lbs 24 24 Operation Sound H/M/L/SL dBA 40 / 33 / 26 / 22 41 / 34 / 27 / 23 Sound Power dBA 56 57
Outdoor Units RKS09JEVJU RKS12JEVJU
Casing Color Ivory White Ivory White
Compressor
Refrigerant Oil
Refrigerant
Airflow Rate m³/min (cfm) H 26.1 (921) 26.1 (921)
Fan
Running Current (Rated) A 3.90-3.52 3.90-3.52 Power Consumption (Rated) W 640 760 Power Factor % 78.9-79.1 93.7-93.9 Starting Current A 4.1 4.8 Dimensions (H×W×D) inch 21-21/32×25-29/32×10-13/16 21-21/32×25-29/32×10-13/16 Packaged Dimensions (H×W×D) inch 23-5/16×30-23/64×13-45/64 23-5/16×30-23/64×13-45/64 Weight Lbs 66 66 Gross Weight Lbs 75 75 Operation Sound dBA 48 48 Sound Power dBA 62 62 Drawing No. C: 3D066330B C: 3D066331B
Indoor Units FTKS09JEVJU FTKS12JEVJU Outdoor Units RKS09JEVJU RKS12JEVJU
(Min.~Max.)
Liquid inch 1/4 1/4 Gas inch 3/8 3/8 Drain inch 5/8 5/8
Type Cross Flow Fan Cross Flow Fan Motor Output W 16 16 Speed Steps 5 Steps, Quiet and Auto 5 Steps, Quiet and Auto
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 750 750 Type FVC50K FVC50K Charge oz 12.5 12.5 Type R-410A R-410A Charge Lbs 2.20 2.20
Type Propeller Propeller Motor Output W 33 33
kW 2.49 (1.30~2.78) 2.93 (1.3~3.52)
Btu/h 8,500 (4,400~9,500) 10,000 (4,400~12,000)
kal/h 2,140 (1,120~2,390) 2,520 (1,120~3,030)
W 680 (330~800) 800 (330~1,180)
Btu/h·W
oz/ft 0.22 0.22
H 9.2 (325) 9.3 (328)
M 7.4 (261) 7.7 (272)
L 5.3 (187) 5.6 (198)
SL 4.0 (141) 4.4 (155)
12.50 (13.33~11.90) 12.50 (13.33~10.20)
Note:
The data are based on the conditions shown in the table below.
Cooling Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
25ft
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Room Air Conditioners J-Series 5
Page 7
Specifications EDUS041011
3.2 Heat Pump
Models
60Hz 208-230V
Capacity Rated (Min.~Max.)
Running Current (Rated) A 4.1-3.7 4.0-3.6 4.1-3.7 4.8-4.3 Power Consumption Rated Power Factor % 79.7-79.9 93.1-93.6 93.8-94.0 93.1-94.0 COP (Rated) (Min.~Max.) W/W 3.66 (3.94~3.48) 3.78 (4.19~4.05) 3.66 (3.94~2.98) 3.78 (4.19~3.20) EER (Rated) (Min.~Max.)
Piping Connections
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length feet 49.2 49.2 Max. Interunit Height Difference feet 39.3 39.3 Chargeless feet 32.8 32.8 Amount of Additional Charge of
Refrigerant
Indoor Units FTXS09JEVJU FTXS12JEVJU
Front Panel Color White White
Airflow Rate m³/min (cfm)
Fan
Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.20-0.18 0.20-0.18 Power Consumption (Rated) W 40 40 Power Factor % 96.2-96.6 96.2-96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) inch 11-9/64×30-5/16×7-51/64 11-9/64×30-5/16×7-51/64 Packaged Dimensions (H×W×D) inch 10-17/64×33-7/32×13-15/32 10-17/64×33-7/32×13-15/32 Weight Lbs 16 16 Gross Weight Lbs 24 24 Operation Sound H/M/L/SL dBA 40 / 33 / 26 / 22 40 / 34 / 28 / 25 41 / 34 / 27 / 23 41 / 35 / 29 / 26 Sound Power dBA 56 57
Outdoor Units RXS09JEVJU RXS12JEVJU
Casing Color Ivory White Ivory White
Compressor
Refrigerant Oil
Refrigerant
Airflow Rate m³/min (cfm) H 26.1 (921) 26.1 (921)
Fan
Running Current (Rated) A 3.90-3.52 3.80-3.42 3.90-3.52 4.60-4.12 Power Consumption (Rated) W 640 735 760 890 Power Factor % 78.9-79.1 93.0-93.4 93.7-93.9 93.0-93.9 Starting Current A 4.1 4.1 4.8 Dimensions (H×W×D) inch 21-21/32×25-29/32 Packaged Dimensions (H×W×D) inch 23-5/16×30-23/64×13-45/64 23-5/16×30-23/64×13-45/64 Weight Lbs 68 68 Gross Weight Lbs 77 77 Operation Sound dBA 48 48 49 Sound Power dBA 62 62 63 Drawing No. C: 3D066292B C: 3D066329B
Indoor Units FTXS09JEVJU FTXS12JEVJU
Outdoor Units
kW 2.49 (1.30~2.78) 2.93 (1.3~3.4) 2.93 (1.3~3.52) 3.52 (1.3~4.8)
Btu/h 8,500 (4,400~9,500) 10,000 (4,400~11,600) 10,000 (4,400~12,000) 12,000 (4,400~16,400)
kal/h 2,140 (1,120~2,390) 2,520 (1,120~2,920) 2,520 (1,120~3,030) 3,030 (1,120~4,130)
(Min.~Max.)
Liquid inch 1/4 1/4 Gas inch 3/8 3/8 Drain inch 5/8 5/8
Type Cross Flow Fan Cross Flow Fan Motor Output W 16 16 Speed Steps 5 Steps, Quiet and Auto 5 Steps, Quiet and Auto
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 750 750 Type FVC50K FVC50K Charge oz 12.5 12.5 Type R-410A R-410A Charge Lbs 2.20 2.20
Type Propeller Propeller Motor Output W 33 33
W 680 (330~800) 775 (310~840) 800 (330~1,180) 930 (310~1,500)
Btu/h·W
oz/ft 0.22 0.22
H 9.2 (325) 9.7 (342) 9.3 (328) 10.1 (357)
M 7.4 (261) 8.1 (286) 7.7 (272) 8.4 (297)
L 5.3 (187) 6.4 (226) 5.6 (198) 6.7 (237)
SL 4.0 (141) 5.6 (198) 4.4 (155) 5.9 (208)
Cooling Heating Cooling Heating
12.50 (13.33~11.90) 12.90 (14.19~13.81) 12.50 (13.33~11.90) 12.90 (14.19~10.90)
RXS09JEVJU RXS12JEVJU
×10-13/16 21-21/32×25-29/32×10-13/16
Note:
The data are based on the conditions shown in the table below.
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25ft
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
6 Room Air Conditioners J-Series
Page 8
EDUS041011 Dimensions
AIRFLOW (INDOOR)
THE MARK () SHOWS PIPING DIRECTION
REAR
30-5/16(770mm)
RIGHTLEFT
1-3/16(30mm)MIN.
INCLUDING MOUNTING PLATE
(SPACE FOR
PERFORMANCE)
7-7/8(200mm)
1-15/16(50mm)MIN.
1-15/16(50mm)MIN.
7-51/64(198mm)
(SPACE FOR
(SPACE FOR
FRONT PANEL FIXING SCREWS
REQUIRED SPACE
MAINTENANCE)
MAINTENANCE)
(INSIDE)
GENERAL RATING NAME PLATE
SIGNAL RECEIVER
TERMINAL BLOCK
OPERATION LAMP
WITH EARTH
TIMER LAMP
TERMINAL
F
F
O
O N
INDOOR UNIT ON/OFF SWITCH
(INSIDE)
11-9/64(283mm)
BOTTOM
ROOM TEMP. THERMISTOR
FLAPS
GAS PIPE φ3/8(φ9.5mm) CuT
(INSIDE)
DRAIN HOSE
(THE LENGTH OF PIPE OUTSIDE
(CONNECTING PART
THE UNIT : ABOUT 15-23/64(390mm))
I.D.
F
F
O
O N
LIQUID PIPE φ1/4(φ6.4mm) CuT
O.D.
φ
9/16(φ14mm)
φ
5/8(φ16mm)
(THE LENGTH OF PIPE OUTSIDE
THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 17-21/64(440mm))
THE UNIT IS ABOUT 17-23/32(450mm))
30-5/16(770mm)
MODEL NAME
SIGNAL TRANSMITTER
15/64(6mm)
21-39/64(549mm)
5/8(16mm)
PLATE
3-31/32(101mm)
11/16(18mm)2-5/16(58mm)
BLADE ANGLE
6-49/64(172mm)
UP/DOWN (AUTOMATIC)
11-9/64(283mm)
1-5/8(41.3mm)
COOLING DRY FAN
45˚ 45˚45˚
2-9/64(54.5mm) 2-1/8(54mm)
1-5/8(41.3mm)
7-3/8(187mm)
WALL HOLE FOR EMBEDDED PIPING
RIGHT/LEFT (MANUAL)
φ
2-9/16(φ65mm) HOLE
WALL HOLE
φ
2-9/16(φ65mm) HOLE
STANDARD LOCATIONS OF WALL HOLES
WIRELESS REMOTE CONTROLLER
45˚
45˚
(ARC452A14)
3D065952B
AIRFLOW (INDOOR)
THE MARK () SHOWS PIPING DIRECTION
REAR
30-5/16(770mm)
RIGHT
LEFT
1-3/16(30mm)MIN.
INCLUDING MOUNTING PLATE
(SPACE FOR
PERFORMANCE)
7-7/8(200mm)
1-15/16(50mm)MIN.
1-15/16(50mm)MIN.
7-51/64(198mm)
(SPACE FOR
(SPACE FOR
FRONT PANEL FIXING SCREWS
REQUIRED SPACE
MAINTENANCE)
MAINTENANCE)
(INSIDE)
GENERAL RATING NAME PLATE
SIGNAL RECEIVER
TERMINAL BLOCK
OPERATION LAMP
WITH EARTH
TIMER LAMP
TERMINAL
F
F
O
O N
INDOOR UNIT ON/OFF SWITCH
(INSIDE)
11-9/64(283mm)
BOTTOM
ROOM TEMP. THERMISTOR
FLAPS
GAS PIPE φ3/8(φ9.5mm) CuT
(INSIDE)
DRAIN HOSE
(THE LENGTH OF PIPE OUTSIDE
(CONNECTING PART
THE UNIT : ABOUT 15-23/64(390mm))
I.D.
F
F
O
O N
LIQUID PIPE φ1/4(φ6.4mm) CuT
O.D.
φ
9/16(φ14mm)
φ
5/8(φ16mm)
(THE LENGTH OF PIPE OUTSIDE
THE HOSE LENGTH OF OUTSIDE
THE UNIT : ABOUT 17-21/64(440mm))
THE UNIT IS ABOUT 17-23/32(450mm))
30-5/16(770mm)
MODEL NAME
SIGNAL TRANSMITTER
15/64(6mm)
21-39/64(549mm)
5/8(16mm)
PLATE
3-31/32(101mm)
11/16(18mm)2-5/16(58mm)
BLADE ANGLE
6-49/64(172mm)
UP/DOWN (AUTOMATIC)
11-9/64(283mm)
1-5/8(41.3mm)
COOLING HEATING DRY
15˚
45˚
45˚
2-9/64(54.5mm) 2-1/8(54mm)
45˚
1-5/8(41.3mm)
7-3/8(187mm)
FAN
WALL HOLE FOR EMBEDDED PIPING
RIGHT/LEFT (MANUAL)
φ
2-9/16(φ65mm) HOLE
WALL HOLE
φ
2-9/16(φ65mm) HOLE
STANDARD LOCATIONS OF WALL HOLES
WIRELESS REMOTE CONTROLLER
45˚
45˚
45˚
(ARC452A12)
3D065951B
4. Dimensions
4.1 Indoor Units
FTKS09/12JEVJU
FTXS09/12JEVJU
Room Air Conditioners J-Series 7
Page 9
Dimensions EDUS041011
DRAIN OUTLET
4-HOLES FOR ANCHOR BOLTS
(I.D5/8 [φ15.9] HOSE FOR CONNECTION
(M8 OR M10)
WITH DRAIN JOINT [ OPTION ] )
18-1/2(470) 3-25/32(96)
1-9/16(40)
7/16(11)
14-29/32(379)
11-11/16(297)
OUTDOOR AIR THERMISTOR
BRAND NAME LABEL
MANUFACTURE'S LABEL
HANDLE
5/16(8)
5/16(8) 1-31/32(50)
10-13/16(275)
15/32(12) 25-29/32(658)
LIQUID STOP VALVE 1/4(φ6.4)CuT
SERVICE PORT
21-21/32(550)
6-5/8(168)
6-3/32(155)
WALL HEIGHT ON AIR OUTLET SIDE
MINIMUM SPACE FOR AIR PASSAGE
4-1/4(108)
=LESS THAN 47-3/16(1200)
IN CASE OF REMOVING
GAS STOP
VALVE
STOP VALVE
3/8(φ9.5)CuT
5-7/8(150)
5-7/8(150)
1-15/16(50)1-15/16(50)1-15/16(50)
3-15/16(100)
1-15/16(50)
UNIT = INCH(mm)
3-15/16(100)
11-13/16(300)
3D065923A
4.2 Outdoor Units
RKS09/12JEVJU, RXS09/12JEVJU
8 Room Air Conditioners J-Series
Page 10
EDUS041011 Wiring Diagrams
PCB 2
PCB 1
S26S27
FIELD WIRING.
