Read these instructions carefully before installation.
Keep this manual in a handy place for future reference.
This manual should be left with the equipment owner.
Lire soigneusement ces instructions avant l’installation.
Conserver ce manuel à portée de main pour référence
ultérieure.
Ce manuel doit être donné au propriétaire de l’équipement.
Lea cuidadosamente estas instrucciones antes de instalar.
Guarde este manual en un lugar a mano para leer en caso
de tener alguna duda.
Este manual debe permanecer con el propietario del
equipo.
4. INDOOR UNIT INSTALLATION ..................................... 5
5. REFRIGERANT PIPING WORK .................................... 8
6. DRAIN PIPING WORK .................................................. 9
7. ELECTRIC WIRING WORK ......................................... 10
8. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER .................................... 11
9. FIELD SETTING .......................................................... 14
10. TEST OPERATION ...................................................... 15
1. SAFETY CONSIDERATIONS
Read these SAFETY CONSIDERATIONS for Installation
carefully before installing air conditioning equipment. After
completing the installation, make sure that the unit operates
properly during the startup operation.
Instruct the customer on how to operate and maintain the
unit. Inform customers that they should store this Installation
Manual with the Operation Manual for future reference.
Always use a licensed installer or contractor to install this
product. Improper installation can result in water or refriger-
ant leakage, electrical shock, re, or explosion.
Meanings of DANGER, WARNING, CAUTION, and NOTE
Symbols:
DANGER
WARNING
CAUTION
NOTE
................ Indicates an imminently haz-
ardous situation which, if not
avoided, will result in death or
serious injury.
.............. Indicates a potentially haz-
ardous situation which, if not
avoided, could result in death
or serious injury.
............... Indicates a potentially haz-
ardous situation which, if not
avoided, may result in minor
or moderate injury. It may
also be used to alert against
unsafe practices.
....................... Indicates situations that may
result in equipment or property damage accidents only.
DANGER
• Refrigerant gas is heavier than air and replaces oxy-
gen. A massive leak can lead to oxygen depletion,
especially in basements, and an asphyxiation hazard
could occur leading to serious injury or death.
• Do not ground units to water pipes, gas pipes, tele-
phone wires, or lightning rods as incomplete grounding can cause a severe shock hazard resulting in
severe injury or death. Additionally, grounding to gas
pipes could cause a gas leak and potential explosion
causing severe injury or death.
• If refrigerant gas leaks during installation, ventilate
the area immediately. Refrigerant gas may produce
toxic gas if it comes in contact with re. Exposure to
this gas could cause severe injury or death.
• After completing the installation work, check that the
refrigerant gas does not leak throughout the system.
• Do not install unit in an area where ammable materi-
als are present due to risk of explosions that can
cause serious injury or death.
• Safely dispose of all packing and transportation
materials in accordance with federal/state/local laws
or ordinances. Packing materials such as nails and
other metal or wood parts, including plastic packing
materials used for transportation, may cause injuries
or death by suffocation.
WARNING
• Only qualied personnel must carry out the installa-
tion work. Installation must be done in accordance
with this installation manual. Improper installation
may result in water leakage, electric shock, or re.
• When installing the unit in a small room, take mea-
sures to keep the refrigerant concentration from
exceeding allowable safety limits. Excessive refrigerant leaks, in the event of an accident in a closed
ambient space, can lead to oxygen deciency.
• Use only specied accessories and parts for installa-
tion work. Failure to use specied parts may result in
water leakage, electric shocks, re, or the unit falling.
• Install the air conditioner on a foundation strong
enough that it can withstand the weight of the unit. A
foundation of insufcient strength may result in the
unit falling and causing injuries.
• Take into account strong winds, typhoons, or earth-
quakes when installing. Improper installation may
result in the unit falling and causing accidents.
• Make sure that a separate power supply circuit is
provided for this unit and that all electrical work is
carried out by qualied personnel according to local,
state and national regulations. An insufcient power
supply capacity or improper electrical construction
may lead to electric shocks or re.
• Make sure that all wiring is secured, that specied
wires are used, and that no external forces act on the
terminal connections or wires. Improper connections
or installation may result in re.
1
English
Page 3
• When wiring, position the wires so that the control
box cover can be securely fastened. Improper positioning of the control box cover may result in electric
shocks, re, or the terminals overheating.
• Before touching electrical parts, turn off the unit.
• This equipment can be installed with a Ground-Fault
Circuit Interrupter (GFCI). Although this is a recognized measure for additional protection, with the
grounding system in North America, a dedicated GFCI
is not necessary.
• When installing or relocating the system, keep the
refrigerant circuit free from substances other than the
specied refrigerant (R410A) such as air. Any presence of air or other foreign substance in the refrigerant circuit can cause an abnormal pressure rise or
rupture, resulting in injury.
• Do not change the setting of the protection devices. If
the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts
other than those specied by Daikin are used, re or
explosion may occur.
CAUTION
• Do not touch the switch with wet ngers. Touching a
switch with wet ngers can cause electric shock.
• Do not allow children to play on or around the unit to
prevent injury.
• Do not touch the refrigerant pipes during and immedi-
ately after operation as the refrigerant pipes may be
hot or cold, depending on the condition of the refrigerant owing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may
suffer burns or frostbite if you touch the refrigerant
pipes. To avoid injury, give the pipes time to return to
normal temperature or, if you must touch them, be
sure to wear proper gloves.
