Daikin FDXM25F3V1B, FDXM35F3V1B, FDXM50F3V1B, FDXM60F3V1B, FDXM25F3V1B9 Installer reference guide [tr]

...
Montör başvuru kılavuzu
Split sistem klimalar
FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B
FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V1B9
Montör başvuru kılavuzu
Split sistem klimalar
Türkçe

İçindekiler

İçindekiler

1 Genel güvenlik önlemleri 2

1.1 Dokümanlar hakkında ............................................................... 2
1.1.1 Uyarı ve simgelerin anlamları ..................................... 2
1.2 Montör için................................................................................. 3
1.2.1 Genel .......................................................................... 3
1.2.2 Montaj sahası.............................................................. 3
1.2.3 Soğutucu akışkan ....................................................... 5
1.2.4 Tuzlu Su...................................................................... 5
1.2.5 Su................................................................................ 5
1.2.6 Elektrik ........................................................................ 6
2 Dokümanlar hakkında 6
2.1 Bu doküman hakkında............................................................... 6
2.2 Bir bakışta montör başvuru kılavuzu ......................................... 7
3 Kutu hakkında 7
3.1 Genel bilgi: Kutu hakkında ........................................................ 7
3.2 İç ünite....................................................................................... 7
3.2.1 Üniteyi ambalajından çıkarmak ve taşımak için.......... 7
3.2.2 İç üniteden aksesuarları çıkarmak için........................ 7
4 Üniteler ve seçenekler hakkında 7
4.1 Genel bilgi: Üniteler ve seçenekler hakkında ............................ 7
4.2 Sistem montaj planı................................................................... 8
4.3 Ünite kombinasyonları ve seçenekleri....................................... 8
4.3.1 İç ünite için olası seçenekler....................................... 8
5 Hazırlık 8
5.1 Genel bilgi: Hazırlık ................................................................... 8
5.2 Montaj sahasının hazırlanması ................................................. 8
5.2.1 İç ünite montaj sahası gereksinimleri.......................... 8
5.3 Soğutucu akışkan borularının hazırlanması .............................. 9
5.3.1 Soğutucu boru gereksinimleri ..................................... 9
5.3.2 Soğutucu akışkan borularının yalıtımı......................... 9
5.4 Elektrik kablolarının hazırlanması ............................................. 9
5.4.1 Elektrik kablolarının hazırlanması hakkında ............... 9
6 Montaj 10
6.1 Genel bilgi: Montaj..................................................................... 10
6.2 İç ünitenin montajı ..................................................................... 10
6.2.1 İç ünitenin monte edilmesi sırasında alınması
gereken önlemler ........................................................ 10
6.2.2 İç ünitenin montajı sırasında uyulacak esaslar ........... 10
6.2.3 Kanal montajı sırasında uyulacak esaslar .................. 11
6.2.4 Drenaj borusu montajı sırasında uyulacak esaslar..... 11
6.3 Soğutucu akışkan borularının bağlanması ................................ 12
6.3.1 Soğutucu borularının bağlanması hakkında ............... 12
6.3.2 Soğutucu borularının bağlantısı yapılırken dikkat
edilecekler................................................................... 12
6.3.3 Soğutucu borularının bağlantısı yapılırken dikkat
edilecekler................................................................... 13
6.3.4 Boru dirsek talimatları ................................................. 13
6.3.5 Boru ucunun konik kesilmesi için................................ 13
6.3.6 Soğutucu akışkan borularını iç üniteye bağlamak için 14
6.3.7 Kaçak kontrolü için...................................................... 14
6.4 Elektrik kablolarının bağlanması ............................................... 14
6.4.1 Elektrik kablolarının bağlanması hakkında ................. 14
6.4.2 Elektrik kablo bağlantıları yapılırken dikkat
edilecekler................................................................... 14
6.4.3 Elektrik kabloları bağlanırken dikkat edilmesi
gerekenler ................................................................... 14
6.4.4 İç ünite üzerine elektrik kablolarını bağlamak için....... 15
6.4.5 Standart kablo bileşenlerinin özellikleri....................... 15
7 Yapılandırma 15
7.1 Saha ayarları ............................................................................. 15
8 Devreye Alma 16
8.1 İşletmeye alma öncesi kontrol listesi .......................................... 16
8.2 Bir test çalıştırması gerçekleştirmek için .................................... 16
8.3 Test çalıştırması yaparken hata kodları ..................................... 17
9 Kullanıcıya teslim 17 10 Bertaraf 17 11 Teknik veriler 17
11.1 Kablo şeması.............................................................................. 18
12 Sözlük 18
1 Genel güvenlik önlemleri