BLK
19
BLK
TRANSMISSION
BLK
GRN/YLW
LED1 H1P
CIRCUIT
BLK
BLK
3
FG
LED2 H2P
BLK
GRN
BLK
2
RECTIFIER
H3
BLK
+
RED
3
1
BLK
OUTDOOR
9
MR10
1
V1
H2
WHT
2
H1
CAUTION
BLK
S1W
1
NOTE THAT OPERATION WILL
F1U
RESTART AUTOMATICALLY IF
X1M
3.15A
THE MAIN POWER SUPPLY IS
+
R1T
TURNED OFF AND THEN BACK
IPM200
SIGNAL
ON AGAIN.
RECEIVER
11125 10S40312916
S32
S200
S6
INDOOR
BLK BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLKBLK
YLW
BLKBLKBLK
WIRELESS
BLU
BLK
RED
WHT
ORG
FG
REMOTE
F1U
1416
S601S602
CONTROLLER
H1~H3
MM
H1P~H2P
M1S
M1F
M1F
R2T
M1S PCB1~PCB3 R1T, R2T
NOTE)
S6~S602
S21
S1W
1.PCB3 SHOWS THE CASE OF X1M
OPTION CONNECTION.
PCB 3
OPTION
: FRAME GROUND : FUSE : HARNESS : PILOT LAMP : FAN MOTOR : SWING MOTOR : PRINTED CIRCUIT BOARD : THERMISTOR : CONNECTOR : OPERATION SWITCH : TERMINAL STRIP : PROTECTIVE EARTH
3D065939A
5. Wiring Diagrams
5.1 Indoor Units
FTKS09/12JEVJU, FTXS09/12JEVJU
5.2 Outdoor Units
RKS09/12JEVJU, RXS09/12JEVJU
Room Air Conditioners J-Series 9
Page 11
Piping Diagrams EDUS041011
INDOOR UNIT
HEAT EXCHANGER
9/32CuT
3/16CuT
9/32CuT
THERMISTOR ON HEAT EXCH.
9/32CuT
9/32CuT
CROSS FLOW FAN
FIELD PIPING (1/4CuT)
M
FAN MOTOR
3/8CuT
FIELD PIPING (3/8CuT)
REFRIGERANT FLOW
COOLING
4D066315
INDOOR UNIT
HEAT EXCHANGER
9/32CuT
3/16CuT
9/32CuT
THERMISTOR ON HEAT EXCH.
9/32CuT
9/32CuT
CROSS FLOW FAN
FIELD PIPING (1/4CuT)
M
FAN MOTOR
3/8CuT
FIELD PIPING (3/8CuT)
REFRIGERANT FLOW
COOLING HEATING
4D066211
6. Piping Diagrams
6.1 Indoor Units
FTKS09/12JEVJU FTXS09/12JEVJU
10 Room Air Conditioners J-Series
Page 12
EDUS041011 Piping Diagrams
OUTDOOR UNIT
HEAT EXCHANGER
9/32CuT
9/32CuT
3/8CuT
MOTOR OPERATED VALV E
3/16CuT
1/4CuT
1/4CuT
3/16CuT
THERMSTOR
MUFFLER
HEAT EXCHANGER
WITH
FILTER
FAN
MOTOR
M
PROPELLER FAN
1/4CuT
3/8CuT
STRAINER
FIELD PIPING
3/16CuT
(1/4CuT)
LIQUID STOP
3/8CuT
VALV E
1/4CuT
REFRIGERANT FLOW
MUFFLER MUFFLER
FIELD PIPING
3/8CuT
DISCHARGE PIPE
COOLING
COMPRESSOR
THERMISTOR
(3/8CuT)
GAS STOP VALV EACCUMULATOR
3D065937
OUTDOOR UNIT
OUTDOOR TEMPERATURE
HEAT EXCHANGER
9/32CuT
THERMISTOR
9/32CuT
3/8CuT
MOTOR OPERATED VALV E
3/16CuT
1/4CuT 1/4CuT
3/16CuT
MUFFLER
THERMISTOR
WITH
HEAT EXCHANGER
FILTER
FAN
MOTOR
M
PROPELLER FAN
1/4CuT
3/8CuT
3/8CuT
STRAINER
FOUR WAY VALV E ON : HEATING
FIELD PIPING
3/16CuT
(1/4CuT)
LIQUID STOP
3/8CuT
VALV E
1/4CuT
REFRIGERANT FLOW
MUFFLER MUFFLER
FIELD PIPING
3/8CuT
DISCHARGE PIPE
COOLING
COMPRESSOR
THERMISTOR
(3/8CuT)
GAS STOP
HEATING
VALV E
ACCUMULATOR
3D065936
6.2 Outdoor Units
RKS09/12JEVJU
RXS09/12JEVJU
Room Air Conditioners J-Series 11
Page 13
Capacity Tables EDUS041011
7. Capacity Tables
7.1 Cooling Only
FTKS09JEVJU + RKS09JEVJU (60Hz 208/230V)
AFR 9.2
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.211.770.492.211.770.552.211.770.612.211.770.642.201.760.672.091.710.72
16.022.02.671.900.522.551.850.572.431.790.632.391.770.652.321.740.682.201.690.73
18.025.02.781.990.532.661.940.582.551.900.632.501.880.652.431.850.682.321.800.73
19.426.72.842.110.532.722.060.582.612.010.632.561.990.65
22.030.03.012.040.532.891.990.582.781.950.632.731.940.652.661.910.682.551.870.73
24.032.03.121.980.543.011.950.592.891.910.642.851.890.662.781.870.692.661.830.74
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.545.170.467.545.170.537.545.170.607.545.170.637.525.150.677.134.830.68
60.871.69.106.140.528.705.790.578.315.460.638.155.330.657.915.140.687.524.830.68
64.477.09.496.180.539.105.850.588.705.530.638.545.400.658.305.220.687.914.920.69
67.080.09.696.260.539.295.930.588.905.620.638.745.500.65
71.6 86.0 10.27 6.02 0.53 9.88 5.71 0.58 9.48 5.42 0.63 9.32 5.31 0.65 9.09 5.15 0.68 8.69 4.88 0.69
75.289.610.675.810.5410.275.520.599.875.250.649.725.150.669.484.990.699.084.740.69
2.49 1.97 0.68 2.37 1.92 0.73
8.50 5.32 0.68 8.10 5.03 0.69
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066175
12 Room Air Conditioners J-Series
Page 14
EDUS041011 Capacity Tables
FTKS12JEVJU + RKS12JEVJU (60Hz 208/230V)
AFR 9.3
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.221.770.542.221.770.612.221.770.692.221.770.722.221.770.762.221.770.84
16.022.02.972.050.602.972.050.672.861.990.742.811.970.762.731.930.792.591.870.85
18.025.03.272.220.623.142.150.683.002.090.742.942.070.762.862.030.802.731.980.86
19.426.73.342.330.623.202.270.683.072.210.743.012.190.76
22.030.03.542.240.633.412.190.693.272.140.753.212.120.773.132.090.813.002.040.86
24.032.03.682.180.633.542.130.693.402.080.753.352.070.773.272.040.813.131.990.87
2.93 2.15 0.80 2.79 2.10 0.86
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.585.200.487.585.200.557.585.200.627.585.200.657.585.200.707.585.200.74
60.871.610.147.100.5910.147.100.679.776.750.749.596.580.769.316.320.798.845.900.80
64.4 77.0 11.17 7.73 0.62 10.70 7.27 0.68 10.24 6.83 0.74 10.05 6.66 0.76 9.77 6.42 0.80 9.30 6.02 0.81
67.0 80.0 11.40 7.81 0.62 10.93 7.36 0.68 10.47 6.93 0.74 10.28 6.76 0.76
71.6 86.0 12.09 7.54 0.63 11.62 7.12 0.69 11.16 6.72 0.75 10.97 6.56 0.77 10.69 6.33 0.81 10.23 5.97 0.81
75.2 89.6 12.55 7.30 0.63 12.08 6.90 0.69 11.62 6.52 0.75 11.43 6.37 0.77 11.15 6.16 0.81 10.69 5.81 0.82
10.00 6.52 0.80 9.53 6.12 0.81
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066176
Room Air Conditioners J-Series 13
Page 15
Capacity Tables EDUS041011
7.2 Heat Pump
FTXS09JEVJU + RXS09JEVJU (60Hz 208/230V)
Cooling
AFR 9.2
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.211.770.492.211.770.552.211.770.612.211.770.642.201.760.672.091.710.72
16.022.02.671.900.522.551.850.572.431.790.632.391.770.652.321.740.682.201.690.73
18.025.02.781.990.532.661.940.582.551.900.632.501.880.652.431.850.682.321.800.73
19.426.72.842.110.532.722.060.582.612.010.632.561.990.65
22.030.03.012.040.532.891.990.582.781.950.632.731.940.652.661.910.682.551.870.73
24.032.03.121.980.543.011.950.592.891.910.642.851.890.662.781.870.692.661.830.74
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.545.170.467.545.170.537.545.170.607.545.170.637.525.150.677.134.830.68
60.871.69.106.140.528.705.790.578.315.460.638.155.330.657.915.140.687.524.830.68
64.477.09.496.180.539.105.850.588.705.530.638.545.400.658.305.220.687.914.920.69
67.080.09.696.260.539.295.930.588.905.620.638.745.500.65
71.6 86.0 10.27 6.02 0.53 9.88 5.71 0.58 9.48 5.42 0.63 9.32 5.31 0.65 9.09 5.15 0.68 8.69 4.88 0.69
75.289.610.675.810.5410.275.520.599.875.250.649.725.150.669.484.990.699.084.740.69
2.49 1.97 0.68 2.37 1.92 0.73
8.50 5.32 0.68 8.10 5.03 0.69
Heating
AFR 9.7
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15.0 –10.0 –5.0 0 6.0 10.0
°C TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.40 0.50 1.68 0.52 1.96 0.55 2.63 0.72 3.03 0.76 3.30 0.78
21.1 1.31 0.51 1.59 0.54 1.87 0.56 2.53 0.74
22.0 1.27 0.52 1.56 0.54 1.84 0.57 2.49 0.74 2.89 0.78 3.15 0.81
24.0 1.24 0.52 1.52 0.55 1.80 0.58 2.45 0.75 2.85 0.79 3.11 0.81
25.0 1.22 0.53 1.50 0.55 1.79 0.58 2.43 0.75 2.83 0.79 3.09 0.82
27.0 1.19 0.53 1.47 0.56 1.75 0.58 2.39 0.76 2.79 0.80 3.05 0.82
2.93 0.78 3.19 0.80
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5.0 14.0 23.0 32.0 43.0 50.0
°F TC PI TC PI TC PI TC PI TC PI TC PI
59.0 4.76 0.50 5.72 0.52 6.68 0.55 8.99 0.72 10.35 0.76 11.25 0.78
70.0 4.47 0.51 5.43 0.54 6.39 0.56 8.64 0.74
71.6 4.35 0.52 5.31 0.54 6.27 0.57 8.51 0.74 9.86 0.78 10.77 0.81
75.2 4.23 0.52 5.19 0.55 6.15 0.58 8.37 0.75 9.72 0.79 10.63 0.81
77.0 4.18 0.53 5.14 0.55 6.10 0.58 8.30 0.75 9.65 0.79 10.56 0.82
80.6 4.06 0.53 5.02 0.56 5.98 0.58 8.16 0.76 9.52 0.80 10.42 0.82
10.00 0.78 10.90 0.80
14 Room Air Conditioners J-Series
Page 16
EDUS041011 Capacity Tables
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066177
Room Air Conditioners J-Series 15
Page 17
Capacity Tables EDUS041011
FTXS12JEVJU + RXS12JEVJU (60Hz 208/230V)
Cooling
AFR 9.3
BF 0.27
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.020.02.221.770.542.221.770.612.221.770.692.221.770.722.221.770.762.221.770.84
16.022.02.972.050.602.972.050.672.861.990.742.811.970.762.731.930.792.591.870.85
18.025.03.272.220.623.142.150.683.002.090.742.942.070.762.862.030.802.731.980.86
19.426.73.342.330.623.202.270.683.072.210.743.012.190.76
22.030.03.542.240.633.412.190.693.272.140.753.212.120.773.132.090.813.002.040.86
24.032.03.682.180.633.542.130.693.402.080.753.352.070.773.272.040.813.131.990.87
2.93 2.15 0.80 2.79 2.10 0.86
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 90.0 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.07.585.200.487.585.200.557.585.200.627.585.200.657.585.200.707.585.200.74
60.871.610.147.100.5910.147.100.679.776.750.749.596.580.769.316.320.798.845.900.80
64.4 77.0 11.17 7.73 0.62 10.70 7.27 0.68 10.24 6.83 0.74 10.05 6.66 0.76 9.77 6.42 0.80 9.30 6.02 0.81
67.0 80.0 11.40 7.81 0.62 10.93 7.36 0.68 10.47 6.93 0.74 10.28 6.76 0.76
71.6 86.0 12.09 7.54 0.63 11.62 7.12 0.69 11.16 6.72 0.75 10.97 6.56 0.77 10.69 6.33 0.81 10.23 5.97 0.81
75.2 89.6 12.55 7.30 0.63 12.08 6.90 0.69 11.62 6.52 0.75 11.43 6.37 0.77 11.15 6.16 0.81 10.69 5.81 0.82
10.00 6.52 0.80 9.53 6.12 0.81
Heating
AFR 10.1
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15.0 –10.0 –5.0 0 6.0 10.0
°C TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.68 0.60 2.01 0.63 2.35 0.66 3.16 0.86 3.64 0.91 3.96 0.94
21.1 1.57 0.62 1.91 0.65 2.25 0.68 3.04 0.88
22.0 1.53 0.62 1.87 0.65 2.21 0.68 2.99 0.89 3.47 0.94 3.79 0.97
24.0 1.49 0.63 1.83 0.66 2.17 0.69 2.95 0.90 3.42 0.95 3.74 0.98
25.0 1.47 0.63 1.81 0.66 2.15 0.69 2.92 0.90 3.40 0.95 3.72 0.98
27.0 1.43 0.64 1.77 0.67 2.10 0.70 2.87 0.91 3.35 0.96 3.67 0.99
3.52 0.93 3.84 0.96
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5.0 14.0 23.0 32.0 43.0 50.0
°F TC PI TC PI TC PI TC PI TC PI TC PI
59.0 5.71 0.60 6.87 0.63 8.02 0.66 10.79 0.86 12.41 0.91 13.50 0.94
70.0 5.36 0.62 6.51 0.65 7.67 0.68 10.37 0.88
71.6 5.22 0.62 6.37 0.65 7.53 0.68 10.21 0.89 11.83 0.94 12.92 0.97
75.2 5.08 0.63 6.23 0.66 7.38 0.69 10.04 0.90 11.67 0.95 12.75 0.98
77.0 5.01 0.63 6.16 0.66 7.31 0.69 9.96 0.90 11.59 0.95 12.67 0.98
80.6 4.87 0.64 6.02 0.67 7.17 0.70 9.79 0.91 11.42 0.96 12.50 0.99
12.00 0.93 13.08 0.96
16 Room Air Conditioners J-Series
Page 18
EDUS041011 Capacity Tables
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
3D066178
Room Air Conditioners J-Series 17
Page 19
Capacity Tables EDUS041011
Capacity correction factor
1
16.4 32.8 49.2
0.9
0.8
R-410A (09/12 class)
Piping length (ft)
(R11493)
Range of the refrigerant additional charge
7.3 Capacity correction factor by the length of refrigerant piping (Reference)
The cooling and the heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit)
<— line : cooling capacity> <--- line : heating capacity>
The graph shows the factor when additional refrigerant of the proper quantity is charged.
