Daikin FDXM25F3V1B, FDXM35F3V1B, FDXM50F3V1B, FDXM60F3V1B, FDXM25F3V1B9 Installer reference guide [sl]

...
Vodnik za monterja
Klimatske naprave s sistemom split
FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B
FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V1B9
Vodnik za monterja
Klimatske naprave s sistemom split
Slovenščina

Kazalo

Kazalo

1 Splošni varnostni ukrepi 2

1.1 O dokumentaciji......................................................................... 2
1.1.1 Pomen opozoril in simbolov........................................ 2
1.2 Za monterja ............................................................................... 3
1.2.1 Splošno....................................................................... 3
1.2.2 Mesto namestitve........................................................ 3
1.2.3 Hladivo........................................................................ 5
1.2.4 Slanica ........................................................................ 5
1.2.5 Voda............................................................................ 5
1.2.6 Električna dela ............................................................ 6
2 O dokumentaciji 6
2.1 O tem dokumentu...................................................................... 6
2.2 Kratek pregled referenčnega vodnika za monterja.................... 7
3 O škatli 7
3.1 Pregled: O škatli ........................................................................ 7
3.2 Notranja enota........................................................................... 7
3.2.1 Za odpakiranje in rokovanje z enoto........................... 7
3.2.2 Odstranjevanje opreme z notranje enote.................... 7
4 O enotah in opcijskih dodatkih 7
4.1 Pregled: O enotah in opcijskih dodatkih .................................... 7
4.2 Razpostavitev sistema .............................................................. 8
4.3 Kombiniranje enot in možnosti .................................................. 8
4.3.1 Možni opcijski dodatki za notranjo enoto .................... 8
5 Priprava 8
5.1 Pregled: Priprava....................................................................... 8
5.2 Priprava mesta namestitve........................................................ 8
5.2.1 Zahteve za namestitveno mesto za notranjo enoto .... 8
5.3 Priprava cevi za hladivo ............................................................ 9
5.3.1 Zahteve za cevi za hladivo.......................................... 9
5.3.2 Izolacija cevi za hladivo .............................................. 9
5.4 Priprava električnega ožičenja .................................................. 9
5.4.1 O pripravi električnega ožičenja.................................. 9
6 Montaža 10
6.1 Pregled: Montaža ...................................................................... 10
6.2 Nameščanje notranje enote ...................................................... 10
6.2.1 Napotki za varnost pri montaži notranje enote............ 10
6.2.2 Navodila pri nameščanju notranje enote..................... 10
6.2.3 Navodila za nameščanje cevovodov........................... 11
6.2.4 Navodila za nameščanje cevi za odvajanje
kondenzata ................................................................. 11
6.3 Povezovanje cevi za hladivo ..................................................... 12
6.3.1 O priključevanju cevi za hladivo.................................. 12
6.3.2 Varnostni ukrepi pri priključevanju cevi za hladivo...... 12
6.3.3 Navodila pri priključevanju cevi za hladivo.................. 13
6.3.4 Napotki za upogibanje cevi......................................... 13
6.3.5 Robljenje konca cevi................................................... 13
6.3.6 Priključevanje cevi za hladivo na notranjo enoto ........ 13
6.3.7 Preverjanje puščanja .................................................. 14
6.4 Priključevanje električnega ožičenja.......................................... 14
6.4.1 O priključevanju električnega ožičenja........................ 14
6.4.2 Napotki za varnost pri priključevanju električnega
ožičenja....................................................................... 14
6.4.3 Napotki za priključevanje električnega ožičenja.......... 14
6.4.4 Priključevanje električnega ožičenja na notranjo
enoto ........................................................................... 15
6.4.5 Specifikacije standardnih komponent ožičenja ........... 15
7 Konfiguracija 15
7.1 Nastavitve sistema .................................................................... 15
8 Zagon 16
8.1 Seznam preverjanj pred zagonom ............................................ 16
8.2 Izvedite preizkus delovanja ........................................................ 16
8.3 Kode napak pri izvajanju preizkusa delovanja ........................... 17
9 Izročitev uporabniku 17 10 Odstranjevanje 17 11 Tehnični podatki 17
11.1 Shema povezav.......................................................................... 18
12 Slovar 18
1 Splošni varnostni ukrepi