1.1 Dokümanlar hakkında

▪ Orijinal doküman İngilizce dilinde yazılmıştır. Diğer dillere orijinal
dilinden çevrilmiştir.
▪ Bu dokümanda açıklanan önlemler, çok önemli hususları
kapsamaktadır, bu nedenle dikkatli şekilde uygulanmalıdır.
▪ Montaj kılavuzu ile montajcı referans kılavuzunda açıklanan
sistem montajı ve tüm faaliyetler yetkili bir montajcı tarafından yerine GETİRİLMELİDİR.

1.1.1 Uyarı ve simgelerin anlamları

TEHLİKE
Ölüm veya ciddi yaralanmalarla sonuçlanacak durumları gösterir.
TEHLİKE: ELEKTRİK ÇARPMASI RİSKİ
Elektrik çarpmasına yol açabilecek durumları gösterir.
TEHLİKE: YANMA RİSKİ
Aşırı yüksek veya aşırı düşük sıcaklıklar nedeniyle yanıklara neden olabilecek durumları gösterir.
TEHLİKE: PATLAMA RİSKİ
Patlamaya yol açabilecek durumları gösterir.
UYARI
Ölüm veya ciddi yaralanmalarla sonuçlanabilecek durumları gösterir.
UYARI: YANICI MADDE
DİKKAT
Küçük veya orta ciddiyette yaralanmalarla sonuçlanabilecek durumları gösterir.
BİLDİRİM
Cihaz hasarları veya maddi hasarla sonuçlanabilecek durumları gösterir.
BİLGİ
Yararlı ipuçlarını veya ilave bilgileri gösterir.
Sembol Açıklama
Montajdan önce, montaj ve kullanım kılavuzu ile kablo bağlantısı talimat yaprağını okuyun.
Bakım ve servis görevlerini yerine getirmeden önce, servis kılavuzunu okuyun.
Daha fazla bilgi için montajcı ve kullanıcı referans kılavuzuna bakın.
2
FDXM25~60F3V1B(9)
Split sistem klimalar
4P550955-1 – 2018.07
1 Genel güvenlik önlemleri

1.2 Montör için

1.2.1 Genel

Ünitenin nasıl monte edilmesi ve çalıştırılması gerektiği konusunda emin DEĞİLSENİZ, satıcınıza danışın.
BİLDİRİM
Cihazların veya aksesuarların hatalı montajı veya bağlanması elektrik çarpmasına, kısa devreye, sızıntılara, yangına veya diğer cihaz hasarlarına neden olabilir. Yalnızca Daikin tarafından üretilen veya onaylanan aksesuarları, opsiyonel cihazları ve yedek parçaları kullanın.
UYARI
Montaj, test ve uygulama malzemelerinin (Daikin kılavuzlarında açıklanan talimatlardan öncelikli olarak) ilgili mevzuata uygun olduğundan emin olun.
DİKKAT
Sistemle ilgili montaj, bakım veya servis çalışmaları gerçekleştirirken uygun kişisel koruyucu malzeme ve ekipmanları (koruyucu eldivenler, koruyucu gözlükler,…) kullanın.
UYARI
Özellikle çocukların oynamasını engellemek için, ambalajdan çıkan naylon torbaları parçalayarak çöpe atın. Olası risk: boğulma.
TEHLİKE: YANMA RİSKİ
▪ Çalışma sırasında veya çalışmadan hemen sonra
soğutucu akışkan borularına, su borularına ve dahili parçalara KESİNLİKLE dokunmayın. Bu parçalar çok sıcak veya çok soğuk olabilir. Normal oda sıcaklığına dönmesi için bekleyin. Mutlaka dokunmanız gerekiyorsa, koruyucu eldiven takın.
▪ Sızan soğutucu akışkana KESİNLİKLE dokunmayın.
UYARI
Ünitenin küçük hayvanlar tarafından bir sığınak olarak kullanılmasını önlemek için gerekli önlemleri alın. Küçük hayvanların elektrikli parçalara temas etmesi arızalara, dumana veya yangına yol açabilir.
DİKKAT
Ünitenin hava girişine veya alüminyum kanatlarına KESİNLİKLE dokunmayın.
BİLDİRİM
▪ Ünitenin üzerine KESİNLİKLE herhangi bir cisim veya
cihaz koymayın.
▪ Ünitenin üzerine KESİNLİKLE çıkmayın, oturmayın ve
basmayın.
BİLDİRİM
Su girişinin önlenmesi için, dış ünitedeki çalışmaların kuru hava koşullarında gerçekleştirilmesi daha uygundur.
İlgili mevzuat uyarınca en azından bakım, onarım çalışmaları, test sonuçları, bekleme süreleri, … hakkında bilgiler içeren bir kayıt defterinin ürünle birlikte tutulması gerekli olabilir.
Ayrıca, en azından aşağıda sıralanan bilgiler mutlaka ürünün kolayca erişilebilen bir yerinde TUTULMALIDIR:
▪ Acil bir durumda sistemin kapatılması için gerekli talimatlar
▪ En yakın itfaiyenin, polisin ve hastanenin isim ve adresleri
▪ İlgili servisin adı, adresi ve gündüz ve gece ulaşılabilecek telefon
numaraları
Avrupa için, bu kayıt defteriyle ilgili hususlar EN378 standardında belirtilmiştir.