• Heat exchanger ns are sharp enough to cut. To avoid
injury, wear glove or cover the ns when working
around them.
• Install drain piping to proper drainage. Improper drain
piping may result in water leakage and property damage.
• Insulate piping to prevent condensation.
• Be careful when transporting the product.
• Do not turn off the power supply immediately after
stopping operation. Always wait for at least 5 minutes
before turning off the power supply. Otherwise, water
leakage may occur.
• Do not use a charging cylinder. Using a charging
cylinder may cause the refrigerant to deteriorate.
• Refrigerant R410A in the system must be kept clean,
dry, and tight.
(a) Clean and Dry -- Foreign materials (including
mineral oils such as SUNISO oil or moisture)
should be prevented from getting into the system.
(b)
Tight -- R410A does not contain any chlorine, does
not destroy the ozone layer, and does not reduce the
earth’s protection again harmful ultraviolet radiation.
R410A can contribute to the greenhouse effect if it is
released. Therefore take proper measures to check
for the tightness of the refrigerant piping installation.
Read the chapter REFRIGERANT PIPING WORK and
follow the procedures.
• Since R410A is a blend, the required additional refrig-
erant must be charged in its liquid state. If the refrigerant is charged in a gaseous state, its composition can
change and the system will not work properly.
• The indoor unit is for R410A. See the catalog for
indoor models that can be connected. Normal operation is not possible when connected to other units.
• Handheld remote controller transmitting distance can
be shorter than expected in rooms with electronic
uorescent lamps (inverter or rapid start types). Install
the indoor unit far away from uorescent lamps as
much as possible.
• Indoor units are for indoor installation only. Outdoor
units can be installed either outdoors or indoors.
• Do not install the air conditioner in the following
locations:
(a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen.
Plastic parts may deteriorate and fall off or result
in water leakage.
(b) Where corrosive gas, such as sulfurous acid gas,
is produced.
Corroding copper pipes or soldered parts may
result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation
of the control system and cause the unit to malfunction.
(d) Where ammable gas may leak, where there is
carbon ber, or ignitable dust suspension in the
air, or where volatile ammables such as thinner
or gasoline are handled. Operating the unit in
such conditions can cause a re.
NOTE
• Install the power supply and control wires for the
indoor and outdoor units at least 3.5 feet (1.0m) away
from televisions or radios to prevent image interference or noise. Depending on the radio waves, a dis-
tance of 3.5 feet (1.0m) may not be sufcient to
eliminate the noise.
• Dismantling the unit, treatment of the refrigerant, oil
and additional parts must be done in accordance with
the relevant local, state, and national regulations.
• Do not use the following tools that are used with
conventional refrigerants: gauge manifold, charge
hose, gas leak detector, reverse ow check valve,
refrigerant charge base, vacuum gauge, or refrigerant
recovery equipment.
• If the conventional refrigerant and refrigerator oil are
mixed in R410A, the refrigerant may deteriorate.
• This air conditioner is an appliance that should not be
accessible to the general public.
• As design pressure is 478 psi (3.3MPa), the wall
thickness of eld-installed pipes should be selected in
accordance with the relevant local, state, and national
regulations.
English
2
Page 4
2. BEFORE INSTALLATION
• When unpacking the unit or moving the unit after
unpacked, be sure to lift it by the four hanger brackets. Avoid putting any pressure on other parts-hori-
zontal aps, the refrigerant piping, drain piping, and
other resin parts.
• Be sure to remove a cushion (corrugated paper) located
between the heat exchanger and the right air lter.
• Be sure to check the type of R410A refrigerant to be used
before installing the unit. (Using an incorrect refrigerant
will prevent normal operation of the unit.)
• The accessories needed for installation must be retained
in your custody until the installation work is completed. Do
not discard them!
• Decide upon a line of transport.
• Leave the unit inside its packaging while moving, until
reaching the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates
together with a rope when lifting, to avoid damage or
scratches to the unit.
• For the installation of an outdoor unit, refer to the installa-
tion manual attached to the outdoor unit.
• When using the wireless remote controller, refer to the
installation manual attached to the wireless remote controller.
• Do not install or operate the unit in rooms mentioned
below.
• Laden with mineral oil, or lled with oil vapor or
spray like in kitchens. (Plastic parts may deteriorate
which could eventually cause the unit to fall out of
place, or could lead to leaks.)
• Where corrosive gas like sulfurous gas exists.
(Copper tubing and brazed spots may corrode
which could eventually lead to refrigerant leaks.)
• Where exposed to combustible gases and where
volatile ammable gas like thinner or gasoline is
used.
(Gas in the vicinity of the unit could ignite.)
• Where machines can generate electromagnetic
waves. (Control system may malfunction.)
• Where the air contains high levels of salt such as
that near the ocean and where voltage uctuates
greatly such as that in factories, vehicles or vessels.
• This unit, both indoor and outdoor, is suitable for installa-
tion in a commercial and light industrial environment. If
installed as a household appliance it could cause electromagnetic interference.
2-1 ACCESSORIES
Check if the following accessories are attached to the
indoor unit.
Name(1) Installation panel
Quantity1 pc.9 pcs.
Shape
Name
Quantity1 pc.1 pc.1 large 4 small
Shape
Name
Quantity2 pcs.
