Daikin FDXM25F3V1B, FDXM35F3V1B, FDXM50F3V1B, FDXM60F3V1B, FDXM25F3V1B9 Installer reference guide [cs]

...
Referenční příručka k
instalaci
Dělené klimatizační systémy
FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B
FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V1B9
Referenční příručka k instalaci
Dělené klimatizační systémy
čeština
Obsah

1 Všeobecná bezpečnostní opatření 2

1.1 O této dokumentaci ................................................................... 2
1.1.1 Význam varování a symbolů....................................... 2
1.2 Pro instalačního technika .......................................................... 3
1.2.1 Obecně ....................................................................... 3
1.2.2 Místo instalace............................................................ 3
1.2.3 Chladivo...................................................................... 5
1.2.4 Solanka....................................................................... 5
1.2.5 Voda............................................................................ 5
1.2.6 Elektrická instalace ..................................................... 6
2 O této dokumentaci 6
2.1 O tomto dokumentu................................................................... 6
2.2 Stručná referenční příručka pro techniky .................................. 7
3 Informace o krabici 7
3.1 Přehled: Informace o krabici...................................................... 7
3.2 Vnitřní jednotka ......................................................................... 7
3.2.1 Rozbalení a manipulace s jednotkou.......................... 7
3.2.2 Sejmutí příslušenství z vnitřní jednotky....................... 7
4 Informace o jednotkách a volitelném
příslušenství 7
4.1 Přehled: Informace o jednotkách a volitelném příslušenství ..... 7
4.2 Uspořádání systému ................................................................. 8
4.3 Kombinace jednotek a volitelných možností ............................. 8
4.3.1 Možné volitelné možnosti pro vnitřní jednotku............ 8
5 Příprava 8
5.1 Přehled: Příprava ...................................................................... 8
5.2 Příprava místa instalace............................................................ 8
5.2.1 Požadavky na místo instalace pro vnitřní jednotku..... 8
5.3 Příprava chladivového potrubí................................................... 9
5.3.1 Požadavek na chladicího potrubí................................ 9
5.3.2 Izolace chladivového potrubí ...................................... 9
5.4 Příprava elektrické instalace ..................................................... 9
5.4.1 Informace o přípravě elektrické instalace ................... 9
8.2 Provedení zkušebního provozu.................................................. 16
8.3 Chybové kódy při provádění testovacího provozu ..................... 17
9 Předání uživateli 17 10 Likvidace 17 11 Technické údaje 17
11.1 Schéma zapojení........................................................................ 18
12 Slovník pojmů 18
1 Všeobecná bezpečnostní
opatření

1.1 O této dokumentaci

▪ Původní dokumentace je napsána vangličtině. Ostatní jazyky jsou
překlady.
▪ Bezpečnostní opatření popsaná v tomto dokumentu zahrnují velmi
důležitá témata. Pečlivě je dodržujte.
▪ Instalace systému a všechny činnosti popsané v instalační
příručce a instalační referenční příručce MUSÍ být provedeny autorizovaným instalačním technikem.