Note:
18 Room Air Conditioners J-Series
Page 20
EDUS041011 Operation Limit
122
114.8
104
86
68
Pull-down period
Continuous operation
Outdoor temp. (˚FDB)
50
32
866857.250 73.4 82.4
Indoor temp. (˚FWB)
Notes:
The graphs are based on the following conditions.
• Equivalent piping length 25ft
• Level difference 0ft
• Air flow rate High
4D066173
Heating
Cooling
68
122
114.8 59
104
50
86
41
32
68
Pull-down period
Outdoor temp. (˚FWB)
23
Continuous operation
Outdoor temp. (˚FDB)
50
Continuous operation
14
32
5
82.468 8673.457.250 (5˚FDB)
Indoor temp. (˚FWB)
50 8668
Notes:
Indoor temp. (˚FDB)
The graphs are based on the following conditions.
• Equivalent piping length 25ft
• Level difference 0ft
• Air flow rate High
3D066174
8. Operation Limit
RKS09/12JEVJU
RXS09/12JEVJU
Room Air Conditioners J-Series 19
Page 21
Sound Level EDUS041011
3.3ft
2.6ft
(R5162)
3.3ft
(R4796)
9. Sound Level
9.1 Measuring Location
Indoor Unit
The Single Split Duct-Free System
Outdoor Unit
1. Operation sound is measured in an anechoic chamber.
2. The data are based on the conditions shown in the table below.
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
Note:
25ft
20 Room Air Conditioners J-Series
Page 22
EDUS041011 Sound Level
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
40 26
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
4D066168
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
41 27
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
4D066169
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
60
20
10
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
10
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
40 26
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
60Hz 60Hz
208/230V 208/230V
(H) (L)
40 28
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
NC-50
NC-40
NC-30
NC-20
NC-10
Heating
3D066170
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
10
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
10
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-50
NC-40
NC-30
NC-20
NC-10
NC-50
NC-40
NC-30
NC-20
NC-10
60Hz 60Hz
208/230V 208/230V
(H) (L)
41 27
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling
60Hz 60Hz
208/230V 208/230V
(H) (L)
41 29
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Heating
3D066171
9.2 Octave Band Level
9.2.1 Indoor Units
FTKS09JEVJU FTKS12JEVJU
FTXS09JEVJU
FTXS12JEVJU
Room Air Conditioners J-Series 21
Page 23
Sound Level EDUS041011
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
4D066163
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
4D066164
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V(H)
48
208/230V 60Hz
60Hz 208/230V
Cooling
NC-60
NC-50
NC-40
NC-30
NC-20
208/230V 60Hz
60Hz 208/230V
Heating
60Hz
208/230V(H)
48
3D066166
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-60
NC-20
NC-40
NC-50
NC-30
48
208/230V(H)
60Hz
Cooling
208/230V 60Hz
60Hz 208/230V
49
208/230V(H)
60Hz
208/230V 60Hz
60Hz 208/230V
Heating
NC-50
NC-20
NC-30
NC-60
NC-40
3D066167
9.2.2 Outdoor Units
RKS09JEVJU RKS12JEVJU
RXS09JEVJU
RXS12JEVJU
22 Room Air Conditioners J-Series
Page 24
EDUS041011 Electric Characteristics
10.Electric Characteristics
Representative Unit Combination Power Supply COMP OFM IFM
Indoor Unit Outdoor Unit Hz-Volts Voltage Range MCA MOP RLA W FLA W FLA
FTKS09JEVJU RKS09JEVJU
FTKS12JEVJU RKS12JEVJU
FTXS09JEVJU RXS09JEVJU
FTXS12JEVJU RXS12JEVJU
60-208
60-230 3.4 0.17 0.18
60-208
60-230 3.4 0.17 0.18
60-208
60-230 3.3 0.17 0.18
60-208
60-230 4.0 0.17 0.18
MAX. 60Hz 253V
MIN. 60Hz 187V
MAX. 60Hz 253V
MIN. 60Hz 187V
MAX. 60Hz 253V
MIN. 60Hz 187V
MAX. 60Hz 253V
MIN. 60Hz 187V
4.4 15
4.4 15
4.3 15
5.2 15
Symbols: Note:
MCA : MIN. CIRCUIT AMPS (A) 1. Maximum allowable voltage variation between phases is 2%.
MOP : MAX OVERCURRENT PROTECTION
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
2. Select wire size based on the larger value of MCA.
3. Instead of fuse, use circuit breaker.
4. Be sure to install a ground leak detector. (One that can handle higher harmonics.) (This unit uses an inverter, which means that it must use a ground leak detector capable handling high harmonics in order to prevent malfunctioning of the ground leak detector itself.)
3.7
3.7
3.7
4.4
33
33
33
33
0.19
0.19
0.19
0.19
40
40
40
40
0.20
0.20
0.20
0.20
3D066179B
Room Air Conditioners J-Series 23
Page 25
Installation Manual EDUS041011
1
Safety Precautions
• Read these Safety Precautions carefully to ensure correct installation.
• This manual classifies the precautions into DANGER, WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety.
DANGER..........Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
........Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTION .........Failure to follow any of CAUTION may in some cases result in grave consequences.
• The following safety symbols are used throughout this manual:
After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual.
Be sure to observe this instruction. Be sure to establish a ground connection. Never attempt.
DANGER
• Refrigerant gas is heavier than air and replaces oxygen. A massive leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• If the refrigerant gas leaks during installation, ventilate the area immediately.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• After completing the installation work, check that the refrigerant gas does not leak.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apar t and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face the danger of death by suffocation.
Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death.
Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
WARNING
• Installation should be left to the authorized dealer or another trained professional.
Improper installation may cause water leakage, electrical shock, fire, or equipment damage.
• Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire or equipment damage.
• Be sure to use the supplied or exact specified installation parts.
Use of other parts may cause the unit to come to fall, water leakage, electrical shock, fire or equipment damage.
• Install the air conditioner on a solid base that is level and can support the weight of the unit.
An inadequate base or incomplete installation may cause injury or equipment damage in the event the unit falls off the base or comes loose.
• Electrical work should be carried out in accordance with the installation manual and the national, state and local electrical wiring codes.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire or equipment damage.
• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. Follow all appropriate electrical codes.
• For wiring, use a wire or cable long enough to cover the entire distance with no splices if possible. Do not use an extension cord. Do not put other loads on the power supply. Use an only a separate dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock, fire or equipment damage.)
• Use the specified types of wires for electrical connections between the indoor and outdoor units. Follow all state and local electrical codes.
Firmly clamp the inter-unit wiring so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating, fire or equipment damage.
• After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical covers, panels or terminals.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock,fire or equipment damage.
• When installing or relocating the system, be sure to keep the refrigerant circuit free from all substances other than the specified refrigerant (R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which may result in rupture, resulting in injury.)
11.Installation Manual
11.1 Indoor Units
24 Room Air Conditioners J-Series
Page 26
EDUS041011 Installation Manual
2
Safety Precautions
Accessories
,
Choosing an Installation Site
• Before choosing the installation site, obtain user approval.
1.
Indoor unit
• The indoor unit should be sited in a place where:
1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air inlet and air outlet have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool (warm) air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the remote controller range,
8)
the unit is at least 3.5 feet (1m) away from any television or radio set (unit may cause interference with the picture or sound).
2.
Wireless remote controller
1) Turn on all the fluorescent lamps in the room, if any, and find the site where remote control signals are properly received by the indoor unit (within 23 feet (7m)).
WARNING
• During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing abnormally high pressure which could lead to equipment damage and personal injury.
• Be sure to install a ground fault circuit interrupter breaker.
Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.
CAUTION
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual.
Inadequate piping may cause water damage.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
Mounting plate
1
Remote controller holder
1
Operation manual
1
Mounting plate fixing screw 3/16” × 1” (M4 × 25mm)
6
Fixing screw for remote controller
holder 1/8” × 13/16” (M3 × 20mm)
2
Installation manual
1
Titanium apatite photocatalytic air-purifying filter
2
Dry battery AAA. LR03
(alkaline)
2
Wireless remote controller
1
Indoor unit fixing screw
3/16” × 1/2” (M4 × 12mm)
2
Indoor unit
A
K
A
E
J
B
F
K
C
G
D
H
Room Air Conditioners J-Series 25
Page 27
Installation Manual EDUS041011
3
Preparation before Installation
1.
Removing and installing front panel
•Removal method
Hook fingers on the tabs on the left and right of the main body, and open until the panel stops. Slide the front panel sideways to disengage the rotating shaft. Then pull the front panel toward you to remove it.
••Installation method
Align the tabs of the front panel with the grooves, and push all the way in. Then close slowly. Push the center of the lower surface of the panel firmly to engage the tabs.
2.
Removing and installing front grille
R
emoval method
1) Remove front panel to remove the air filter.
2) Remove 2 screws from the front grille.
3) In front of the

mark of the front grille, there are 3 upper hooks. Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand.
When there is no work space because the unit is close to ceiling
CAUTION
• Be sure to wear protection gloves.
Place both hands under the center of the front grille, and while pushing up, pull it toward you.
• Installation method
1) Install the front grille and firmly engage the upper hooks (3 locations).
2) Install 2 screws of the front grille.
3) Install the air filter and then mount the front panel.
3.
How to set the different addresses
When two indoor units are installed in one room, the two wireless remote controllers can be set for different addresses.
1) In the same way as when connecting to an HA system, remove the metal plate electrical wiring cover.
2) Cut the address jumper (JA) on the printed circuit board.
3) Cut the address jumper (J4) in the remote controller.
