Daikin FDXM25F3V1B, FDXM35F3V1B, FDXM50F3V1B, FDXM60F3V1B, FDXM25F3V1B9 Installer reference guide [ro]

...
Ghidul de referinţă al
instalatorului
Instalații de aer condiționat în sistem split
FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B
FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V1B9
Ghidul de referinţă al instalatorului
Instalații de aer condiționat în sistem split
romană
Cuprins

1 Măsuri de siguranţă generale 2

1.1 Despre documentaţie ................................................................ 2
1.1.1 Explicaţia avertizărilor şi simbolurilor.......................... 2
1.2 Pentru instalator ........................................................................ 3
1.2.1 Date generale ............................................................. 3
1.2.2 Locul instalării ............................................................. 3
1.2.3 Agent frigorific............................................................. 5
1.2.4 Apa sărată................................................................... 5
1.2.5 Apă.............................................................................. 5
1.2.6 Electric ........................................................................ 6
2 Despre documentaţie 6
2.1 Despre acest document ............................................................ 6
2.2 Ghidul rapid de referinţă al instalatorului................................... 7
3 Despre cutie 7
3.1 Prezentare generală: despre cutie ............................................ 7
3.2 Unitatea interioara ..................................................................... 7
3.2.1 Pentru a despacheta și manipula unitatea.................. 7
3.2.2 Pentru a scoate accesoriile din unitatea interioară ..... 7
4 Despre unităţi şi opţiuni 7
4.1 Prezentare generală: despre unităţi şi opţiuni ........................... 7
4.2 Configurația sistemului .............................................................. 8
4.3 Combinarea unităților și opțiuni ................................................. 8
4.3.1 Opţiuni posibile pentru unitatea interioară .................. 8
5 Pregătirea 8
5.1 Prezentare generală: pregătirea................................................ 8
5.2 Pregătirea locului de instalare ................................................... 8
5.2.1 Cerinţele locului de instalare pentru unitatea
interioară..................................................................... 8
5.3 Pregătirea tubulaturii agentului frigorific .................................... 9
5.3.1 Cerințele tubulaturii de agent frigorific ........................ 9
5.3.2 Izolarea tubulaturii de agent frigorific.......................... 9
5.4 Pregătirea cablajului electric ..................................................... 9
5.4.1 Despre pregătirea cablajului electric........................... 9
6 Instalarea 10
6.1 Prezentare generală: instalarea ................................................ 10
6.2 Montarea unităţii interioare........................................................ 10
6.2.1 Precauţii la montarea unităţii interioare....................... 10
6.2.2 Instrucţiuni pentru instalarea unității interioare ........... 10
6.2.3 Instrucţiuni la instalarea tubulaturii.............................. 11
6.2.4 Instrucţiuni pentru instalarea tubulaturii de evacuare . 12
6.3 Conectarea tubulaturii agentului frigorific .................................. 12
6.3.1 Despre racordarea tubulaturii de agent frigorific......... 12
6.3.2 Măsuri de precauţie la racordarea tubulaturii de
agent frigorific ............................................................. 13
6.3.3 Indicații la racordarea tubulaturii de agent frigorific .... 13
6.3.4 Indicaţii privind îndoirea ţevilor.................................... 13
6.3.5 Pentru a evaza capătul ţevii........................................ 13
6.3.6 Pentru a conecta tubulatura agentului frigorific la
unitatea interioară ....................................................... 14
6.3.7 Pentru a verifica existenţa scurgerilor......................... 14
6.4 Conectarea cablajului electric ................................................... 14
6.4.1 Despre conectarea cablajului electric ......................... 14
6.4.2 Precauţii la conectarea cablajului electric................... 14
6.4.3 Indicaţii pentru conectarea cablajului electric ............. 15
6.4.4 Pentru a conecta cablajul electric la unitatea
interioară..................................................................... 15
6.4.5 Specificaţii pentru componentele cablajului standard. 15
7 Configurare 16
7.1 Reglaje locale............................................................................ 16
8.1 Listă de verificare înaintea dării în exploatare............................ 16
8.2 Efectuarea probei de funcţionare ............................................... 16
8.3 Codurile de eroare în timpul efectuării probei de funcţionare..... 17
9 Predarea către utilizator 17 10 Dezafectarea 17 11 Date tehnice 17
11.1 Schema de conexiuni ................................................................. 18
12 Glosar 18
1 Măsuri de siguranţă generale