1.1.1 Význam varování a symbolů

NEBEZPEČÍ
Označuje situaci, která bude mít za následek smrt nebo vážné zranění.
NEBEZPEČÍ: RIZIKO ZABITÍ ELEKTRICKÝM PROUDEM
Označuje situaci, která může mít za následek usmrcení elektrickým proudem.
NEBEZPEČÍ: RIZIKO POPÁLENÍ
Označuje situaci, která může mít za následek popálení v důsledku extrémně vysokých nebo nízkých teplot.
6 Instalace 10
6.1 Přehled: Instalace...................................................................... 10
6.2 Montáž vnitřní jednotky ............................................................. 10
6.2.1 Bezpečnostní opatření při montáži vnitřní jednotky .... 10
6.2.2 Pokyny k montáži vnitřní jednotky............................... 10
6.2.3 Pokyny k instalaci kanálů............................................ 11
6.2.4 Pokyny pro instalaci vypouštěcího potrubí.................. 11
6.3 Připojení potrubí chladiva.......................................................... 12
6.3.1 O připojení potrubí chladiva........................................ 12
6.3.2 Bezpečnostní upozornění pro připojování potrubí
chladiva....................................................................... 12
6.3.3 Pokyny pro připojování potrubí chladiva..................... 13
6.3.4 Pokyny pro ohýbání potrubí........................................ 13
6.3.5 Rozšiřování konců trubek ........................................... 13
6.3.6 Připojení potrubí chladiva k vnitřní jednotce ............... 14
6.3.7 Kontrola těsnosti ......................................................... 14
6.4 Připojení elektrického vedení .................................................... 14
6.4.1 Informace o připojování elektrického vedení .............. 14
6.4.2 Bezpečnostní opatření při zapojování elektrického
vedení ......................................................................... 14
6.4.3 Pokyny k zapojování elektrického vedení................... 14
6.4.4 Připojení elektrické kabeláže k vnitřní jednotce.......... 15
6.4.5 Specifikace standardních součástí zapojení............... 15
7 Konfigurace 15
7.1 Provozní nastavení.................................................................... 15
8 Uvedení do provozu 16
8.1 Kontrolní seznam před uvedením do provozu........................... 16
NEBEZPEČÍ: RIZIKO VÝBUCHU
Tento symbol označuje situaci, která může mít za následek výbuch.
VÝSTRAHA
Označuje situaci, která může mít za následek smrt nebo vážné zranění.
VÝSTRAHA: HOŘLAVÝ MATERIÁL
UPOZORNĚNÍ
Označuje situaci, která může mít za následek lehčí nebo střední zranění.
POZNÁMKA
Označuje situaci, která může mít za následek poškození zařízení nebo majetku.
INFORMACE
Označuje užitečné tipy nebo doplňující informace.
Symbol Vysvětlení
Před instalaci si prostudujte návod instalaci a návod k obsluze a schémat zapojení elektrické kabeláže.
Před prováděním údržby nebo servisu si prostudujte servisní příručku.
Referenční příručka k instalaci
2
FDXM25~60F3V1B(9)
Dělené klimatizační systémy
4P550955-1 – 2018.07
1 Všeobecná bezpečnostní opatření
Symbol Vysvětlení
Další informace naleznete v návodu k instalaci a uživatelské příručce.

1.2 Pro instalačního technika

1.2.1 Obecně

Pokud si NEJSTE jisti způsoby instalace nebo obsluhy jednotky, kontaktujte svého dodavatele.
POZNÁMKA
Nesprávná instalace nebo připojení zařízení či příslušenství mohou způsobit úraz elektrickým proudem, zkrat, netěsnosti, požár nebo jiné poškození zařízení. Používejte pouze příslušenství, volitelné vybavení a náhradní díly vyrobené nebo schválené Daikin.
VÝSTRAHA
Ujistěte se, že instalace, zkoušení a použité materiály odpovídají platným předpisům (nad pokyny popsanými v dokumentaci Daikin).
UPOZORNĚNÍ
Používejte adekvátní osobní ochranné pomůcky (ochranné rukavice, bezpečnostní brýle,…) při instalaci, údržbě nebo provádění servisu systému.
VÝSTRAHA
Roztrhněte a vyhoďte plastové obaly, aby si snimi nikdo, zvláště děti, nehrál. Možné riziko: udušení.
NEBEZPEČÍ: RIZIKO POPÁLENÍ
▪ NEDOTÝKEJTE se rozvodů chladiva, vody ani
vnitřních součástí během a bezprostředně po ukončení provozu. Mohou být příliš horké nebo studené. Poskytněte dostatek času, aby se u nich vyrovnala normální teplota. Pokud se jich musíte dotknout, používejte ochranné rukavice.
▪ NEDOTÝKEJTE se náhodně uniklého chladiva přímo.
VÝSTRAHA
Proveďte přiměřená opatření, aby malá zvířata nemohla jednotku použít jako svůj úkryt. Malá zvířata mohou svým dotykem selektrickými částmi způsobit poruchu, kouř nebo požár.
UPOZORNĚNÍ
NEDOTÝKEJTE se vstupu vzduchu ani hliníkových žaluzií jednotky.
POZNÁMKA
▪ Na horní stranu (horní desku) jednotky
NEPOKLÁDEJTE žádné předměty ani přístroje.
▪ Na horní stranu jednotky NESEDEJTE,
NEVYLÉZEJTE, ani NESTOUPEJTE.
POZNÁMKA
Práce na venkovní jednotce je nejlépe provádět v suchém počasí, aby se zabránilo vniknutí vody.
V souladu s platnou legislativou může být nutné s produktem poskytnout záznamovou knihu obsahující minimálně následující údaje: informace o údržbě, opravách, výsledcích testů, intervalech pohotovostního režimu atd.
V přístupné části produktu MUSÍ být k dispozici minimálně následující informace:
▪ Pokyny pro vypnutí systému v případě nouze. ▪ Název a adresa hasičského sboru, policie a lékařské záchranné
služby. ▪ Název, adresa a denní a noční telefonní čísla pro zajištění služby. V Evropě obsahuje směrnice k vedení tohoto deníku zařízení norma
EN378.