1.2.2 Montaj sahası

▪ Ünite etrafında servis ve hava sirkülasyonu için yeterli boşluk
bırakın.
▪ Montaj sahasının ünitenin ağırlığına ve titreşimlerine
dayanabileceğinden emin olun.
▪ Alanın iyi havalandırıldığından emin olun. Havalandırma deliklerini
engellemeyin.
▪ Ünitenin düz durduğundan emin olun.
Üniteyi KESİNLİKLE aşağıda belirtilen yerlere monte etmeyin:
▪ Potansiyel olarak patlayıcı ortamlar.
▪ Elektromanyetik dalgalar yayan makinelerin bulunduğu ortamlar.
Elektromanyetik dalgalar, kontrol sistemine zarar verebilir ve cihazın arızalanmasına yol açabilir.
▪ Tutuşabilir gaz (örneğin; tiner veya gazolin) kaçakları, karbon
fiberi, tutuşabilir tozlar nedeniyle yangın riski bulunan ortamlar.
▪ Korozif gazların (örnek: sülfürik asit gazı) bulunduğu ortamlar.
Bakır boruların veya lehimlenmiş parçaların korozyonu soğutucu akışkan kaçaklarına neden olabilir.
R32 soğutucu kullanan ekipmanlar için talimatlar
Uygunsa.
UYARI
▪ DELMEYİN veya YAKMAYIN.
▪ Buz çözme işlemini hızlandırmak veya ekipmanı
temizlemek için üretici tarafından önerilenler dışında yöntemler KULLANMAYIN.
▪ R32 soğutucunun KOKUSUZ olduğuna dikkat edin.
UYARI
Cihaz mekanik hasarlara maruz kalmayacak şekilde ve sürekli çalışan ateşleme kaynaklarının (örnek: açık alevler, çalışan bir gazlı gereç veya çalışan bir elektrikli ısıtıcı) bulunmadığı iyi havalandırılan bir odada saklanmalı ve oda büyüklüğü aşağıda belirtildiği gibi olmalıdır.
BİLDİRİM
▪ Daha önce kullanılmış olan bağlantıları tekrar
KULLANMAYIN.
▪ Montajda soğutucu sisteminin kısımları arasında
yapılan bağlantılar bakım amacıyla erişilebilir olmalıdır.
UYARI
Montaj, servis, bakım ve onarım işlemlerinin Daikin talimatlarına ve ilgili mevzuata (örneğin ulusal gaz yönetmeliği) uyduğundan ve sadece yetkili kıişiler tarafından yapıldığından emin olun.
Montaj alanı gereksinimleri
BİLDİRİM
▪ Boru tesisatı fiziksel hasarlardan korunacaktır.
▪ Boru tesisatı asgari düzeyde tutulacaktır.
FDXM25~60F3V1B(9) Split sistem klimalar 4P550955-1 – 2018.07
3
1 Genel güvenlik önlemleri
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
UYARI
Cihazlar R32 soğutucu içeriyorsa, cihazların içinde monte edildiği, çalıştırıldığı ve depolandığı odanın zemin alanı aşağıdaki tabloda tanımlanan minimum zemin alanı A'dan (m2) büyük OLMALIDIR. Bu durum şunlara uygulanır:
▪ Soğutucu kaçak sensörü olmayan iç üniteler; soğutucu
kaçak sensörü bulunan iç üniteler için montaj kılavuzuna başvurun
▪ Kapalı mekana monte edilen dış üniteler (örn. kış
bahçesi, garaj, makine odası)
▪ Havalandırılmayan hacimlerde bulunan boru tesisatı
Minimum zemin alanını belirlemek için
1 Sistemdeki toplam soğutucu şarjını belirleyin (= fabrikadaki
soğutucu şarjı + şarj edilen ilave soğutucu miktarı).
2 Hangi grafik veya tablonun kullanılacağını belirleyin.
▪ İç üniteler için: Ünite tavana monteli, duvara monteli yoksa
döşeme tipi mi?
▪ İç mekanda kurulan veya depolanan dış üniteler ve
havalandırılmayan hacimlerde bulunan saha boruları için bu durum montaj yüksekliğine bağlıdır:
Eğer montaj yüksekliği … ise Bu durumda … için olan grafik
veya tablo kullanılır
<1,8m Döşeme tipi üniteler 1,8≤x<2,2m Duvara monteli üniteler ≥2,2m Tavana monteli üniteler
3 Minimum zemin alanını belirlemek için grafik veya tabloyu
kullanın.
4
m Sistemdeki toplam soğutucu şarjı
A
Minimum zemin alanı
min
(a) Ceiling-mounted unit (=Tavana monteli ünite) (b) Wall-mounted unit (=Duvara monteli ünite)
FDXM25~60F3V1B(9)
Split sistem klimalar
4P550955-1 – 2018.07
1 Genel güvenlik önlemleri
(c) Floor-standing unit (=Döşeme tipi ünite)