1.1 O dokumentaciji

▪ Izvorna dokumentacija je pisana v angleščini. Dokumentacija v
drugih jezikih je prevod.
▪ Varnostni ukrepi, opisani v tem dokumentu, obravnavajo zelo
pomembne teme; skrbno se jih držite.
▪ Namestitev sistema in vse dejavnosti, opisane v priročniku za
montažo in v vodiču za inštalaterja, mora izvesti kvalificiran inštalater.

1.1.1 Pomen opozoril in simbolov

NEVARNOST
Označuje situacijo, ki vodi v smrt in hude telesne poškodbe.
NEVARNOST: SMRTNA NEVARNOST ZARADI ELEKTRIČNEGA UDARA
Označuje situacijo, ki lahko povzroči smrt zaradi električnega udara.
NEVARNOST: NEVARNOST OPEKLIN IN OZEBLIN
Označuje situacijo, ki lahko povzroči opekline ali ozebline zaradi izredno visokih ali izredno nizkih temperatur.
NEVARNOST: NEVARNOST EKSPLOZIJE
Označuje situacijo, ki lahko povzroči eksplozijo.
OPOZORILO
Označuje situacijo, ki lahko povzroči smrt in hude telesne poškodbe.
OPOZORILO: VNETLJIV MATERIAL
POZOR
Označuje situacijo, ki lahko povzroči manjše ali srednje nevarne telesne poškodbe.
OPOMBA
Označuje situacijo, ki lahko povzroči poškodbe opreme ali lastnine.
INFORMACIJE
Označuje uporabne nasvete ali dodatne informacije.
Simbol Razlaga
Pred namestitvijo preberite navodila za montažo in uporabo ter shemo z navodili za ožičenje.
Preden začnete izvajati vzdrževalne in servisne postopke preberite priročnik za servisiranje.
2
Klimatske naprave s sistemom split
FDXM25~60F3V1B(9)
4P550955-1 – 2018.07
1 Splošni varnostni ukrepi
Simbol Razlaga
Za več informacij glejte vodnik za monterja in uporabnika.

1.2 Za monterja

1.2.1 Splošno

Če NISTE prepričani, kako montirati ali upravljati enoto, se obrnite na svojega prodajalca.
OPOMBA
Nestrokovna montaža ali priklop naprave in opreme lahko povzroči električni udar, kratek stik, uhajanje tekočin ali požar ali drugače poškoduje napravo ali opremo. Uporabljajte samo dodatke, opcijsko opremo in nadomestne dele, ki jih izdela ali odobri Daikin.
OPOZORILO
Montaža, preizkus in uporabljeni materiali morajo biti (razen z navodili, opisanimi v dokumentaciji Daikin) skladni tudi z veljavno zakonodajo.
POZOR
Pri nameščanju, vzdrževanju ali servisiranju sistema uporabljajte ustrezno osebno zaščitno opremo (zaščitne rokavice, varnostna očala…).
OPOZORILO
Raztrgajte in odvrzite plastične vreče, da se z njimi nihče ne bi mogel igrati, zlasti ne otroci. Možna nevarnost: zadušitev.
NEVARNOST: NEVARNOST OPEKLIN IN OZEBLIN
▪ NE dotikajte se cevi za hladivo, cevi za vodo in
notranjih delov med delovanjem ali neposredno po delovanju. Lahko so prevroči ali premrzli. Počakajte, da se njihova temperatura normalizira. Če se jih morate dotikati, si nadenite zaščitne rokavice.
▪ Z golo kožo se NE dotikajte ponesreči razlitega hladiva.
OPOZORILO
Z zagotavljanjem primernih ukrepov preprečite, da bi enota postala zavetišče za majhne živali. Majhne živali, ki se dotaknejo električnih delov, lahko povzročijo okvare, dim ali požar.
POZOR
Ne dotikajte se odprtine za vstop zraka ali aluminijastih platic enote.
OPOMBA
▪ Na vrh enote NE postavljajte predmetov ali opreme. ▪ NE sedite na napravi, ne plezajte nanjo in ne stojte na
njej.
OPOMBA
Dela na zunanji enoti je najbolje opraviti v suhem vremenu, da bi se izognili vdoru vode.
V skladu z zadevno zakonodajo bo treba morda skupaj z izdelkom priskrbeti dnevnik, v katerem se beležijo najmanj: podatki o vzdrževanju, popravila, rezultati testov, obdobja pripravljenosti…
Najmanj naslednje informacije MORAJO biti zagotovljene na dostopnem mestu izdelka:
▪ Navodila za izklop sistema v nujnem primeru
▪ Naziv in naslov gasilske službe, policije in bolnišnice ▪ Ime, naslov ter dnevna in nočna telefonska številka za servis Potrebne smernice za tak dnevnik za Evropo podaja standard
EN378.