1.2.2 Místo instalace

▪ Kolem jednotky ponechte dostatečný prostor pro účely servisu a
zajištění potřebného oběhu vzduchu. ▪ Ujistěte se, že místo instalace vydrží hmotnost jednotky a vibrace. ▪ Zajistěte, aby prostor byl dobře odvětrán. NEBLOKUJTE otvory
pro vstup a výstup vzduchu. ▪ Jednotka musí být vodorovná.
Jednotku NEINSTALUJTE na místa s následujícími vlastnostmi: ▪ Potenciálně výbušné ovzduší. ▪ V místech, kde je instalováno vybavení, jež vydává
elektromagnetické vlnění. Elektromagnetické vlny by mohly rušit
řídicí systém a způsobit poruchu funkce zařízení. ▪ V místech, kde hrozí nebezpečí požáru v důsledku úniku
hořlavých plynů (příklad: ředidlo nebo benzín), kde se nachází
uhlíková vlákna, hořlavý prach. ▪ V místech, kde vznikají korozívní plyny (například oxid siřičitý
nebo sírový). Koroze měděného potrubí nebo spájených dílů by
mohla způsobit únik chladiva.
Pokyny pro zařízení používající chladivo R32
Je-li použito.
VÝSTRAHA
▪ Nepropichujte ani nespalujte. ▪ Nepoužívejte žádné prostředky pro odmrazování nebo
čištění zařízení, kromě těch, jež jsou doporučeny výrobcem.
▪ Mějte se na pozoru před chladivem R32, které nemají
žádný zápach.
VÝSTRAHA
Zařízení musí být uloženo v dobře větrané místnosti se správnými rozměry bez nepřetržitě pracujících zdrojů zažehnutí (například otevřený plamen, pracující plynové zařízení nebo elektrické topidlo), aby se zabránilo mechanickému poškození.
POZNÁMKA
▪ Nepoužívejte opakovaně spoje, které jste již jednou
použili.
▪ Spoje zhotovené při instalaci mezi součástmi systému
chladiva musí být přístupné pro účely údržby.
VÝSTRAHA
Zajistěte, aby instalace, testování a použité materiálů splňovaly příslušné pokyny Daikin a legislativu, například národní předpisy pro plynové instalace a byly provedeny pouze autorizovanými osobami.
Prostorové požadavky pro instalaci
POZNÁMKA
▪ Potrubí musí být chráněno před fyzickým poškozením. ▪ Instalace potrubí musí být minimalizována.
FDXM25~60F3V1B(9) Dělené klimatizační systémy 4P550955-1 – 2018.07
Referenční příručka k instalaci
3
1 Všeobecná bezpečnostní opatření
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
VÝSTRAHA
Pokud zařízení obsahuje chladivo R32, pak MUSÍ být podlahová plocha místnosti, ve které je zařízení nainstalováno, provozováno a uloženo větší, než minimální podlahová plocha, definovaná v tabulce níže A (m2). To platí pro:
▪ Vnitřní jednotky bez snímače úniku chladiva; v případě
vnitřních jednotek se snímačem úniku chladiva se informujte v instalační příručce
▪ Venkovní jednotky nainstalované nebo uložené uvnitř
(například zimní zahrada, garáž, technická místnost)
▪ Provozní potrubí v nevětraných místnostech
Stanovení minimální podlahové plochy
1 Stanovte objem celkové náplně chladiva v systému (= tovární
náplň chladiva + dodatečná náplň chladiva).
2 Stanovte, který graf nebo tabulku máte použít.
▪ Pro vnitřní jednotky: Je jednotka namontovaná na stropě,
stěně nebo stojí na podlaze?
▪ Pro venkovní jednotky nainstalované nebo skladované ve
vnitřních prostorách a pro provozní potrubí v nevětraných prostorách toto závisí na výšce instalace:
Pokud je výška instalace… Pak použijte graf nebo tabulku
pro…
<1,8m Podlahové jednotky 1,8≤x<2,2m Jednotky k montáži na stěnu ≥2,2m Jednotky k montáži na strop
3 Pro stanovení minimální podlahové plochy použijte graf nebo
tabulku.
Referenční příručka k instalaci
4
m Celkové množství náplně chladiva vsystému
A
Minimální podlahová plocha
min
(a) Ceiling-mounted unit (=Jednotky k montáži na strop) (b) Wall-mounted unit (=Jednotky k montáži na stěnu)
FDXM25~60F3V1B(9)
Dělené klimatizační systémy
4P550955-1 – 2018.07
1 Všeobecná bezpečnostní opatření
(c) Floor-standing unit (=Podlahové jednotky)