Push the rotating shaft of the front panel into the groove.
mar

k area
(3 locations)
Upper hook
Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand. (3 locations)
Push down.
Upper hook
1) Push up.
2) Pull toward you.
ADDRESS
EXIST
CUT12
JA
JA
ADDRESS
J4
EXIST
1
CUT 2
J4
26 Room Air Conditioners J-Series
Page 28
EDUS041011 Installation Manual
4
Indoor Unit Installation Drawings
How to attach the indoor unit
Hook the claws of the bottom frame
Mounting plate
A
The mounting plate should be installed on a wall which can support the
Mounting plate fixing screw
B
3/16” × 1” (M4 × 25mm)
Front panel
1-15/16” (50mm) or more from walls (on both sides)
Air filters
Titanium apatite photocatalytic
C
air-purifying filter (2)
Air filter
weight of the indoor unit.
1-3/16” (30mm) or more from ceiling
3/16” × 5/8” (M4 × 16mm)
Opening service lid
Service lid is opening/closing type.
Opening method
to the mounting plate. If the claws are difficult to hook, remove the front grille.
How to remove the indoor unit
Push up the marked area (at the lower part of the front grille) to release the claws. If it is difficult to release, remove the front grille.
Service lid
1) Remove the service lid screws.
2) Pull out the service lid diagonally down in the direction of the arrow.
3) Pull down.
Caulk pipe hole gap with putty.
Front grille
Mounting
A
plate
Bottom frame
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe’s cut line.
Wrap the insulation pipe with the finishing tape from bottom to top.
Mark (rear side)
Clip
Filter frame
Titanium apatite photocatalytic
Ta b
Room Air Conditioners J-Series 27
air-purifying filter
Fixing screw for remote
F
controller holder 1/8” × 13/16” (M3 × 20mm)
D Wireless remote controller
Before screwing the remote controller holder to the wall, make sure that control signals are properly received by indoor unit.
E Remote controller holder
Page 29
Installation Manual EDUS041011
5
Indoor Unit Installation
1.
Installing the mounting plate
• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the boring points on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
* The removed pipe port cover can be kept in the mounting plate pocket.
Removed pipe port cover
A
Mounting plate
Use tape measure as shown.
Position the end of a tape measure at .
Liquid pipe end
Gas pipe end
Through­the-wall hole φ2-9/16 (φ65)
Recommended mounting plate retention spots (5 spots in all)
Place a leveler on raised tab.
9-33/64
(241.7)
1-5/8
(41.3)
13-1/64 (330.5)
13-1/32
(331)
6-19/64
(160)
2-1/8
(54)
30-5/16
(770)
9-33/64
(241.7)
1-5/8
(41.3)
2-9/64
(54.5)
6-19/64
(160)
1-31/32
(50)
4-31/32
(101)
4-47/64
(120.5)
7-63/64
(203)
9-23/32
(247)
Drain hose position
unit: inch (mm)
(Bolt size: 3/8 (M10)) (Bolt size: 3/8 (M10))
28 Room Air Conditioners J-Series
Page 30
EDUS041011 Installation Manual
6
Indoor Unit Installation
2.
Boring a wall hole and installing wall embedded pipe
• For walls containing metal frame or metal board, be sure to use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage.
1) Bore a feed-through hole of 2-9/16 inch (65mm) in the wall so it has a
down slope toward the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole
gap with putty.
3.
Installing indoor unit
• In the case of bending or curing refrigerant pipes, keep the following precautions in mind. Abnormal sound may be generated if improper work is conducted.
1) Do not strongly press the refrigerant pipes onto the bottom frame.
2) Do not strongly press the refrigerant pipes on the front grille, either.
3-1. Right-side, right-back, or right-bottom piping
1) Attach the drain hose to the underside of the refrigerant pipes with an adhesive vinyl tape.
2) Wrap the refrigerant pipes and drain hose together with insulation tape.
3) Pass the drain hose and refrigerant pipes through the wall hole, then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide.
4) Open the front panel, then open the service lid.
5) Pass the inter-unit wiring from the outdoor unit through the feed-through wall hole and then through the back of the indoor unit. Pull them through the front side. Bend the ends of tie wires upward for easier work in advance. (If the inter-unit wiring ends are to be stripped first, bundle wire ends with adhesive tape.)
6) Press the bottom frame of the indoor unit with both hands to set it on the mounting plate hooks. Make sure the wires do not catch on the edge of the indoor unit.
Inside Outside
Caulking
Wall embedded pipe (field supply)
Wall hole cover (field supply)
Wall embedded pipe (field supply)
φ2-9/16” ( 65mm)
1)
2)
Right-bottom piping
Right-side piping
Right-back piping
Bind coolant pipe and drain hose together with insulating tape.
Remove pipe port cover here for right-side piping.
Remove pipe port cover here for right-bottom piping.
Mounting plate
A
When stripping the ends of inter-unit wiring in advance, bind right ends of wires with insulating tape.
Hang indoor unit’s hook here.
Inter-unit wiring
Mounting plate
A
Room Air Conditioners J-Series 29
Page 31
Installation Manual EDUS041011
7
3-2. Left-side, left-back, or left-bottom piping
1) Attach the drain hose to the underside of the refrigerant pipes
with adhesive vinyl tape.
2) Be sure to connect the drain hose to the drain port in place of a
drain plug.
3) Shape the refrigerant pipes along the pipe
path marking on the mounting plate.
4) Pass drain hose and refrigerant pipes
through the wall hole, then set the indoor unit on mounting plate hooks, using the markings at the top of indoor unit as a guide.
5) Pull in the inter-unit wiring.
6) Connect the inter-unit piping.
7) Wrap the refrigerant pipes and drain hose together with insulation tape as
right figure, in case of setting the drain hose through the back of the indoor unit.
8) While exercising care so that the inter-unit wiring do not catch indoor unit,
press the bottom edge of indoor unit with both hands until it is firmly caught by the mounting plate hooks. Secure indoor unit to the mounting plate with indoor unit fixing screws 3/16 × 1/2 inch (M4 × 12mm).
3-3. Wall embedded piping
• Insert the drain hose to this depth so it won’t be pulled out of the drain pipe.
Remove pipe port cover here for left-bottom piping.
Remove pipe port cover here for left­side piping.
Left-bottom piping
Left-side piping
Left-back piping
How to set drain plug.
No gap.
Do not apply lubricating oil (refrigeration oil) when inserting. Application of causes deterioration and drain leakage of the plug.
Insert a hexagonal wrench 3/16” (4mm).
Drain hose
Caulk this hole with putty or caulking material.
Bind with vinyl tape.
A
Mounting plate
Wrap insulating tape around the bent portion of refrigerant pipes. Overlap at least half the width of the tape with each turn.
Refrigerant pipes
Drain hose
Bottom frame
H Indoor unit fixing screw
3/16” × 1/2” (M4 × 12mm) (2 point)
Mounting plate
A
Inter-unit wiring
Inner wall
Vinyl chloride drain pipe (VP-30)
Drain hose1-15/16” (50mm)
or more
Insert the drain hose to this depth so it won’t be pulled out of drain pipe.
Outer wall
How to replace the drain plug and drain hose
• Replacing onto the left side
1) Remove the insulation fixing screws on the right to remove the drain hose.
2) Reattach the insulation fixing screw on the right as it was. * (Forgetting to attach this may cause water
leakages.)
3) Remove the drain plug on the left side and attach it to the right side.
4) Insert the drain hose and tighten with included insulation fixing screw.
Drain hose attachment position
* The drain hose is on the back of the unit.
Front side of unit
Attachment on the left side
Insulation fixing screw
Drain hose Drain hose
Attachment on the right side (factory default)
Right sideLeft side
Insulation fixing screw
30 Room Air Conditioners J-Series
Page 32
EDUS041011 Installation Manual
8
Indoor Unit Installation
4.
Wiring
1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut onto the conduit mounting plate.
2) Strip wire ends (9/16 inch (15mm)).
3) Match wire colors with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the corresponding terminals.
4) Connect the ground wires to the corresponding terminals.
5) Pull wires to make sure that they are securely latched up.
6) In case of connecting to an adapter system. Run the remote control cable and attach the S21.
7) Shape the wires so that the service lid fits securely, then close service lid.
WARNING
• Do not use tapped wires, strand wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
• When carrying out wiring connection, take care not to pull at the conduit.
5.
When connecting to a wired remote controller
* If work space is available on the right side of the indoor unit, the work
can be performed with the electrical component box attached. Omit the steps involved with removing and installing the electrical component box in order to perform the work more efficiently.
5-1. Remove the front grille (2 screws).
5-2. Remove the service lid (1 screw).
5-3. Remove the cover from the indoor unit electrical
component box [Figure 1].
*5-4.
Remove the indoor unit electrical component box.
1) Remove the louver.
2) Disconnect the communication wiring.
3) Disconnect the connector (S200).
4) Remove the thermistor from the heat exchanger.
5) Remove the electrical component box installation screw (1 screw).
123
Terminal block
Electrical component box
Use the specified wire type.
Shape wires so that the service lid will fit securely.
1 2 3
123
L1L
2
When wire length exceeds 33ft (10m), use AWG14 wires.
Outdoor unit
Indoor unit
Conduit mounting plate
Conduit
Lock nut
Back
Use AWG16 or AWG14 wire for the inter-unit wiring.
Disengage the tab.
Figure 1: Removing the cover from
the indoor unit electrical component box
Disengage the tab.
Cover of the indoor unit electrical component box
Room Air Conditioners J-Series 31
Page 33
Installation Manual EDUS041011
9
5-5. Prepare the accessory (separate product) [Figure 2].
1) Remove the cover from the accessory (separate product).
2) Insert the connection cord into connector “S21” (white) in the accessory (separate product).
3) Route each of the connection cords through the cut-outs in the accessor y, then reinstall the accessory cover in its original position.
4) Insert the accessory (separate product) connector into connector “S403” in the indoor unit electrical component box. Then route the connection cord through the cut-out in the indoor unit electrical component box.
5-6. Install the cover of the electrical component box in its original position [Figure 3].
5-7. Install the accessory (separate product) [Figure 3].
1) Install the accessory (separate product) into the indoor unit electrical component box.
2) Route the connection cord as shown in [Figure 3].
* 5-8. Install the indoor unit electrical component box in its original position.
1) Install the louver.
2) Install the electrical component box (1 screw).
3) Install the thermistor in its original position on the heat exchanger.
4) Install the connector (S200) in its original position.
5) Connect the communication wiring in its original position.
5-9. Install the front grille in its original position (2 screws).
5-10. Install the service lid (1 screw).
Figure 2: Preparing the accessory
Remove the accessory cover.
Accessory
Insert “S403”.
Disengage the tab.
Route each of the
“S21”
connection cords.
Figure 3: Installing the accessory
Install the accessory cover in its original position.
Accessory cover
Accessory
Accessory cover
Install the accessory.
Route the connection cords through the cut-outs.
Cut-outs for the connection cords
Cut-out for the “S403” connection
Cut-out for the connection cord
32 Room Air Conditioners J-Series
Page 34
EDUS041011 Installation Manual
10
Indoor Unit Installation
6.
Drain piping
1) Connect the drain hose, as described right.
2) Remove the air filters and pour some water into the drain pan to check the water flows smoothly.
3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.
[Figure of hose front end]
4) When extending the drain hose, use a commercially available extension hose with an inner diameter of 5/8 inch (16mm). Be sure to thermally insulate the indoor section of the extension hose.
5) When connecting a rigid polyvinyl chloride pipe (nominal diameter 1/2 inch (13mm)) directly to the drain hose attached to the indoor unit as with embedded piping work, use any commercially available drain socket (nominal diameter 1/2 inch (13mm)) as a joint.
Refrigerant Piping Work
1.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
The drain hose should be inclined downward.
No trap is permitted.
Do not put the end of the hose in water.
φ11/16” (φ18mm)φ5/8” (φ16mm)
φ5/8”
(φ16mm)
The drain hose provided to indoor unit.
Indoor unit drain hose
φ5/8”
(φ16mm)
Extension drain hose
Heat insulation tube (field supply)
Commercially available drain socket (nominal diameter 1/2 inch (13mm))
Commercially available rigid polyvinyl chloride pipe (nominal diameter 1/2 inch (13mm))
The drain hose provided to indoor unit.
φ18
Set exactly at the position shown below.
A
Flaring
Die
A
0-0.020 inch (0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch (1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch (1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
(Cut exactly at
right angles.) Remove burrs.
Check
Flare’s inner surface must be flaw-free.
The pipe end must be evenly flared in a perfect circle.
Make sure that the flare nut is fitted.
Room Air Conditioners J-Series 33
Page 35
Installation Manual EDUS041011
11
2.
Refrigerant piping
CAUTION
• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
2-1. Caution on piping handling
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.
2-2.
Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to
0.045kcal/mh°C))
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Gas side Liquid side
Gas pipe thermal
insulation
Liquid pipe thermal
insulation
O.D. 3/8 inch (9.5mm) O.D. 1/4 inch (6.4mm)
I.D. 0.427-0.590 inch
(12-15mm)
I.D. 0.315-0.393 inch
(8-10mm)
Minimum bend radius Thickness 0.393 inch (10mm) Min.
