1.1About this document ...................................................................................................................................................... 5
1.2Meaning of warnings and symbols.................................................................................................................................6
2 General safety precautions8
2.1For the installer............................................................................................................................................................... 8
2.1.2Installation site ............................................................................................................................................... 9
2.1.3Refrigerant — in case of R410A or R32.......................................................................................................... 12
8.2.3Airflow direction ............................................................................................................................................. 31
8.3To operate the system.................................................................................................................................................... 32
9 Energy saving and optimum operation33
10 Maintenance and service34
10.1 Precautions for maintenance and service ...................................................................................................................... 34
10.2 Cleaning the unit ............................................................................................................................................................. 35
10.2.1To clean the air outlet and exterior ............................................................................................................... 35
10.2.2To clean the front panel................................................................................................................................. 35
10.2.3To clean the air filter ...................................................................................................................................... 36
10.3 Maintenance before a long stop period......................................................................................................................... 37
10.4 Maintenance after a long stop period............................................................................................................................ 37
10.5 About the refrigerant...................................................................................................................................................... 38
11 Troubleshooting39
11.1 Symptoms that are NOT system malfunctions............................................................................................................... 40
11.1.1Symptom: The system does not operate....................................................................................................... 40
11.1.2Symptom: The fan speed does not correspond to the setting...................................................................... 40
11.1.3Symptom: The fan direction does not correspond to the setting................................................................. 40
11.1.4Symptom: White mist comes out of a unit (Indoor unit) .............................................................................. 41
11.1.5Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)........................................................ 41
11.1.6Symptom: The user interface reads "U4" or "U5" and stops, but then restarts after a few minutes.......... 41
11.1.7Symptom: Noise of air conditioners (Indoor unit)......................................................................................... 41
11.1.8Symptom: Noise of air conditioners (Indoor unit, outdoor unit).................................................................. 41
11.1.9Symptom: Dust comes out of the unit........................................................................................................... 41
11.1.10 Symptom: The units can give off odours ....................................................................................................... 41
Installer and user reference guide
2
12 Relocation42
13 Disposal43
For the installer44
14 About the box45
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Table of contents
14.1 Overview: About the box ................................................................................................................................................ 45
14.2 Indoor unit ...................................................................................................................................................................... 45
14.2.1To unpack and handle the unit ...................................................................................................................... 45
14.2.2To remove the accessories from the indoor unit .......................................................................................... 46
15.1.1Identification label: Indoor unit ..................................................................................................................... 47
15.2 About the indoor unit ..................................................................................................................................................... 47
15.3 System layout .................................................................................................................................................................. 48
15.4 Combining units and options .......................................................................................................................................... 49
15.4.1Possible options for the indoor unit............................................................................................................... 49
16 Unit installation50
16.1 Preparing the installation site......................................................................................................................................... 50
16.1.1Installation site requirements of the indoor unit .......................................................................................... 50
16.2 Opening and closing the unit .......................................................................................................................................... 52
16.2.1To remove the front panel............................................................................................................................. 52
16.2.2To re-install the front panel ........................................................................................................................... 52
16.2.3To remove the front grille.............................................................................................................................. 52
16.2.4To re-install the front grille ............................................................................................................................ 53
16.2.5To open the service cover.............................................................................................................................. 54
16.2.6To close the service cover.............................................................................................................................. 54
16.3 Mounting the indoor unit ............................................................................................................................................... 54
16.3.1To install the mounting plate......................................................................................................................... 54
16.3.2To drill a wall hole........................................................................................................................................... 56
16.3.3To remove the pipe port cover ...................................................................................................................... 57
16.3.4To hook the unit on the mounting plate........................................................................................................ 58
16.3.5To pass the pipes through the wall hole........................................................................................................ 58
16.3.6To provide drainage........................................................................................................................................ 59
17.2.5To flare the pipe end...................................................................................................................................... 65
17.2.6To connect the refrigerant piping to the indoor unit.................................................................................... 66
18 Electrical installation67
18.1 About connecting the electrical wiring .......................................................................................................................... 67
18.1.1Precautions when connecting the electrical wiring....................................................................................... 67
18.1.2Guidelines when connecting the electrical wiring......................................................................................... 68
18.1.3Specifications of standard wiring components.............................................................................................. 69
18.2 To connect the electrical wiring to the indoor unit ....................................................................................................... 69
19 Finishing the indoor unit installation73
19.1 To fix the unit on the mounting plate ............................................................................................................................ 73
20.2 Precautions when commissioning .................................................................................................................................. 74
20.3 Checklist before commissioning ..................................................................................................................................... 74
20.4 To perform a test run...................................................................................................................................................... 75
21 Configuration76
21.1 Field setting ..................................................................................................................................................................... 76
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
22 Hand-over to the user80
23 Troubleshooting81
23.1 Solving problems based on error codes ......................................................................................................................... 81
This appliance is intended to be used by expert or trained users in shops, in light
industry, and on farms, or for commercial and household use by lay persons.