1.2.3 Chladivo

Je-li použito. Další informace naleznete v instalační příručce nebo referenční příručce instalací pro vaši aplikaci.
POZNÁMKA
Ujistěte se, že potrubí rozvodu chladiva splňuje veškeré platné předpisy. V Evropě se toto řídí normou EN378.
POZNÁMKA
Ujistěte se, že potrubí na místě instalace a přípojky NEJSOU vystaveny namáhání.
VÝSTRAHA
Během zkoušek NIKDY netlakujte zařízení pomocí vyššího tlaku než je maximální přípustný tlak (viz typový štítek na jednotce).
VÝSTRAHA
Dávejte pozor na možné riziko požáru v případě úniku chladiva. Pokud dojde k úniku chladiva, ihned proveďte odvětrání místnosti. Možná rizika:
▪ Nadměrné koncentrace chladiva v ovzduší v uzavřené
místnosti může vést k nedostatku kyslíku.
▪ Pokud se chladivo dostane do styku s ohněm, může
vznikat jedovatý plyn.
NEBEZPEČÍ: RIZIKO VÝBUCHU Režim odčerpávání – únik chladiva. Chcete-li odčerpat
systém a došlo k úniku v chladicím okruhu:
▪ NEPOUŽÍVEJTE funkci automatického odčerpávání,
díky které můžete shromáždit veškeré chladivo ze systému ve venkovní jednotce. Možný dopad: Samozápal a výbuch kompresoru v důsledku pronikání vzduchu do pracujícího kompresoru.
▪ Použijte samostatný odsávání, aby NEMUSEL
pracovat kompresor jednotky.
VÝSTRAHA
VŽDY chladivo zachyťte. NEVYPOUŠTĚJTE je přímo do prostředí. Použijte podtlakové čerpadlo pro odsátí instalace.
POZNÁMKA
Po připojení veškerého potrubí se ujistěte, že nedochází k žádnému úniku plynu. Použijte dusík pro detekci úniku plynu.
POZNÁMKA
▪ Chcete-li se vyhnout poškození kompresoru,
NEDOPLŇUJTE do systému více chladiva, než je specifikované množství.
▪ Když chcete otevřít systém chladiva, MUSÍ být s
chladivem manipulováno podle platné legislativy.
VÝSTRAHA
Ujistěte se, že v systému není žádný kyslík. Chladivo může být plněno pouze po provedení zkoušky těsnosti a podtlakového sušení.
▪ V případě, že je doplnění chladiva zapotřebí, zkontrolujte typový
štítek jednotky. Je na něm uveden typ chladiva a potřebné množství náplně.
▪ Jednotka je z výroby naplněna chladivem a v závislosti na
rozměru a délce potrubí mohou některé systémy vyžadovat dodatečnou náplň chladiva.
▪ Používejte výhradně nástroje pro typ chladiva použitý v tomto
systému, aby se zajistila odolnost vůči tlaku a zabránilo se
vniknutí cizích látek do systému. ▪ Naplňte kapalné chladivo následujícím způsobem:
Jestliže… Pak…
Je přítomna přečerpávací (sifonová) hadice
(tj. láhev musí být označena “hadice pro plnění kapaliny připojena” nebo podobným textem).
NENÍ přítomna přečerpávací (sifonová) hadice
▪ Tlakové láhve s chladivem otevírejte pomalu. ▪ Chladivo doplňujte v kapalné formě. Jeho přidání v plynném stavu
může zabránit normálnímu provozu.
UPOZORNĚNÍ
Po skončeném doplnění chladiva nebo během přestávek ihned uzavřete ventil nádrže s chladivem. Pokud ventil NENÍ uzavřen ihned, zbývající tlak může naplnit další chladivo. Možný dopad: Nesprávné množství chladiva.
Plnění provádějte s lahví ve svislé poloze.
Plnění provádějte s lahví v obrácené poloze.