1.1 Despre documentaţie

▪ Documentaţia originală este scrisă în limba engleză. Toate
celelalte limbi reprezintă traduceri.
▪ Precauţiile descrise în acest document acoperă subiecte foarte
importante, respectaţi-le cu atenţie.
▪ Instalarea sistemului, și toate activitățile descrise în manualul de
instalare și ghidul de referință de instalare trebuie efectuate de către un instalator autorizat.

1.1.1 Explicaţia avertizărilor şi simbolurilor

PERICOL
Indică o situaţie care duce la deces sau rănire gravă.
PERICOL: RISC DE ELECTROCUTARE
Indică o situaţie care poate duce la electrocutare.
PERICOL: RISC DE ARSURI
Indică o situaţie care poate duce la arsuri din cauza temperaturilor extrem de scăzute sau de ridicate.
PERICOL: RISC DE EXPLOZIE
Indică o situaţie care poate duce la explozie.
AVERTIZARE
Indică o situaţie care poate duce la deces sau rănire gravă.
AVERTIZARE: MATERIAL INFLAMABIL
PRECAUŢIE
Indică o situaţie care poate duce la rănirea minoră sau mai puţin gravă.
NOTIFICARE
Indică o situaţie care poate duce la distrugerea echipamentului sau bunurilor.
INFORMAŢII
Indică sfaturi utile sau informaţii suplimentare.
Simbol Explicaţie
Înainte de instalare, citiți manualul de instalare şi exploatare, și foaia cu instrucţiuni pentru cablaj.
Înainte de efectuarea lucrărilor de întreţinere şi service, citiți manualul de service.
Pentru informații suplimentare, consultați ghidul de referinţă pentru instalator și utilizator.
8 Darea în exploatare 16
Ghidul de referinţă al instalatorului
2
Instalații de aer condiționat în sistem split
FDXM25~60F3V1B(9)
4P550955-1 – 2018.07
1 Măsuri de siguranţă generale

1.2 Pentru instalator

1.2.1 Date generale

Dacă NU sunteți sigur cum să instalaţi sau să exploataţi unitatea, contactaţi distribuitorul.
NOTIFICARE
Instalarea sau conectarea necorespunzătoare a echipamentului sau accesoriilor poate cauza electrocutare, scurtcircuit, scăpări, incendiu sau alte deteriorări ale echipamentului. Utilizaţi numai accesorii, echipament opţional şi piese de rezervă fabricate sau aprobate de Daikin.
AVERTIZARE
Asiguraţi-vă că instalarea, testarea şi materialele utilizate sunt conforme legislaţiei în vigoare (pe lângă instrucţiunile descrise în documentaţia Daikin).
PRECAUŢIE
Purtaţi echipamentul adecvat de protecţie personală (mănuşi de protecţie, ochelari de protecţie etc.) la instalarea, întreţinerea sau deservirea sistemului.
AVERTIZARE
Îndepărtaţi pungile de plastic ale ambalajului ca să nu ajungă la îndemâna altor persoane, în special a copiilor. Riscul posibil: sufocarea.
PERICOL: RISC DE ARSURI
▪ NU atingeţi tubulatura agentului frigorific, a apei sau
componentele interne în timpul funcţionării şi imediat după aceea. Aceasta poate fi foarte fierbinte sau foarte rece. Lăsaţi-o să revină la temperatura normală. Dacă trebuie să o atingeţi, purtaţi mănuşi de protecţie.
▪ NU atingeţi niciodată agentul frigorific scurs accidental.
AVERTIZARE
Luaţi măsurile necesare pentru a împiedica animalele de talie mică să se adăpostească în unitate. Animalele de talie mică care ating piesele electrice pot cauza defecţiuni, fum sau incendiu.
PRECAUŢIE
NU atingeţi priza de aer sau aripioarele din aluminiu ale unităţii.
NOTIFICARE
▪ NU puneţi niciun obiect sau echipament pe unitate. ▪ NU vă urcaţi, nu vă aşezaţi şi nu staţi pe unitate.
NOTIFICARE
Se recomandă executarea lucrărilor la unitatea exterioară când atmosfera este uscată, pentru a evita infiltraţiile.
În conformitate cu legislația în vigoare, poate fi necesară asigurarea unui registru jurnal cu produsul, conținând cel puțin: informaţii privind întreţinerea, lucrările de reparaţii, rezultatele testelor, perioadele de așteptare,…
De asemenea, TREBUIE furnizate cel puțin următoarele informații într-un loc accesibil la produs:
▪ Instrucțiuni pentru oprirea sistemului în caz de urgență ▪ Numele și adresa pompierilor, poliției și spitalului ▪ Numele, adresa și numerele de telefon de zi și de noapte pentru
service
În Europa, EN378 furnizează îndrumările necesare pentru acest registru jurnal.