1-3/16 inch (30mm) or more
Thickness 0.031 inch (0.8mm) (C1220T-O)
Do not apply refrigeration oil to the outer surface.
Flare nut
Apply refrigeration oil to the inner surface of the flare.
Do not apply refrigeration oil to the flare nut avoid tightening with over torque.
[Apply oil]
Tor que wrench
Piping union
Flare nut
Spanner
[Tighten]
Flare nut tightening torque
Gas side Liquid side
3/8 inch (9.5mm) 1/4 inch (6.4mm)
24.1-29.4ft • lbf
(32.7-39.9N • m)
10.4-12.7ft • lbf
(14.2-17.2N • m)
Wall
If no flare cap is available, cover the flare mouth with tape to keep dirt or water out.
Be sure to place a cap.
Rain
Gas pipe
Liquid pipe
Gas pipe insulation
Liquid pipe insulation
Finishing tape
Drain hose
Inter-unit wiring
Be sure to use insulation that is designed for use with HVAC Systems.
34 Room Air Conditioners J-Series
Page 36
EDUS041011 Installation Manual
12
Trial Operation and Testing
1.
Trial operation and testing
1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.
For Heat pump
In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temperature.
1) Trial operation may be disabled in either mode depending on the room temperature. Use the remote controller for trial operation as described below.
2) After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to 28°C) in cooling mode, 68°F to 75°F (20°C to 24°C) in heating mode).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
For Cooling only
• Select the lowest programmable temperature.
1) Trial operation in cooling mode may be disabled depending on the room temperature. Use the remote controller for trial operation as described below.
2) After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to 28°C)).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts,
such as fin movement, are working properly.
• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some
time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation
mode when the circuit breaker is opened again.
2.
Test items
Test items
Symptom
(diagnostic display on RC)
Check
Indoor and outdoor units are installed properly on solid bases. Fall, vibration, noise
No refrigerant gas leaks.
Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
System is properly grounded. Electrical leakage
The specified wires are used for inter-unit wiring connections. Inoperative or burn damage
Indoor or outdoor unit’s air inlet or air outlet has clear path of air. Stop valves are opened.
Incomplete cooling/heating function
Indoor unit properly receives remote control commands. Inoperative
1) Press “ON/OFF” button to turn on the system.
2) Press “TEMP” button (2 locations) and “MODE” button at the same time.
3) Press “MODE” button twice. (“ ” will appear on the display to indicate that trial operation mode is selected.)
4) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press “ON/OFF” button.
Trial operation from remote controller
3P253189-1
Room Air Conditioners J-Series 35
Page 37
Installation Manual EDUS041011
1
Safety Precautions
• Read these Safety Precautions carefully to ensure correct installation.
• This manual classifies the precautions into DANGER, WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety.
DANGER............... Indicates an imminently hazardous situation which, if not avoided, will result in death or serious
injury.
WARNING ............. Failure to follow any of WARNING is likely to result in such grave consequences as death or serious
injury.
CAUTION .............. Failure to follow any of CAUTION may in some cases result in grave consequences.
• The following safety symbols are used throughout this manual:
• After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual.
Be sure to observe this instruction. Be sure to establish a ground connection. Never attempt.
DANGER
• Refrigerant gas is heavier than air and replaces oxygen. A massive leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• If the refrigerant gas leaks during installation, ventilate the area immediately.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• After completing the installation work, check that the refrigerant gas does not leak.
Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face the danger of death by suffocation.
• Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death.
• Do not ground units to telephone wires or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
WARNING
• Installation should be left to the authorized dealer or another trained professional.
Improper installation may cause water leakage, electrical shock, fire, or equipment damage.
• Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire or equipment damage.
• Be sure to use the supplied or exact specified installation parts.
Use of other parts may cause the unit to come to fall, water leakage, electrical shock, fire or equipment damage.
• Install the air conditioner on a solid base that is level and can support the weight of the unit.
An inadequate base or incomplete installation may cause injury or equipment damage in the event the unit falls off the base or comes loose.
• Electrical work should be carried out in accordance with the installation manual and the national, state and local electrical wiring codes.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire or equipment damage.
• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. Follow all appropriate electrical codes.
• For wiring, use a wire or cable long enough to cover the entire distance with no splices if possible. Do not use an extension cord. Do not put other loads on the power supply. Use an only a separate dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock, fire or equipment damage.)
• Use the specified types of wires for electrical connections between the indoor and outdoor units. Follow all state and local electrical codes.
Firmly clamp the inter-unit wiring so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating, fire or equipment damage.
11.2 Outdoor Units
36 Room Air Conditioners J-Series
Page 38
EDUS041011 Installation Manual
2
Safety Precautions
WARNING
• After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical covers, panels or terminals.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, fire or equipment damage.
• When installing or relocating the system, be sure to keep the refrigerant circuit free from all substances other than the specified refrigerant (R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which may result in rupture, resulting in injury.)
• During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing abnormally high pressure which could lead to equipment damage and personal injur y.
• Be sure to install a ground fault circuit interrupter breaker.
Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.
CAUTION
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual.
Inadequate piping may cause water damage.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
Room Air Conditioners J-Series 37
Page 39
Installation Manual EDUS041011
3
Accessories
Accessories supplied with the outdoor unit:
Precautions for Selecting the Location
1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit wiring at least 10 feet (3m) away from television and radio sets. This is to prevent interference to images and sounds. (Noises may be heard even if they are more than 10 feet (3m) away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.
NOTE
Cannot be installed hanging from ceiling or stacked.
CAUTION
When operating the air conditioner in a low outdoor ambient temperature, be sure to follow the instructions described below.
• To prevent exposure to wind, install the outdoor unit with its suction side facing the wall.
• Never install the outdoor unit at a site where the suction side may be exposed directly to wind.
• To prevent exposure to wind, it is recommended to install a baffle plate on the air discharge side of the outdoor unit.
• In heavy snowfall areas, select an installation site where the snow will not affect the unit.
(A) Installation manual 1
(B) Drain plug (Heat pump models)
There is on the bottom packing case.
1
Construct a large canopy. Construct a pedestal.
Install the unit high enough off the ground to prevent burying in snow.
38 Room Air Conditioners J-Series
Page 40
EDUS041011 Installation Manual
4
Outdoor Unit
Installation Drawings
CAUTION
Set the piping length from
4.92ft (1.5m) to 49.2ft (15m).
Wrap the insulation pipe with the finishing tape from bottom to top.
In sites with poor drainage, use block bases for outdoor unit. Adjust foot height until the unit is leveled. Otherwise, water leakage or pooling of water may occur.
Where there is a danger of the unit falling, use foot bolts, or wires.
Allow space for piping and electrical servicing.
9-27/32 (250) from wall
unit: inch (mm)
O.D. 3/8 inch (9.5mm)
Gas pipe
Liquid pipe
O.D. 1/4 inch (6.4mm)
0.22oz/ft
Max. allowable length
39.3ft (12m)
49.2ft (15m)
Max. allowable height
Additional refrigerant required for refrigerant pipe exceeding 33ft (10m) in length.
*
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced perfomance.
*
The suggested shortest pipe length is 4.92ft (1.5m), in order to avoid noise from the outdoor unit and vibration. (Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used.)
4.92ft (1.5m)
Min. allowable length
18-1/2 (470)
(Foot bolt-hole centers)
(From unit’s side)
3-25/32 (96)
(Foot bolt-hole
centers)
11-13/16 (300)
How to remove the stop valve cover
Remove the screw on the stop valve cover. Slide the lid downward to remove it.
How to attach the stop valve cover
Insert the upper part of the stop valve cover into the outdoor unit to install. Tighten the screws.
Stop valve cover
*
Room Air Conditioners J-Series 39
Page 41
Installation Manual EDUS041011
5
Installation Guidelines
• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4 inch (1200mm) or less.
Precautions on Installation
• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their length are 3/4 inch (20mm) from the foundation surface.
Outdoor Unit Installation
1.
Installing outdoor unit
1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings”.
2) If drain work is necessary, follow the procedures below.
2.
Drain work (Heat pump models)
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 1-1/4 inch (30mm) in height under the outdoor unit’s feet.
3) In cold areas, do not use a drain hose with the outdoor unit. (Otherwise, drain water may freeze, impairing heating performance.)
More than 1-15/16 (50) More than 1-15/16 (50)
More than 5-7/8 (150) More than 3-15/16 (100)
More than 1-15/16 (50) More than 3-15/16 (100)
Side view
47-1/4 (1200) or less
Wall facing one side Walls facing two sides
Top view
Top view
unit: inch (mm)
More than 5-7/8 (150)
More than 11-13/16 (300)
More than 1-15/16 (50)
Walls facing three sides
3/4”
(20mm)
Drain port
Bottom frame
Drain plug
Hose (available commercially, inner dia. 5/8 inch (16mm))
40 Room Air Conditioners J-Series
Page 42
EDUS041011 Installation Manual
6
Outdoor Unit Installation
3.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
4.
Refrigerant piping
CAUTION
• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
A
Check
Flare’s inner surface must be flaw-free.
The pipe end must be evenly flared in a perfect circle.
Make sure that the flare nut is fitted.
(Cut exactly at
right angles.) Remove burrs.
Flaring
Set exactly at the position shown below.
A
0-0.020 inch
(0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch (1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch (1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
Die
Flare nut tightening torque Gas side Liquid side 3/8 inch (9.5mm) 1/4 inch (6.4mm)
24.1-29.4ft lbf 10.4-12.7ft lbf
(32.7-39.9N m) (14.2-17.2N m)
Valve cap tightening torque Gas side Liquid side 3/8 inch (9.5mm) 1/4 inch (6.4mm)
15.9-20.2ft lbf 15.9-20.2ft lbf
(21.6-27.4N m) (21.6-27.4N m)
Service port cap 7.9-10.8ft lbf tightening torque
(10.8-14.7N m)
Torque wrench
Piping union
Flare nut
Spanner
[Tighten]
Do not apply refrigeration oil to the outer surface.
Flare nut
Apply refrigeration oil to the inner surface of the flare.
Do not apply refrigeration oil to the flare nut avoid tightening with over torque.
[Apply oil]
••
••
••
Room Air Conditioners J-Series 41
Page 43
Installation Manual EDUS041011
7
5.
Purging air and checking gas leakage
• When piping work is completed, it is necessary to purge the air and check for gas leakage.
WARNING
• Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
• If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge additional refrigerant.
• Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque.
*1. Pipe length vs. vacuum pump run time.
*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. Check
all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).
1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.
2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi). (High-pressure valve subsequently requires no operation.)
3) Do vacuum pumping and make sure that the compound pressure gauge reads –29.9inHg (–0.1MPa).*1.
4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump. (Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.
5) Remove caps from liquid stop valve and gas stop valve.
6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. Close it after 5 seconds, and check for gas leakage. Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods. After the check is complete, wipe all soapy water off.
7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves. (Do not attempt to turn valve rod beyond its stop.)
8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.
Pipe length Up to 49.2ft (15m)
Run time Not less than 10 min.
Compound pressure gauge
Pressure meter
High­pressure valve
Low-pressure valve
Vacuum pump
Service port
Liquid stop valve
Valve caps
Gas stop valve
Charging hoses
Gauge manifold
42 Room Air Conditioners J-Series
Page 44
EDUS041011 Installation Manual
8
Outdoor Unit Installation
6.
Refilling the refrigerant
Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cau se the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon attached” displayed on it.)
•Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
7.
Refrigerant piping work
7-1 Cautions on pipe handling
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.
7-2 Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C))
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Gas side Liquid side
Gas pipe
thermal insulation
Liquid pipe
thermal insulation
O.D. 3/8 inch
(9.5mm)
O.D. 1/4 inch
(6.4mm)
I.D. 0.472-0.591 inch
(12-15mm)
I.D. 0.315-0.393 inch
(8-10mm)
Minimum bend radius Thickness 0.393 inch (10mm) Min.
1-3/16 inch (30mm) or more
Thickness 0.031 inch (0.8mm) (C1220T-O)
Filling a cylinder with an attached siphon
Stand the cylinder upright when filling.
There is a siphon pipe inside, so the cylinder need not be upside-down to fill with liquid.
Filling other cylinders
Turn the cylinder upside-down
when filling.
Wall
If no flare cap is available, cover the flare mouth with tape to keep dirt or water out.
Be sure to place a cap.
Rain
Gas pipe
Liquid pipe
Gas pipe insulation
Liquid pipe insulation
Finishing tape
Drain hose
Inter-unit wiring
Be sure to use insulation that is designed for use with HVAC Systems.
Room Air Conditioners J-Series 43
Page 45
Installation Manual EDUS041011
9
Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
How to forced cooling operation mode
Using the indoor unit ON/OFF button
Press the indoor unit ON/OFF button for at least 5 seconds. (Operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes. To force a trial operation to stop, press the indoor unit ON/OFF button.
