• Indoor Unit • FAQ-C
TABLE OF CONTENTS
FAQ-C
1Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wiring Diagrams - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8 External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9 Sound data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
• Split - Sky Air • FAQ-C
1

• Indoor Unit • FAQ-C
1 Features
Indoor Unit Split - Sk FAQ-CWall mounte
For rooms with no false ceilings nor free floor space
• Flat, stylish front panel blends easily within any interior décor and is
more easy to clean
• Can easily be installed in both new and refurbishment projects
• Reduced energy consumption thanks to specially developed DC fan
1
motor
• The air is comfortably spread up and downwards thanks to 5 different
discharge angles that can be programmed via the remote control
• Maintenance operations can be performed easily from the front of the
unit
• No optional adapter needed for DIII-connection, link your unit into the
wider building management system.
Home leave
operation
Wired remote
control
Fan only Auto cooling-
Centralised
control
heating
changeover
Auto-restart Self diagnosis Drain pump kit Twin/triple/
Vertical auto
swing
Fan speed
steps
Dry programme Air filter Weekly timer Infrared remote
control
double twin
application
2
• Split - Sky Air • FAQ-C

• Indoor Unit • FAQ-C
2 Specifications
2-1 Technical Specifications FAQ71C FAQ100C *FAQ125C
Power input Cooling Nom. kW 0.051 0.061 -
Heating Nom. kW 0.068 0.061 -
Casing Colour Fresh White -
Material Resin -
Dimensions Unit Height/Width/
Depth
Packed unit Height/Width/
Depth
Weight Unit kg 13 17 17
Packed unit kg 19 24 -
Heat exchanger Length mm 863 963 -
Rows Quantity 2 Fin pitch mm 1.2 Passes Quantity 4 6 Face area m² 0.279 0.347 Stages Quantity 18 20 Empty tubeplate
hole
Fin Type Cross fin coil (Multi slit fins and Hi-XB tubes) -
Fan Type Cross flow fan -
Quantity 1 Air flow rate Cooling High m³/min 18 26 -
Fan motor Model QCL9663MA QCL1096M -
Speed Steps 3 Output High W 48 64 Phase x Voltage V DC310 DC325 Full load amps
(FLA)
Sound power level Cooling dBA 61 65 -
Heating dBA 61 65 -
Sound pressure level Cooling High/Nom./Low dBA 45/42/40 49/45/41 -/-/-
Heating High/Nom./Low dBA 45/42/40 49/45/41 -/-/-
Control systems Infrared remote control BRC7EB518 -
Wired remote control BRC1D52 / BRC1E52A/B Refrigerant Type R-410A Piping connections Liquid Type/OD mm Flare connection/9.52 /-
Gas Type/OD mm Flare connection/15.9 /-
Drain VP13 (I.D. 13/O.D. 18) -
Heat insulation Foamed polystyrene / Foamed polyethylene -
Quantity 0 -
Heating High m³/min 18 26 -
Cooling A 0.3 0.4 Heating A 0.4 -
mm 290/1,050/238 340/1,200/240 340/1,200/240
mm 366/1,147/337 429/1,310/325 -/-/-
Nom. m³/min 16 23 Low m³/min 14 19 -
Nom. m³/min 16 23 Low m³/min 14 19 -
3
2
Standard Accessories : Installation and operation manual; Quantity : 1;
Standard Accessories : Installation panel;
Standard Accessories : Insulation tape;
Standard Accessories : Screws;
Standard Accessories : Clamps;
Standard Accessories : Screw cover;
2-2 Electrical Specifications FAQ71C FAQ100C *FAQ125C
Power supply Phase 1~ 1~
Frequency Hz 50/60 50/60
Voltage V 220-240/220 220-240/220
• Split - Sky Air • FAQ-C
3