1.2.2 Locul instalării

▪ Lăsaţi spaţiu suficient în jurul unităţii pentru a permite deservirea
şi circulaţia aerului.
▪ Asiguraţi-vă că locul instalării face faţă greutăţii unităţii şi
vibraţiilor.
▪ Asiguraţi-vă că zona este bine ventilată. NU blocați orificiile de
ventilație.
▪ Asiguraţi-vă că unitatea se află pe loc drept.
NU instalaţi unitatea în următoarele locuri: ▪ În medii cu pericol de explozie. ▪ În locuri unde există instalaţii care emit unde electromagnetice.
Undele electromagnetice pot perturba sistemul de comandă, cauzând defectarea echipamentului.
▪ În locurile în care există riscul incendiilor din cauza scurgerilor
gazelor inflamabile (de exemplu: diluant sau benzină), fibre de carbon sau pulberi inflamabile.
▪ În locuri în care se produce gaz exploziv (de exemplu: gaz de acid
sulfuric). Corodarea conductelor de cupru sau a pieselor lipite poate cauza scăpări de agent frigorific.
Instrucțiuni pentru echipamentele care utilizează agent frigorific R32
Dacă este cazul.
AVERTIZARE
▪ NU perforați și nu aruncați în foc. ▪ NU folosiți mijloace de accelerare a procesului de
dezghețare sau pentru curățare, altele decât cele recomandate de fabricant.
▪ Rețineți că agentul frigorific R32 NU conține odorizant.
AVERTIZARE
Aparatul va fi păstrat astfel încât să se prevină deteriorarea mecanică, și într-o încăpere bine ventilată fără surse de aprindere cu funcționare continuă (de ex.: flacără deschisă, un aparat cu gaz în funcțiune sau un încălzitor electric în funcțiune), și având dimensiunea încăperii conform celor de mai jos.
NOTIFICARE
▪ NU reutilizaţi racordurile care au fost deja utilizate. ▪ Racordurile efectuate în instalație între piesele
sistemului de agent frigorific trebuie să fie accesibile în scopuri de întreținere.
AVERTIZARE
Asigurați-vă că instalarea, service+ul, întreținerea și reparațiile sunt conforme instrucțiunilor din Daikin precum și legislației în vigoare (de exemplu, reglementările naționale privind gazele) și sunt executate numai de persoane autorizate.
Cerințele spațiului de instalare
NOTIFICARE
▪ Tubulatura trebuie protejată față de deteriorarea fizică. ▪ Instalația de tubulatură trebuie menținută la minim.
FDXM25~60F3V1B(9) Instalații de aer condiționat în sistem split 4P550955-1 – 2018.07
Ghidul de referinţă al instalatorului
3
1 Măsuri de siguranţă generale
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
AVERTIZARE
Dacă aparatele conțin agent frigorific R32, atunci suprafața podelei încăperii în care sunt instalate, exploatate și păstrate, TREBUIE să fie mai mare decât suprafața minimă a podelei definită în tabelul de mai jos A (m2). Aceasta se aplică la:
▪ Unități interioare fără senzor de scurgere a agentului
frigorific; în cazul unităților interioare cu senzor de scurgere a agentului de răcire, consultați manualul de instalare
▪ Unități exterioare instalate sau păstrate în interior (de
ex., grădina de iarnă, garaj, sala de mașini)
▪ Tubulatura în spațiile neventilate
Pentru a determina suprafața minimă a podelei
1 Determinați încărcătura totală de agent frigorific din sistem
(= încărcătura de agent frigorific din fabrică + cantitatea suplimentară de agent frigorific încărcat).
2 Determinați graficul sau tabelul care se utilizează.
▪ Pentru unităţile interioare: Unitatea este montată pe tavan,
montată pe perete sau instalată pe podea?
▪ Pentru unitățile exterioare instalate sau păstrate în interior, și
tubulatura de legătură în spații neventilate, acest lucru depinde de înălțimea de instalare:
Dacă înălțimea de instalare este…
Atunci utilizați graficul sau tabelul pentru…
<1,8m Unități instalate pe podea 1,8≤x<2,2m Unităţi montate pe perete ≥2,2m Unităţi montate pe tavan
3 Utilizați graficul sau tabelul pentru a determina suprafața
minimă a podelei.
Ghidul de referinţă al instalatorului
4
m Încărcătura totală de agent frigorific în sistem
A
Suprafața minimă a podelei
min
(a) Ceiling-mounted unit (= unitate montată pe tavan) (b) Wall-mounted unit (= unitate montată pe perete)
FDXM25~60F3V1B(9)
Instalații de aer condiționat în sistem split
4P550955-1 – 2018.07
1 Măsuri de siguranţă generale
(c) Floor-standing unit (= unitate instalată pe podea)