(3) Paper pattern
for installation
(6) Securing
screw
(2) Attachment screw
for the installation panel
(4) Insulating
tape
(7) Insulating
tube
1 long
1 short
M4 × 25L
(5) Clamp
(Other)
• Operation
manual
• Installation
manual
Shape
• Warranty
card
M4 × 12L
2-2 OPTIONAL ACCESSORIES
Remote controllerModel
Wired typeBRC1E73
Wireless typeBRC7E818
WARNING
• Entrust installation to the place of purchase or an autho-
rized serviceman. Improper installation could lead to leaks
and, in worse cases, electric shock of re.
• Use of unspecied parts could lead to the unit falling,
leaks and, in worse cases, electric shock or re.
NOTE
• Be sure to read this manual before installing the indoor
unit.
3
English
Page 5
FOR THE FOLLOWING ITEMS, TAKE
[ Space required for installation [in. (mm)] ]
SPECIAL CARE DURING CONSTRUCTION
AND CHECK AFTER INSTALLATION IS
FINISHED.
(1) Items to be checked after completion of work
Items to be checked
Are the indoor and outdoor
units xed rmly?
Is the gas leak test nished?
Is the unit fully insulated?
Does drainage ow
smoothly?
Does the power supply
voltage correspond to that
shown on the name plate?
Are wiring and piping
correct?
Is the unit safely
grounded?
Is wiring size according to
specications?
Is something blocking the
air outlet or inlet of either
the indoor or outdoor unit?
Are refrigerant piping
length and additional
refrigerant charge noted
down?
Did you check that no
wiring connection screws
were loose?
If not properly done,
what is likely to occur
The units may drop, vibrate
or make noise.
It may result in insufcient
cooling or heating.
Condensate water may
drip.
Condensate water may
drip.
The unit may malfunction
or the components may
burn out.
The unit may malfunction
or the components may
burn out.
It may be dangerous at
electric leakage.
The unit may malfunction
or the components burn
out.
It may result in insufcient
cooling.
The refrigerant charge in
the system is not clear.
Electric shock or re.
Check
• Where the wall is strong enough to bear the indoor
unit weight.
• Where sufcient clearance for installation and mainte-
nance can be ensured.
(Refer to Fig. 1 and Fig. 2)
• Where optimum air distribution can be ensured.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where the wall is not signicantly tilted.
• Where piping between indoor and outdoor unit is
possible within the allowable limit.
(Refer to the installation manual of the outdoor unit.)
• Install the indoor and outdoor units power supply
wiring and connecting wires at least 3.5ft. (1m) away
from televisions or radios in order to prevent image
interference or noise.
(Depending on the radio waves, a distance of 3.5ft.
(1m) may not be sufcient enough to eliminate the
noise.)
• Where the cool (warm) air reaches all across the
room.
≥ 2 (50)≥ 2 (50)
Fig. 1
Also review the “SAFETY CONSIDERATIONS”
(2) Items to be checked at delivery
Items to be checkedCheck
Did you explain how to operate the unit while showing
the operation manual to your customer?
Did you give the operation manual over to your cus-
tomer?
2-3 NOTE TO THE INSTALLER
Be sure to instruct customers how to properly operate the
unit (especially cleaning lters, operating different functions,
and adjusting the temperature) by having them carry out
operations themselves while looking at the manual.
3. SELECTING INSTALLATION SITE
(1) Select an installation site where the following condi-
tions are fullled and has the customer’s approval.
•
Where there will be no possible dripping of water from
the refrigerant pipe, drain pipe, etc., in the area between
the unit and ceiling, and in the attic just above the unit.
English
≥ 3-1/2 (90)
Obstruction
≤ 4-3/4 (120)
≥ 1-1/4 (30)
≥ 100 (2500)
(from floor)
For installation
in high places.
Floor
Fig. 2
4
Page 6
(2) Consider whether the place where the unit will be
installed can support the full weight of the unit, and
reinforce it with boards and beams, etc. if needed
before proceeding with the installation. Also, reinforce the area to prevent vibration and noise before
installing.
(The installation pitch can be found on the paper
pattern for installation (3), so refer to it when considering the necessity for reinforcing the location.)
(3) The indoor unit may not be directly installed on the
wall. Use the attached installation panel (1) before
installing the unit.
DANGER
• Do not install unit in an area where ammable materials
are present due to risk of explosion resulting in serious
injury or death.
WARNING
• If the supporting structural members are not strong
enough to take the unit’s weight, the unit could fall out of
place and cause serious injury.
(c) Secure the installation panel (1) to the wall using
either screws or bolts.
• If using the attachment screws for the installation
panel (2), attach using at least 4 screws on either
side, for a total of 9 screws of the recommended
installation cleat position on the included paper
pattern for installation (3).
• If using bolts, attach using a M8 - M10 bolt or
equivalent (for a total of 2 bolts) on either side.
• If dealing with concrete, use commercially avail-
able foundation bolts (M8 - M10 or equivalent).
(3) If using the left, bottom-left, or bottom-right posi-
tions for the piping, cut out the through-hole for the
piping in the front grille. (Refer to Fig. 4)
Left pipe
Back-left pipe
Bottom-left pipe
4. INDOOR UNIT INSTALLATION
• Use only accessories and parts which are of the desig-
nated specication when installing.