1.2.3 Soğutucu akışkan

Mevcutsa. Daha fazla bilgi için, uygulamanızın montaj kılavuzuna veya montör başvuru kılavuzuna bakın.
BİLDİRİM
Soğutucu akışkan boru montajının ilgili mevzuata uygun olduğundan emin olun. Avrupa'daki ilgili standart EN378 sayılı standarttır.
BİLDİRİM
Saha borularının ve bağlantılarının gerilime maruz KALMADIĞINDAN emin olun.
UYARI
Testler sırasında ürünü KESİNLİKLE (ünitelerin etiketlerinde belirtilen) izin verilen maksimum basıncın üzerinde bir değerde basınçlandırmayın.
UYARI
Soğutucu akışkan kaçaklarına karşı gerekli önlemleri alın. Soğutucu gaz kaçağı meydana gelirse, ortamı iyice havalandırın. Olası riskler:
▪ Kapalı bir odada soğutucu akışkan
konsantrasyonlarının aşırı yüksek olması, oksijen yetersizliğine neden olabilir.
▪ Soğutucu gazın ateşle temas etmesi halinde zehirli bir
gaz açığa çıkabilir.
▪ Yalnızca sistemde kullanılan soğutucu akışkan tipine özel aletler
kullanın; böylece basınç direncini sağlar ve sisteme yabancı madde girişini önlersiniz.
▪ Sıvı soğutucu akışkanı şu şekilde şarj edin:
Eğer Ardından,
Bir sifon tüpü mevcuttur
(örn., “Sıvı doldurma sifonu takılı” işareti taşıyan tüp)
Bir sifon tüpü mevcut DEĞİLDİR Tüp baş aşağı konumdayken şarj
▪ Soğutucu akışkan tüplerini yavaşça açın.
▪ Soğutucu akışkanı sıvı fazda doldurun. Gaz fazda doldurulması,
normal çalışmayı engelleyebilir.
DİKKAT
Soğutucu yükleme prosedürü yerine getirildiğinde veya ara verildiğinde, soğutucu tüpünün vanasını hemen kapatın. Vana derhal KAPATILMAZSA, kalan basınç ilave soğutucu şarj edebilir. Olası sonuç: Yanlış soğutucu miktarı.
Tüp baş yukarı konumdayken şarj edin.
edin.
TEHLİKE: PATLAMA RİSKİ
Gaz toplama – Soğutucu kaçağı. Sistemin gazını
toplamak istiyorsanız ve soğutucu devresinde kaçak varsa:
▪ Sistemdeki tüm soğutucuyu dış ünitede toplayabilen
ünitenin otomatik gaz toplama fonksiyonunu KULLANMAYIN. Olası sonuç: Çalışan kompresörün içine giden hava yüzünden kendiliğinden yanma ve kompresörün patlaması.
▪ Ünitenin kompresörünün çalışmak zorunda
KALMAYACAĞI ayrı bir geri kazanma sistemi kullanın.
UYARI
Soğutucu akışkanı DAİMA geri kazanın. KESİNLİKLE doğrudan atmosfere salınmasına izin vermeyin. Kurulumu boşaltmak için bir vakum pompası kullanın.
BİLDİRİM
Tüm borular bağlandıktan sonra, gaz kaçağı olmadığından emin olun. Gaz kaçağı kontrolü için nitrojen kullanın.
BİLDİRİM
▪ Kompresörün bozulmasını önlemek için, belirlenmiş
miktardan fazla soğutucu şarj ETMEYİN.
▪ Soğutucu sisteminin açılması gerektiğinde, soğutucu
ilgili mevzuata göre işlem GÖRMELİDİR.
UYARI
Sistemde oksijen bulunmadığından emin olun. Soğutucu ancak kaçak testi ve vakumlu kurutma işlemi gerçekleştirildikten sonra yüklenebilir.
▪ Yeniden şarj edilmesi gerekiyorsa, ünite üzerindeki etikete bakın.
Etikette soğutucu akışkan tipi ve gerekli miktarı yazılıdır.
▪ Ünite, fabrikada soğutucu akışkanla doldurulur, ancak boru
çaplarına ve uzunluklarına bağlı olarak bazı ünitelere ilave soğutucu akışkan doldurulması gerekebilir.