Using the main unit’s remote controller
1) Press the “ON/OFF” button. (Operation will start.)
2) Press the “TEMP” button and the “MODE” button at the same time.
3) Press the “MODE” button twice. (
“”
will be displayed and the unit will enter trial operation.)
4) Press the “MODE” button to return the operation mode to cooling.
• Trial operation will stop automatically after around 30 minutes. To force a trial operation to stop, press the “ON/OFF” button.
CAUTION
• When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
• After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced operation.
Gas stop valve
Valve cap
Hexagonal wrench
Close
Liquid stop valve
44 Room Air Conditioners J-Series
Page 46
EDUS041011 Installation Manual
10
Wiring
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
• Be sure to install a ground fault circuit interrupter breaker. (One that can handle higher harmonics.) (This unit uses an inverter, which means that it must be used a ground fault circuit interrupter breaker capable handling harmonics in order to prevent malfunctioning of the ground fault circuit interrupter breaker itself.)
• Use an all-pole disconnection type breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring connection, take care not to pull at the conduit.
• Do not turn on the safety breaker until all work is completed.
1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the connection wires between the indoor and outdoor units so that the terminal numbers match. Tighten the terminal screws securely. We recommend a flathead screwdriver be used to tighten the screws. The screws are packed with the terminal board.
<Work before wiring>
A protection plate is fixed for protection from the high-voltage section. Before staring wiring work, dismount the protection plate by removing the 2 screws and dismount the conduit mounting plate cover by removing the 1 screw.
<Method of mounting conduit>
1) Pass wires through the conduit and secure them with a lock nut.
2) After completing the work, reattach the conduit mounting plate cover and the protection plate to its original position.
Observe the notes mentioned following when wiring to the power supply terminal board. Precautions to be taken for power supply wiring. Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to unavoidable reasons, be sure to observe the following instruction. Place the round crimp-style terminals on the wires up to the covered part and secure in place.
1 2 3
123
Safety breaker 15A
Ground fault circuit interrupter breaker
Ground
If the length of a connection wire is 33ft (10m) or more, use AWG14 wire.
Firmly fix the wires with the terminal screws.
Outdoor unit
Indoor unit
Power supply 60Hz 208-230V
Use AWG 14 wires.
L1L
2
1 2 3
1 2 3
Power supply terminal block
Use the specified wire type and connect it securely. Shape wires so that the service lid and stop valve cover fit securely.
Conduit mounting plate
Conduit
Lock nut
Conduit mounting plate cover
Protection plate
Screw
Screws
Stranded wire
Round crimp-style terminal
Room Air Conditioners J-Series 45
Page 47
Installation Manual EDUS041011
11
CAUTION
• When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. Problems with the work may cause heat and fires.
3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
Strip wire end to this point.
Excessive strip length may cause electrical shock or leakage.
Good Wrong
Stripping wire at terminal block
46 Room Air Conditioners J-Series
Page 48
EDUS041011 Installation Manual
12
Trial Operation and Testing
1.
Trial operation and testing
1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.
For heat pump
• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable
temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (78˚F to 82˚F (26˚C to 28˚C) in coo ling mode, 68˚F to 75˚F (2 0˚C to 24˚C) in heating mode).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
For cooling only
• Select the lowest programmable temperature.
1) Trial operation in cooling mode may be disabled depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (78˚F to 82˚F (26˚C to 28˚C)).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts,
such as fin movement, are working properly.
• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some
time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation
mode when the circuit breaker is opened again.
2.
Test items
Test items
Symptom
(diagnostic display on RC)
Check
Indoor and outdoor units are installed properly on solid bases. Fall, vibration, noise
No refrigerant gas leaks.
Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
System is properly grounded. Electrical leakage
The specified wires are used for inter-unit wiring connections. Inoperative or burn damage
Indoor or outdoor unit’s air inlet or air outlet has clear path of air. Stop valves are opened.
Incomplete cooling/heating function
Indoor unit properly receives remote control commands. Inoperative
Room Air Conditioners J-Series 47
3P253189-4
Page 49
Safety Considerations EDUS041011
12. Safety Considerations
Read these SAFETY CONSIDERATIONS for Operations carefully before operating air conditioning equipment. Make sure that the unit operates properly during the startup operation. Instruct the customer on how to operate and maintain the unit.
Inform customers that they should store this Operation Manual with the Installation Manual for future reference. Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols:
DANGER .............. Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING ............ Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION ............. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.
NOTE ................... Indicates situations that may result in equipment or property-damage accidents only.
• Do not install the unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death.
• Any abnormalities in the operation of the air conditioner such as smoke or fire could result in severe injury or death. Turn off the power and contact your dealer immediately.
• Refrigerant gas may produce toxic gas if it comes into contact with fire, such as from a fan, heater, stove, or cooking device. Exposure to this gas could cause severe injury or death.
• For refrigerant leakage, consult your dealer. Refrigerant gas is heavier than air and replaces oxygen. A massive leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• If equipment utilizing a burner is used in the same room as the air conditioner, there is the danger of oxygen deficiency which could lead to an asphyxiation hazard resulting in serious injury or death. Be sure to ventilate the room sufficiently to avoid this hazard.
• Safely dispose of the packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
• Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face the danger of death by suffocation.
• Contact your dealer for repair and maintenance. Improper repair and maintenance may result in water leakage, electric shock, and fire. Only use accessories made by Daikin that are specifically designed for use with the equipment and have them installed by a professional.
• Contact your dealer to move and reinstall the air conditioner. Incomplete installation may result in water leakage, electric shock, and fire.
• Never let the indoor unit or the remote controller get wet. Water can cause an electric shock or a fire.
• Never use flammable spray such as hair spray, lacquer, or paint near the unit. Flammable spray may cause a fire.
• When a fuse blows out, never replace it with one of incorrect ampere ratings or different wires. Always replace any blown fuse with a fuse of the same specification.
• Never remove the fan guard of the unit. A fan rotating at high speed without the fan guard is very dangerous.
• Never inspect or service the unit by yourself. Contact a qualified service person to perform this work.
• Turn off all electrical power before doing any maintenance to avoid the risk of serious electric shock; never sprinkle or spill water or liquids on the unit.
• Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock.
• Do not allow children to play on or around the unit to prevent injury.
48 Room Air Conditioners J-Series
Page 50
EDUS041011 Safety Considerations
• The heat exchanger fins are sharp enough to cut. To avoid injury wear gloves or cover the fins while working around them.
• Do not put a finger or other objects into the air inlet or air outlet. The fan is rotating at high speed and will cause injury.
• Check the unit foundation for damage on a continuous basis, especially if it has been in use for a long time. If left in a damaged condition the unit may fall and cause injury.
• Placing a flower vase or other containers with water or other liquids on the unit could cause a shock or fire if a spill occurs.
• Do not touch the air outlet or horizontal blades while the swing flap is in operation because fingers could get caught and injured.
• Never touch the internal parts of the controller. Do not remove the front panel because some parts inside are dangerous to touch. To check and adjust internal parts, contact your dealer.
• Do not use the air conditioner for any other purposes other than comfort cooling or heating. Do not use the unit for cooling precision instruments, food, plants, animals or works of art.
• Do not place items under the indoor unit as they may be damaged by condensates that may form if the humidity is above 80% or if the drain outlet gets blocked.
• Before cleaning, stop the operation of the unit by turning the power off or by pulling the supply cord out from its receptacle. Otherwise, an electric shock and injury may result.
• Do not wash the air conditioner with excessive water. An electric shock or fire may result.
• Avoid placing the controller in a spot splashed with water. Water entering the controller may cause an electric shock or damage the internal electronic parts.
• Do not operate the air conditioner when using a room-fumigation type of insecticide. Failure to observe this could cause the chemicals to be deposited in the unit and can endanger the health of those who are hypersensitive to chemicals.
• Do not turn off the power immediately after stopping operation. Always wait for at least five minutes before turning off the power. Otherwise, water leakage may occur.
• The appliance is not intended for use by young children or infirm persons without supervision.
• The remote controller should be kept away from children so they cannot play with it.
• Consult with the installation contractor for cleaning.
• Incorrect cleaning of the inside of the air conditioner could make the plastics parts break and cause water leakage or electric shock.
• Do not touch the air inlet or aluminum fin of the air conditioner as they can cut and cause injury.
• Do not place objects in direct proximity of the outside unit. Do not let leaves and other debris accumulate around the unit. Leaves are a hotbed for small animals which can enter the unit. Once inside the unit, animals can cause the unit to malfunction, and cause smoke or fire when they make contact with electrical parts.
• Never press the button of the remote controller with a hard, pointed object. The remote controller may be damaged.
• Never pull or twist the electric wire of the remote controller. It may cause the unit to malfunction.
• Do not place appliances that produce open flames in places that are exposed to the air flow of the unit or under the indoor unit. It may cause incomplete combustion or deformation of the unit due to the heat.
• Do not expose the controller to direct sunlight. The LCD display can become discolored and may fail to display the data.
Room Air Conditioners J-Series 49
Page 51
Safety Considerations EDUS041011
• Do not wipe the controller operation panel with benzene, thinner, chemical dust cloth, etc. The panel may get discolored or the coating can peel off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. Then wipe it with another dry cloth.
• Dismantling of the unit, disposal of the refrigerant, oil, and additional parts, should be done in accordance with the relevant local, state, and national regulations.
• Operate the air conditioner in a sufficiently ventilated area and not surrounded by obstacles. Do not use the air conditioner in the following places.
a. Places with a mist of mineral oil, such as cutting oil. b. Locations such as coastal areas where there is a lot of salt in the air. c. Locations such as hot springs where there is a lot of sulfur in the air. d. Locations such as factories where the power voltage varies a lot. e. In cars, boats, and other vehicles. f. Locations such as kitchens where oil may splatter or where there is steam in the air. g. Locations where equipment produces electromagnetic waves. h. Places with an acid or alkaline mist. i. Places where fallen leaves can accumulate or where weeds can grow.
• Take snow protection measures. Contact your dealer for the details of snow protection measures, such as the use of a snow protection hood.
• Do not attempt to do electrical work or grounding work unless you are licensed to do so. Consult with your dealer for electrical work and grounding work.
• Pay Attention to Operating Sound. Be sure to use the following places: a. Places that can sufficiently withstand the weight of the air conditioner yet can suppress the operating sound and
vibration of the air conditioner.
b. Places where warm air from the air outlet of the outside unit or the operating sound of the outside unit does not
annoy neighbors.
• Make sure that there are no obstacles close to the outside unit. Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit.
• Consult your dealer if the air conditioner in operation generates unusual noise.
• Make sure that the drainpipe is installed properly to drain water. If no water is discharged from the drainpipe while the air conditioner is in the cooling mode, the drainpipe may be clogged with dust or dirt and water leakage from the indoor unit may occur. Stop operating the air conditioner and contact your dealer.
50 Room Air Conditioners J-Series
Page 52
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 51
Page 53
Safety Considerations EDUS041011
52 Room Air Conditioners J-Series
Page 54
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 53
Page 55
Safety Considerations EDUS041011
54 Room Air Conditioners J-Series
Page 56
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 55
Page 57
Safety Considerations EDUS041011
56 Room Air Conditioners J-Series
Page 58
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 57
Page 59
Safety Considerations EDUS041011
58 Room Air Conditioners J-Series
Page 60
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 59
Page 61
Safety Considerations EDUS041011
60 Room Air Conditioners J-Series
Page 62
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 61
Page 63
Safety Considerations EDUS041011
62 Room Air Conditioners J-Series
Page 64
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 63
Page 65
Safety Considerations EDUS041011
64 Room Air Conditioners J-Series
Page 66
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 65
Page 67
Safety Considerations EDUS041011
66 Room Air Conditioners J-Series
Page 68
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 67
Page 69
Safety Considerations EDUS041011
68 Room Air Conditioners J-Series
Page 70
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 69
Page 71
Safety Considerations EDUS041011
70 Room Air Conditioners J-Series
Page 72
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 71
Page 73
Safety Considerations EDUS041011
72 Room Air Conditioners J-Series
Page 74
EDUS041011 Safety Considerations
Room Air Conditioners J-Series 73
Page 75
Safety Considerations EDUS041011
3P253185-1
74 Room Air Conditioners J-Series
Page 76
EDUS041011 Optional Accessories
13.Optional Accessories
13.1 Option List
13.1.1 Indoor Units
Option Name FTK(X)S09/12JEVJU
1 Wired Remote Controller
2 Interface Adaptor for Wired Remote Controller KRP980B1
3 Wired Remote Controller Cord
Titanium Apatite Photocatalytic Air-Purifying Filter
4
(without Frame) 2
5 Remote Controller Loss Prevention with Chain KKF910A4
1 An interface adaptor (KRP980B1) and a cord (BRCW901A03 or BRCW901A08) are necessary.2 Standard accessory
13.1.2 Outdoor Units
1 BRC944B2
Length 3 m (Shielded Wire) BRCW901A03
Length 8 m (Shielded Wire) BRCW901A08
KAF970A46
Option Name RKS09/12JEVJU RXS09/12JEVJU
1 Drain Plug KKP937A4
2 Air Direction Adjustment Grille KPW937A4
Room Air Conditioners J-Series 75
Page 77
Optional Accessories EDUS041011
Switch box
(Field supplied parts)
Machine screws (M4 x 16)
For the field supplied switch box, use optional accessories KJB1111A or KJB2121A.