1.2.2 Mesto namestitve

▪ Zagotovite dovolj prostora okoli enote za servisiranje in kroženje
zraka.
▪ Prepričajte se, da bo mesto namestitve preneslo težo enote in
tresljaje.
▪ Prepričajte se, da je območje dobro prezračeno. NE blokirajte
prezračevalnih odprtin.
▪ Pazite, da bo enota izravnana.
Enote NE nameščajte na naslednja mesta: ▪ V potencialno eksplozivnem okolju. ▪ Na mestih, kjer so stroji, ki oddajajo elektromagnetne valove.
Elektromagnetni valovi lahko motijo krmilni sistem in lahko povzročijo okvare na opremi.
▪ Na mestih, kjer obstaja nevarnost požara zaradi uhajanja vnetljivih
plinov (primer: razredčilo ali bencin), ogljikovih vlaken ali vnetljivega prahu.
▪ Na mestih, kjer nastajajo korozivni plini (primer: kisli žvepleni plin).
Zaradi korozije bakrenih cevi ali zvarov bi lahko začelo puščati hladivo.
Navodila za opremo, ki uporablja hladivo R32
Če se uporablja.
OPOZORILO
▪ NE prebadajte in ne zažigajte. ▪ NE uporabite sredstev in načinov za pospeševanje
odmrzovanja ali čiščenja opreme, razen tistih, ki jih priporoča proizvajalec.
▪ Bodite pozorni na to, da je R32 BREZ vonja.
OPOZORILO
Naprava mora biti skladiščena tako, da se prepreči mehanske poškodbe, in v dobro prezračenem prostoru, kjer ni neprestano prisotnih virov vžiga (na primer: odprtega plamena, delujoče naprave na plin ali delujočega električnega grelnika). Poleg tega mora biti prostor v izmeri, navedeni v nadaljevanju.
OPOMBA
▪ Spojev, ki so že bili uporabljeni, NE uporabljajte znova. ▪ Spoji, ki so bili narejeni na inštalaciji med deli
hladilnega sistema, morajo biti dostopni za vzdrževanje.
OPOZORILO
Prepričajte se, da so namestitev, servisiranje, vzdrževanje in popravila izvedeni v skladu z navodili Daikin in v skladu z veljavno zakonodajo (na primer predpisom o plinu) in da jih izvajajo pooblaščene osebe.
Zahteve namestitve po prostoru
OPOMBA
▪ Cevovod mora biti zaščiten pred fizičnimi poškodbami. ▪ Cevi mora biti najmanj, kar je mogoče.
FDXM25~60F3V1B(9) Klimatske naprave s sistemom split 4P550955-1 – 2018.07
3
1 Splošni varnostni ukrepi
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
OPOZORILO
Če je v napravah hladivo R32, MORA biti kvadratura prostora, v katerega se namešča, v katerem deluje ali je skladiščena naprava, večja od najmanjše kvadrature prostora, določene v spodnji tabeli A (m2). To velja za:
▪ Notranje enote brez tipala za puščanje hladiva; v
primeru notranjih enot s tipalom za puščanje hladiva glejte priročnik za montažo
▪ Zunanje enote, nameščene ali skladiščene v notranjih
prostorih (npr. zimski vrt, garaža, strojnica)
▪ Cevovode v neprezračenih prostorih
Da bi določili najmanjšo potrebno kvadraturo prostora
1 Izračunajte skupno količino hladiva v sistemu (= tovarniška
polnitev hladiva + dolito hladivo).
2 Določite, kateri grafikon ali tabelo uporabiti.
▪ Za notranje enote: Je enota nameščena na strop, na steno
ali stoji na tleh?
▪ Za zunanje enote, nameščene ali skladiščene v notranjih
prostorih, in za cevovode v neprezračenih prostorih, je kvadratura odvisna od višine namestitve:
Če je višina namestitve… Uporabite grafikon ali tabelo
za…
<1,8m Stoječe enote 1,8≤x<2,2m Enote, nameščene na steno ≥2,2m Enote, nameščene na strop
3 Uporabite grafikon ali tabelo za določanje minimalne kvadrature
prostora.
4
m Skupna polnitev hladiva v sistemu
A
Najmanjša kvadratura prostora
min
(a) Ceiling-mounted unit (= Enota, nameščena na stropu) (b) Wall-mounted unit (= Enota, nameščena na steni)
FDXM25~60F3V1B(9)
Klimatske naprave s sistemom split
4P550955-1 – 2018.07
1 Splošni varnostni ukrepi
(c) Floor-standing unit (= Stoječi tip enote)