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow
the instructions from Daikin and, in addition, comply with applicable legislation and
are performed by qualified persons only. In Europe and areas where IEC standards
apply, EN/IEC 60335-2-40 is the applicable standard.
Documentation set
1 | About the documentation
This document is part of a documentation set. The complete set consists of:
▪ General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the indoor unit)
▪ Indoor unit installation and operation manual:
- Installation and operation instructions
- Format: Paper (in the box of the indoor unit)
▪ Installer and user reference guide:
- Preparation of the installation, good practices, reference data,…
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your dealer.
The original documentation is written in English. All other languages are
translations.
Technical engineering data
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
▪ A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
▪ The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Installer and user reference guide
5
1 | About the documentation
1.2 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or
cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
SymbolExplanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
For more information, see the installer and user reference
guide.
Installer and user reference guide
6
The unit contains rotating parts. Be careful when servicing or
inspecting the unit.
Symbols used in the documentation:
SymbolExplanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
1 | About the documentation
SymbolExplanation
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Installer and user reference guide
7
2 | General safety precautions
2 General safety precautions
2.1 For the installer
2.1.1 General
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
▪ Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return
to normal temperature. If you MUST touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in
electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY
use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable
legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially
children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
Installer and user reference guide
8
CAUTION
▪ Do NOT place any objects or equipment on top of the unit.
▪ Do NOT sit, climb or stand on the unit.
In accordance with the applicable legislation, it might be necessary to provide a
logbook with the product containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the
product:
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
2.1.2 Installation site
2 | General safety precautions
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
▪ Provide sufficient space around the unit for servicing and air circulation.
▪ Make sure the installation site withstands the weight and vibration of the unit.
▪ Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
▪ In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Instructions for equipment using R32 refrigerant
WARNING
▪ Do NOT pierce or burn.
▪ Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
▪ Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a wellventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater) and have a room
size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Installer and user reference guide
9
2 | General safety precautions
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
▪ there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the
minimum floor area A (m²).
▪ no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching device);
▪ only auxiliary devices approved by the manufacturer are used in the duct work;
▪ air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
NOTICE
▪ Precautions shall be taken to avoid excessive vibration or pulsation to
refrigeration piping.
▪ Protection devices, piping and fittings shall be protected as far as possible against
adverse environmental effects.
▪ Provision shall be made for expansion and contraction of long runs of piping.
▪ Piping in refrigerating systems shall be designed and installed such as to minimise
the likelihood of hydraulic shock damaging the system.
▪ The indoor equipment and pipes shall be securely mounted and guarded such
that accidental rupture of equipment or pipes cannot occur from events such as
moving furniture or reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant
leaks.
NOTICE
▪ Do NOT re-use joints and copper gaskets which have been used already.
▪ Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
Installation space requirements
WARNING
This appliance contains R32 refrigerant. For the minimum floor area of the room in
which the appliance is stored refer to installation and operation manual of the
outdoor unit.
NOTICE
▪ Pipework shall be protected from physical damage.
▪ Installation of pipework shall be kept to a minimum.
To determine the minimum floor area
Installer and user reference guide
10
1Determine the total refrigerant charge in the system (= factory refrigerant
▪ For indoor units: Is the unit ceiling-mounted, wall-mounted or floor-
standing?
▪ For outdoor units installed or stored indoors, this depends on the installation
height:
If the installation height is…Then use the graph or table for…
<1.8mFloor-standing units
1.8≤x<2.2mWall-mounted units
≥2.2mCeiling-mounted units
3Use the graph or table to determine the minimum floor area.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
m Total refrigerant charge in the system
A
Minimum floor area
min
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)
Installer and user reference guide
11
2 | General safety precautions
2.1.3 Refrigerant — in case of R410A or R32
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
▪ Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Selfcombustion and explosion of the compressor because of air going into the
operating compressor.
▪ Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen
to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
▪ When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
Installer and user reference guide
12
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
2 | General safety precautions
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after
performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of
oxygen going into the operating compressor.
▪ In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the
system.
▪ Charge the liquid refrigerant as follows:
IfThen
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid
filling siphon attached")
A siphon tube is NOT presentCharge with the cylinder upside down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
2.1.4 Electrical
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before
servicing. The voltage MUST be less than 50VDC before you can touch electrical
components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service cover is removed.
Installer and user reference guide
13
2 | General safety precautions
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
categoryIII condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable legislation.
▪ All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
▪ NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
▪ Make sure to install the required fuses or circuit breakers.