CAUTION
• Install so that the unit does not tilt to either side or forward.
• Do not hold the unit by the horizontal aps when lifting it.
(This may damage the horizontal aps.)
(1) Open the piping through-hole.
• The refrigerant pipe and drain pipe can be routed out
in one of 5 directions: left, bottom-left, back-left,
bottom-right, and back-right. (Refer to Fig. 3)
• Using the paper pattern for installation (3), choose
where to route the piping out of the unit, and drill a
through-hole (f3-1/8” (f80)) in the wall.
Open the hole so that there is a downward slope for
the drain piping. (See “6. DRAIN PIPING WORK”)
(2) Attach the installation panel (1) to the wall.
(a) Check the location for the hole using the included
paper pattern for installation (3).
• Choose a location so that there is at least a 3-5/8”
(90 mm) gap between the ceiling and the main
unit.
(b) Temporarily attach the installation panel (1) at the
temporary-securing position on the paper pattern for
installation (3) and use a level to make sure the drain
hose is either level or tilted slightly downward.
Back-right pipe
Bottom-right pipe
Fig. 3
Front grille
Cut out along
the groove.
Cut away
Fig. 4
5
English
Page 7
(4) Remove the front panel and the control box cover.
Insulating tape (4)
Ta b
(Refer to Fig. 5)
< How to remove the front panel and control box
cover >
(1) Open the front panel by lifting from the bottom to the
point where it stops.
(2) Push the panel spacers on either side of the front
panel towards the center of the main unit and
remove.
(You can also remove it by sliding the front panel
either to the left or right and pulling it forward.)
(3) Remove the screw from the control box cover and
pull the tab forward.
Panel
spacer
(2)(2)
Panel
spacer
Fig. 5
Front panel
(1)
Panel
spacer
Control box cover
(3)
Ta b
Screw
(5) Point the pipe in the direction it will be routed out of
the unit.
For bottom-right and back-right piping
(Refer to Fig. 6)
• Wrap the drain hose and the refrigerant piping
together with the insulating tape (4) so that the drain
hose is below the refrigerant piping.
Refrigerant piping
Tab positionTab position
(3)
(3)(3)
Screw position
(2)
Screw position
Front grille
(4)
(2)(2)
Fig. 7
• Remove the drain plug, the insulating tube, and the drain
hose from the drain pan and replace.
(Refer to Fig. 8)
• Connect the eld refrigerant piping ahead of time, match-
ing it to the liquid pipe and gas pipe marks engraved on
the installation panel (accessory) (1).
< Replacing the drain hose and drain plug >
(1) Remove the drain plug and insulating tube.
(2) Remove the drain hose and replace onto the left side.
(3) Replace the drain plug and the insulating tube onto the
right side.
Insulating tube
Make sure
there are
no gaps.
Fig. 8
Insert using a
hexagon wrench
(5/32 in. (4 mm)).
Drain plug
Do not place
lubricant
(refrigerant oil)
when inserting.
This may cause
deterioration and
water leaks.
Fig. 6
Drain hose
For left, bottom-left, and back-left piping
• Remove the front grille. (Refer to Fig. 7)
< How to remove the front grille >
Remove the front grille as described below when securing the indoor unit with screws or when attaching
Optional Accessories (wireless remote controller,
adapter PC board, etc.).
(1) Remove the front panel.
(2) Remove the screws (3 places) securing the front
grille.
(3) Remove the tabs (3 places) securing the front grille
by pushing them in the direction of the arrows.
(4) Making sure not to catch the horizontal aps, remove
the front grille by pulling in the direction of the arrow.
(6) Hook the indoor unit onto the installation panel.
(Refer to Fig. 9)
• Placing buffering material between the wall and the
indoor unit at this time will make work easier.
Hook the indoor unit hook onto
Control box cover
Front panelFront grille
Be sure to pass all
wires through
the wiring guide.
Refrigerant piping
(There are 2 places.)
Wiring (locally procured)
Transmission wiring,
Remote controller wiring
the installation panel (1).
Ta b
Fig. 9
Place buffering
material
Wall
Power supply
wiring,
Ground wiring
Conduit
Installation panel
(accessory) (1)
For bottom-right and back-right piping
• Pass the drain hose and the refrigerant piping to the
wall.
English
6
Page 8
(7) Pass power supply wiring from conduit and control
wiring through the wiring guide in the back of the
unit, to the front of the unit. (For connecting the
power supply wiring to the unit, see “8-1 HOW TO
CONNECT WIRINGS”)
(8) Connect the piping. (See “5. REFRIGERANT PIPING
WORK” and Fig. 10)
Secure with
vinyl tape.
Drain hose
(9) Push on both bottom edges of the indoor unit using
both hands and hook the tab on the back of the
indoor unit onto the installation panel (1).
(Refer to Fig. 9)
• At this time remove the buffering material placed in
step (6).
• Make sure power supply wiring, transmission wiring,
ground wiring and remote controller wiring are not
caught inside the indoor unit.
When screwing in the indoor unit
• Remove the front grille. (Refer to Fig. 7)
• Secure the indoor unit to the installation panel (1) with
the securing screws (6). (Refer to Fig. 11)
Installation panel
(accessory) (1)
Transmission
wiring and remote
controller wiring
Seal with putty
corking material.