1.2.3 Hladivo

Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik za monterja za vašo uporabo.
OPOMBA
Napeljava cevi mora biti skladna z veljavno zakonodajo. Zadevni standard za Evropo je EN378.
OPOMBA
Poskrbite, da zunanje cevi in priključki NE bodo obremenjeni.
OPOZORILO
Med testiranjem v izdelku NIKOLI ne smete vzpostaviti tlaka, višjega od maksimalnega dovoljenega tlaka (ki je naveden na nazivni ploščici enote).
OPOZORILO
Izvedite varnostne ukrepe, če pride do puščanja hladiva. Če hladilni plin uhaja, nemudoma prezračite prostor. Možne nevarnosti:
▪ Previsoka koncentracija hladiva v zaprtem prostoru
lahko povzroči pomanjkanje kisika.
▪ Če pride hladilni plin v stik z ognjem, se lahko tvorijo
strupeni plini.
NEVARNOST: NEVARNOST EKSPLOZIJE Izčrpavanje – Puščanje hladiva. Če želite sistem izčrpati
in nekje na tokokrogu hladilnega sredstva pušča:
▪ NE uporabljajte funkcije za samodejno izčrpavanje na
enoti, s katero lahko zberete vse hladivo iz sistema v zunanji enoti. Možna posledica: Samoizgorevanje in eksplozija kompresorja zaradi zraka, ki pride v delujoč kompresor.
▪ Uporabite ločen sistem za izčrpavanje, tako da
kompresorju enote NI treba delovati.
OPOZORILO
Hladivo VEDNO zberite. NE izpuščajte jih neposredno v okolje. Uporabite vakuumsko črpalko, da boste izpraznili napeljavo.
OPOMBA
Ko so vse cevi priključene, se prepričajte, da plin ne uhaja. S pomočjo dušika preverite, ali plin uhaja.
OPOMBA
▪ Preprečevanje okvare kompresorja, NE dolijte več
hladiva, kot je navedeno v specifikaciji.
▪ Kadar je treba sistem hladiva odpreti, morate s
hladivom ravnati v skladu z zadevno zakonodajo.
OPOZORILO
Pazite, da v sistemu ni kisika. Hladivo lahko natočite šele, ko opravite preizkus tesnjenja in vakuumsko praznjenje.
▪ Če je potrebno vnovično polnjenje, glejte nazivno ploščico enote.
Na njej sta označeni vrsta hladiva in potrebna količina.
▪ Enota je tovarniško napolnjena s hladivom. Odvisno od velikosti in
dolžine cevi je treba v nekaterih sistemih dotočiti hladivo.
▪ Da bi zagotovili upornost tlaka in preprečili vdor drugih snovi v
sistem, uporabljajte samo orodje, zasnovano posebej za vrsto hladiva, uporabljeno v sistemu.
▪ Hladivo točite upoštevaje naslednje:
Če Potem
Je prisotna sifonska cev (tj., na jeklenki je oznaka “Liquid
filling siphon attached” (pritrjena sifonska cev za tekoče hladivo))
Sifonska cev NI prisotna Pri polnjenju mora biti jeklenka
▪ Počasi odprite vsebnike hladiva. ▪ Hladivo točite v tekočem stanju. Dodajanje hladiva v plinskem
stanju lahko onemogoči normalno delovanje.
POZOR
Ko je postopek dolivanja hladiva dokončan ali ga prekinete, takoj zaprite ventil rezervoarja za hladivo. Če se ventil NE zapre takoj, lahko preostanek tlaka napolni dodatno hladivo. Možna posledica: Nepravilna količina hladiva.
Pri polnjenju mora biti jeklenka postavljena pokonci.
obrnjena na glavo.