KJB2121A
CAUTION
1. No switch box or staple is supplied. Prepare them locally.
2. No remote controller cord is supplied. Prepare the optional remote controller cord 4 wire.
3. Be sure to turn off the power to any apparatus connected prior to mounting.
4. Prior to mounting equipment, touch something metallic such as a doorknob to remove static electricity from your body. Never touch the remote controller board or the adapter board.
5. Keep the wiring away from any other power source lines to avoid electric noise (external noise).
6. Select a flat surface, wherever possible, to mount the remote controller. To prevent deformation of the cases, do not overtighten the mounting screws.
Insert a bladed screwdriver into the concave ( ) in the remote controller lower case to remove the upper case assembly (two locations).
(1) Exposed mounting
Secure the remote controller lower case with the two supplied wood screws.
(2) Embedded mounting
Secure the remote controller lower case with the two supplied machine screws.
The remote controller board is located on the upper case. Take care not to scratch the board with the screwdriver.
1. Securing the remote controller lower case
Upper case
Lower case
Screwdriver
To remove, insert and twist the screwdriver slightly.
Wood screws (φ3.5mm x 16mm)
KJB1111A
13.2 <BRC944B2> Wired Remote Controller
13.2.1 Installation Manual
76 Room Air Conditioners J-Series
Page 78
EDUS041011 Optional Accessories
Remove the upper case of the remote control adapter and secure the lower case assembly.
During mounting of the remote controller cord, be careful not to pinch or otherwise damage the wires. (Remote controller cord 4 wire)
2. Securing the remote control adapter
3. Wiring
4.
Placing the upper case assembly of the remote controller and the upper case of the remote controller adapter back into their original positions
5. Temperature indication change
Wood screws (φ3.5mm x 16mm)
(Mounting with supplied wood screws)
Remote control adapter (attached)
(Mounting with supplied double-face adhesive tape)
Double-face adhesive tape
Attached five-wire cord
Remote controller cord (Note 1)
Connector
Connector
Connector
Tie-band (to secure the cord)
Tie-band (to secure the cord)
Tie-band (to secure the cord)
Upper case
assembly
Lower case
(Cord drawn out on the back)
Catch the lower hook first.
(Cord drawn out on the top)
To remote control adapter
Remote controller
board
Remote controller
board
Note 1) Ground the both ends of the shielded wire.
Using wire cutters, make a notch for wiring and then seal the notch to ensure it is waterproof.
To indoor unit S21-HA connector
Remote controller cord 4 wire
Item No.
BRCW901A03
BRCW901A08
Length
Approx. 3m (10ft)
Approx. 8m (26ft)
To change from Celsius temperature indication to Fahrenheit one
Press and hold down at the
same time for 5 seconds while the Celsius temperature is indicated.
See Operation Manual
3P202923-2B
Room Air Conditioners J-Series 77
Page 79
Optional Accessories EDUS041011
4
Controller Commands and their Corresponding Functions
Run indicator lamp (green)
ON/OFF button
Press to start the system. Press again to stop the system.
Mode select button
Swing button
Timer setting button
Sets the current time and timer.
Temperature adjustment button
Adjusts the temperature setting.
Airflow rate button
Adjusts the airflow rate.
Time setting button for the timer
Display
Timer select button
Displays the operating conditions.
Clock setting button
( page 9)
( page 7)
( page 5)
Selects an operation mode.
Displays the operating conditions.
Selects one of the following: ONE TIME timer ON DAILY timer ON TIMER OFF
CAUTION
•This remote controller cannot be used together with a standard wireless remote controller. Otherwise, what appears on this remote controller's display may fail to correspond to actual operating conditions.
13.2.2 Operation Manual
78 Room Air Conditioners J-Series
Page 80
EDUS041011 Optional Accessories
5
Preparation before Operation
Checking the power
If nothing appears on the remote controller's display, turn on the circuit breaker.
Setting the current time
1
Press
.
The current time starts blinking.
lights up.
2
Press and set the current time.
Hold the button down to rapidly advance the time.
3
Press
.
(This completes the current time setting)
The clock's accuracy is ±30 seconds per month.
blinks.
2
1
·
3
Avoid overcooling or overheating.
Moderate room temperature setting contributes to power saving.
Hang a blind or a curtain on the window.
This will enhance the cooling/heating effect by intercepting direct sunlight and drafts.
A clogged air filter reduces
the cooling/heating effect and wastes energy. Clean the air filter monthly (every two weeks as required) or so.
Please take note of the following points
Electric power is consumed even when the air
conditioner is not in operation.
When the unit is not used for a long period of
time such as during off-season, turn off the breaker.
Operating conditions
If the operation is continued under any
conditions other than the following, the safety device may work to stop the operation. Also, dew may form on the indoor unit and drip from it. (Cooling/DRY)
Operation limit differ according to the model.
Notes
To use the unit efficiently
Recommended temperature setting
For cooling ·············· 26~28˚C (79˚F~82˚F) For heating ············· 20~22˚C (68˚F~72˚F)
Cooling
DRY
Heating
Outdoor temp.
Room temp. Indoor humidity
Outdoor temp.
Room temp. Indoor humidity
Outdoor temp.
Room temp.
-10 to 46
˚C (14˚F to 115˚F)
18 to 32
˚C (64˚F to 90˚F)
Less than 80%
-10 to 46
˚C (14˚F to 115˚F)
18 to 32
˚C (64˚F to 90˚F)
Less than 80%
-15 to 20
˚C (5˚F to 68˚F)
Less than 27
˚C
Room Air Conditioners J-Series 79
Page 81
Optional Accessories EDUS041011
6
1 Press and hold down at the
same time for 5 seconds while the Celsius temperature is indicated.
Preparation before Operation
2 Press and hold down at the
same time for 5 seconds while the Fahrenheit temperature is indicated.
Setting Temperature Indication change
Temperature indication can be changed between Celsius and Fahrenheit before use.
1·2
Notes
Temperature indication change between Celsius and Fahrenheit on the remote controller
Change the temperature indication in the modes other than the DRY mode.
In the DRY mode, temperature indication setting cannot be changed because the temperature is not indicated.
When the Fahrenheit temperature indication is changed to Celsius one, the temperature value
(0.5˚C) will be rounded up. Thus, the preset temperature may be changed.
Example:
A preset temperature of 65˚F (equivalent to 18.5˚C) will be changed to 19˚C (66˚F) b y changing the temperature indication. In this case, if you change the Celsius temperature indication again to the Fahrenheit one, the preset temperature is shown not as 65˚F but as 66˚F (equivalent to 19˚C). If the preset temperature is 66˚F (equivalent to 19˚C) and is changed to the Celsius temperature indication, the indication becomes 19˚C (66˚F). In this case, no change by the temperature indication change is observed.
When the temperature indication change is set, the preset temperature is transmitted to the
indoor unit so that the reception sound will be heard from the indoor unit.
To change from Celsius temperature indication to Fahrenheit one
To change from Fahrenheit temperature indication to Celsius one
80 Room Air Conditioners J-Series
Page 82
EDUS041011 Optional Accessories
7
1
Press
to select your desired
operation mode.
Each time the button is pressed, the mode
changes as follows.
The system does not have the FAN mode.
Automatic · DRY · Cooling · Heating Operation
2
Press .
The run indicator lamp lights up.
Select your desired operation mode. Once preset, the system can get restarted in the same operation mode.
1
2
Run indicator lamp (green)
(Automatic)
(DRY)
(Heating)
(Cooling)
(DRY) (Cooling)
Cooling only model
Heat pump model
To stop the operation:
Press again.
The run indicator lamp goes out.
In Automatic, the temperature setting and
operation mode (DRY, Cooling or Heating) are automatically selected according to the room temperature and outdoor temperature at the time of starting operation.
DRY operation
In this mode, humidity is removed from the air.
Note
While running in the DRY mode, you may
feel cool or warm air from the air outlet. In this case, readjust the airflow direction with the vertical airflow direction louvers. (except Duct Connected type)
Automatic operation
Room Air Conditioners J-Series 81
Page 83
Optional Accessories EDUS041011
8
Heating operation
Since the heating operation is performed by
taking the heat from outdoor into the room, the heating capacity decreases as the outdoor temperature lowers. If the room is not heated sufficiently, it is recommended to use other heating appliance at the same time.
Since the air conditioner heats the whole room
by circulating hot air, it takes some time to heat the entire room completely.
If the outdoor unit gets frosted during heating
operation, the heating capacity is decreased. In this case, the unit starts defrosting operation.
No hot air comes out of the indoor unit during
defrosting operation.
To adjust the temperature and airflow rate:
To adjust the airflow direction:
( page 9)
Operation
mode
Setting to be adjusted
Automatic DRYCooling Heating
(Temperature)
(Airflow rate)
Temperature cannot be adjusted.
Airflow rate cannot be adjusted.
Temperature is adjustable.
Recommended temperature
Cooling : 26˚C-28˚C (79˚F~82˚F)
Five levels of airflow rate setting from " " to " " plus " " are available.
Heating : 20˚C-22˚C (68˚F~72˚F)
When the unit runs in the cooling or heating mode at a low airflow rate, the cooling or heating effect
may be insufficient.
82 Room Air Conditioners J-Series
Page 84
EDUS041011 Optional Accessories
9
Notes
In fixing the horizontal airflow direction, keep the horizontal airflow direction louvers tilted
downward in the heating mode, and keep them nearly horizontal level in the cooling or DRY mode. This will enhance the cooling and heating effect.
On the air conditioners with vertical and horizontal swing function, be sure to adjust the airflow
directions using the remote controller. Do not forcibly adjust louvers by hand or a malfunction may occur.
Adjusting Airflow Direction
1 Press
during operation
.
Each time the button is pressed, the airflow
direction louvers change their movement.
Adjust the airflow direction for maximum comfort.
To adjust the Airflow Direction
1
Wall Mounted Types (without horizontal swing function)
The horizontal airflow direction louvers move up and down.
The louvers stop just when the button is pressed.
Swing
Airflow direction louvers stop
Adjustment of horizontal airflow direction
The automatic moving range of the horizontal airflow direction louvers varies depending on the
operation mode.
Room Air Conditioners J-Series 83
Page 85
Optional Accessories EDUS041011
10
Wall Mounted Type (with horizontal swing function)
The horizontal airflow direction louvers move up and down.
The horizontal airflow direction louvers stop just when the button is pressed. Then the vertical ones start moving right and left.
The vertical airflow direction louvers stop just when the button is pressed.
Swing horizontally
Swing vertically
Airflow direction louvers stop
The vertical and horizontal louvers cannot move at the same time.
Note
The operating procedure and remote controller display are different depending on the
indoor unit being connected.
Read How to Adjust the Airflow Direction in the air conditioner’s Operation Manual.
Duct Connected Type (without swing function)
This function cannot be used.
84 Room Air Conditioners J-Series
Page 86
EDUS041011 Optional Accessories
11
Timer Operation
To select the ONE TIME timer
mode:
1
Press
to select the ONE TIME
timer mode.
Each time the button is pressed,
the modes change as follows.
The Timer Operation feature automatically turns off operation when you go to sleep and turns it back on when you wake up. Use the DAILY Timer mode on weekdays, and the ONE TIME timer mode on weekends.
To cancel the timer settings:
1 Press to clear the timer settings.
Precautions in setting the timer
Before starting the timer operation, make sure
the current time is correct. If not, set the clock correctly. (
page 5)
In making time settings,
is displayed to
make it easy to disable the timer too.
If one minute has passed before making any
timer setting, the previous timer settings are
reintroduced and the timer is on standby.
In this case, use the
(time setting) button
and make your desired timer settings.
ONE TIME timer
DAILY timer
TIMER OFF
ON time
OFF time
(Timer settings displayed)
1
2·4·6
3·5
The timer lamp lights up.
The ONE TIME or DAILY TIMER disappears from the display, and the timer lamp goes out too.
Notes
Even when the timer has been off, its
programmed settings are still in memory.
If the system has the timer control ON but
you start and stop it manually using the ON/OFF button before the designated ON time, the system will restart again at the programmed ON time.
Timer operation
When the ON timer is programmed, the
system starts one hour (maximum) earlier so that the temperature set by the remote controller is reached just in time.
When the ONE TIME timer is programmed,
the current time is no longer displayed.
Room Air Conditioners J-Series 85
Page 87
Optional Accessories EDUS041011
12
1
Press
to select the ONE TIME timer.
2 Press .
3 Press to make the ON timer setting.
Example of display with the ONE TIME timer programmed
ONE TIME timer
Once the timer has been activated and then deactivated, it is in the OFF mode. The ON or OFF timers can be programmed.
light up.