1.2.3 Agent frigorific

Dacă este cazul. Consultaţi manualul de instalare sau ghidul de referinţă al instalatorului pentru aplicaţia dvs. pentru detalii suplimentare.
NOTIFICARE
Asiguraţi-vă că instalarea conductelor agentului frigorific respectă legislaţia în vigoare. În Europa, standardul în vigoare este EN378.
NOTIFICARE
Aveți grijă ca tubulatura de legătură și racordurile să NU fie tensionate.
AVERTIZARE
În timpul probelor, NU presurizaţi produsul cu o presiune mai mare decât cea maximă admisă (conform indicaţiilor de pe placa de identificare a unităţii).
AVERTIZARE
Luaţi măsuri suficiente în cazul scurgerilor agentului frigorific. Dacă există scurgeri ale agentului de răcire gazos, ventilaţi imediat zona. Riscuri posibile:
▪ Concentraţiile în exces de agent frigorific în încăperi
închise pot duce la lipsa oxigenului.
▪ Se poate produce gaz toxic dacă agentul frigorific
gazos intră în contact cu focul.
PERICOL: RISC DE EXPLOZIE Evacuare – scurgere de agent frigorific. Dacă doriți să
evacuați, și există o scurgere în circuitul agentului frigorific:
▪ NU utilizați funcţia automată de evacuare a unității, cu
care puteți colecta tot agentul frigorific din sistem în unitatea exterioară. Consecinţă posibilă: Autocombustie și explozie a compresorului din cauza aerului care pătrunde în compresorul aflat în funcțiune.
▪ Utilizați un sistem separat de recuperare, astfel încât
compresorul unității să nu trebuiască să funcționeze.
AVERTIZARE
Recuperaţi ÎNTOTDEAUNA agentul frigorific. NU eliberaţi agentul frigorific direct în atmosferă. Folosiţi o pompă de vid pentru a evacua instalaţia.
NOTIFICARE
După conectarea întregii tubulaturi, asiguraţi-vă că nu există scurgeri de gaz. Utilizaţi azot pentru a efectua detectarea scurgerii de gaz.
NOTIFICARE
▪ Pentru a evita defectarea compresorului, NU încărcați
mai mult decât cantitatea specificată de agent frigorific.
▪ Când sistemul de agent frigorific urmează să fie
deschis, agentul frigorific trebuie tratat în conformitate cu legislaţia aplicabilă.
AVERTIZARE
Asiguraţi-vă că nu există oxigen în sistem. Agentul frigorific se poate încărca numai după efectuarea testului de scurgere şi a uscării vidate.
▪ În cazul în care este necesară reîncărcarea, consultaţi placa de
identificare a unităţii. Specifică tipul de agent frigorific şi cantitatea necesară.
▪ Unitatea este încărcată cu agent frigorific din fabrică; în funcţie de
dimensiunile şi lungimile conductelor, unele sisteme pot necesita încărcarea suplimentară cu agent frigorific.
▪ Utilizaţi numai scule exclusiv pentru tipul de agent frigorific utilizat
în acest sistem pentru a asigura rezistenţa necesară faţă de presiune şi pentru a împiedica pătrunderea materialelor străine în sistem.
▪ Încărcați agentul frigorific lichid după cum urmează:
Dacă Atunci
Există tub de sifon (respectiv, butelia este marcată
cu „Sifon atașat pentru umplerea cu lichid”)
NU există tub de sifon Încărcați cu butelia răsturnată.
▪ Deschideți încet buteliile cu agent frigorific. ▪ Încărcați agentul frigorific sub formă lichidă. Adăugarea sub formă
de gaz poate împiedica funcţionarea normală.
PRECAUŢIE
Când procedura de încărcare a agentului frigorific s-a terminat sau când este întrerupt, închideţi imediat ventilul rezervorului de agent frigorific. Dacă ventilul NU este închis imediat, presiunea rămasă ar putea încărca agent frigorific suplimentar. Consecinţă posibilă: Cantitate incorectă de agent frigorific.
Încărcați cu butelia verticală.