1.2.4 Slanica

Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik za monterja za vašo uporabo.
OPOZORILO
Izbira slanice MORA biti skladna z veljavno zakonodajo.
OPOZORILO
Izvedite varnostne ukrepe, če pride do puščanja slanice. Če slanica izteka, takoj prezračite območje in se obrnite na lokalnega prodajalca.
OPOZORILO
Temperatura okolja v notranjosti enote je lahko bistveno višja od temperature v prostoru, npr. 70°C. V primeru iztekanja slanice lahko vroči deli enote povzročijo nevarno situacijo.
OPOZORILO
Uporaba in namestitev sistema MORATA biti skladni z varnostnimi in okoljskimi previdnostnimi ukrepi, ki jih določa veljavna zakonodaja.

1.2.5 Voda

Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik za monterja za vašo uporabo.
OPOMBA
Kakovost vode mora ustrezati Direktivi EU 98/83ES.
FDXM25~60F3V1B(9) Klimatske naprave s sistemom split 4P550955-1 – 2018.07
5

2 O dokumentaciji

1.2.6 Električna dela

NEVARNOST: SMRTNA NEVARNOST ZARADI ELEKTRIČNEGA UDARA
▪ Izklopite napajanje, preden odstranjujete pokrov
stikalne omarice, priklapljate električno ožičenje ali se dotikate električnih delov.
▪ Pred servisiranjem odklopite napajanje za več kot
1 minuto in izmerite napetost na priključkih kondenzatorjev glavnega tokokroga ali električnih sestavnih delih. Napetost MORA biti nižja od 50V DC, preden se lahko dotaknete električnih sestavnih delov. Za mesta priključkov glejte vezalno shemo.
▪ Električnih sestavnih delov se NE dotikajte z mokrimi
rokami.
▪ Enote NE puščajte brez nadzora, če ste z nje odstranili
servisni pokrov.
OPOZORILO
Če NI nameščeno, JE NUJNO v fiksno ožičenje namestiti glavno stikalo ali druge možnosti odklopa, ki imajo ločen stik na vseh polih in omogočajo popolni odklop v pogojih previsoke napetosti kategorijeIII.
OPOZORILO
▪ Uporabljajte LE bakrene vodnike. ▪ Pazite, da bodo električne napeljave ustrezale veljavni
zakonodaji.
▪ Vse lokalno ožičenje mora biti izvedeno skladno z
vezalno shemo, priloženo izdelku.
▪ NIKOLI ne stiskajte šopov kablov in pazite, da NE
pridejo v stik s cevmi ali z ostrimi robovi. Prepričajte se, da na priključne sponke ne pritiska nič z zunanje strani.
▪ Pazite, da boste zagotovo namestili ozemljitveni
vodnik. Ne ozemljujte naprave s pomočjo komunalne cevi, prenapetostnega odvodnika ali ozemljitve telefona. Nepopolna ozemljitev lahko povzroči električni šok.
▪ Zagotovo uporabite ločeno električno vezje. NIKOLI ne
delite vira napajanja z drugo napravo.
▪ Pazite, da boste zagotovo namestili zahtevane