▪ Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
▪ When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
CAUTION
▪ When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
▪ When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
▪ The length of the conductors between the power supply stress relief and the
terminal block itself MUST be as such that the current-carrying wires are
tautened before the earth wire is in case the power supply is pulled loose from
the stress relief.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness, do as shown in the figure
above.
▪ For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Installer and user reference guide
14
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
2 | General safety precautions
Install power cables at least 1 m away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 m may not be
sufficient.
WARNING
▪ After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes on and off while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Installer and user reference guide
15
3 | Specific installer safety instructions
3 Specific installer safety instructions
Always observe the following safety instructions and regulations.
General
WARNING
Make sure installation, servicing, maintenance, repair and applied materials follow
the instructions from Daikin and, in addition, comply with applicable legislation and
are performed by qualified persons only. In Europe and areas where IEC standards
apply, EN/IEC 60335-2-40 is the applicable standard.
Unit installation (see
"16Unit installation"[450]
WARNING
The appliance using R32 refrigerant shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously operating ignition
sources (e.g. open flames, an operating gas appliance, or an operating electric
heater). The room size shall be as specified in the General safety precaution.
CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and
wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
Refrigerant piping installation (see
CAUTION
Piping MUST be installed according to instructions given in "17 Piping
installation" [4 62]. Only mechanical joints (e.g. braze+flare connections) that are
compliant with the latest version of ISO14903 can be used.
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this unit to guarantee its lifetime. The drying material may
dissolve and damage the system.
)
"17Piping installation"[462]
)
Installer and user reference guide
16
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
CAUTION
Install the refrigerant piping or components in a position where they are unlikely to
be exposed to any substance which may corrode components containing refrigerant,
unless the components are constructed of materials that are inherently resistant to
corrosion or are suitably protected against corrosion.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
3 | Specific installer safety instructions
Electrical installation (see
WARNING
▪ All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
▪ If the power supply has a missing or wrong N-phase, equipment might break
down.
▪ Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
▪ Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
"18Electrical installation"[467]
)
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact
point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Installer and user reference guide
17
For the user
For the user
Installer and user reference guide
18
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
4 User safety instructions
Always observe the following safety instructions and regulations.
4.1 General
WARNING
If you are NOT sure how to operate the unit, contact your
installer.
WARNING
This appliance can be used by children aged from 8 years
and above and persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge if
they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the
hazards involved.
4 | User safety instructions
Children SHALL NOT play with the appliance.
Cleaning and user maintenance SHALL NOT be made by
children without supervision.
WARNING
To prevent electrical shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet hands.
▪ Do NOT place any objects containing water on the unit.
CAUTION
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Installer and user reference guide
19
4 | User safety instructions
▪ Units are marked with the following symbol:
▪ Batteries are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with
unsorted household waste. Do NOT try to dismantle the system yourself: the
dismantling of the system, treatment of the refrigerant, of oil and of other parts
must be done by an authorized installer and must comply with applicable
legislation.
Units must be treated at a specialized treatment facility for reuse, recycling and
recovery. By ensuring this product is disposed of correctly, you will help to
prevent potential negative consequences for the environment and human
health. For more information, contact your installer or local authority.
This means that the batteries may NOT be mixed with unsorted household
waste. If a chemical symbol is printed beneath the symbol, this chemical symbol
means that the battery contains a heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility for reuse. By
ensuring waste batteries are disposed of correctly, you will help to prevent
potential negative consequences for the environment and human health.
4.2 Instructions for safe operation
WARNING
▪ Do NOT modify, disassemble, remove, reinstall or repair
the unit yourself as incorrect dismantling or installation
may cause an electric shock or fire. Contact your dealer.
▪ In case of accidental refrigerant leaks, make sure there
are no naked flames. The refrigerant itself is entirely
safe and non-toxic. R410A is a non-combustible
refrigerant, and R32 is a mildly flammable refrigerant,
but they will generate a toxic gas when they accidentally
leak into a room where combustible air from fan
heaters, gas cookers, etc. is present. Always have
qualified service personnel confirm that the point of
leakage has been repaired or corrected before resuming
operation.
Installer and user reference guide
20
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
4 | User safety instructions
CAUTION
▪ NEVER touch the internal parts of the controller.
▪ Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may
happen. For checking and adjusting the internal parts,
contact your dealer.
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been
carried out correctly by an installer.
CAUTION
It is unhealthy to expose your body to the air flow for a
long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently
if equipment with burner is used together with the system.
CAUTION
Do NOT operate the system when using a room
fumigation-type insecticide. Chemicals could collect in the
unit, and endanger the health of people who are
hypersensitive to chemicals.
CAUTION
▪ ALWAYS use a user interface to adjust the angle of the
flap. When the flap is swinging and you move it forcibly
by hand, the mechanism will break.