Refrigerant piping
Transmission wiring and
remote controller wiring
A arrow view
Refrigerant piping
Conduit
Wrap the insulating tape overlapping
at least half the width with each wrap.
Wrap the insulating tape all the way
to the L-shaped bend.
Fig. 10
• Seal the piping through-hole with putty corking mate-
rial.
A
Fig. 11
Refrigerant piping
Insulating tape
(accessory) (4)
M4 × 12L
(accessory) (6)
7
English
Page 9
5. REFRIGERANT PIPING WORK
Torque wrench
Coat the flared inner surface only
〈For refrigerant piping of outdoor unit, see the installation manual attached to the outdoor unit.〉〈Execute thermal insulation work completely on both
sides of the gas piping and the liquid piping.
Otherwise, a water leak can occur.〉
(When using a heat pump, the temperature of the gas piping
can reach up to approximately 250°F (120°C), so use insulation which is sufciently resistant.)
〈Also, in cases where the temperature and humidity of
the refrigerant piping sections might exceed 86°F (30°C)
or RH80 %, reinforce thermal insulation (13/16 (20mm) or
thicker) for the refrigerant piping. Condensation may
form on the surface of the insulating material.〉〈Before refrigerant piping work, check which type of
refrigerant is used. Proper operation is not possible if
the type of refrigerant is not the same.〉
DANGER
• Refrigerant gas may produce toxic gas if it comes in
contact with re such as from a fan, heater, stove or
cooking device. Exposure to this gas could result in severe
injury or death.
with ester oil or ether oil
Fig. 13
CAUTION
• Use the are nut included with the unit.
• Refer to Table 1 for the corresponding tightening torque.
Table 1
Piping
size
[in. (mm)]
f 3/8
(9.5)
f 5/8
(15.9)
Tightening
torque
[lbf·ft. (N·m)]
24.1 – 29.4
(36.3±3.6)
45.6 – 55.6
(68.6±6.8)
Dimension for
processing are
A [in. (mm)]
0.504 – 0.520
(13.0±0.2)
0.760 – 0.776
(19.5±0.2)
Flare shape
[in. (mm)]
45˚±2˚
A
90˚±2˚
R0.016-0.031
(0.4-0.8)
NOTE
• Use a pipe cutter and a aring tool suitable for the type of
refrigerant.
• To prevent dust, moisture or other foreign matter from
inltrating the tube, either pinch the end or cover it with
tape.
• Do not allow anything other than the designated refriger-
ant to get mixed into the refrigerant circuit, such as air, etc.
• If refrigerant gas leaks while working on the unit, ventilate
the room thoroughly right away.
• The refrigerant is pre-charged in the outdoor unit.
• Use copper alloy seamless pipes.
• Be sure to use both a spanner and a torque wrench
together, when connecting or disconnecting pipes to/from
the unit. (Refer to Fig. 12)
• Refer to “Table 1” for the dimensions of are.
• When connecting the are nut, coat the ared inner sur-
face only with ester oil or ether oil, rotate three or four
times rst, then screw in.
(Refer to Fig. 13)
Spanner
CAUTION
• Do not excessively tighten the are nut.
Doing so will break the are nut and refrigerant leakage
may occur.
• Make sure that all parts around the are are free of oil.
The drain pan and the resin part may be deteriorated if oil
is attached.
CAUTION
• Do not use ux when brazing refrigerant piping. Therefore,
use the phosphor copper brazing lter metal (BCuP) which
does not require ux.
(Flux has an extremely negative effect on refrigerant
piping systems. For instance, if chlorine based ux is
used, it will cause pipe corrosion. If the ux contains
uorine, it will damage the refrigerant oil.)
English
Union joint
Flare nut
Fig. 12
8
Page 10
• When brazing the refrigerant piping, carry out nitrogen
Refrigerant piping
Part to be
brazed
Taping
Pressure-reducing valve
Hand valve
Nitrogen
Fig. 14
Nitrogen
Field piping
Clamp (large)
( See “4. INDOOR UNIT INSTALLATION” )
substitution (inserting nitrogen into the refrigerant piping to
substitute air with nitrogen (refer to NOTE below)) and
then begin brazing. Once this is done, connect the indoor
unit with a are connection.
CAUTION
• Be sure to insulate the eld piping all the way to the piping
connection inside the unit. Any exposed piping may cause
condensate or burns if touched.
• Use of oxygen may cause an explosion resulting in seri-
• Set nitrogen pressure to about 2.9 psi (0.02 Mpa) with a
• After checking for gas leaks, be sure to insulate the pipe
DANGER
ous injury or death. Only use nitrogen gas.
NOTE
pressure-reducing valve if brazing while inserting nitrogen
into the piping. (Refer to Fig. 14)
connections using the piping insulating tube and insulating
tape (4). The insulating tape (4) should be wrapped from
the L-shaped bend all the way to the end inside the unit.
(Refer to Fig. 15)
Tape of insulating tube
Indoor unit
piping
Indoor unit piping
insulating tube
(accessory) (5)
Tape of insulating tube
Insulating tape
(accessory) (4)
See “ 4. INDOOR UNIT
INSTALLATION ”
Start wrapping
L-shaped
bend
6. DRAIN PIPING WORK
(1) Install the drain piping. (Refer to Fig. 16)
• The drain pipe should be short with a downward slope
and should prevent air pockets from forming.