1.2.4 Solanka

Pokud je to vhodné. Další informace o vašem použití viz instalační návod nebo referenční příručka pro instalačního technika.
VÝSTRAHA
Výběr solanky MUSÍ být v souladu s příslušnými předpisy.
VÝSTRAHA
Zajistěte náležitá bezpečnostní opatření v případě úniku solanky. Jestliže dojde k úniku solanky, odvětrejte ihned celý prostor a kontaktujte svého místního prodejce.
VÝSTRAHA
Teplota okolí uvnitř jednotky může být mnohem vyšší než v pokoji, např. 70°C. V případě úniku solanky mohou horké součásti uvnitř jednotky vytvořit nebezpečnou situaci.
VÝSTRAHA
Použití a instalace MUSÍ splňovat bezpečnostní opatření a opatření na ochranu životního prostředí stanovená v příslušné legislativě.

1.2.5 Voda

Pokud je to vhodné. Další informace o vašem použití viz instalační návod nebo referenční příručka pro instalačního technika.
POZNÁMKA
Kvalita vody musí odpovídat směrnici EU 98/83 EC.
FDXM25~60F3V1B(9) Dělené klimatizační systémy 4P550955-1 – 2018.07
Referenční příručka k instalaci
5

2 O této dokumentaci

1.2.6 Elektrická instalace

NEBEZPEČÍ: RIZIKO ZABITÍ ELEKTRICKÝM PROUDEM
▪ Před sundáním krytu rozváděcí skříňky, před
prováděním jakéhokoliv připojení nebo před dotykem elektrických součástí vypněte přívod elektrické energie.
▪ Před prováděním servisu musí být přívod energie
vypnut delší dobu než 1 minutu a změřte napětí na svorkách kondenzátorů hlavního okruhu nebo elektrických součástech. Napětí MUSÍ být nižší než 50V(stejn.) než se budete moci dotknout elektrických součástí. Umístění svorek naleznete na schématu zapojení.
▪ NEDOTÝKEJTE se elektrických součástí mokrými
prsty.
▪ NENECHÁVEJTE jednotku bez dozoru, když je
demontovaný servisní kryt.
VÝSTRAHA
Pokud není instalace provedena z výrobního závodu, na pevném kabelovém vedení MUSÍ být nainstalován hlavní spínač nebo jiné prostředky pro odpojení, mající oddělené kontakty na všech pólech tak, aby to zajišťovalo odpojení při přepětí za stavu kategorieIII.
VÝSTRAHA
▪ Používejte POUZE měděné vodiče. ▪ Zajistěte, aby všechny velikosti vodičů byly v souladu s
platnou legislativou.
▪ Veškerá elektrická instalace MUSÍ být provedena v
souladu se schématem zapojení dodávaným s produktem.
▪ Dbejte na to, aby NEDOŠLO k sevření svázaných
kabelů a zajistěte, aby tyto kabely NEPŘICHÁZELY do styku s potrubím a s ostrými okraji. Zajistěte, aby na svorkovnici nepůsobily žádné vnější síly.
▪ Zajistěte instalaci zemnicího vodiče. Jednotku
NEUZEMŇUJTE k potrubí, bleskosvodu ani uzemnění telefonního vedení. Nedokonalé uzemnění může způsobit úraz elektrickým proudem.