▪ Be careful when adjusting the louvers. Inside the air
outlet, a fan is rotating at high speed.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
CAUTION
NEVER expose little children, plants or animals directly to
the airflow.
Installer and user reference guide
21
4 | User safety instructions
WARNING
Do NOT place a flammable spray bottle near the air
conditioner and do NOT use sprays near the unit. Doing so
may result in a fire.
Maintenance and service (see
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any
maintenance task.
CAUTION
Do NOT insert fingers, rods or other objects into the air
inlet or outlet. When the fan is rotating at high speed, it
will cause injury.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere
ratings or other wires when a fuse blows out. Use of wire
or copper wire may cause the unit to break down or cause
a fire.
"10Maintenance and service"[434]
)
CAUTION
After a long use, check the unit stand and fitting for
damage. If damaged, the unit may fall and result in injury.
CAUTION
Before accessing terminal devices, make sure to interrupt
all power supply.
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop
operation and turn all power supplies off. Otherwise, an
electric shock and injury may result.
WARNING
Be careful with ladders when working in high places.
CAUTION
Installer and user reference guide
22
Turn off the unit before cleaning the air outlet, exterior,
front panel and air filter.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
4 | User safety instructions
WARNING
Do NOT let the indoor unit get wet. Possible consequence:
Electric shock or fire.
About the refrigerant (see
WARNING: MILDLY FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly
flammable. Refer to the outdoor unit specifications for the
type of refrigerant to be used.
WARNING
The appliance using R32 refrigerant shall be stored so as to
prevent mechanical damage and in a well-ventilated room
without continuously operating ignition sources (e.g. open
flames, an operating gas appliance, or an operating electric
heater). The room size shall be as specified in the General
safety precaution.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
"10.5About the refrigerant"[438]
)
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
R410A is a non-combustible refrigerant, and R32 is a mildly
flammable refrigerant; they normally don’t leak. If the
refrigerant leaks in the room and comes into contact with
fire from a burner, a heater, or a cooker, this may result in
a fire (in case of R32), or the formation of a harmful gas.
Turn off any combustible heating devices, ventilate the
room, and contact the dealer from where you purchased
the unit.
Do not use the unit until a service person confirms that the
part from which the refrigerant leaked has been repaired.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Installer and user reference guide
23
4 | User safety instructions
Troubleshooting (see
WARNING
Stop operation and shut off the power if anything
unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may
cause breakage, electric shock or fire. Contact your dealer.
"11Troubleshooting"[439]
)
Installer and user reference guide
24
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
5 About the system
b
c
a
d
e
WARNING
▪ Do NOT modify, disassemble, remove, reinstall or repair the unit yourself as
incorrect dismantling or installation may cause an electric shock or fire. Contact
your dealer.
▪ In case of accidental refrigerant leaks, make sure there are no naked flames. The
refrigerant itself is entirely safe and non-toxic. R410A is a non-combustible
refrigerant, and R32 is a mildly flammable refrigerant, but they will generate a
toxic gas when they accidentally leak into a room where combustible air from fan
heaters, gas cookers, etc. is present. Always have qualified service personnel
confirm that the point of leakage has been repaired or corrected before resuming
operation.
NOTICE
Do NOT use the system for other purposes. In order to avoid any quality
deterioration, do NOT use the unit for cooling precision instruments, food, plants,
animals, or works of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future system extensions) is available
in technical engineering data and should be consulted. Contact your installer to
receive more information and professional advice.
5 | About the system
5.1 System layout
INFORMATION
The following illustration is an example and might NOT match your system layout.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
a Indoor unit
b Outdoor unit
c User interface
d Refrigerant piping + trasmission cable
Installer and user reference guide
25
5 | About the system
a
c
d
b
e
f
g
h
e Drain pipe
a Front panel
b Front grille
c Service cover
d Air filters
e Drain hose
f Refrigerant pipes
g Electrical wiring
h User interface
Installer and user reference guide
26
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
6 User interface
CAUTION
▪ NEVER touch the internal parts of the controller.
▪ Do NOT remove the front panel. Some parts inside are dangerous to touch and
NOTICE
Do NOT wipe the controller operation panel with benzine, thinner, chemical dust
cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily
dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the
panel clean. Wipe it with another dry cloth.
NOTICE
NEVER press the button of the user interface with a hard, pointed object. The user
interface may be damaged.
6 | User interface
appliance problems may happen. For checking and adjusting the internal parts,
contact your dealer.
NOTICE
NEVER pull or twist the electric wire of the user interface. It may cause the unit to
malfunction.
This operation manual offers a non-exhaustive overview of the main functions of
the system.
For more information about the user interface, see the operation manual of the
installed user interface.
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
Installer and user reference guide
27
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.