1.2.4 Apa sărată

Dacă este cazul. Consultaţi manualul de instalare sau ghidul de referinţă al instalatorului pentru aplicaţia dvs. pentru detalii suplimentare.
AVERTIZARE
Alegerea apei sărate TREBUIE să fie în conformitate cu legislaţia în vigoare.
AVERTIZARE
Luaţi măsuri suficiente în cazul scurgerii apei sărate. Dacă se scurge apă sărată, ventilaţi imediat zona şi contactaţi reprezentantul local.
AVERTIZARE
Temperatura ambiantă din interiorul unităţii poate fi mai ridicată decât cea din încăpere, de ex. 70°C. În cazul unei scurgeri a apei sărate, componentele fierbinţi din unitate pot duce la o situaţie periculoasă.
AVERTIZARE
Utilizarea şi instalarea aplicaţiei TREBUIE să fie conforme cu precauţiile privind siguranţa şi mediul înconjurător specificate în legislaţia în vigoare.

1.2.5 Apă

Dacă este cazul. Consultaţi manualul de instalare sau ghidul de referinţă al instalatorului pentru aplicaţia dvs. pentru detalii suplimentare.
FDXM25~60F3V1B(9) Instalații de aer condiționat în sistem split 4P550955-1 – 2018.07
Ghidul de referinţă al instalatorului
5

2 Despre documentaţie

NOTIFICARE
Asiguraţi-vă că apa are o calitate conformă cu Directiva UE 98/83CE.