ONE TIME
blinks.
Each time the button is pressed,
the setting changes in a 10­minute increment or decrement. Hold the button down to advance quickly.
When the ON timer is not used, save the setting as
4 Press .
5
Press
to make the OFF timer setting.
6 Press .
(The ONE TIME timer is now programmed.)
Both of the ON and OFF time cannot be set as
blinks.
When the OFF timer is not used, save the setting as .
ONE TIME timer programmed. The set time is displayed.
ON timer activated and system starts. The ON timer setting no longer displays.
OFF timer activated, and system stops. The timer setting no longer displays.
Notes
In the following cases, reset the
clock (the time setting is kept in the
memory).
The circuit breaker has been
activated.
The power fails.
86 Room Air Conditioners J-Series
Page 88
EDUS041011 Optional Accessories
13
Timer Operation
To select the DAILY timer mode:
1
Press
to select the DAILY timer mode.
Each time the button is pressed, the modes
change as follows.
To cancel the timer settings:
1 Press to clear the timer settings.
Example of display with DAILY timer programmed
ONE TIME timer
DAILY timer
TIMER OFF
The timer lamp lights up.
1 2
1 2
ON time
24-hour timer display
OFF time
Timers
The settings of timers and can be seen at a glance.
Two pairs of ON and OFF time settings can be programmed.
(Timer settings displayed)
1
2·3
2
The ONE TIME or
DAILY TIMER , and the timer lamp are no longer displayed.
Timers and programmed.
Timer alone programmed.
1 1
2
Note
The system starts and stops
repeatedly until the DAILY timer is set off. Before you leave home for a long time, set the DAILY timer off.
Room Air Conditioners J-Series 87
Page 89
Optional Accessories EDUS041011
14
1
Press
to select the DAILY timer.
2
Make the ON and OFF time settings.
Take the steps from to .
Program example: 8:00
~ 10:00, and 18:00 ~ 23:00
DAILY timer
After programming, the system starts and stops each day at the preset times. Two pairs of time settings can be programmed.
(Example: 8:00
~ 10:00, and 18:00 ~ 23:00)
DAILY timer indication appears.
lights up.
3
Press
.
The DAILY timer is now programmed.
Note
If the following appears on the display, the timer must be reprogrammed.
The 24-hour timer display is blinking.
The 24-hour timer display is blinking.
This means that Timers and are programmed for the same time settings. New time settings must be made.
This means that the timer has not been programmed yet.
When the timer is not used, save the setting as
Press Press
to make the timer setting.
1
Procedure
Settings
ON time setting
OFF time setting
OFF time setting
2
ON time setting
2
1




Timer Timer
When the timer is not used, save the setting as
88 Room Air Conditioners J-Series
Page 90
EDUS041011 Optional Accessories
15
Cleaning
Cleaning the remote controller
Wipe it clean with soft, dry cloth. Do not use any water hotter than 40˚C (104˚F), or volatile liquids such as benzine, gasoline and thinner, polishing powder, or anything hard such as a scrub brush.
When the unit is not used for a long time
On a sunny day, keep the system running for
half a day in the FAN mode to dry it up inside.
3
12
FAN mode
1
Press
to select the cooling
mode.
2
Press
to adjust the set
temperature to 32˚C (90˚F).
3
Press .
The airflow rate remains the same, and is not
adjustable.
Run the system when the room temperature
is below 28˚C (82˚F).
Finally turn off the circuit breaker dedicated for
the room air conditioner.
Clean the air filter and place it back into
position.
3P202922-2B
Room Air Conditioners J-Series 89
Page 91
Optional Accessories EDUS041011
Inside indoor unit
This set
S602 S601
S403
S21
Option BRC944A2B
PCB of indoor unit
Note: Wires indicated by thick lines are not provided to the set.
Flap (in control of wind directions upward and downward)
Mounting position of the set
Electrical component box
Safety Precautions
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies precautions into WARNING and CAUTION.
This set is an interface that connects a wired remote controller to a room air conditioner.
Be sure to follow all the precautions below ; they are all important for ensuring safety.
WARNING :
Failure to follow WARNING is very likely to result in such grave consequences as death or serious injury.
CAUTION : Failure to follow CAUTION may result in serious
injury or property damage, and in certain circumstances, may result in a grave consequence.
WARNING
CAUTION
After installation is complete, test the operation of the PCB set to check for problems, and explain how to use the set to the end-user.
Starting and stopping the air conditioner and making mode and temperature
settings in the air conditioner through the wired remote controller (within a range of 18˚C to 32˚C while in cooling mode, 14˚C to 30˚C while in heating mode, but no temperature settings while in ventilation mode).
Monitoring the operating conditions, occurrence of errors, and contents of
errors of the air conditioner through the wired remote controller.
Restoring the operating condition of the air conditioner to the previous
condition at the time of power recovery in case of power failure.
Group control (i.e., the control a number of indoor units through a single
remote controller)
Monitoring of the following items:
Indoor temperature and operating conditions of thermo, compressor, indoor fan, electric heater, and humidifier
Control of the following items:
Forced thermo OFF, filter sign display and reset, and air-conditioner charge management
Energy-saving reference, low-noise reference, and demand reference
The set does not support the following functions.
Check that the set is provided with the following components.
Component Component
Installation Manual
11
Quantity Quantity
Main component
Mounting Position Wiring
Components
Outline/Features
• Installation should be left to the dealer or another qualified professional.
Improper installation by yourself may cause malfunction, electrical shock, or fire.
Install the set according to the instructions given in this manual.
Incomplete or improper installation may cause malfunction, electrical shock, or fire.
Be sure to use the standard attachments or the genuine parts.
Use of other parts may cause malfunction, electrical shock, or fire.
• Disconnect power to the connected equipment before starting installation.
Failure to do so may cause malfunction, electrical shock, or fire.
• An earth leakage circuit breaker should be installed.
If the breaker is not installed, electrical shock may occur.
Do not install the set in a location where there is danger of exposure to inflammable gas.
Gas accumulated around the unit at the worst may cause fire.
• To prevent damage due to electrostatic discharge, touch your hand to a nearby metal object (doorknob, aluminum sash, etc.) to discharge static electricity from your body before touching this kit.
Static electricity can damage this kit.
• Lay this cable separately from other power cables to avoid external electrical noises.
Mounting Procedure
Mounting position of the set
Electrical component box
13.3 <KRP980B1> Interface Adaptor for Wired Remote Controller
90 Room Air Conditioners J-Series
Page 92
EDUS041011 Optional Accessories
Rotating shaft
Service lid
Screw
Push down.
Upper hook
Upper hook
2) Pull toward you.
1) Push up.
Removing and installing front panel
Removing and installing front grille
Opening service lid of indoor unit
• Removal method
1)Place your fingers in the indentations on the main unit (one each on the left and right sides), and open the panel until it stops.
2)Continue to open the front panel further while sliding the panel to the right and pulling it toward you in order to disengage the rotating shaft on the left side. To disengage the rotating shaft on the right side, slide the panel to the left while pulling it toward you.
• Installation method
Align the tabs of the front panel with the grooves, and push all the way in. Then close slowly. Push the center of the lower surface of the panel firmly to engage the tabs.
Place both hands under the center of the front grille, and while pushing up, pull it toward you.
Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand. (3 locations)
<
When there is no work space because
the unit is close to ceiling
>
• Removal method
1)Remove front panel to remove the air filter.
2)Remove the screws (2) from the front grille.
3)In front of the mark of the front grille, there are 3 upper hooks. Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand.
The service lid is of removable type.
• Opening method
1)Remove the single screw of the service lid.
2)Pull out the service lid frontward.
• Installation method
1)Install the front grille and firmly engage the upper hooks (3 locations).
2)Install 2screws of the front grille.
3)Install the air filter and then mount the front panel.
Be sure to wear protection gloves.
CAUTION
Indentations on the main unit
Push the rotating shaft of the front panel into the groove.
mark area (3 locations)
Upper hook
Room Air Conditioners J-Series 91
Page 93
Optional Accessories EDUS041011
Positions of communication wiring and mounting
screw of electrical component box
Fig. 1
Position of thermistor
Fig. 3
Position of each
connector
Fig. 2
Electrical component box
Removing electrical component cover
Removing electrical component box
On completion of the connection of the electrical component (this set), mount the removed parts to the original positions.
If there is a workspace on the right-hand side of the indoor unit, the installation work can be conducted without removing the electrical component box.
On completion of the connection of the electrical component (this set), mount the removed parts to the original positions.
* Refer to the surface page for the removal of each part in detail.
*1 Remove the front panel.
*2 Remove the front grille.
*3 Remove the service lid of the indoor unit.
4 Remove the cover of the electrical component cover.
1. Remove the flap (in control of wind directions upward and downward).
2. Disconnect the communication wiring (see Fig. 1).
3. Disconnect the S200 connector (see Fig. 2).
4. Disconnect the heat changer from the thermistor (see Fig. 3).
5. Remove the mounting screw of the electrical component box, and remove the electrical component box (see Fig. 1).
If there is a workspace on the right-hand side of the indoor unit, the installation work can be conducted without removing the electrical component box.
WARNING
• Be sure to turn OFF the power at the time of installation work.
Do not touch any electric parts with the power turned ON. Otherwise, an electric shock may be received.front panel.
Mounting screw of electrical component box.
Remove the tabs.
Electric component cover
Tab
Mounting screw of electrical component box
Flap
Communication wiring
Thermistor
Make sure that the mounting bracket of the thermistor will not fall off.
S200
92 Room Air Conditioners J-Series
Page 94
EDUS041011 Optional Accessories
Preparing the electrical component (this set).
Installing electrical component
Remove the electrical component cover.
Disengage the tab.
S21
Route each connection cord through the cut-out.
Electrical component
Cut-outs
Electric component cover
Cut-out A
S403 connection cut-out
Cut-out B
S403 connection cut-out
Cut-out C
Connection cord cut-out
*1 Connection cord cut-out
Routing connection cord
S403 connection cord
Connection cord
Fig. 1
Fig. 2
Connecting electrical component (this set)
1.
Prepare the electrical component (this set).
(See Fig. 1)
1) Remove the electrical component cover
of the set.
2) Insert the connection cord into the S21
connector (white) of the set.
3) Route each connection cord through the
cut-out of the set and mount the electrical
component cover to the original position.
4) Insert the connector of the set into the
S403 in the indoor unit electrical
component connector. Then route the
connection cord to the cut-out (cut-out A)
in the indoor unit electrical component.
2.
Mount the electrical component cover to
the original position. (See Fig. 2)
3.
Mount the set. (See Fig. 2)
1) Mount the set to the electrical component
box of the indoor unit.
2) Route the connection cord as shown in
Fig. 2 (Routing connection cord).
*1 Route the connection cord through the cut-out (cut-out A).
Insert the cord into the S403.
Fit in.
Place the connection cord to come in contact with the protruding part.
Connection cord
Protruding part
Install the electrical component cover in its original position.
Install the electrical component.
Push the electrical component until it snaps into engagement with the tab.
Electrical component
Electric component cover
Tab
3P214218-1
Room Air Conditioners J-Series 93
Page 95
Optional Accessories EDUS041011
b)
Checking the parts
Installation of Louver
CAUTION
Louver
1piece1piece
Shape
Quantity
Selection of Installation Location
Check the following parts
a)
Before Installation
Installation Procedure
Use when installing in a location that meets the following conditions.
When installing near the border to a neighbor's houseIf exhaust blows directly on passers-by because outdoor unit is installed facing a road.Changing the fan direction of the outdoor unit to prevent it blowing directly on shrubbery, etc.
Installation is possible in the four directions:
upward, downward, rightward, and leftward.
The installation screws are attached to the louver.First temporarily attach the louver with 4 screws,
then check that the angle is correct, and finally tighten the screws fully.
1.Install so that a short circuit is prevented.
2.For the use in snowy regions, avoid installation with the air outlet facing upward. Install so that the air outlet faces leftward, rightward, or down­ward. Snow accumulates in the air outlet of the outdoor unit, causing malfunction of the main body of the outdoor unit.
3.Be advised that if the fan direction is up,
dead leaves and other foreign matter easily accumulates in the exhaust vent.
Name
With 4 screws
Installation manual
Prepared hole pitch 435mm Fan partition
Prepared hole pitch 435mm Fan partition
Part A
(see figure below)
The prepared hole is in between the grating of the grille. Part A (prepared hole) cross section (the shape of either a or b)
Grille grating
Prepared hole Prepared hole
Grille grating
4P104499-1A
13.4 <KPW937A4> Air Direction Adjustment Grille
94 Room Air Conditioners J-Series
Page 96
Specifications, designs and other content appearing in this brochure are current as of April 2010 but subject to change without notice.
AMERICAS
1645 Wallace Drive, Suite 110
Carrollton, TX75006
info@daikinac.com
www.daikinac.com
EDUS041011 Printed in U.S.A. 04/2010 B AK
Loading...