• Watch out for the points in Fig. 16 when performing
drain work.
Make sure the drain
hose is at a downward
slope.
Make sure the tip is
not under water even
when flooding.
Drain hoseDrain hose
(Downward
slope)
Fig. 16
• When extending the drain hose, use a commercially
available drain hose for extension, and be sure to
insulate the extended section of the drain hose which
is indoors. (Refer to Fig. 17)
Insulating tube
(field supply)
Drain hose for extension
(field supply)
Indoor unit
drain hose
Indoor unit piping insulating
tube
Tape of insulating tube
Seam of Insulating tube
Attach the tape of insulating tube
so that there are no gaps in the
seam of insulating tube.
Fig. 15
9
Insulating tape (accessory) (4)
Fig. 17
• Make sure the diameter of the drain hose for exten-
sion is the same as the indoor unit drain hose (hard
vinyl chloride, I.D. 1/2 in. (13 mm)) or larger.
• In case of converging multiple drain hoses, install
them referring to Fig. 18.
• Select diameter of drain hose which adapts to the
capacity of the unit connected.
English
Page 11
4 in. (100 mm)
or more
Fig. 18
(Slope of at least 1/100)
(2) Make sure the drain piping works properly.
• After drain piping work is complete, perform a drain-
age check by opening the front panel, removing the air lter, pouring water into the drain pan, and making
sure water ows smoothly out of the drain hose.
(Refer to Fig. 19)
Plastic container
for pouring
Drain pan
Fig. 19
Make sure not to splash the water.
DANGER
• Do not ground units to water pipes, telephone wires or
lightning rods because incomplete grounding could cause
a severe shock hazard resulting in severe injury or death,
and to gas pipes because a gas leak could result in an
explosion which could lead to severe injury or death.
7-2 ELECTRICAL CHARACTERISTICS
UnitsPower supply Fan motor
ModelHzVolts
FAQ18TAVJU
FAQ24TAVJU
60 208/230
Voltage
range
Max. 253
Min. 187
MCA MOPWFLA
0.515430.4
0.615430.5
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
W: Fan Motor Rated Output (W)
FLA: Full Load Ampere (A)
7-3 SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
CAUTION
• Drain piping connections
Do not connect the drain piping directly to sewage pipes
that smell of ammonia. The ammonia in the sewage might
enter the indoor unit through the drain piping and corrode
the heat exchanger.
Keep in mind that it will block the drain pipe and cause
water to collect.
7. ELECTRIC WIRING WORK
7-1 GENERAL INSTRUCTIONS
• All eld supplied parts and materials and electric works
must conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to also “WIRING DIAGRAM”
attached to the unit.
• For details of remote controller wiring, refer to the installa-
tion manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down power supply to
the entire system must be installed.
• Refer to the installation manual attached to the outdoor
unit for the size of power supply wiring connected to the
outdoor unit, the capacity of the circuit breaker and switch,
and wiring instructions.
• Be sure to ground the air conditioner.
Remote controller wiring
Transmission wiring
2-conductor,
stranded
non-shielded
copper cable
PVC/vinyl
jacket
(NOTE)
AWG18-16
(0.75-
1.25 mm
2
Model
FAQ18TAVJU
FAQ24TAVJU
Power supply wiring
Fuse
SizeWireSize
Wiring size
and length
15A
must
comply
with local
codes.
Allowable lengths of transmission wiring and remote controller
wiring are as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280 ft (1,000 m)
(2) Indoor unit – Remote controller:
Max. 1640 ft (500 m)
NOTE
• Vinyl cord with sheath or cable (Insulated thickness :
1/16in. (1 mm) or more)
)
English
10
Page 12
8. WIRING EXAMPLE AND HOW TO SET
Conduit
Transmission
Insulating tube (short)
THE REMOTE CONTROLLER
8-1 HOW TO CONNECT WIRINGS
• Conduit for power supply wiring
Unscrew and remove the conduit mounting plate from the
control box. (Refer to Fig. 20)
Fix a conduit to the plate with a lock nut and reattach them
at original position.
(accessory) (7)
Insulating tube (long)
(accessory) (7)
Clamp (small)
(accessory) (5)
(1 in. (25 mm))
Clamp (small)
(accessory) (5)
Powe r
supply
wiring
Ground
wiring
wiring
Control box
• Power supply wiring and ground wiring
Unscrew and remove the control box cover.
Thread the power supply wiring and ground wiring through
the included insulating tube (short) (7) and secure them
with the included clamp (small) (5). (Refer to Fig. 21)
Connect the power supply wiring and ground wiring to the
power supply terminal block (3P).
When doing this, rmly secure using the included clamp
(small) (5) according to the gure.
(Refer to Fig. 22)
• Transmission wiring and remote controller wiring
Unscrew and remove the control box cover.
Thread the remote controller wiring and transmission
wiring through the included insulating tube (long) (7) and
secure them with the included clamp (small) (5).
(Refer to Fig. 21)
Connect the remote controller wiring and the transmission
wiring to the terminal block (6P).
When doing this, tie the remote controller wiring and the
transmission wiring using the included clamp (small) (5)
and then rmly secure using the included clamp (small)
(5) according to the gure.
(Refer to Fig. 22)
Screw
<Back side>
<Front side>
Lock nut
Conduit mounting
plate
Refrigerant
piping
Fig. 20
Power supply
terminal block (3P)
Ground terminal
Ground wiring
Clamp (small) (accessory) (5)
(3 places)
Cut off any excess
material after tightening.