1.2.4 Tuzlu Su

Mevcutsa. Daha fazla bilgi için, uygulamanızın montaj kılavuzuna veya montör başvuru kılavuzuna bakın.
UYARI
Tuzlu su seçimi MUTLAKA ilgili mevzuata uygun olarak yapılmalıdır.
UYARI
Tuzlu su kaçaklarına karşı gerekli önlemleri alın. Tuzlu su kaçağı durumunda alanı derhal havalandırın ve satıcınıza danışın.
UYARI
Ünite içerisindeki ortam sıcaklığı, örn. 70°C gibi oda içerisindeki sıcaklıktan çok daha yüksek olabilir. Tuzlu su kaçağı olması durumunda, ünite içerisindeki sıcak parçalar tehlikeli durumlar ortaya çıkartabilir.
UYARI
Uygulamanın kullanımı ve montaj MUTLAKA ilgili mevzuatta güvenlik ve çevre ile ilgili olarak belirtilen önlemler dikkate alınarak gerçekleştirilmelidir.

1.2.5 Su

Mevcutsa. Daha fazla bilgi için, uygulamanızın montaj kılavuzuna veya montör başvuru kılavuzuna bakın.
BİLDİRİM
Su kalitesinin 98/83 EC sayılı AB direktifine uygun olduğundan emin olun.
FDXM25~60F3V1B(9) Split sistem klimalar 4P550955-1 – 2018.07
5