varovalke ali prekinjala vezij.
▪ Zagotovo namestite odklopnik z uhajanjem toka. Če
tega ne storite, lahko pride do električnega udara ali požara.
▪ Ko nameščate zemljostično zaščito, pazite, da je
združljiva z inverterjem (odporna na visokofrekvenčne električne šume), da bi se izognili nepotrebnemu odpiranju zaščite.
OPOMBA
Varnostni ukrepi pri napeljavi napajalnih vodnikov:
▪ NE priključujte vodnikov različnih debelin na priključne
sponke napajanja (ohlapnost napajalnih vodnikov lahko povzroči neobičajno segrevanje).
▪ Pri priključevanju vodnikov enake debeline naredite
tako, kot je prikazano na sliki zgoraj.
▪ Za ožičenje uporabite predvideni napajalni vodnik in ga
trdno priključite, nato pa zavarujte, da bi preprečili, da se zunanja sila prenese na priključno ploščo.
▪ Uporabite ustrezen izvijač za privijanje vijakov na
priključku. Izvijač z malim nastavkom lahko poškoduje glavo vijaka in onemogoči ustrezno zategovanje.
▪ S premočnim zategovanjem lahko vijake na priključkih
polomite.
Namestite napajalne kable vsaj 1 meter stran od televizijskih ali radijskih sprejemnikov, da bi se izognili motnjam. Odvisno od radijskih valov tudi 1meter lahko ni dovolj, da bi se preprečil šum.
OPOZORILO
▪ Ko zaključite napeljavo električnih kablov, se
prepričajte, da so vsi električni sestavni deli in vse priključne sponke v omarici z električnimi sestavnimi deli varno pritrjeni.
▪ Obvezno zaprite vse pokrove, preden zaženete enoto.
OPOMBA
Velja samo, če je napajanje trifazno in je način zagona kompresorja VKLOP/IZKLOP.
Če obstaja možnost, da bi do obrnjene faze prišlo po trenutnem izpadu in se napajanje vklaplja in izklaplja med delovanjem izdelka, priključite vezje za zaščito pred obrnjeno fazo lokalno. Delovanje izdelka z obrnjeno fazo lahko povzroči okvaro kompresorja in drugih delov.
2 O dokumentaciji

2.1 O tem dokumentu

INFORMACIJE
Prepričajte se, da ima uporabnik natisnjeno dokumentacijo in ga prosite, naj jo shrani.
Ciljni prejemniki
Pooblaščeni monterji
6
INFORMACIJE
Uporaba naprave je predvidena za strokovnjake oziroma usposobljene uporabnike v delavnicah, v manj zahtevnem industrijskem okolju ter na kmetijah oziroma za nestrokovnjake v poslovnem okolju in gospodinjstvih.
Komplet dokumentacije
Ta dokument je del kompleta dokumentacije. Celotno dokumentacijo sestavljajo:
Splošni varnostni ukrepi:
▪ Varnostna navodila, ki jih morate prebrati pred montažo ▪ Format: Papirni izvod (v škatli notranje enote)
FDXM25~60F3V1B(9)
Klimatske naprave s sistemom split
4P550955-1 – 2018.07