Power supply wiring
Remote controller wiring and
transmission wiring
Terminal block (6P)
<
Wiring clamp method
Clamp (small)
(accessory) (5)
Insulating tube
Remote
controller
wiring
(1 in. (25 mm))
Fig. 21
L1
>
Power supply wiring
Ground wiring
Transmission
wiring
REMOTE
CNTRL
Remote
controller
wiring
L2
F1 F2 T1 T2P1 P2
FORCED
TRANSMISSION
WIRING
OFF
11
Clamp (small)
(accessory) (5)
Insulating tube
Fig. 22
English
Page 13
WARNING
Attach insulation sleeve
• Never connect power supply wiring to the terminal block
for remote controller wiring as this could damage the
entire system.
• Use only specied wire and connect wires to the terminal
tightly. Be careful wires do not place external stress on
terminals. Keep wires in neat order so as not to obstruct
other equipment. Make sure that the control box cover ts
tightly. Incomplete connections could result in overheating
and, in worse case, result in electric shock or re.
• To avoid a short circuit in the control box, be sure to apply
sealing material or putty (not included) to the wiring hole
to prevent the inltration of water as well as insects or
other small creatures. Otherwise a short-circuit may occur
inside the control box.
2. Tightening torque for the terminal screws.
• Use the correct screwdriver for tightening the terminal
screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw
will not be properly tightened.
• If the terminal screws are tightened too hard, screws
might be damaged.
• Refer to the table below for the tightening torque of
the terminal screws.
TerminalSize
Remote controller,
Transmission wiring and
Forced off terminal block (6P)
Power supply and Ground
terminal block (3P)
M3.5
Tightening torque
M4
[lbf·ft. (N·m)]
0.59 – 0.71
(0.80 – 0.96)
0.89 – 1.03
(1.2 – 1.4)
CAUTION
• When clamping the wirings, be sure no tension is applied
to the wire connections by using the included clamp. Also,
when wiring, make sure the cover on the control box ts
snugly by arranging the wirings neatly and attaching the
control box cover rmly. When attaching the control box
cover, make sure no wirings get caught in the edges. Pass
wiring through holes to prevent damage to them.
• Make sure the remote controller wiring and transmission
wiring between the units, and other electrical wiring do not
pass through the same locations outside the unit, separating them by at least 2 in. (50 mm), otherwise electrical
noise (external static) could cause incorrect operation or
breakage.
[ PRECAUTIONS ]
1. Use round crimp-style terminals for connecting wires to
the power supply terminal block.
(Refer to Fig. 23)
If unavailable, observe the following points when wiring.
• Do not connect wires of different gauge to the same
power supply terminal.
(Looseness in the connection may cause overheating.)
• Use the specied electric wire. Connect the wire
securely to the terminal. Lock the wire down without
applying excessive force to the terminal.
3. Do not connect wires of different gauge to the same
ground terminal. Looseness in the connection may
lessen protection.
4. Keep transmission wiring at least 2 in. (50 mm) away
from power supply wiring. The equipment may malfunc-
tion if subjected to electrical (external) noise.
5. For remote controller wiring, refer to the installation
manual attached to the remote controller.
8-2 WIRING EXAMPLE
COMPLETE SYSTEM EXAMPLE
Power supply
Main
switch
Outdoor unit
Indoor unit
Remote controller
Fig. 24
Power supply wire
Transmission wire
Disconnect switch
Fuse/Breaker
Round crimp-style
terminal
English
Electric wire
Fig. 23
12
Page 14
1. When using 1 remote controller (Normal operation)
Power Supply
T
F
208/230V
1~ 60Hz
L1L2
Outdoor unit
L1L
Indoor unit
Control box
IN/D OUT/D
F
1 F2 F1 F2
P1P
2
2
F1F2T1T
2
P1P
2
Remote
controller
Fig. 25
8-3 CONTROL BY 2 REMOTE
CONTROLLERS (Controlling 1 indoor unit by 2
remote controllers)
• When using 2 remote controllers, one must be set to
“MAIN” and the other to “SUB”.
〈Main/sub changeover〉
• Refer to the installation manual supplied with the remote
controller.
〈Wiring method〉
(1) Remove the control box cover.
(2) Add the remote controller 2 (SUB) to the terminal block
for remote controller (P¹, P²) in the control box. (There is
no polarity.)
1P2P1F2F1T2
REMOTE
CONTRL
TRANSMISSION
WIRING
FORCED
OFF
Remote controller wiring
terminal block
2. When using 2 remote controllers
Power Supply
208/230V
1~ 60Hz
L1L2
Indoor unit
Outdoor unit
Control box
IN/D OUT/D
F
1 F2 F1 F2
P1P2F1F2T1T
L1L
2
P1P
2
For use with
2 remote
controllers
2
P1P
2
Fig. 26
[ PRECAUTIONS ]
1. Do not ground the equipment on gas pipes, water pipes
or lightning rods, or crossground with telephones.
Improper grounding could result in electric shock.
2. The remote controller wiring (P¹ and P²) and transmis-
sion wiring (F¹ and F²) have no polarity.