2 Dokümanlar hakkında

1.2.6 Elektrik

TEHLİKE: ELEKTRİK ÇARPMASI RİSKİ
▪ Anahtar kutusu kapağını çıkartmadan, herhangi bir
elektrik kablosunu bağlamadan veya elektrikli parçalara temas etmeden önce tüm güç beslemelerini KAPALI konuma getirin.
▪ Servis işlemine başlamadan önce, güç beslemesini
1 dakikadan daha uzun bir süre kesin ve ana devre kapasitörlerinin veya elektrikli bileşenlerin terminalleri arasındaki gerilimi ölçün. Elektrikli bileşenlere dokunulabilmesi için, gerilimin MUTLAKA 50 V DC değerinin altında olması gerekir. Terminallerin konumları için, kablo şemasına bakın.
▪ Elleriniz ıslakken, KESİNLİKLE elektrikli bileşenlere
dokunmayın.
▪ Servis kapağı açık konumdayken, KESİNLİKLE
ünitenin başından ayrılmayın.
UYARI
Fabrikada monte EDİLMEMİŞ ise, aşırı gerilim kategori III koşulunda bağlantıyı tam kesen tüm kutuplarda kontak ayırma özelliğine sahip bir ana anahtar veya başka bir bağlantı kesme vasıtası sabit kablo tesisatına monte EDİLMELİDİR.
UYARI
▪ YALNIZCA bakır teller kullanın.
▪ Saha kablo tesisatının ilgili mevzuata uygun
olduğundan emin olun.
▪ Tüm saha kabloları MUTLAKA ürünle verilen kablo
şemalarına uygun olarak bağlanmalıdır.
▪ Kablo demetlerini KESİNLİKLE sıkmayın ve kabloların,
borulara ve keskin kenarlara temas ETMEDİĞİNDEN emin olun. Terminal bağlantılarına dışarıdan baskı uygulanmadığından emin olun.
▪ Topraklama kablosunun takıldığından emin olun.
Üniteyi KESİNLİKLE bir şebeke borusuna, darbe emicisine veya telefon topraklamasına topraklamayın. Topraklamanın yetersiz yapılması elektrik çarpmasına yol açabilir.
▪ Özel olarak ayrılmış bir güç devresinin kullanıldığından
emin olun. Başka bir cihazla paylaşılan bir güç beslemesini KESİNLİKLE kullanmayın.
▪ Gerekli sigortaların ve devre kesicilerin takıldığından
emin olun.
▪ Bir toprak kaçağı kesicisinin takıldığından emin olun.
Aksi takdirde, elektrik çarpmasına veya yangına neden olabilir.
▪ Topraklama kaçağı koruyucu monte edilecekse,
topraklama kaçağı koruyucusunun gereksiz yere açılmasını önlemek için bu koruyucunun inverter ile uyumlu (yüksek frekanslı elektrik karışımına dayanıklı) olduğundan emin olun.
BİLDİRİM
Güç kabloları döşenirken alınması gereken önlemler:
▪ Güç terminal bloğuna farklı kalınlıktaki kablolar
BAĞLAMAYIN (güç kablolarındaki gevşeklikler anormal ısınmaya neden olabilir).
▪ Aynı kalınlıktaki kabloları bağlarken, yukarıdaki şekilde
gösterildiği gibi yapın.
▪ Kablolama için, belirtilen güç kablolarını kullanın ve bu
kabloları sağlam şekilde bağlayın ve ardından terminal kartına harici basınç uygulanmasını önlemek için sabitleyin.
▪ Terminal vidalarını sıkmak için uygun bir tornavida
kullanın. Küçük başlı bir tornavida, vida başına zarar verebilir ve vidanın doğru şekilde sıkılmasını engelleyebilir.
▪ Terminal vidaları aşırı sıkılırsa kırılabilir.
Olası karışmaları önlemek için, güç kablolarını televizyon ve radyolara en az 1 metre uzaktan geçirin. Radyo dalgalarına bağlı olarak, 1metre mesafe yeterli olmayabilir.
UYARI
▪ Elektrik işleri tamamlandıktan sonra, her bir elektrikli
bileşenin ve elektrikli bileşen kutusu içindeki terminalin sağlam şekilde bağlandığını onaylayın.
▪ Üniteyi çalıştırmadan önce tüm kapakların
kapatıldığından emin olun.
BİLDİRİM
Yalnızca güç kaynağının trifaze olması ve kompresörde bir AÇIK/KAPALI başlangıç yönteminin bulunması durumunda geçerlidir.
Ürün çalışırken anlık bir kesintinin veya gücün gidip gelmesinin ardından ters fazın devreye girmesi ihtimali varsa, ters faz koruma devresini lokal olarak monte edin. Ürünün ters fazda çalıştırılması, kompresöre ve diğer parçalara zarar verebilir.
2 Dokümanlar hakkında

2.1 Bu doküman hakkında

BİLGİ
Kullanıcının ilgili dokümanların çıktısını aldığından emin olun ve kullanıcıdan bu dokümanları daha sonra başvurmak üzere saklamasını isteyin.
Hedef okuyucu
Yetkili montörler
6
BİLGİ
Bu cihaz mağazalarda, hafif endüstriyel tesislerde ve çiftliklerde uzmanlar veya eğitimli kullanıcılar tarafından veya ticari alanlarda ve konutlarda normal kullanıcılar tarafından kullanılmak üzere tasarlanmıştır.
Doküman seti
Bu doküman bir doküman setinin bir parçasıdır. Tam set şu dokümanları içerir:
FDXM25~60F3V1B(9)
Split sistem klimalar
4P550955-1 – 2018.07