1.2.6 Electric

PERICOL: RISC DE ELECTROCUTARE
▪ OPRIŢI toate sursele de alimentare înainte de a scoate
capacul cutiei de distribuţie, conecta cablurile electrice sau atinge piesele electrice.
▪ Deconectaţi reţeaua mai mult de 1 minut şi măsuraţi
tensiunea la borne a condensatoarelor circuitului principal sau a componentelor electrice înainte de deservire. Tensiunea TREBUIE să fie mai mică de 50 V c.c. înainte de a putea atinge componentele electrice. Pentru amplasarea bornelor, consultaţi
schema de conexiuni. ▪ NU atingeţi componentele electrice cu mâinile ude. ▪ NU lăsaţi unitatea nesupravegheată când este scos
capacul de deservire.
AVERTIZARE
Dacă NU este instalat din fabrică, pe cablajul fix TREBUIE instalat un întrerupător principal sau alte mijloace de deconectare, cu separarea contactelor la toţi polii, asigurând astfel deconectarea completă la supratensiune de categoria aIII-a.
AVERTIZARE
▪ Utilizaţi NUMAI cabluri din cupru. ▪ Asigurați conformitatea cablajului de legătură cu
legislația în vigoare. ▪ Întregul cablaj de legătură trebuie executat în
conformitate cu schema de conexiuni furnizată cu
produsul. ▪ Nu strângeţi NICIODATĂ mănunchiurile de cabluri şi
aveţi grijă ca acestea să NU vină în contact cu
tubulatura şi cu muchiile ascuţite. Asiguraţi-vă că pe
conexiunile de pe borne nu se aplică o presiune
externă. ▪ Asiguraţi-vă că instalaţi cablul de împământare. NU
conectaţi împământarea unităţii la o conductă de
utilităţi, la un circuit absorbant de impulsuri sau la o
linie de împământare telefonică. Legarea incompletă la
pământ poate cauza electrocutare. ▪ Aveţi grijă să folosiţi un circuit electric de alimentare
special alocat. Nu folosiţi NICIODATĂ o sursă de
alimentare în comun cu un alt aparat. ▪ Aveți grijă să instalați siguranţele sau disjunctoarele
necesare. ▪ Aveți grijă să instalați un protector pentru scurgeri la
pământ. Nerespectarea celor de mai sus poate duce la
electrocutare sau incendiu. ▪ Când instalaţi siguranţa pentru scurgerea la pământ
aveţi grijă să fie compatibil cu invertorul (rezistent la
zgomot electric de înaltă frecvenţă) pentru a evita
deschiderea inutilă a protectorului pentru scurgerea la
pământ.
NOTIFICARE
Precauţii la pozarea cablajului alimentării de la reţea:
▪ Nu conectaţi cablaje de diferite secțiuni la regleta de
conexiuni a alimentării (slăbirea cablajului de alimentare poate cauza încălziri anormale).
▪ Când conectaţi cabluri de aceeaşi grosime, procedaţi
aşa cum este prezentat în figura de mai sus.
▪ Pentru cablare, utilizaţi cablul de alimentare indicat şi
conectaţi strâns, apoi fixaţi pentru a preveni exercitarea unei presiuni exterioare asupra plăcii de borne.
▪ Utilizaţi o şurubelniţă corespunzătoare pentru
strângerea şuruburilor bornelor. O şurubelniţă cu cap mic va deforma capul, făcând imposibilă strângerea corespunzătoare.
▪ Strângerea exagerată a şuruburilor bornelor le poate
rupe.
Instalaţi cablurile de alimentare la cel puţin 1metru de televizoare sau aparate radio pentru a preveni interferenţa. În funcţie de undele radio, distanţa de 1metru poate să nu fie suficientă.
AVERTIZARE
▪ După finalizarea lucrărilor electrice, confirmaţi că
fiecare componentă şi bornă electrică din interiorul cutiei de componente electrice este bine conectată.
▪ Asiguraţi-vă că sunt închise toate capacele înainte de a
porni unitatea.
NOTIFICARE
Valabil numai dacă alimentarea electrică este trifazată şi compresorul are o metodă de pornire de tip PORNIRE/ OPRIRE.
Dacă există posibilitatea fazelor inversate după o întrerupere de moment a alimentării în timpul funcţionării produsului, montaţi pe plan local un circuit de protecţie la inversarea fazelor. Funcţionarea produsului cu faze inversate poate duce la defectarea compresorului şi a altor componente.
2 Despre documentaţie

2.1 Despre acest document

INFORMAŢII
Asiguraţi-vă că utilizatorul are documentaţia tipărită şi rugaţi-l să o păstreze pentru consultare ulterioară.
Public ţintă
Instalatori autorizaţi
INFORMAŢII
Acest aparat este destinat utilizării de către utilizatori instruiţi sau experţi în magazine, în industria uşoară sau în ferme sau utilizării în scop comercial sau privat de către persoane nespecializate.
Ghidul de referinţă al instalatorului
6
Set documentaţie
Acest document face parte din setul documentaţiei. Setul complet este format din:
FDXM25~60F3V1B(9)
Instalații de aer condiționat în sistem split
4P550955-1 – 2018.07
Loading...
+ 14 hidden pages