Remote
controller 1
(MAIN)
Remote
controller 2
(SUB)
Fig. 27
8-4 REMOTE CONTROL (FORCED OFF AND ON/
OFF OPERATION)
• Connect input lines from the outside to the terminals T¹
and T² on the terminal block (6P) for remote controller to
achieve remote control.
• See “9. FIELD SETTING” for details on operation.
1F2
P
1P2
REMOTE
TRANSMISSION
CONTRL
WIRING
Fig. 28
Wire specicationSheathed vinyl cord or 2 core cable
GaugeAWG18 – 16 (0.75-1.25 mm
LengthMax. 328 ft. (100 m)
External terminal
Contact that can ensure the minimum
applicable load of 15 V DC, 1 mA.
1T2
FORCED
OFF
T
Input A
2
)
13
8-5 CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the
group No. For details, refer to the manual of each optional
controllers for centralized control.
English
Page 15
9. FIELD SETTING
〈Field settings may have to be performed using the
remote controller, depending on the type of installation.〉
(1) Make sure the control box covers are closed on the
indoor and outdoor units.
(2) Depending on the type of installation, make the eld
settings from the remote controller after the power is
turned on, following the installation manual attached
to the remote controller.
• The settings can select “Mode No.”, “FIRST CODE
NO.” and “SECOND CODE NO.”.
• The “Field Settings” included with the remote control-
ler lists the order of the settings and method of operation.
FIELD SET MODE
Field Settings
Unit No.
0
0–01
–––
4
–––
8
FIRST CODE NO.
Mode
1–01
–––
5
–––
9
Setting
SECOND CODE NO.
20
2–02
–––
6
–––
a
3–01
–––
7
–––
b
Mode No.
9-2 SETTING AIRFLOW RATE INCREASE MODE
• It is possible to raise set airow (HIGH and LOW) from the
eld. Change the SECOND CODE NO. as shown in
Table3 to suit your needs.
(SECOND CODE NO. is factory set to “01” for Standard.)
Table 3
SettingMode No.
Standard
A little increase02
Increase02
230
FIRST
CODE NO.
SECOND
CODE NO.
01
9-3 REMOTE CONTROL SETTING
• Forced off and ON/OFF operation should be selected by
selecting the SECOND CODE NO. as shown in Table 4.
Table 4
External ON/OFF inputMode No.
Forced off
ON/OFF operation02
* Factory set
221
FIRST
CODE NO.
• Input A of forced off and ON/OFF operation work as
shown in Table 5.
SECOND
CODE NO.
01*
Fig. 29
• Lastly, make sure the customer keeps the installation
manual, along with the operating manual, in a safe place.
〈When using wireless remote controllers〉
• When using wireless remote controllers, wireless remote
controller address setting is necessary. Refer to the installation manual attached to the wireless remote controller
for setting instructions.
9-1 SETTING FILTER SIGN
• Remote controllers are equipped with display air lter
signs to display the time to clean air lters.
• Change the SECOND CODE NO. according to Table 2
depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to “01” for air lter
contamination-light)
Table 2
Setting
Air lter contamination-light
Air lter contamination-heavy
Spacing time of
display air lter
sign
Approx. 200hours
Approx. 100hours02
Mode
No.
200
FIRST
CODE
NO.
SECOND
CODE
NO.
01
Table 5
Forced offON/OFF operation
Input A “on” to force a stop
(remote controller reception
prohibited)
Input A “off” to allow remote
controller
Unit operated by changing input
A from “off” to “on”
Unit stopped by changing input
A from “on” to “off”
English
14
Page 16
10. TEST OPERATION
• The operation lamp of the remote controller will ash when
a malfunction occurs. Check the malfunction code on the
display to identify the point of trouble. An explanation of
malfunction codes and the corresponding trouble is provided in “Service precautions” of the outdoor unit.
If the display shows any of the following, there is a possibility that the wiring was done incorrectly or that the
power is not on, so check again.
Remote controller
display
“ A8 ”
“ U3 ”
“
”
“ U4 ”
“ UH ”
None
• Error in power supply voltage to indoor
unit.
• Test operation of outdoor unit has not
been nished.
• There is a short circuit at the FORCED
OFF terminals (T¹, T²)
• The power on the outdoor unit is off.
• The outdoor unit has not been wired for
power supply.
• Incorrect wiring for the transmission
wiring and / or FORCED OFF wiring.
• The power on the indoor unit is off.
• The indoor unit has not been wired for
power supply.
• Incorrect wiring for the remote controller
wiring, the transmission wiring and / or
the FORCED OFF wiring.
Contents
CAUTION
• After the test operation is completed, check the items
mentioned in 2. BEFORE INSTALLATION (2) Items to be checked at delivery on page 4.
If the interior nish work is not completed when the test
operation is nished, for protection of the air conditioner,
ask the customer not to operate the air conditioner until
the interior nish work is completed.
If the air conditioner is operated, the inside of the indoor
unit may be polluted by substances generated from the
coating and adhesives used for the interior nish work and
cause water splash and leakage.
To the operator carrying out test operation
• After the test operation is completed, before delivering the
air conditioner to the customer, conrm that the control
box cover, the air lter and suction grille are attached.
In addition, explain the power supply status (power supply
ON/OFF) to the customer.
15
English
Page 17
5151 San Felipe, Suite 500
Houston, TX 77056
3PN07521-5H
EM17A032
(1809)
HT
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.