▪ Použijte samostatný elektrický obvod. NIKDY
nepoužívejte elektrický obvod společný s jiným zařízením.
▪ Zajistěte instalaci všech požadovaných pojistek a
jističů.
▪ Zajistěte instalaci jističe svodového zemnícího proudu.
Zanedbání této zásady může způsobit úraz elektrickým proudem nebo požár.
▪ Při instalaci ochrany proti zemnímu spojení dbejte na
to, aby tato ochrana byla kompatibilní s invertorem (odolnému proti vysokofrekvenčnímu elektrickému šumu), aby nedocházelo ke zbytečnému rozpojování této ochrany.
POZNÁMKA
Bezpečnostní opatření při pokládce elektrického zapojení:
▪ NEPŘIPOJUJTE vodiče o různé tloušťce ke
svorkovnici napájení (průvěs vodičů napájení může způsobit abnormální zahřívání).
▪ Při zapojování vodičů o stejné tloušťce se řiďte
obrázkem nahoře.
▪ Pro zapojení použijte stanovený napájecí vodič a
pevně jej připojte, poté zajistěte, aby se zabránilo možnosti vlivu vnější síly na desku svorkovnice.
▪ Pro utažení šroubů svorkovnice použijte vhodný
šroubovák. Příliš malý šroubovák může poškodit hlavu šroubu a nebude možné jeho dostatečné utažení.
▪ Přetažení šroubů svorkovnice je může poškodit.
Z důvodů zamezení rušení obrazu dbejte na to, aby byl napájecí kabel veden ve vzdálenosti nejméně 1 m od televizních a rozhlasových přijímačů. Podle typu radiových vln nemusí být vzdálenost 1metr k eliminaci šumu dostatečná.
VÝSTRAHA
▪ Po dokončení elektrického zapojení se ujistěte, zda
jsou všechny elektrické součásti a svorky uvnitř elektrické rozvodné skříňky bezpečně zapojeny.
▪ Před spuštěním jednotky se ujistěte, že jsou uzavřeny
všechny kryty.
POZNÁMKA
Platí pouze v případě třífázového zdroje napájení a kompresor se spouští metodou ZAPNUTÍ/VYPNUTÍ.
Pokud existuje možnost záměny fází po krátkodobém výpadku proudu a napájení je vypnuto a opět zapnuto během provozu zařízení, připojte místní ochranný okruh proti záměně fází. Spuštění výrobku se zaměněnými fázemi může poškodit kompresor a další součásti.
2 O této dokumentaci

2.1 O tomto dokumentu

INFORMACE
Zkontrolujte, zda má uživatel tištěnou dokumentaci a požádejte jej, aby si ji ponechal pro budoucí potřebu.
Určeno pro:
Autorizovaní instalační technici
INFORMACE
Tento spotřebič je určen k použití odborníky nebo školenými uživateli v obchodech, v lehkém průmyslu a na farmách, nebo pro komerční a domácí použití určenými osobami.
Referenční příručka k instalaci
6
Soubor dokumentace
Tento dokument je součástí souboru dokumentace. Kompletní soubor se skládá z následujících částí:
FDXM25~60F3V1B(9)
Dělené klimatizační systémy
4P550955-1 – 2018.07